FC2060 Sinteso™

Fire control panel


FS20 series (MP4.0)

 Modular, prefabricated, microprocessor-controlled fire control panel with inte-


grated user-friendly operating unit for up to max. 1512 addresses
 Processes signals from various detector systems like:
– FD20 devices of the Sinteso series
– collective fire detectors of the MS7/9/24, DS11, Synova 600, SIGMACON series
– addressable fire detectors of the MS9i series
 Fire control panel can be used as stand-alone version or can be networked
 Up to 64 stations (fire control panels and fire terminals) can be connected in
one network
 Integrated degraded mode function
 Redundant network node, degraded mode operation according to EN 54
 Fast Ethernet interface for a heterogeneous network
 Option of printer, key switches, LED displays
 Slots for serial ports and max. 5 extra cards
 Emergency power supply for emergency operating time of up to 72 hours
 Recognition and automatic read-in (auto configuration) of all FDnet devices,
ready for operation immediately
 Time and situation-dependent changeover of detector parameter sets
 Floor repeater devices, alarm devices and mimic displays in detector loop
(FDnet)
 Flexible programming of complex applications and controls
 Stored data can be uploaded via remote access
 Firmware download of all processor controlled control panel components

Building Technologies
CPS Fire Safety
System overview

FC2040
FT2040

Repeater
FN2002

FCnet/SAFEDLINK
FC2060
Fire control panel
SintesoWorks,
SintesoView

MS9i

FDT241

Camera FDCI222
FDL241-9 FDO2x1
Video Fire
Controller Fire controls
FDCL221
via FCI2008-A1
FT2011
Floor repeater display FDV241 4 inputs
Conventional horn line
24V FDOOT241-9 via FCI2009-A1
24 VDC ext. FDnet stub line FDF2x1-9
possible max. 1512 addresses

FDSB221 / 4 outputs
FDSB291 FDSB229
FDOOTC241
FDS229 FDCW241
24VDC ext. FT2010 FDCIO222
Floor repeater terminal
FDM22x FDS221 4 inputs

FDCIO223
FDM22x
Detector line for Mimic display FDOOT271
GMT detectors, Siemens or FT2001-A1
SynovaTM SynoLINE300 24 VDC ext.
possible collective
Radio detectors MS7/9/24, DS11,
Synova 600, SIGMACON

FDnet Collectively MS9i I/Os (programmable)


4 integrated loops (8 with loop 8 lines per line card 2 loops per line card (with 12 free programmable in-
extension) + 4 loops with max. max. 100 addresses per line puts/outputs per I/O card
252 addresses per line card card)
Mixed usage possible, but with a max. of 5 cards per control panel.

2
Building Technologies
CPS Fire Safety
Networking topologies

Up to 32 fire control panels und fire control terminals can be connected in a single clus-
ter (FCnet/SAFEDLINK) or up to 16 stations when the cluster is connected to a danger
management system.

Using a fiber-optic Backbone (FCnet/LAN) up to 14 of the above mentioned clusters


(with up to 16 stations each) can be networked. The entire network may contain up to
64 stations.

 For details about system networking, please refer to product data sheet 008955.
3
Building Technologies
CPS Fire Safety
Characteristics

– The FC2060 is a modular fire control panel with integrated operating unit for large in-
stallations and for modernizing large older fire detection installations.
– The FC2060 processes signals from Sinteso, collective MS7/9/24, DS11,
Synova 600, SIGMACON and addressable MS9i devices.
– An integrated card cage with 5 slots allows
– FDnet line cards FCL2001-A1 to be used (for extra lines)
– Collective line cards FCL2002-A1
– MS9i line cards FCL2003-A1
– I/O card FCI2008-A1 (with 12 programmable inputs/outputs)
– Mixed use of all line and I/O cards possible.
– In the event of a defect, the extra line cards can be replaced without the control panel
having to be powered down.
– The fire control panel may be used as a stand-alone unit or networked.
– Using the user-friendly engineering tool SintesoWorks, the control panels can be
configured to create a customized solution.
– Adaptation of customer texts on the terminal itself or using the configuration tool.
– Up to 2000 events can be stored and recalled according to various criteria.
– Automatic daylight saving time switchover.
– Integration to Siemens Danger Management System.

Functional elements

Operating unit
The following are located on the operating unit:
– CPU module and electronic components for operating unit
– Ethernet connection
– Plug-ins for RS232, RS485 modules and networking modules (SAFEDLINK)
– Space for 'Kaba' or 'Nordic' key switch
– Space for event printer

Periphery board
The following are located on the peripheral board:
– Connection terminals for FDnet loops, remote transmission (alarm, fault), horn out-
puts, programmable control inputs/outputs, monitored alarm and fault output, de-
grade supply, power supply
– 2 plug-ins for loop extension (FDnet)

Card cage (5 slots)


There is a card cage on the rear housing panel for use of max. 5 line cards (FDnet, col-
lective, MS9i) and/or I/O cards.

Power supply unit 150 W, emergency power supply


Provides the hardware with the necessary power and charges the batteries
– The batteries supply emergency power in case of power failure

4
Building Technologies
CPS Fire Safety
Housing
A pivoting mounting panel can be installed on the housing backplane to allow installa-
tion of:
– 1 fire brigade periphery module
– 2 sounder modules (can also be mounted onto the U-rail TS35)

Configuration
The engineering tool (SintesoWorks) permits the system to be adapted to specific cus-
tomers' requirements.

Application ranges

The FC2060 is ideally suited to large applications, e.g. for industrial plants, office com-
plexes, chemicals, manufacturing etc. During modernization, it is also suited to a grad-
ual seamless transition from older systems to Sinteso.

Operation

Each control panel has an integrated operating panel. The control panel can also be
operated from a separate FT2040 operator terminal or any other control panel.

 For details and further information, please refer to product data sheet 009386.

5
Building Technologies
CPS Fire Safety
Overview of FC2060-AA fire control panel (modular)

Control panel Housing extensions


FC2060-AA FH2004-A1 FH2005-A1
Housing (Large) Housing (Large extension) Housing (Large)
430 x 398 x 260 mm 430 x 796 x 260 mm

Space for larger batteries


2 x FA2007-A1 (45 Ah) or
2 x FA2008-A1 (65 Ah) or
2 x FA2009-A1 (100 Ah)

4 loops
with power supply (150 W) Space for larger batteries
Max. battery capacity 45 Ah – 4 x FA2006-A1 (26 Ah) or
with card cage (5 slots) 4 x FA2007-A1 (45 Ah) or
for extra line cards like 2 x FA2008-A1 (65 Ah) or
FDnet, collective, MS9i 2 x FA2009-A1 (100 Ah)
or I/O card

Printer Operating add-ons External printer


FTO2001-A1 FCM2006-A1 FCM2007-A1 DL3750+
Event printer 48 display groups 96 display groups Matrix printer (external)
can be fitted with one red + one yellow LED with one red + one yellow LED RS232 interface

RS232 module must be for retrofitting for retrofitting RS232 module must be
ordered separately ordered separately

6
Building Technologies
CPS Fire Safety
FC2060 configuration in housing (Large)

25

26
12
2 28 1
31

9 5

28

30
15
14
13
10 3
18 16
17 18
27
23
24
8
4

20

7
21 19
29
9
11
22

Basic equipment Designation Notes


1 Rear (Large) FHA2005-A1
2 Periphery board (4 loops) FCI2004-A1 Items 1-6 –> basic equipment
3 Power supply (SV 24V-150 W) V24230-Z6-A4
4 Mains terminals on TS35 DIN rail – Space for socket, relay modules etc.
5 Operating unit FCM200x-xx System operation and CPU at the same time, incl. cover cap
6 Card cage (5 slots) FCA2008-A1 For FDnet, collective, MS9i line cards and I/O cards
7 Space for batteries – 2 x 12 V / 7… 45 Ah
Expansion
8 Relay module Z3B171 Relay for fire controls
9 Event printer FTO2001-A1 For event logging
Key switch (Kaba) FTO2005-C1
10 For operating access rights
Key switch (Nordic) FTO2006-B1
11 Mounting plate FHA2007-A1 E.g. for fire brigade periphery module
12 Loop extension (FDnet) FCI2003-A1 For loop extension of 2 to 4, number of addresses remains the same
13 Line card (FDnet) FCL2001-A1 For extra FDnet lines, 4 lines total 252 addresses per card
14 Line card (collective) FCL2002-A1 For 8 collective lines MS7/9/24, DS11, Synova 600, SIGMACON
15 Line card (MS9i) FCL2003-A1 For 2 addressable MS9i lines (max. 100 addresses)
16 RS485 module (isolated) FCA2002-A1 For peripheral devices with RS485 port
17 RS232 module (isolated) FCA2001-A1 For participant with RS232 port
18 Network module (SAFEDLINK) FN2001-A1 For networking various stations

7
Building Technologies
CPS Fire Safety
19 Repeater (SAFEDLINK) FN2002-A1 For the extension of the system bus FCnet, max. 1 between 2 stations
(mounting direct onto plane surface, onto a U-rail TS35 or in housings
FDCH291/292)
20 Sounder module FCA2005-A1 For split-up of 1 to 4 conventional horn lines
Battery (12 V, 7 Ah, VDS) FA2003-A1
Battery (12 V, 12 Ah, VDS) FA2004-A1
21 For emergency power supply
Battery (12 V, 26 Ah, VDS) FA2006-A1
Battery (12 V, 45 Ah, VDS) FA2007-A1
22 Fire brigade periphery module FCI2001-D1 For Germany (FBF, FSD, ÜE, FSE, ÖA, KL)
rd
23 Battery kit (9 Volt) FCA2010-F1 For 9 Volt battery (3 voltage source for France)
24 Lithium battery 9 V / 1 Ah – For FCA2010-F1
rd
25 19" mounting kit FHA2016-A1 For the installation in 3 party housings
26 FM blind 2 HU FHA2015-A1 For the recess mounting of housings
License key L1 or FCA2012-A1 For SintesoView (Visualizer)
27
License key (L2) FCA2013-A1 For Management System (also includes SintesoView )
28 Cable kit (communication) FCA2014-A1 For flexible cable connections to the modules on the operating unit
29 Power supply kit (150 W, B) FP2005-A1 For additional power supply
30 I/O card FCI2008-A1 12 programmable inputs/outputs
31 Relay module Z3B171 Space for U-rail TS35 L=70 mm (on site) for max. 4 relay modules

Technical data

Mains voltage AC 230 V


Power supply 150 W
Operating voltage DC 21 … 28.6 V
Operating current max. 5 A
Battery capacity 2 x 12 V, 45 Ah
Battery monitoring / mains monitoring yes / yes
Connectable detector series Sinteso, MS7/9/24, MS9i, DS11,
Synova 600, SIGMACON
Number of FDnet addresses max. 1512
Number of lines
Integrated FDnet or stub lines 4/8
– with loop extension 8 / 16
FDnet (4 per line card) max. 20
Collective (8 per line card) max. 40
MS9i (2 per line card) max. 10
Integrated inputs/outputs
– Relay output
– Remote transmission alarm 1
– Remote transmission fault 1
– Monitored outputs
– Alarm 1
– Fault 1
– Horn 2
– Free programmable inputs/outputs 12
Free programmable inputs/outputs with max. 5 extra 60 (12 per card)
I/O cards
Operating unit integrated
Plug-in position for RS232, RS485 serial ports 2
Plug-in position for network modules 2
Plug-in position for loop extension 2
Slots for line cards (on fitted card cage) max. 5
Mounting spaces for cable kit (communication) 2
Sounder module max. 2
Ethernet connection RJ45 1
Operating temperature -8… +42 °C
Storage temperature -20 … + 60 °C
Humidity (no condensation permitted) ≤95 % rel.
Dimensions (W x H x D)
– Without cover cap 430 x 796 x 260 mm
– With cover cap 430 x 796 x 288 mm
Color
– Housing grey, ~RAL 7035
– Cover cap white, ~RAL 9010
Protection category (IEC 60529) IP30
Standards EN 54-2, EN 54-4
Approvals
– VdS / LPCB G208202 / pending

8
Building Technologies
CPS Fire Safety
Details for ordering

Type Art. no. Designation Weight


FC2060-AA A5Q00023048 Fire control panel (modular) 20.800 kg
Extensions Z3B171 BPZ:4843830001 Relay module 250 V AC / 10 A (1 relay) 0.042 kg
FTO2001-A1 A5Q00010126 Event printer 0.250 kg
– A5Q00017619 Replacement printer rolls (10 rolls) 0.090 kg
FTO2005-C1 A5Q00010113 Key switch (Kaba) 0.013 kg
FTO2006-B1 A5Q00010129 Key switch (Nordic) 0.050 kg
FHA2007-A1 A5Q00010151 Mounting plate 0.800 kg
FCI2003-A1 A5Q00010136 Loop extension (FDnet) 0.064 kg
FCL2001-A1 A5Q00009875 Line card (FDnet) 0.120 kg
FCL2002-A1 A5Q00010502 Line card (collective) 0.120 kg
FCL2003-A1 A5Q00010044 Line card (MS9i) 0.120 kg
FCI2008-A1 S54400-A6-A1 I/O card (programmable) 0.120 kg
FCA2002-A1 A5Q00009923 RS485 module (isolated) 0.067 kg
FCA2001-A1 A5Q00005327 RS232 module (isolated) 0.068 kg
FN2001-A1 A5Q00012851 Network module (SAFEDLINK) 0.077 kg
FN2002-A1 S24236-B2502-A1 Repeater (SAFEDLINK) 0.154 kg
FCA2005-A1 A5Q00014866 Sounder module 0.140 kg
FCA2014-A1 A5Q00023027 Cable kit (communication) 0.224 kg
FCI2001-D1 A5Q00013100 Fire brigade periphery module 0.482 kg
FH2004-A1 A5Q00018778 Housing (Large extension) 11.820 kg
FH2005-A1 A5Q00019543 Housing (Large) 15.400 kg
FCM2006-A1 A5Q00021771 Operating add-on (2xLED ind.) 2.600 kg
FCM2007-A1 A5Q00021772 Operating add-on (4xLED ind.) 2.800 kg
FCA2010-F1 A5Q00012569 Battery kit (9 Volt) (France only) 0.100 kg
– A5Q00004142 Lithium battery 9 V / 1 Ah, for FCA2010-F1 0.037 kg
FHA2016-A1 A5Q00020179 19" mounting kit 3.000 kg
FHA2015-A1 A5Q00024621 FM blind 2 HU 5.100 kg
FN2006-A1 S54400-A61-A1 Fiber network module (SM) 0.770 kg
FN2007-A1 S54400-A62-A1 Fiber network module (MM) 0.770 kg
Auxiliary power supply FP2003-A1 A5Q00016005 Power supply kit (70 W) 0.650 kg
FP2004-A1 A5Q00020825 Power supply kit (150 W, A) for installation 1.366 kg
into empty housing
FP2005-A1 A5Q00018779 Power supply kit (150 W, B) for cascading 1.100 kg
Networks (backbone) FN2008-A1 S54400-F94-A1 Ethernet-Switch 0,800 kg
FN2009-A1 S54400-F95-A1 Security module 0,800 kg
FHA2029-A1 S54400-B79-A1 Mounting kit for Ethernet switch (Comfort) 0,500 kg
FHA2030-A1 S54400-B81-A1 Mounting kit for Ethernet switch (Large 0,500 kg
Ext.)
Batteries FA2003-A1 A5Q00019353 Battery (12 V, 7 Ah, VDS) 2.450 kg
FA2004-A1 A5Q00019354 Battery (12 V, 12 Ah, VDS) 3.930 kg
FA2005-A1 A5Q00019677 Battery (12 V, 17 Ah, VDS) 5.640 kg
FA2006-A1 A5Q00019356 Battery (12 V, 26 Ah, VDS) 7.572 kg
FA2007-A1 A5Q00022897 Battery (12 V, 45 Ah, VDS) 15.320 kg
FA2008-A1 A5Q00019357 Battery (12 V, 65 Ah, VDS) 22.000 kg
FA2009-A1 A5Q00023101 Battery (12 V, 100 Ah, VDS) 32.360 kg
Software license FCA2012-A1 A5Q00018856 License key (L1) 0.010 kg
FCA2013-A1 A5Q00018857 License key (L2) 0.010 kg
External printer DL3750+ A5Q00023962 Matrix printer (external) 7.300 kg
Spare part – A5Q00023963 Black typewriter ribbon for printer DL3750+ 0.078 kg

9
Building Technologies
CPS Fire Safety
Siemens Switzerland Ltd
Infrastructure & Cities Sector
Building Technologies Division
International Headquarters © 2012 Copyright by
CPS Fire Safety Siemens Switzerland Ltd
Gubelstrasse 22
CH-6301 Zug Data and design subject to change without notice.
Tel. +41 41 724 24 24 Supply subject to availability.
www.siemens.com/buildingtechnologies
Document no.. A6V10087844_h_en_-- Manual FS20
Edition 04.2012 Section 1

You might also like