NICE900
User Manual
No.16, Youxiang Road, Yuexi Town, Wuzhong District, Suzhou 215104, P.R.China
Tel: +86-512-6879 5207
Fax: +86-512-6285 6720
Data code:19010269
NICE900 User Manual Preface
Preface
Thank you for purchasing the NICE900 series integrated door machine controller.
The NICE900 series integrated door machine controller (shorted as "the NICE900" or "the
controller" hereinafter) is a variable frequency controller specialized for driving the door
machine system such as elevator door, cold storage door, and subway door.
It integrates door open/close logic control and motor drive, and implements control on the
entire door system with door open/close commands from the external system. The NICE900
can drive the AC asynchronous motor and permanent synchronous motor (PMSM), and
supports two control modes, speed control and distance control. Applicable to various
applications, it can meet drive and control requirements of most door systems.
This manual describes correct use of the NICE900, including product features, safety
information and precautions, installation, parameter setting, commissioning, and
troubleshooting. Read and understand the manual before using the product, and keep it
carefully for reference to future maintenance.
Notes
•• The drawings in the manual are sometimes shown without cover or protective guard. Remember
to install the cover or protective guard as specified first, and then perform operations in
accordance with the instructions.
•• The drawings in the manual are shown for description only and may not match the product that
you have purchased.
•• The instructions are subject to change due to product upgrade, specification modification, as
well as the efforts to increase the accuracy and convenience of the manual.
•• Contact our regional agent or customer service center if the manual delivered is lost or
damaged.
•• Contact our customer service center if you have problems during the use.
•• Email: [email protected]
-1-
Contents
Preface.......................................................................................................................1
Chapter 1 Safety Information and Precautions..........................................................6
1.1 Safety Information................................................................................................................ 6
1.2 Precautions.......................................................................................................................... 9
In this manual, the notices are graded based on the degree of danger:
•• DANGER indicates that severe personal injury or even death may result due to improper
operation.
•• CAUTION indicates that personal injury or equipment damage may result due to improper
operation.
Read the following safety notices carefully so that you understand how to install, commission,
operate and maintain the equipment. Inovance assumes no liability or responsibility for any
injury or loss caused by improper operation of the equipment described in the manual.
DANGER
•• Do not install the equipment if you find the controller damaged upon unpacking.
•• Do not install the equipment if the packing list does not conform to the product you receive.
CAUTION
•• Handle the equipment with care during transportation. Otherwise, the equipment may be
damaged.
•• Do not touch the components with your hands. Failure to comply will result in static electricity
damage.
■■ During Installation
DANGER
•• Mount the controller on incombustible surface such as metal. Keep it far away from flammable
materials. Failure to comply may result in a fire.
•• Do not loosen the fixed screws of the components, especially the screws with red mark.
CAUTION
•• Do not drop wire end or screw into the controller. Otherwise, the controller may be damaged.
•• Install the controller in places free of vibration and direct sunlight.
-6-
NICE900 User Manual Chapter 1 Safety Information and Precautions
■■ At Wiring
DANGER
•• Wiring must be performed only by qualified personnel under instructions described in this
manual. Failure to comply may result in unexpected accidents.
•• A circuit breaker must be used to isolate the power supply and the controller. Failure to comply
may result in a fire.
•• Tie the controller to ground properly according to the standard. Failure to comply may result in
electric shock.
DANGER
•• Never connect the power cables to the output terminals (U, V, W) of the controller. Pay attention
to the marks of the wiring terminals and ensure correct wiring. Failure to comply will result in
damage to the controller.
•• Ensure that the cabling satisfies the EMC requirements and the local codes. Use wire sizes
recommended in the manual. Failure to comply may result in accidents.
•• Use the shielded cable for the encoder, and ensure that the shield is reliably grounded at one
end.
•• Use a twisted cable with twisted distance of 20−30 mm as the communication cable, and ensure
that the shield is reliably grounded.
■■ Before Power-On
DANGER
DANGER
-7-
Chapter 1 Safety Information and Precautions NICE900 User Manual
■■ After Power-On
DANGER
•• Do not open the cover of the controller after power-on. Failure to comply may result in electric
shock.
•• Do not touch any input or output terminal of the controller with hands. Failure to comply may
result in electric shock.
DANGER
•• Do not touch the rotating part of the motor during the motor auto-tuning or running. Failure to
comply may result in personal injury.
•• Do not change the factory parameters. Otherwise, the equipment may be damaged.
■■ During Running
DANGER
•• Do not touch the fan or the discharging resistor to check the temperature. Otherwise, you may
get burnt.
•• Signal detection must be performed only by qualified personnel during operation. Failure to
comply will result in personal injury or damage to the controller.
CAUTION
•• Avoid objects falling into the controller when it is running. Failure to comply will result in damage
to the controller.
•• Do not start/stop the controller by opening or closing the contactor. Failure to comply will result
in damage to the controller.
■■ During Maintenance
DANGER
•• Do not repair or maintain the controller at power-on. Failure to comply will result in electric
shock.
•• Repair or maintenance of the controller must be performed only by qualified personnel.
Otherwise, personal injury or equipment damage may result.
•• Set the parameters again after the controller is replaced. All the pluggable components must
be plugged or removed only after power-off.
-8-
NICE900 User Manual Chapter 1 Safety Information and Precautions
1.2 Precautions
1. Motor Insulation Test
Perform an insulation test on the motor under the following conditions:
-- Before the motor is used for the first time
-- When the motor is reused after being stored for a long time
-- During periodic inspection
This is to prevent the poor insulation of motor windings from damaging the controller.
The motor must be disconnected from the controller during the insulation test. A 500-volt
megameter is recommended for this test, and the insulation resistance must not be less
than 5 MΩ.
2. Motor Heat and Noise
The output of the controller is pulse width modulation (PWM) wave with certain harmonic
wave, and therefore, the motor temperature rise, noise, and vibration are slightly greater
than those at running with the mains frequency.
3. Voltage-sensitive device or capacitor on the output side of the controller
The controller outputs PWM waves, and therefore, do not install the capacitor for improving
power factor or lightning protection voltage-sensitive resistor on the output side of the
controller. Otherwise, the controller may suffer transient overcurrent or even be damaged.
4. Use outside the rated voltage
The controller must not be used outside the allowable voltage range specified in this
manual. Otherwise, components inside the controller may be damaged. If required, use
a corresponding voltage step-up or step-down device to match the power voltage to the
rated voltage range for the controller.
5. Surge Suppressor
The controller has a built-in varistor for suppressing the surge voltage generated when
the inductive loads (electromagnetic contactor, electromagnetic relay, solenoid valve,
electromagnetic coil and electromagnetic brake) around the controller are switched on or
off. If the inductive loads generate very high surge voltage, use a surge suppressor for the
inductive load or use a surge suppressor together with a diode.
Note
Do not connect the surge suppressor to the output side of the controller.
-9-
Chapter 1 Safety Information and Precautions NICE900 User Manual
7. Disposal
The electrolytic capacitors in the main circuit and PCB board may explode when they are
burnt. Poisonous gas is generated when the plastic parts are burnt. Treat them as ordinary
industrial waste.
8. Adaptable Motor
-- The standard adaptable motor is an adaptable four-pole squirrelcage asynchronous
induction motor and AC PMSM. Select the proper controller model according to the motor
ratings.
-- To reach better control result, perform motor auto-tuning based on actual conditions. For a
PMSM, motor auto-tuning is mandatory.
-- The controller might alarm or be damaged when a short circuit exists on cables or
inside the motor. Therefore, perform the insulation short circuit test when the motor and
cables are newly installed or during routine maintenance. During the test, disconnect the
controller from the tested parts
- 10 -
2
Product Information
Chapter 2 Product Information NICE900 User Manual
NICE D A S 0P2
Nameplate
position Nameplate
2.2 Structure
Figure 2-2 Structure of the NICE900
Fan Reserved
- 12 -
NICE900 User Manual Chapter 2 Product Information
- 13 -
Chapter 2 Product Information NICE900 User Manual
Item Specifications
Indoors
Installation
Free from direct sunlight, dust, corrosive gas, combustible gas, oil
location
mist, vapor, drip and salt
Lower than 1000 m
Altitude
Deratedif the altitude is above 1000 m
Ambient -10°C to +40°C
temperature Derated if ambient temperature is within 45–50°C
Humidity Less than 95% RH, non-condensing
Vibration < 5.9 m/s2 (0.6 g)
Storage
Environment -20°C to +60°C
temperature
Natural cooling for 0.2 kW
Cooling method
Forced air cooling for 0.4 kW and 0.75 kW
Ingress
IP20
protection
Storage
Indoors, clean and dry
location
Packed in standard box and transported by coach, train, aircraft
Transportation
or ship.
Vibration during
15 m/s2 (1.5 g) when SIN vibration is 9–200 Hz
transportation
- 14 -
3
Mechanical and Electrical Installation
Chapter 3 Mechanical and Electrical Installation NICE900 User Manual
4-φ5
129
147
66
204.7
213.7 Unit: mm
≥ 100
≥ 50 ≥ 50
≥ 100
Cold air
- 16 -
NICE900 User Manual Chapter 3 Mechanical and Electrical Installation
b) Vertical installation
Figure 3-4 Vertical installation diagram
- 17 -
Chapter 3 Mechanical and Electrical Installation NICE900 User Manual
UVW
LN P PB
Ground NICE900
In the applications with large inertia such as the cold storage door, a regen. resistor is required.
Select a proper one according to the recommended models listed in the following table.
- 18 -
NICE900 User Manual Chapter 3 Mechanical and Electrical Installation
Controller Model Power of Regen. Resistor (W) Resistance of Regen. Resistor (Ω)
NICE-D-A-S0P2 80 W ≥ 250 Ω
NICE-D-A-SOP4 80 W ≥ 200 Ω
NICE-D-A-SOP7 80 W ≥ 150 Ω
Function
Name Type Mark Remarks
Description
1. TA-TB: normally closed (NC)
TA-TC: normally open (NO)
TA1/TB1/TC1 Contact capacity:
Door state Relay output
TA2/TB2/TC2 Relay output 250 ACV, 3A; 30 VDC, 1 A
output terminal and grounding
TA3/TB3/TC3 2. Insulation voltage class
between contact and control
circuit: 2.5 kVAC
- 19 -
Chapter 3 Mechanical and Electrical Installation NICE900 User Manual
Function
Name Type Mark Remarks
Description
Used as the non-contact
switch or power supply for the
24 VDC power
+24V encoder.
supply
Internal 24 V Maximum output current: 200
power supply mA
Isolated with the internal 24 V
24 V power
COM power common terminal of the
Encoder and common
controller
control signal
input terminal PGA Encoder phase A
Open-collector output or push-
Encoder input PGB Encoder phase B
pull output
PGZ Encoder phase Z
Optocoupler isolation, low level
active
Digital input DI1 to DI8 Digital signal input
Input voltage range: 0–30 VDC
Input impedance: 3.3 kΩ
External 24 V
MP24 External switch-mode power
External 24 V power supply
supply for communication and
power supply External power
MCOM analog terminals
common
CANbus
CAN+ differential signal
positive CANbus communication
interface, twisted shielded
CANbus cable recommended
Communication CAN- differential signal
terminal Communication negative
(reserved) Modbus
485+ differential signal Standard
positive Modbuscommunication
Modbus interface, twisted shielded
485- differential signal cable recommended
negative
CZA1 Load cell analog
Analog input Input voltage range: 0–10 VDC
GND signal input
Software
Software burning
Reserved burning RJ45 -
interface
interface
Check the peripheral wiring before power-on to ensure device and personal safety:
1. The wiring is performed according to the instructions.
2. All switches act reliably.
3. Check the inter-phase resistance of the main circuit to ensure that there is no short circuit
to ground.
- 20 -
NICE900 User Manual Chapter 3 Mechanical and Electrical Installation
- 21 -
Chapter 3 Mechanical and Electrical Installation NICE900 User Manual
- 22 -
4
Operation and Trial Running
Chapter 4 Operation and Trial Running NICE900 User Manual
Function indicator
D1 D2 D3 D4
Data display
UP key
Programming key PRG ENTER Confirm key
STOP
Shift key Stop/Reset key
RES
Down key
1. Indicator Descriptions
Table 4-1 Indicator descriptions
Meaning of ON at Stop
Indicator Meaning of ON During Running
Speed Control Distance Control
D1 DI1 signal active DI1 signal active External door close command
D2 DI2 signal active Phase A and B signal correct During door close
D3 DI3 signal active Phase Z signal active During door open
D4 DI4 signal active DI4 signal active External door open command
Enter the menu interfaces level by level, and confirm the parameter
ENTER Confirm
setting.
STOP Stop the running in the running state and reset the operation in the
Stop/Reset
RES fault state.
- 24 -
NICE900 User Manual Chapter 4 Operation and Trial Running
OPEN Door open Open the door in the operation panel operation mode.
CLOSE Door close Close the door in the operation panel operation mode.
15.00 PRG
F0 ENTER
PRG
Level-II menu
(Select the
function code)
PRG F003 ENTER F004 ENTER
Next function
ENTER code
Level-III menu
(Set the value of
PRG
Not to save
24.00 To save
the function code) the setting the setting
You can return to Level II from Level III by pressing PRG or ENTER .
•• After you press ENTER , the system saves parameter setting first, and then goes back to
Level II and shifts to the next function code.
•• After you press PRG , the system does not save parameter setting, but directly returns to
Level II and remains at the current function code.
Here is an example of changing the value of F0-04 to 15.00 Hz.
- 25 -
Chapter 4 Operation and Trial Running NICE900 User Manual
PRG
F000 F004 ENTER F005
PRG
00.00
ENTER
15.00 To save the
setting
In Level III menu, if the parameter has no blinking digit, it means that the parameter cannot be
modified. This may be because:
•• Such a function code is only readable, such as actually detected parameter and running
record parameter.
•• Such a function code cannot be modified in the running state and can only be changed at
stop.
PRG
FA00 FA02 FA03
ENTER
PRG
00.00 ENTER
- 26 -
NICE900 User Manual Chapter 4 Operation and Trial Running
In the stop/running state without fault, you can view the parameters circularly by pressing .
The parameters to be displayed are set in by setting FA-00 and FA-01.
Figure 4-5 Shift between parameters displayed in the running/stop state
Frequency reference
Output torque
Output current
Frequency reference
Frequency reference
Running frequency
PRG 0000
ENTER
1234
- 27 -
Chapter 4 Operation and Trial Running NICE900 User Manual
Function
Value Description
Code
Operation panel control
It is mainly used in motor auto-tuning. The door machine runs at the
frequency set in F0-04.
0
(Default) You can control door open or close by pressing OPEN or CLOSE , and stop the
STOP
door machine by pressing RES
on the operation panel.
The demonstration time interval and times are set in group F7 parameters.
- 28 -
NICE900 User Manual Chapter 4 Operation and Trial Running
- 29 -
Chapter 4 Operation and Trial Running NICE900 User Manual
End
Press ENTER. After "TUNE" is displayed,
press "OPEN" to start motor auto-tuning.
3. During with-load auto-tuning, ensure that the door is fully closed. Press OPEN to make the
motor slowly open the door at 25% of the rated speed and press CLOSE to make the motor
close the door after the door opens to a certain distance.
After three times of such operations, the controller calculates all parameters and completes
with-load auto-tuning.
4. During with-load auto-tuning, if the motor does not run or the running direction is
inconsistent with the actual door open/close command, it indicates that motor wiring is
- 30 -
NICE900 User Manual Chapter 4 Operation and Trial Running
incorrect. You need to replace any two of UVW phases and perform motor auto-tuning
again.
5. The identified encoder zero position angle is viewed or modified in F1-14. This parameter
must not be modified after motor auto-tuning; otherwise, the controller may not run
properly.
This parameter obtained through with-load auto-tuning is not so accurate as that obtained
through no-load auto-tuning. Perform no-load auto-tuning if conditions are allowed.
6. If Er19 is reported during identification of the encoder zero position angle, check whether
encoder wiring is correct.
- 31 -
Chapter 4 Operation and Trial Running NICE900 User Manual
Single-phase
220 VAC L
power supply Door motor
N
U
V M
NICE900 W
Main circuit
Control circuit
- 32 -
NICE900 User Manual Chapter 4 Operation and Trial Running
Frequency
F3-03
F3-00
F3-05
Time
Door open command ON OFF
Door open OFF ON
slow-down signal
Door open limit signal OFF ON
When the door open command is active, the door machine accelerates to the speed set in
F3-00. After the low speed door open time reaches the setting of F3-02, the door machine
accelerates to normal speed set in F3-03.
After the door open slow-down signal is active, the door machine decelerates to the speed
set in F3-05. After the door open limit signal is active, the door machine enters the door open
holding state with the holding torque set in F3-08.
Figure 4-12 Door close running curve in speed control
Frequency
F4-03
F4-09
F4-00
F4-05
F4-07
Time
Door close command ON OFF
Door close OFF ON
slow-down signal
Door close limit signal OFF ON
When the door close command is active, the door machine accelerates to the speed set in
F4-00. When the low speed door close time reaches the setting of F4-02, the door machine
accelerates to normal speed set in F4-03.
When the door close slow-down signal is active, the door machine decelerates to the speed
set in F4-05. When the door close limit signal is active, the door machine enters the door close
holding state:
•• Holding speed: F4-07
•• Holding time: F4-08
•• Holding torque: F4-12
•• Door vane retraction speed and time: F4-09 and F4-10
- 33 -
Chapter 4 Operation and Trial Running NICE900 User Manual
Single-phase
220 VAC L
power supply Door motor
N U
V M
NICE900 W
Main circuit
Function +24V
Encoder
code setting PGA
PGB
Input common PGZ
COM COM Shield
grounded
DI1 Input
TA1 common
P24 BM Output common
DI2
TC1 B1 Door open output
DI3 TB1 Door close
F9-09 = 2 limit X5 B2 Door close output
DI4 TA2
Door open TC2 Car top
F9-05 = 1 input signal DI5 TB2 Fault alarm board
F9-10 = 5
F9-06 = 2 Door close DI6 MCTC-CTB
input signal TA3
DI7 TC3
TB3 Door open
F9-11 = 1 X3
DI8 limit
Control circuit
- 34 -
NICE900 User Manual Chapter 4 Operation and Trial Running
4) The shield of the encoder cable is grounded on the end connected to the controller (only
one end is grounded to prevent interference).
3. Related parameter setting
F0-02 = 2 (Door machine manual control) The controller closes the door at the
frequency set in F6-01
Set door open/close limit according to The controller opens the door at door
system configuration (ship if not required) close limit and closes the door again at
door open limit
Set F6-00 = 1 to enable door width auto- After door close limit, the controller stores
tuning. the data obtained in F6-02 and F6-03.
Press "OPEN" or "CLOSE" to start door Door width = F6-02 + F6-03 x 10000
width auto-tuning.
End
- 35 -
Chapter 4 Operation and Trial Running NICE900 User Manual
Frequency
F3-03
F3-00
F3-05
Time
Door open command ON OFF
F6-04 x door width
Door open OFF ON
slow-down pulse
F6-05 x door width
OFF ON
Door open limit pulse F6-06 x door width
When the door open command is active, the door machine accelerates to the speed set in F3-
00.
When the door open position reaches (F6-04 x door width), the door machine accelerates to
the speed set in F3-03.
When the door open position reaches (F6-05 x door width), the door machine enters the
deceleration and creeping state with the speed set in F3-05 and deceleration time set in F3-
06.
When the door open position reaches (F6-06 x door width), the door machine continues low
speed creeping, and then enters the door open holding state, with the holding torque set in F3-
08. The door position is reset to 100%.
After the door open command is cancelled, the torque holding state ends.
Figure 4-16 Door close running curve in distance control mode
Frequency
F4-03
F4-09
F4-00
F4-05
F4-07
Time
Door close command ON OFF
F6-07 x door width
Door close ON
OFF
slow-down pulse
F6-08 x door width
Door close limit pulse OFF ON
F6-09 x door width
When the door close command is active, the door machine accelerates to the speed set in F4-
00.
When the door close position reaches (F6-07 x door width), the door machine accelerates to
the speed set in F4-03.
When the door close position reaches (F6-08 x door width), the door machine decelerates to
the speed set in F4-05.
- 36 -
NICE900 User Manual Chapter 4 Operation and Trial Running
When the door close position reaches (F6-09 x door width), the door machine decelerates
again to the speed set in F4-07. It is recommended that F6-09 ≥ 96.0%; reduce F6-09 if there
is pulse loss during door open/close.
Set the threshold for retracting the door vane in F6-20. After the door vane is retracted and
door limit is reached, the door machine enters the torque holding state, with the speed set in
F4-07 and holding torque set in F4-12. The door position is reset to 0.
After the door close command is cancelled, the torque holding state ends.
F3-03
F4-03
F3-00
F4-00
F3-05
0
Time
Door close command
After the time reaches the deceleration time in F5-00, the controller re-opens the door at low
speed, and enters normal speed running state after the time set in F3-02.
After the door open slow-down signal is active, the controller enters the low speed running
state and opens the door to the open limit position, and then outputs the door open limit signal.
- 37 -
Chapter 4 Operation and Trial Running NICE900 User Manual
Function Parameter
Setting Description
Code Name
F4-14 = 2
Upon door close hindered, the controller stops
immediately, outputs the door close hindered signal,
and does not respond to the door close command
within 10s. However, if the controller receives the door
0: Reserved close or RUN (door open/close) cancellation command
within the time, it executes door close immediately
1: Output door
rather than restricted by the 10s time counting.
close hindered
Working mode F4-14 = 3
signal
F4-14 upon door The controller re-opens the door upon door close
2: Immediate
close hindered hindered, and does not respond to the external door
stop
open/close commands during door re-open.
3: Door re-
Door close hindered occurs on one of the following
open
conditions during door close:
•• The light curtain/safety edge signal is active.
•• The output torque is larger than the door close
hindered torque.
•• The door close time exceeds the value of F5-02.
Door close It is used to set the filter time when door close is
F4-15 hindered 0–9999 ms hindered. If it is set to 0, door close hindered is not
judging time detected.
F4-20 T2
Low speed 0.00 Hz to F1-
F4-18 at door close 04 Curve 1
hindered 2.00 Hz F4-19 T1
V2 V1 Running
F4-18 F4-17 frequency (Hz)
Normal speed 0.00–150.0%
F4-19
torque 100.0% F4-17 to F4-20 are used to judge door close hindered.
Set them according to the requirement:
V1 (F4-17) ≥ V2 (F4-18), T1 (F4-19) ≤ T2 (F4-20)
Low speed 0.00–150.0% The torque threshold for judging door close hindered
F4-20
torque 100.0% is curve 1 shown in the figure. The shadow part shows
that door close hindered occurs.
It is used to set the time for the system to decelerate
Abnormality from the door close speed to 0 when door close is
F5-00 deceleration 0.1–5.0s hindered. Set this parameter to the minimum value
time as possible when ensuring that over-current does not
occur during deceleration.
- 38 -
NICE900 User Manual Chapter 4 Operation and Trial Running
Function Parameter
Setting Description
Code Name
It is used to limit the door close time. If the controller
does not receive the door close limit signal within the
Door close time, it determines that door close is hindered, and
F5-02 0–9999s
time limit performs door re-open or zero speed holding based on
the setting of F4-14.
This parameter is invalid when it is set to 0.
- 39 -
Chapter 4 Operation and Trial Running NICE900 User Manual
- 40 -
5
Function Code Table
Chapter 5 Function Code Table NICE900 User Manual
After pressing PRG key and then or key, the Level-I menu is displayed,
corresponding to the following function code groups:
- 42 -
NICE900 User Manual Chapter 5 Function Code Table
Function Min.
Parameter Name Setting Range Default Property
Code Unit
Group F0: Basic Parameters
0: Sensorless vector control
(SVC)
F0-00 Control mode 1 1 ★
1: Closed-loop vector control
(CLVC)
Door open/close mode 0: Speed control
F0-01 1 1 ★
selection 1: Distance control
0: Operation panel control
1: Door machine terminal
control
F0-02 Command source selection 2: Door machine manual 0 1 ★
control
3: Door machine auto
demonstration
Running frequency under 0.01
F0-04 0.00 to F1-04 5.00 Hz ☆
operation panel control Hz
F0-05 Input signal quick setting 0–2 1 1 ★
0.01
F0-06 Speed at low speed running 0.00 to F1-04 4.00 Hz ☆
Hz
F0-07 Carrier frequency 2.0–16.0 kHz 8.0 kHz 0.1 kHz ☆
Group F1: Motor Parameters
0: Asynchronous motor
F1-00 Motor type 8.0 kHz 0.1 kHz ★
1: PMSM
F1-01 Rated motor power 0–750 W 1 1 ★
Model
F1-02 Rated motor voltage 0–250 V 1V ★
dependent
F1-03 Rated motor current 0.001–9.900 A 100 V 1V ★
Model
F1-04 Rated motor frequency 1.00–99.00 Hz 0.001 A ★
dependent
0.01
F1-05 Rated motor speed 0–9999 RPM 24.00 Hz ★
Hz
- 43 -
Chapter 5 Function Code Table NICE900 User Manual
Function Min.
Parameter Name Setting Range Default Property
Code Unit
Stator phase resistance of Model
F1-06 0.00–99.99 Ω 0.01 Ω ★
PMSM dependent
Rotor phase resistance of Model
F1-07 0.00–99.99 Ω 0.01 Ω ★
asynchronous motor dependent
Leakage inductance of Model 0.01
F1-08 0.0–99.99 mH ★
asynchronous motor dependent mH
Mutual inductance of Model
F1-09 0–999.9 mH 0.1 mH ★
asynchronous motor dependent
Magnetizing current of Model
F1-10 0.001–9.900 A 0.001 A ★
asynchronous motor dependent
Model
F1-11 Shaft D inductance of PMSM 0.0–999.9 mH 0.1 mH ★
dependent
Model
F1-12 Shaft Q inductance of PMSM 0.0–999.9 mH 0.1 mH ★
dependent
Model
F1-13 Back EMF of PMSM 0–250 1 ★
dependent
Encoder zero position angle Model
F1-14 0.0–359.9° 0.1° ★
of PMSM dependent
Model
F1-15 Real-time angle of PMSM 0.0–359.9° 0.1° ●
dependent
0: No auto-tuning
1: Static auto-tuning for
asynchronous motor
2: Complete auto-tuning for
F1-16 Motor auto-tuning mode asynchronous motor 0 1 ★
3: No-load auto-tuning for
PMSM
4: With-load auto-tuning for
PMSM
Group F2: Performance Control Parameters
Speed loop proportional gain
F2-00 0–100 15 1 ☆
1
F2-01 Speed loop integral time 1 0.01–10.00s 1.00s 0.01s ☆
0.01
F2-02 Switchover frequency 1 0.00 to F2-05 5.00 Hz ☆
Hz
Speed loop proportional gain
F2-03 0–100 15 1 ☆
2
F2-04 Speed loop integral time 2 0.01–10.00s 1.00s 0.01s ☆
F2-05 Switchover frequency 2 F2-02 to F1-04 30 1 ☆
Current loop proportional
F2-06 10–500 120 1 ☆
gain
F2-07 Current loop integral gain 10–500 50 1 ☆
- 44 -
NICE900 User Manual Chapter 5 Function Code Table
Function Min.
Parameter Name Setting Range Default Property
Code Unit
F2-08 Slip compensation coefficient 50%–200% 100% 1% ☆
F2-09 Inertia compensation 0–9999 0 1 ★
F2-10 Torque boost 0.0%–30.0% 8.0% 0.1% ☆
F2-11 Over-excitation gain 0–200 64 1 ☆
1: Based on pulses
F2-12 Initial position judging method 2: Using data of other tested 1 1 ★
PMSM
F2-13 Feedback speed filter level 0–20 0 1 ☆
F2-14 Encoder PPR 1–9999 2048 1 ★
0: Forward direction
F2-15 Encoder direction selection 1 1 ★
1: Reverse direction
Group F3: Door Open Running Curve Parameters
0.01
F3-00 Door open startup low speed 0.00 Hz to F3-03 5.00 Hz ☆
Hz
Door open startup
F3-01 0.1–999.9s 1.0s 0.1s ☆
acceleration time
Low speed running time for
F3-02 door open startup in speed 0.1–999.9s 1.0s 0.1s ☆
control
0.01
F3-03 Door open normal speed 0.00 Hz to F1-04 15.00 Hz ☆
Hz
F3-04 Door open acceleration time 0.1–999.9s 2.0s 0.1s ☆
0.01
F3-05 Door open ending low speed 0.00 Hz to F3-03 3.00Hz ☆
Hz
F3-06 Door open deceleration time 0.1–999.9s 1.5s 0.1s ☆
Torque switchover threshold
F3-07 0.0%–150.0% 50.0% 0.1% ☆
at door open limit
Door open limit holding
F3-08 0.0%–150.0% 50.0% 0.1% ☆
torque
F3-09 Door open hindered torque 0.0%–150.0% 80.0% 0.1% ☆
F3-10 Door open startup torque 0.0% to F3-09 0.0% 0.1% ★
Door open hindered judging
F3-11 0–9999 ms 0ms 1 ms ☆
time
0.01
F3-12 Door open limit low speed 0.00 Hz to F3-03 3 Hz ☆
Hz
0.01
F3-13 Door re-open speed 0.00 Hz to F3-03 0 Hz ☆
Hz
Group F4: Door Close Running Curve Parameters
0.01
F4-00 Door close startup low speed 0.00 Hz to F4-03 4.00 Hz ☆
Hz
- 45 -
Chapter 5 Function Code Table NICE900 User Manual
Function Min.
Parameter Name Setting Range Default Property
Code Unit
Door close startup
F4-01 0.1–999.9s 1.0s 0.1s ☆
acceleration time
Low speed running time for
F4-02 door close startup in speed 0.1–999.9s 1.0s 0.1s ☆
control
0.01
F4-03 Door close normal speed 0.00 Hz to F1-04 12.00 Hz ☆
Hz
F4-04 Door close acceleration time 0.1–999.9s 2.0s 0.1s ☆
0.01
F4-05 Door close ending low speed 0.00 Hz to F4-03 2.00 Hz ☆
Hz
F4-06 Door close deceleration time 0.1–999.9s 1.5s 0.1s ☆
0.01
F4-07 Door close limit low speed 0.00 Hz to F4-03 1.00 Hz ☆
Hz
Low speed running time at
F4-08 0–9999 ms 300 ms 1 ms ☆
door close limit
0.01
F4-09 Door vane retraction speed 0.00 to F4-03 2.00 Hz ☆
Hz
Door vane retraction running
F4-10 0–9999 ms 500 ms 1 ms ☆
time
Torque switchover threshold
F4-11 0.0%–150.0% 50.0% 0.1% ☆
at door close limit
Door close limit holding
F4-12 0.0%–150.0% 30.0% 0.1% ☆
torque
F4-13 Door close hindered torque 0.0%–150.0% 100.0% 0.1 ★
0: Reserved
1: Output door close
Working mode upon door
F4-14 hindered signal 1 1 ★
close hindered
2: Immediate stop
3: Door re-open
Door close hindered judging
F4-15 0–9999 ms 500 ms 1 ms ☆
time
Door close normal speed at 0.01
F4-16 5.00 to F1-04 10.00 Hz ☆
fire emergency Hz
Normal speed at door close 0.01
F4-17 F4-18 to F1-04 12.00 Hz ☆
hindered Hz
Low speed at door close 0.01
F4-18 0.00 Hz to F1-04 2.00 Hz ☆
hindered Hz
F4-19 Normal speed torque 0.00%–150.0% 100.0% 0.1% ☆
F4-20 Low speed torque 0.00%–150.0% 100.0% 0.1% ☆
Group F5: Door Open/Close Auxiliary Parameters
Abnormality deceleration
F5-00 0.1–5.0s 0.3s 0.1 ☆
time
- 46 -
NICE900 User Manual Chapter 5 Function Code Table
Function Min.
Parameter Name Setting Range Default Property
Code Unit
F5-01 Door open time limit 0–999.9s 30.0s 1s ☆
F5-02 Door close time limit 0–999.9s 0s 1s ☆
F5-03 Low speed running time limit 0–999.9s 0s 1s ☆
Delay of external door open
F5-04 0–999.9s 60.0s 1s ☆
command
Delay of external door close
F5-05 0–999.9s 60.0s 1s ☆
command
F5-06 Door open curve 0, 1 1 1 ★
10.0%–50.0% (acceleration/
Start segment time of door deceleration time, start
F5-07 20.0% 0.1% ★
open acceleration S curve segment + rising segment ≤
90%)
10.0%–80.0% (acceleration/
Rising segment time of door deceleration time, start
F5-08 60.0% 0.1% ★
open acceleration S curve segment + rising segment ≤
90%)
10.0%–50.0% (acceleration/
Start segment time of door deceleration time, start
F5-09 20.0% 0.1% ★
open deceleration S curve segment + falling segment ≤
90%)
10.0%–80.0% (acceleration/
Falling segment time of door deceleration time, start
F5-10 60.0% 0.1% ★
open deceleration S curve segment + falling segment ≤
90%)
Start segment time of door
F5-11 0, 1 1 1 ★
close acceleration S curve
10.0%–50.0% (acceleration/
Rising segment time of door deceleration time, start
F5-12 20.0% 0.1% ★
close acceleration S curve segment + rising segment ≤
90%)
10.0%–80.0% (acceleration/
Start segment time of door deceleration time, start
F5-13 60.0% 0.1% ★
close deceleration S curve segment + rising segment ≤
90%)
10.0%–50.0% (acceleration/
Falling segment time of door deceleration time, start
F5-14 20.0% 0.1% ★
close deceleration S curve segment + falling segment ≤
90%)
10.0%–80.0% (acceleration/
Start segment time of door deceleration time, start
F5-15 60.0% 0.1% ★
open acceleration S curve segment + falling segment ≤
90%)
F5-16 Speed deviation threshold 0%–80% 50% 0% ☆
Time for determining speed
F5-17 0–5000 ms 400 ms 1 ms ☆
deviation too large
- 47 -
Chapter 5 Function Code Table NICE900 User Manual
Function Min.
Parameter Name Setting Range Default Property
Code Unit
Door close steady speed
F5-18 0–9999 ms 200 ms 1 ms ★
delay
F5-19 Fault braking current 0.1%–150.0% 100% 0.1% ★
Group F6: Distance Control Parameters
Door width auto-tuning 0: Disabled
F6-00 0 1 ★
function 1: Enabled
0.01
F6-01 Door width auto-tuning speed 0 to F0-04 3.00 Hz ☆
Hz
F6-02 Low bits of door width pulse 0–9999 0 1 ★
F6-03 High bits of door width pulse 0–9999 0 1 ★
Low speed running distance
F6-04 of door open startup in 0.0%–30.0% 10.0% 0.1% ☆
distance control
Door open slow-down point
F6-05 60.0%–90.0% 70.0% 0.1% ☆
in distance control
Door open limit point in
F6-06 80.0%–99.0% 96.0% 0.1% ☆
distance control
Low speed running distance
F6-07 of door close startup in 0.0%–30.0% 10.0% 0.1% ☆
distance control
Door close slow-down point
F6-08 60.0%–90.0% 70.0% 0.1% ☆
in distance control
Door close limit point in
F6-09 80.0%–99.0% 96.0% 0.1% ☆
distance control
F6-10 Output torque display 0.0-1–80.0% 0.0% 0.1% ☆
Low bits of the door open
F6-11 0–9999 0 1 ★
limit switch position
High bits of the door open
F6-12 0–9999 0 1 ★
limit switch position
Position of the door close
F6-13 0–9999 0 1 ★
limit switch
Torque setting for door width
F6-14 0.0%–150.0% 80.0% 0.1% ★
auto-tuning or initial running
Low bits of the pulse of door
F6-15 0–9999 0 1 ★
open slow-down point
High bits of the pulse of door
F6-16 0–9999 0 1 ★
open slow-down point
Low bits of the pulse of door
F6-17 0–9999 0 1 ★
close slow-down point
High bits of the pulse of door
F6-18 0–9999 0 1 ★
close slow-down point
- 48 -
NICE900 User Manual Chapter 5 Function Code Table
Function Min.
Parameter Name Setting Range Default Property
Code Unit
Pulse at door open limit
F6-19 0.0%–99.9% 0.0% 0.1% ☆
output
Pulse at door close limit
F6-20 0.0%–99.9% 0.0% 0.1% ☆
output
F6-21 Door position feedback pulse 0.0%–99.9% 33.0% 0.1% ☆
Group F7: Distance Control Parameters
Door open limit holding time
F7-00 1.0–999.9s 0.1s 2.0s ★
in demonstration mode
Door close limit holding time
F7-01 1.0–999.9s 0.1s 2.0s ★
in demonstration mode
Actual door open and close
F7-02 0–9999 0 1 ☆
times in demonstration mode
Limit of door open and close
F7-03 0–9999 0 1 ☆
times in demonstration mode
Group F8: Auxiliary Parameters
F8-00 Software version 0.00–99.99 1.00 0.01 ●
F8-01 Module temperature 0–100°C 0°C 1°C ●
F8-02 Fault auto reset times 0–100 0 1 ★
F8-03 Brake use ratio 0–100% 100% 1% ☆
F8-04 Accumulative power-on time 0–9999 h 0 1 ★
Reserved (working time:
F8-05 0 0 1 ★
minutes)
F8-06 Accumulative running time 0–9999 h 0 1 ★
Reserved (working time:
F8-07 0 0 1 ★
minutes)
Accumulative working time
F8-08 0–9999 h 0 1 ★
setting
Accumulative operation time
F8-09 0–9999 h 0 1 ★
setting
F8-10 Auxiliary function selection 0–9999 12 1 ★
F8-12 Drive function selection 0–9999 0 1 ★
F8-14 Overload coefficient 0–10.00 2.00 0.01 ☆
Group F9: Auxiliary Parameters
F9-00 Terminal filter time 0–100 ms 20 ms 1 ms ☆
- 49 -
Chapter 5 Function Code Table NICE900 User Manual
Function Min.
Parameter Name Setting Range Default Property
Code Unit
0: Invalid
F9-01 DI1 function selection 1: Door open command 0 1 ★
2: Door close command
3: External reset signal
F9-02 DI2 function selection 4: Forbid terminal input 0 1 ★
during door open
5: Forbid terminal input
during torque holding
F9-03 DI3 function selection 0 1 ★
6: Low speed door close
command
7: Fire emergency input
F9-04 DI4 function selection 8 to 109: Reserved 0 1 ★
10/110: Light curtain signal
NO/NC
F9-05 DI5 function selection 11/111: Safety edge signal 1 1 ★
NO/NC
12/112: Door open limit
F9-06 DI6 function selection signal NO/NC 2 1 ★
13/113: Door close limit
signal NO/NC
14/114: Door open slow-
F9-07 DI7 function selection down signal NO/NC 10 1 ★
15/115: Door close slow-
down signal NO/NC
F9-08 DI8 function selection 16/116: Door lock signal NO/ 6 1 ★
NC
0: Invalid
1: Door open limit signal
output 0
Relay output selection (TA1/
F9-09 2: Door close limit signal 2 1 ★
TB1/TC1)
output 0
3: Door open limit signal
output 1
4: Door close limit signal
output 1
5: Fault signal output 1
Relay output selection (TA2/
F9-10 6: Reserved 5 1 ★
TB2/TC2)
7: Door open limit signal
output 2
8: Door close limit signal
output 2
9: Door lock signal output
10: Door re-open signal
Relay output selection (TA3/ output
F9-11 1 1 ★
TB3/TC3)
11: Hindering signal output
12: Door position feedback
output
- 50 -
NICE900 User Manual Chapter 5 Function Code Table
Function Min.
Parameter Name Setting Range Default Property
Code Unit
Group FA: Display and Fault Parameters
FA-00 Display in running state 1–511 319 1 ☆
FA-01 Display in stop state 1–63 39 1 ☆
FA-02 1st fault type 0–30 0 1 ●
FA-03 1st fault prompt 0–9 0 1 ●
FA-04 2nd fault type 0–30 0 1 ●
FA-05 2nd fault prompt 0–9 0 1 ●
FA-06 3rd fault type 0–30 0 1 ●
FA-07 3rd fault prompt 0–9 0 1 ●
FA-08 4th fault type 0–30 0 1 ●
FA-09 4th fault prompt 0–9 0 1 ●
FA-10 5th fault type 0–30 0 1 ●
FA-11 5th fault prompt 0–9 0 1 ●
FA-12 Bus voltage upon latest fault 0–999.9 V 0V 0.1 V ●
Output current upon latest
FA-13 0–99.00 A 0.00 A 0.01 A ●
fault
Running frequency upon 0.01
FA-14 0–99.00 Hz 0.00 Hz ●
latest fault Hz
0.0–180.0% (percentage
Output torque upon latest
FA-15 of output torque to rated 0.0% 0.1% ●
fault
torque)
Input terminal status upon
FA-16 0–1023 0 1 ●
latest fault
Output terminal status upon
FA-17 0–15 0 1 ●
latest fault
FA-18 Terminal state display * * * ●
FA-19 Input signal display * * * ●
FA-20 Output signal display * * * ●
FA-21 Parameter display selection 0–9999 0 1 ☆
FA-22 Display 1 0–9999 0 1 ●
FA-23 Display 2 0–9999 0 1 ●
FA-24 Analog voltage display 0.00–10.10 V 0.00 V 0.01 V ●
Low bit of current door
FA-25 0–9999 0 1 ●
position
High bit of current door
FA-26 0–9999 0 1 ●
position
FA-27 Door machine state display 0–9999 0 1 ●
FA-28 Door direction judgment * * * ●
- 51 -
Chapter 5 Function Code Table NICE900 User Manual
Function Min.
Parameter Name Setting Range Default Property
Code Unit
Group FF: Factory Parameters (Reserved)
FF-00 Reserved - - - ●
Group FP: Display and Fault Parameters
FP-00 User password 0–9999 0 1 ☆
0: No function
1: Restore the default setting
FP-01 Parameter update 0 1 ★
2: Clear fault records and
time
- 52 -
6
Description of Function Codes
Chapter 6 Description of Function Codes NICE900 User Manual
•• 0: Speed control
In this mode, four travel switches need to be installed on the door. They are door open
deceleration switch, door open limit switch, door close deceleration switch and door close
limit switch.
The controller instructs deceleration at the slow-down point and judges door open/close
limit based on signals from the limit switches.
•• 1: Distance control
In the distance control mode, door width pulses must be obtained through auto-
tuning. After relevant door open/close curve parameters are set, the controller instructs
deceleration and judges door open/close limit.
If a DI is allocated with door open/close limit signal in group F9, the controller judges door
open/close limit based on the related limit signal from the DI.
RUN or stop of the door machine is controlled by using the operation panel. Press OPEN to
STOP
instruct forward rotation, press CLOSE to instruct reverse rotation, and press RES
o stop the
door machine.
In such control mode, the controller runs as a general controller and does not execute the
special door machine logics.
- 54 -
NICE900 User Manual Chapter 6 Description of Function Codes
using the operation panel. Press OPEN to instruct forward rotation, press CLOSE to
STOP
instruct reverse rotation, and press RES
to stop the door machine.
Press OPEN or CLOSE to repeat door open/close demonstration. The time interval and times
of door open/close demonstration are set in group F7.
STOP
Press RES
to stop the door machine.
Note
•• Door width auto-tuning is valid only in the door machine manual control mode (F0-02 = 2).
•• Motor auto-tuning is valid only in the operation panel control mode (F0-02 = 0).
It is used to set the running frequency when the speed is input via operation panel.
It is used to quickly set the NO/NC feature of signals input from the limit switches and slow-
- 55 -
Chapter 6 Description of Function Codes NICE900 User Manual
down switches in the speed control mode (F0-01 = 0). When F0-05 is set to a non-zero value,
the NO/NC feature of the corresponding input signals are as follows:
F0-05 = 1 F0-05 = 2
F9-01 = 13 (Door close limit NO) F9-01 = 113 (Door close limit NC)
F9-02 = 15 (Door close deceleration NO) F9-02 = 115 (Door close deceleration NC)
F9-03 = 14 (Door open deceleration NO) F9-01 = 114 (Door open deceleration NC)
F9-04 = 12 (Door open limit NO) F9-01 = 112 (Door open limit NC)
It is used to set the speed at first-time running after power-on or inspection when the distance
control mode is used or the low speed door close input is active.
It is used to adjust the carrier frequency of the controller, aiming to reduce motor noise,
avoid resonance of the mechanical system, and reduce the leakage current to the earth and
interference generated by the controller.
If the carrier frequency is low, output current has high harmonics, and the power loss and
temperature rise of the motor increase.
If the carrier frequency is high, power loss and temperature rise of the motor declines.
However, the system has an increase in power loss, temperature rise and interference.
Adjusting the carrier frequency will exert influences on the aspects listed in the following table.
- 56 -
NICE900 User Manual Chapter 6 Description of Function Codes
Function
Parameter Name Setting Range Default Min. Unit
Code
F1-01 Rated motor power 0–750 W Model dependent 1W
F1-02 Rated motor voltage 0–250 V 100 V 1V
F1-03 Rated motor current 0.001–9.900 A Model dependent 0.001 A
F1-04 Rated motor frequency 1.00–99.00 Hz 24.00 Hz 0.01 Hz
F1-05 Rated motor speed 0–9999 RPM 180 RPM 1 RPM
Set the parameters according to the motor nameplate. Ensure that these motor parameters
are set correctly. Incorrect setting affects the motor auto-tuning and the vector control effect.
Function
Parameter Name Setting Range Default Min. Unit
Code
F1-06 Stator phase resistance of PMSM 0.00–99.99 Ω Model dependent 0.01 Ω
Rotor phase resistance of 0.01 Ω
F1-07 0.00–99.99 Ω Model dependent
asynchronous motor
Leakage inductance of 0.01 mH
F1-08 0.0–99.99 mH Model dependent
asynchronous motor
Mutual inductance of asynchronous 0.1 mH
F1-09 0–999.9 mH Model dependent
motor
Magnetizing current of 0.001 A
F1-10 0.001–9.900 A Model dependent
asynchronous motor
F1-11 Shaft D inductance of PMSM 0.0–999.9 mH Model dependent 0.1 mH
F1-12 Shaft Q inductance of PMSM 0.0–999.9 mH Model dependent 0.1 mH
F1-13 Back EMF of PMSM 0–250 Model dependent 1
Encoder zero position angle of 0.1°
F1-14 0.0–359.9° Model dependent
PMSM
F1-15 Real-time angle of PMSM 0.0–359.9° Model dependent 0.1°
Select a proper motor model according to the adaptable motor power. If there is a great
difference between the actual motor power and the adaptable motor power, the system control
performance will degrade.
F1-06 to F1-14 are updated automatically after motor auto-tuning is completed successfully.
For an asynchronous motor, the NICE900 obtains the corresponding parameters through
complete auto-tuning or static auto-tuning. If the onsite conditions does not allow motor auto-
tuning, manually input the value of these parameters by referring to data of the motor with the
same nameplate parameters.
Each time F1-01(Rated motor power) is changed, the controller automatically resumes
parameters F1-06 to F1-10 to the default values.
For a PMSM, the NICE900 can obtain F1-06 and F1-11 to F1-14 through complete auto-
tuning. After F1-01 is changed, the related parameters will not update.
F1-15 is used to display the magnetic pole position of the motor in real time.
- 57 -
Chapter 6 Description of Function Codes NICE900 User Manual
Note
Motor auto-tuning can be performed only in the operation panel control mode (F0-02 = 0). Before
motor auto-tuning, set motor ratings (F1-00 to F1-05) and PPR of the encoder (F2-14) correctly.
If a PMSM is used, motor auto-tuning is mandatory in one of the following conditions:
•• Before first-time running
•• When the motor/encoder is replaced
•• When wiring of the encoder is changed
PMSM running is prohibited before motor auto-tuning succeeds, because it may result in runaway. If
locked-rotor occurs, it indicates that motor auto-tuning fails.
1. After setting F1-16, press ENTER . Then "TUNE" is displayed and blinks.
2. Press the OPEN or CLOSE to start auto-tuning, and "TUNE" stops blinking. The auto-tuning
STOP
process can be stopped by pressing RES
.
3. After the auto-tuning ends, the operation panel restores to the display at stop state. F1-16
resumes to 0 automatically.
The values of F1-16 are described as follows:
•• 0: No auto-tuning
•• 1: Static auto-tuning for asynchronous motor
It applies to the applications where complete auto-tuning cannot be performed because
the asynchronous motor must be connected with the load. The stator resistance, rotor
resistance and leakage inductance are obtained from auto-tuning. The magnetizing current
and mutual inductance can be calculated.
•• 2: Complete auto-tuning for asynchronous motor
Complete auto-tuning is preferred to ensure dynamic control performance of the controller.
This mode requires the motor to be disconnected from the load.
The controller performs static auto-tuning first. Then according to the default system
setting, the controller accelerates to 80% of the rated motor frequency within 2s, keeps the
frequency for a certain period and then decelerates to zero speed within 2s.
•• 3: No-load auto-tuning for PMSM
The following parameters are obtained by auto-tuning:
-- F1-14 (Encoder zero position angle of PMSM)
-- F1-06 (Stator phase resistance of PMSM)
-- F1-11 (Shaft D inductance of PMSM)
- 58 -
NICE900 User Manual Chapter 6 Description of Function Codes
If the door is in the close state, press OPEN to start auto-tuning. If the door is in the
completely open state, press CLOSE to start auto-tuning. The controller opens or closes the
door slowly at 25% of the rated motor frequency, repeats the action and instructs reverse
running. After three times of auto-tuning, the controller calculates all related parameters
and completes with-load auto-tuning.
If locked-rotor occurs during door open or close after you press OPEN or CLOSE , motor
wiring or encoder wiring is incorrect. Correct the wiring and perform motor auto-tuning
again.
For more details on auto-tuning, refer to section 4.3.
- 59 -
Chapter 6 Description of Function Codes NICE900 User Manual
•• F2-00 and F2-01 are PI regulation parameters when the running frequency is smaller than
the value of F2-02 (Switchover frequency 1).
•• F2-03 and F2-04 are PI regulation parameters when the running frequency is larger than
the value of F2-05 (Switchover frequency 2).
•• If the running frequency is between F2-02 and F2-05, the speed loop PI parameters are
obtained from the weighted average value of the two groups of PI parameters (F2-00, F2-
01 and F2-03, F2-04), as shown in the following figure.
Figure 6-1 Relationship between running frequencies and PI parameters
PI
parameters
F2-00
F2-01
F2-03
F2-04
The speed dynamic response characteristics in vector control can be adjusted by setting the
proportional gain and integral time of the speed regulator.
To achieve a faster system response, increase the proportional gain and reduce the integral
time. Be aware that this may lead to system oscillation.
The recommended adjustment method is as follows:
If the default setting cannot meet the requirements, make proper adjustment. Increase the
proportional gain first to ensure that the system does not oscillate, and then reduce the integral
time to ensure that the system has quick response and small overshoot.
If both F2-02 (Switchover frequency 1) and F2-05 (Switchover frequency 2) are 0, only F2-03
and F2-04 are valid.
Note
Improper PI parameter setting may cause too large speed overshoot and even overvoltage when
overshoot drops.
F2-06 and F2-07 are current loop adjusting parameters in vector control. Generally, you need
not adjust these two parameters because the required control performance can be achieved
with their default values.
They are adjusted in the same way as PI parameters.
- 60 -
NICE900 User Manual Chapter 6 Description of Function Codes
It is used only in CLVC mode. It affects the dynamic performance and load current of the motor
and requires no adjustment generally.
This parameter compensates for insufficient torque production by boosting output voltage of
the controller. But very large setting will result in motor overheat and controller overcurrent.
Increase this parameter when a heavy load is applied but the startup torque of the motor is
insufficient.
If it is set to 0.0%, fixed torque boost is enabled.
The over-excitation gain restrains rise of bus voltage to avoid overvoltage during deceleration.
The larger the over-excitation gain is, the better the restraining result will be.
Set this parameter to 0 in the applications where the inertia is small or where there is regen.
resistor.
Increase this parameter properly in the applications where the inertia is large.
It is used to set the filter level of the encoder feedback speed. You need not modify it generally.
In the applications where interference is serious or the encoder PPR is small but CLVC is
adopted, increase this parameter properly to stabilize motor running.
- 61 -
Chapter 6 Description of Function Codes NICE900 User Manual
Note
In the applications where the motor is of small power or the load inertia is small, a large value of this
parameter may result in serious motor overshoot or oscillation.
Be cautious that it will resume to 0 when the default settings are restored.
The travel switches of the door machine in the speed control mode are installed according to
the following figure.
Figure 6-2 Installation of travel switches in speed control mode
Set the parameters in group F3 related to speed control correctly. Set the deceleration
switches and limit switches properly. The door open running curve in speed control is shown in
the following figure.
- 62 -
NICE900 User Manual Chapter 6 Description of Function Codes
F3-02
F3-01 F3-04 F3-06
F3-00
F3-05
Time
Door open command ON OFF
Door open OFF ON
slow-down signal
OFF ON
Door open limit signal
- 63 -
Chapter 6 Description of Function Codes NICE900 User Manual
2. When the door open position reaches (F6-04 x door width), the door machine accelerates
to the speed set in F3-03 within the acceleration time set in F3-04.
3. When the door open position reaches (F6-05 x door width), the door machine decelerates
to creep, with the speed =set in F3-05 and deceleration time set in F3-06.
4. When the door open position reaches (F6-06 x door width), the door machine continues
low speed creeping, and then enters the door open holding state, with the holding torque
set in F3-08. The door position is reset to 100%.
5. After the command is cancelled, the torque holding state ends. If torque holding needs to
continue, increase the delay time set in F5-04.
6. The dotted line part in the figure indicates the running curve when F5-06 (Door open
curve) = 0 (Linear acceleration/deceleration).
It is valid only in distance control. After the door reaches the set door open limit position, if the
output torque is greater than F3-07, the door controller resets the width pulses to 100% and
enters the door open limit torque holding state.
If the output torque is not greater than F3-07 after locked-rotor occurs, decrease F3-07 slightly
to smaller than the output torque), ensuring that the door width pulses can be reset.
It is used to set the holding torque after the door open limit position is reached.
It is used to set the door open hindered torque during door open.
Upper limit of door open torque = F3-09 + 10.0%
It is used to set the torque at startup of door open to ensure the good startup result of the door
machine.
Actual startup torque = F3-10 x Rated motor torque
It is used to set the filter time when the door open is hindered. If it is set to 0, door open
hindered is not detected.
- 64 -
NICE900 User Manual Chapter 6 Description of Function Codes
It is used to set the target frequency at which the door machine runs when the door open limit
signal is received or the pulses reach the door open limit requirement during open.
At door close hindered during door open deceleration or door open due to light curtain
hindered, the door machine re-opens the door at the speed set in this parameter. After door
open limit, the controller decelerates to the speed set in F3-12.
If this parameter is set to 0, this function is invalid.
Set the parameters in group F4 related to speed control correctly, and define the slow-down
switches and limit switches properly. The door close running curve in speed control is shown in
the following figure.
Figure 6-5 Door close running curve in speed control mode
The dotted line part indicates the running curve
when F5-06 = 0 (Linear acceleration/deceleration).
Frequency
F4-03
F4-08
F4-02
F4-01 F4-06 F4-10
F4-04
F4-09
F4-00 F4-11 and
F4-05 F4-12
F4-07
Time
Door close command ON OFF
Door close OFF ON
slow-down signal
Door close limit signal OFF ON
- 65 -
Chapter 6 Description of Function Codes NICE900 User Manual
Note
For synchronous door vane, set F4-09 and F4-07 to the same value.
Set the parameters in group F6 related to distance control correctly. The door close running
curve in distance control is shown in the following figure
Figure 6-6 Door close running curve in distance control mode
The dotted line part indicates the running curve
when F5-06 = 0 (Linear acceleration/deceleration).
Frequency
F4-03
- 66 -
NICE900 User Manual Chapter 6 Description of Function Codes
5. After door vane retraction is completed and the rotor is locked, the door machine enters
the torque holding state at the speed set in F4-07 and holding torque set in F4-12. The
door width is reset to 0.
6. After the door close command becomes inactive, the torque holding state ends. If torque
holding needs to continue, decrease the delay time in F5-05.
7. The dotted line part in the figure indicates the door close running curve when F5-06 (Door
open curve) = 0 (Linear acceleration/deceleration).
Note
For synchronous door vane, set F4-09 and F4-07 to the same value.
It is used to set the target frequency at which the door machine runs when the controller
receives the door close limit signal or the pulses reach the door close limit requirement during
door close.
The door machine runs at the low speed set in F4-07 after receiving the door close limit signal.
When the running time is equal to or larger than F4-08, the door machine enters the door vane
retraction stage.
It is used to set the running speed at the door vane retraction stage during door close.
If the door vane retraction running time is equal to or larger than F4-10, the door machine
decelerates again.
It is valid only in distance control. After the door vane is retracted, if the controller output torque
is greater than F4-11, the controller resets the door width to 0 and enters the door close limit
torque holding state.
- 67 -
Chapter 6 Description of Function Codes NICE900 User Manual
It is used to set the door close holding torque after the door close limit is reached.
•• 0: Reserved
•• 1: Output door close hindered signal
After door close hindered occurs, the relay with this function outputs a corresponding
signal.
•• 2: Immediate stop
The controller stops immediately and outputs the door close hindered signal. It does not
respond to any door close command 10s after this fault occurs. It executes the door close
command again immediately after a door close command is given again or the RUN
command is cancelled.
•• 3: Door re-open
The controller does not respond to the external door open/close commands during the
door re-open.
Door close hindered means that the output torque is greater than the door close hindered
torque during door close.
It is used to set the filter time when door close is hindered. If it is set to 0, door close hindered
is not detected.
It is used to set the normal-speed running speed at door close when the fire emergency input
signal is active.
Function
Parameter Name Setting Range Default Min. Unit
Code
F4-17 Normal speed at door close hindered F4-18 to F1-04 12.00 Hz 0.01 Hz
F4-18 Low speed at door close hindered 0.00 Hz to F1-04 2.00 Hz 0.01 Hz
F4-19 Normal speed torque 0.00%–150.0% 100.0% 0.1%
F4-20 Low speed torque 0.00%–150.0% 100.0% 0.1%
These four parameters are used to judge how to handle door close hindered.
- 68 -
NICE900 User Manual Chapter 6 Description of Function Codes
Hinder torque
(%)
F4-20 T2
Curve 1
F4-19 T1
V2 V1 Running
F4-18 F4-17 frequency (Hz)
1. According to the preceding figure, set these parameters according to the requirement:
V1 (F4-17) ≥ V2 (F4-18), T1 (F4-19) ≤ T2 (F4-20)
2. The torque threshold for judging door close hindered is curve 1 shown in the figure. The
shadow part shows that door close hindered occurs.
It is used to set the time for the system to decelerate from the door close speed to zero speed
when door close is hindered. Set this parameter to the minimum value as possible when
ensuring that overcurrent does not occur during deceleration.
It is used to limit the door open time. If the controller does not receive the door open limit signal
(pulse loss occurs in distance control mode) within the time, it performs door open timeout
protection (Er28).
This parameter is invalid when it is set to 0.
It is used to limit the door close time. If the controller does not receive the door close limit
signal within the time, it determines that door close is hindered, and performs door re-open or
zero speed holding based on the setting of F4-14.
This parameter is invalid when it is set to 0.
- 69 -
Chapter 6 Description of Function Codes NICE900 User Manual
It is used to set the maximum running time of low speed door open and close when the
low speed running signal is enabled. Set this parameter based on the actual situation.
The value must be equal to or greater than the sum of the door open and door close time
setting (parameter group of door open and close running curve); otherwise, Er26 is reported,
indicating that the parameter setting is incorrect. The correct setting implements protection of
the door machine in low speed running state in the case of abnormalities.
The normal running time does not exceed the setting of this parameter. When the door open
limit switch and door close limit switch fail, and an abnormality occurs (for example, the
controller cannot determine whether door open/close reaches the limit switch), the running
time exceeds the setting. In this case, Er30 is reported, indicating a door open/close operation
error in low speed running.
This parameter is invalid when it is set to 0.
It is used to set the torque holding time upon door open limit, that is, the holding time of the
door open running state when the door open limit signal is active but the door open command
from the terminal becomes inactive.
If the actual holding time exceeds the value of this parameter, the controller stops. If the
door open command is cancelled when door open limit is not reached, the controller stops
immediately. At this moment, the delay function is invalid.
When it is set to 9999s, the delay of external door open command remains valid.
It is used to set the torque holding time upon door close limit, that is, the holding time of the
door close running state when the door close limit signal is active but the door close command
from the terminal becomes inactive.
If the actual holding time exceeds the value of this parameter, the controller stops. If the
door close command is cancelled when door close limit is not reached, the controller stops
immediately. At this moment, the delay function is invalid.
When it is set to 9999s, the delay of external door close command remains valid.
It is used to set the running curve of the door machine during door open.
•• 0: Linear acceleration/deceleration
•• 1: S curve acceleration/deceleration
- 70 -
NICE900 User Manual Chapter 6 Description of Function Codes
It is used to set the running curve of the door machine during door close.
•• 0: Linear acceleration/deceleration
•• 1: S curve acceleration/deceleration
Function
Parameter Name Setting Range Default Min. Unit
Code
Start segment time of 10.0%–50.0% (acceleration/
F5-07 door open acceleration S deceleration time, start segment + 20.0% 0.1%
curve rising segment ≤ 90%)
Rising segment time of 10.0%–80.0% (acceleration/
F5-08 door open acceleration S deceleration time, start segment + 60.0% 0.1%
curve rising segment ≤ 90%)
Start segment time of 10.0%–50.0% (acceleration/
F5-09 door open deceleration S deceleration time, start segment + 20.0% 0.1%
curve falling segment ≤ 90%)
Falling segment time of 10.0%–80.0% (acceleration/
F5-10 door open deceleration S deceleration time, start segment + 60.0% 0.1%
curve falling segment ≤ 90%)
Start segment time of 10.0%–50.0% (acceleration/
F5-12 door close acceleration S deceleration time, start segment + 20.0% 0.1%
curve rising segment ≤ 90%)
Rising segment time of 10.0%–80.0% (acceleration/
F5-13 door close acceleration S deceleration time, start segment + 60.0% 0.1%
curve rising segment ≤ 90%)
Start segment time of 10.0%–50.0% (acceleration/
F5-14 door close deceleration S deceleration time, start segment + 20.0% 0.1%
curve falling segment ≤ 90%)
Falling segment time of 10.0%–80.0% (acceleration/
F5-15 door close deceleration S deceleration time, start segment + 60.0% 0.1%
curve falling segment ≤ 90%)
These eight parameters are used to define the S curve features of each segment speed during
running of the controller.
Each curve that combines the acceleration segment and deceleration segment is symmetric.
Take acceleration of S curve 1 in the following figure as an example.
- 71 -
Chapter 6 Description of Function Codes NICE900 User Manual
T2 T2
T1
T1
Acceleration Deceleration Time
segment segment
T1 stands for F5-07, during which the output frequency change slope (that is, speed change
rate) increases gradually. T2 is stands for F5-08, during which the output frequency change
slope reduces gradually to low speed frequency. Between T1 and T2, the output frequency
change slope keeps unchanged.
The speed deviation detection function of the NICE900 is effective only in the CLVC mode.
The controller determines whether the deviation between the running frequency and the
frequency reference is too large based on the value of F5-16. If the deviation remains too large
for more than the time set in F5-17, the controller reports Er32 and performs protection for too
large speed deviation.
When F5-16 is set to 0, the controller does not detect speed deviation.
It is used to set the steady speed delay at door close. The controller determines whether door
close is hindered only after the steady speed delay in F5-18.
After detecting overspeed, reversal or encoder signal abnormality, the controller performs
braking with the current set in this parameter and reports the fault after completion of braking.
If this parameter is set to 0, this function is invalid.
- 72 -
NICE900 User Manual Chapter 6 Description of Function Codes
•• 0: Disabled
•• 1: Enabled
F6-00 = 1 in the prerequisite of F0-02 = 2.
After you press OPEN or CLOSE , door width auto-tuning is started. The door machine runs with
the close-open-close logic, and stores the door width upon door open limit and locked-rotor.
For details on the operation, see Chapter 4.
It records the number of pulses in real time during door open in distance control. When the
number of pulses is equal to or greater than the value (door width x F6-04), the door machine
switches over from door open startup low speed (F3-00) to door open normal speed (F3-03).
It records the number of pulses in real time during door open in distance control. When the
number of pulses is equal to or greater than the value (door width x F6-05), the door machine
switches over from door open startup normal speed (F3-03) to door open ending low speed
(F3-05).
It records the number of pulses in real time during door open in distance control. When the
number of pulses is equal to or greater than the value (door width x F6-06), the door machine
performs related processing of door open limit.
- 73 -
Chapter 6 Description of Function Codes NICE900 User Manual
It records the number of pulses in real time during door close in distance control. When the
number of pulses is equal to or less than value (door width x (100% – F6-07)), the door
machine switches over from door open startup low speed (F3-00) to door open normal speed
(F3-03).
It records the number of pulses in real time during door close in distance control. When the
number of pulses is equal to or less than the value (door width x (100% – F6-08)), the door
machine switches over from door close startup low speed (F4-03) to door close ending low
speed (F4-05).
It records the number of pulses in real time during door close in distance control. When the
number of pulses is equal to or less than the value (door width x (100% – F6-09)), the door
machine performs related processing of door close limit.
It facilitates the torque setting for door width auto-tuning or initial running (F6-14) at door width
auto-tuning for asynchronous motor. After the door width auto-tuning is complete and the rotor
is locked, ensure that F6-14 is slightly smaller than F6-10.
The three parameters are used to record the positions of the limit switches obtained during
door width auto-tuning. During normal running, when the door open limit switch is valid, the
door position is restored to: F6-12 x 10000 + F6-11. When the door close limit switch is valid,
the door position is restored to the setting of F6-13.
- 74 -
NICE900 User Manual Chapter 6 Description of Function Codes
It is used to set the torque upper limit during door width auto-tuning and first power-on running.
This parameter is valid only in distance control. For details, see Chapter 4.
The four parameters are used to set the positions of the slow-down points.
The slow-down point is set based on the number of pulses rather than a percentage of the
door width.
Position of the door open slow-down point = F6-16 x 10000 + F6-15
Position of the door close slow-down point = F6-18 x 10000 + F6-17
It is valid only in distance control. When the door width position is larger than F6-21, the door
- 75 -
Chapter 6 Description of Function Codes NICE900 User Manual
position feedback signal is output. It is used together with F9-12 (Door position feedback signal
output).
It is used to set the time from torque holding upon door open limit to reverse door close in
demonstration mode. Set this parameter based on actual demonstration requirements.
It is used to set the time from torque holding upon door close limit to forward door open in
demonstration mode. Set this parameter based on actual demonstration requirements.
It is used to record the times of door open and close for demonstration. The parameter value
is stored automatically at power failure. Upon door open/close limit after power-on again, the
value is calculated by adding 1 for each door open/close to the original value.
The demonstration mode is an automatically cyclic running process, described as follows:
2. The door machine closes the door at a low speed, and opens the door based on the
running curve upon door close limit.
3. The door machine starts timing upon door open limit, and automatically performs reverse
door close after the time reaches the value set in F7-00.
4. The door machine starts timing upon door close limit, and performs reverse door open
after the time reaches the value set in F7-01.
STOP
5. This process is repeated until you press RES
to stop the controller. Then the
demonstration process ends.
Demonstration running can be performed in speed control or distance control mode. It applies
to demonstration and aging test.
- 76 -
NICE900 User Manual Chapter 6 Description of Function Codes
It is used to set the limit of door open and close times in demonstration mode. When the
actual door open and close times in demonstration mode is equal to or greater than F7-03,
demonstration running ends automatically. When F7-03 is set to 0, this function is invalid, and
demonstration running does not end automatically.
The controller stops running after a fault occurs, and automatically resets and continues
running after an interval of 2s.
If this parameter is set to 0, the automatic reset function is disabled, and faults must be
reset manually. If no fault occurs or manual reset is performed within an hour, the controller
automatically clears the reset times.
Note
The controller does not automatically reset faults Er19 (Motor auto-tuning fault), Er26 (Prompt of
incorrect parameter setting), and Er27 (Door width auto-tuning fault).
It is valid for the controller with a built-in braking unit and used to adjust the braking effect of
the brake unit.
It is used to record the actual accumulative power-on operation time (hour) of the controller.
After the value exceeds the maximum value 9999 hours, the controller starts a new round of
counting.
It is used to record the accumulative running time (hour). After the value exceeds the maximum
- 77 -
Chapter 6 Description of Function Codes NICE900 User Manual
- 78 -
NICE900 User Manual Chapter 6 Description of Function Codes
If the output current exceeds the value (rated motor current x F8-14), the controller reports
fault Er11, indicating motor overload.
It is used to set the terminal sensitivity. If DI terminals are liable to interference and may cause
malfunction, increase the value of this parameter to enhance the anti-interference capability.
However, increase of DI filter time will reduce response of DI terminals.
These parameters are used to set the functions of DI terminals DI1 to DI8. Note that the same
signal (except the value "0") must not be repeatedly allocated to different DIs.
•• 0: Invalid
•• 1: Door open command
•• 2: Door close command
•• 3: External reset signal
It is allocated to the external fault reset terminal.
•• 4: Forbid terminal input during door open
When this signal is active, the controller does not respond to external door open
commands.
- 79 -
Chapter 6 Description of Function Codes NICE900 User Manual
•• 0: Invalid
•• 1: Door open limit signal output 0
During door open, the controller outputs this signal after the controller receives the door
open limit signal or the counting pulses reach the value for door open limit.
•• 2: Door close limit signal output 0
- 80 -
NICE900 User Manual Chapter 6 Description of Function Codes
During door close, the controller outputs this signal after the controller receives the door
close limit signal or the counting pulses reach the value for door close limit.
•• 3: Door open limit signal output 1
During door open, the controller outputs this signal after the controller receives the door
open limit signal or the counting pulses reach the value for door open limit, and the
hindered torque reaches the value set in F3-07.
•• 4: Door close limit signal output 1
During door close, the controller outputs this signal after the controller receives the door
close limit signal or the counting pulses reach the value for door close limit, and the ratio of
the hindered torque to the rated torque reaches the value set in F4-11.
•• 5: Fault signal output 1
Er26 is only a prompt rather than a fault.
•• 6: Reserved
•• 7: Door open limit signal output 2
During door open, the controller outputs this signal after the controller receives the door
open limit signal or the counting pulses reach the value for door open limit, the door lock
signal becomes inactive, and the ratio of the hindered torque to the rated torque reaches
the value set in F3-07.
•• 8: Door close limit signal output 2
During door close, the controller outputs this signal after the controller receives the door
close limit signal or the counting pulses reach the value at door close limit, the door lock
signal becomes inactive, and the ratio of the hindered torque to the rated torque reaches
the value set in F4-11.
•• 9: Door lock signal output
It is simultaneous with the door lock signal input.
•• 10: Door re-open signal output
This signal is output during door re-open.
•• 11: Hindering signal output
This signal is output when door close is hindered.
•• 12: Door position feedback output
When the door width position is greater than F6-21, the door position feedback signal is
output.
It is used to set the parameters displayed on the operation panel when the door machine is in
- 81 -
Chapter 6 Description of Function Codes NICE900 User Manual
Bit0
1
Bit1
2
Bit2
4
Bit3
8
Bit4
16
Bit5
32
Bit6
0
Bit7
0
Bit8
256
Convert binary value to
decimal, and set this decimal
on the operation panel
By default, all 16 parameters are displayed; therefore, the value set on the operation panel is:
1 + 2 + 4 +8+16+32+0+0+256 = 319
The method of viewing FA-00 is as follows:
- 82 -
NICE900 User Manual Chapter 6 Description of Function Codes
In the running state, the display of FA-00 is a decimal value. You can press to view the
parameter indicated by each bit circularly.
Figure 6-10 Shift between parameters displayed in the running state
Output torque
Output current
Frequency reference
Running frequency
It is used to set the parameters displayed on the operation panel when the door machine is in
the running state.
FA-00 includes 6 binary bits, each defining a parameter. A total of 6 parameters can be can be
displayed during running.
The 6 binary bits correspond to the running parameters listed in the following table.
The method of viewing and setting FA-01 is the same as that of FA-00.
- 83 -
Chapter 6 Description of Function Codes NICE900 User Manual
These parameters record the latest five faults and detailed information about the latest fault.
For details, see Chapter 4.
Note that Er26 is only a message prompting that the parameter setting is incorrect, and is not
stored in the fault record.
It is used to view the states of the corresponding input and output terminals. When the terminal
is input active or output active, the corresponding LED segment is ON. The LEDs are arranged
as 1, 2, 3, and 4 from left to right.
1 2 3 4
A A A A
F B F B F B F B
G G G G
E C E C E C E C
D DP D DP D DP D DP
The meaning of each segment is defined in the following table.
Segment Segment
Meaning of ON LED2 LED3 Meaning of ON
(LED1) (LED4)
A DI1 input active A TA1 and TC1 ON
B DI2 input active B TA2 and TC2 ON
C DI3 input active C TA3 and TC3 ON
Door open Door close
D DI4 input active running running D
E DI5 input active procedure (for procedure (for E
viewing and viewing and Reserved
F DI6 input active commissioning) commissioning) F
G DI7 input active G
Blink, indicating normal
DP DI8 input active DP
RS485 communication
- 84 -
NICE900 User Manual Chapter 6 Description of Function Codes
It is used to view the input signal state. When an input signal is active, the corresponding LED
is ON. The LEDs are arranged as 1, 2, 3, and 4 from left to right.
1 2 3 4
A A A A
F B F B F B F B
G G G G
E C E C E C E C
D DP D DP D DP D DP
The meaning of each segment is defined in the following table.
Segment
Segment Segment Meaning
Meaning of ON Meaning of ON (LED3 &
(LED1) (LED2) of ON
LED4)
Door open command
A A Reserved
active
Door close command
B B Light curtain signal active
active
External reset signal
C C Safety edge signal active
active
Forbid terminal input Door open limit signal
D D
during door open active active
Reserved Reserved
Forbid terminal input
Door close limit signal
E during torque holding E
active
active
Low speed door open Door open slow-down
F F
input active signal active
Fire emergency input Door close slow-down
G G
active signal active
DP Reserved DP Door lock signal active
It is used to view the output signal state. When an input signal is active, the corresponding
LED is ON. The LEDs are arranged as 1, 2, 3, and 4 from left to right.
1 2 3 4
A A A A
F B F B F B F B
G G G G
E C E C E C E C
D DP D DP D DP D DP
- 85 -
Chapter 6 Description of Function Codes NICE900 User Manual
Segment
Segment Segment Meaning
Meaning of ON Meaning of ON (LED3 &
(LED1) (LED2) of ON
LED4)
Door open limit signal Door lock signal
A A
output 0 output
Door close limit signal Door re-open
B B
output 0 signal output
Door open limit signal Hindering signal
C C
output 1 output
Door close limit signal
D D Reserved Reserved
output 1
E Fault signal output 1 E
F Reserved F
Reserved
Door open limit signal
G G
output 2
Door close limit signal
DP DP
output 2
FA-21 is used to set the actually displayed content of FA-22 and FA-23 for fault identification
and commissioning onsite. The meanings of values are as follows:
- 86 -
NICE900 User Manual Chapter 6 Description of Function Codes
It is used to view the state of the door machine, such as door open, door close, or running.
•• 0: No function
•• 1: Restore the default setting
•• 2: Clear fault records and time
- 87 -
Chapter 6 Description of Function Codes NICE900 User Manual
- 88 -
7
Maintenance and Troubleshooting
Chapter 7 Maintenance and Troubleshooting NICE900 User Manual
7.1 Maintenance
CAUTION
The filter capacitor still has residual voltage after the power supply is cut off. Thus, do not repair
or maintain the controller immediately. Wait at least 10 minutes and ensure that the bus voltage
measured by multimeter is not higher than 36 V.
- 90 -
NICE900 User Manual Chapter 7 Maintenance and Troubleshooting
Note
Before measuring the insulating resistance with megameter (500 VDC megameter
recommended), disconnect the main circuit from the controller. Do not use the
insulating resistance meter to test the insulation of the control circuit. The high voltage
test need not be performed again because it has been completed before delivery.
- 91 -
Chapter 7 Maintenance and Troubleshooting NICE900 User Manual
Fault
Description Cause Troubleshooting Remarks
Code
1. The main circuit output
1. Eliminate external faults
is grounded or short-
Overcurrent such as wiring error.
circuited.
Er02 during 2. Perform motor auto-
2. Motor auto-tuning is
acceleration tuning again.
performed improperly.
3. Reduce the burst load.
3. The load is too heavy.
1. The main circuit output 1. Eliminate external
is grounded or short- problems such as wiring
circuited. error.
Overcurrent
2. Motor auto-tuning is 2. Perform motor auto-
Er03 during
performed improperly. tuning again.
deceleration
3. The load is too heavy. 3. Reduce the burst load.
4. The deceleration rate is 4. Modify the related
too short. parameters.
1. Eliminate external
1. The main circuit output problems such as wiring
is grounded or short- error.
circuited. 2. Perform motor auto-
Overcurrent
2. Motor auto-tuning is tuning again.
Er04 at constant
performed improperly. 3. Reduce the burst load.
speed
3. The load is too heavy. 4. Choose a proper
4. Strong interference encoder and uses a
exists on the encoder. shielded cable for the
encoder.
1. The input voltage is too 1. Reduce the input
high. voltage.
Overvoltage
2. The braking resistance 2. Choose a proper brake
Er05 during
is too large. resistor.
acceleration
3. The acceleration rate is 3. Modify the related
too short. parameters.
1. The input voltage is too 1. Reduce the input
high. voltage.
Overvoltage
2. The braking resistance 2. Choose a proper brake
Er06 during
is too large. resistor.
deceleration
3. The deceleration rate is 3. Modify the related
too short. parameters.
1. The input voltage is too 1. Reduce the input
Overvoltage
high. voltage.
Er07 at constant
2. The braking resistance 2. Choose a proper brake
speed
is too large. resistor.
1. Instantaneous power
failure occurs on the input The controller
1. Eliminate external power resets
power supply.
Undervoltage supply problems. automatically
Er09 2. The input voltage is too
protection 2. Contact the agent or the after the voltage
low.
vendor. becomes
3. The control board is normal.
abnormal.
- 92 -
NICE900 User Manual Chapter 7 Maintenance and Troubleshooting
Fault
Description Cause Troubleshooting Remarks
Code
1. The guide rail of the
1. Check the guide rail of
System elevator door is blocked by
Er10 the elevator door.
overloaded stuff.
2. Reduce the load.
2. The load is too heavy.
1. The guide rail of the
1. Check the guide rail of A large setting of
elevator door is blocked by
the elevator door. F8-14 may cause
Motor stuff.
Er11 2. Reduce the load. motor overheat.
overload 2. The load is too heavy.
3. Set F8-14 to a proper Use the default
3. The value of F8-14 is value.
value.
too small.
1. The wiring of the main
1. Check the wiring. The controller
Power output circuit is loose on the
Er13 2. Rectify faults of the decelerates and
phase loss output side.
motor. stops.
2. The motor is damaged.
The controller
decelerates
1. The ambient 1. Reduce the ambient and stops, and
Module temperature is too high. temperature. automatically
Er14
overheat 2. The fan is damaged. 2. Replace the fan. resets after the
3. The air filter is blocked. 3. Clear the air filter. temperature
becomes
normal.
EEPROM An EEPROM reading or Contact the agent or
Er16
fault writing abnormality occurs. vendor.
Current The control board is Contact the agent or
Er18
detection fault abnormal. vendor.
1. Enter the motor
1. The motor parameters
parameters correctly.
are incorrectly set.
2. Check the lead wire of
Motor auto- 2. Parameter identification
Er19 the motor.
tuning timeout times out.
3. Check wiring of the
2. The encoder for the
encoder and ensure the
PMSM is abnormal.
PPR is set correctly.
1. The encoder model is 1. Use an open-collector
improper. ABZ phase resolver.
Er20 Encoder fault
2. Wiring of the resolver is 2. Eliminate wiring
incorrect. problems.
- 93 -
Chapter 7 Maintenance and Troubleshooting NICE900 User Manual
Fault
Description Cause Troubleshooting Remarks
Code
1. F5-01 (Door open time
limit) is smaller than the
total door open time.
2. F5-02 (Door close time
1. Set F5-01 to larger than
limit) is smaller than the
the total door open time.
total door close time.
2. Set F5-02 to larger than
3. During door width auto-
the total door close time.
tuning, F0-02 (Command
3. Set F0-02 to 2 or F0- It is only a
Parameter source selection) is not set
01 to 1 during door width prompt, and not
Er26 setting to 2 (Door machine manual
auto-tuning. recorded as a
incorrect control), or F0-01 (Door
4. When F1-00 (Motor fault.
open/close control mode)
is not set to 1 (Distance type selection) is set
control). to 1 (PMSM), set F0-
00 (Control mode) to 1
4. F0-00 (Control mode) is
(CLVC).
set to 0 (SVC).
2. F0-00 is set to 0 (SVC)
when the controller drives
a PMSM.
1. Check wiring of the
1. The door width obtained encoder and related
through door width auto- parameters.
Door width tuning is smaller than 20 2. Check the mechanical
Er27 auto-tuning pulses. system of the door
fault 2. Distance control running machine.
is performed before door 3. Perform door width
width auto-tuning. auto-tuning before starting
distance control running.
1. The door open limit
1. Check the door open
signal is abnormal or The controller
Door open limit signal.
Er28 incorrectly set. can reset
timeout 2. Check wiring of the
3. The wire to the pulse automatically.
encoder.
encoder is broken.
1. The door open/close
1. Check the door close
Low speed limit signal is abnormal or The controller
limit signal.
Er30 door open/ incorrectly set. can reset
2. Check wiring of the
close timeout 2. The wire of the pulse automatically.
encoder.
encoder is broken.
1. Clear the stuff in the
1. The guide rail of the
guide rail.
elevator door is blocked by
stuff. 2. Set the upper limit of
Door open The controller
door open torque to a
Er31 hindered 2. The door open hindering can reset
proper value.
protection parameters are incorrectly automatically.
set. 3. Set F3-11 (Door open
hindered judging time) to a
proper value.
- 94 -
NICE900 User Manual Chapter 7 Maintenance and Troubleshooting
Fault
Description Cause Troubleshooting Remarks
Code
1. Acceleration or
deceleration is too abrupt. 1. Increase the
2. The motor angle acceleration or
Speed obtained through auto- deceleration time.
Er32 deviation tuning is incorrect, causing 2. Perform angle auto-
protection runaway. tuning again.
3. The speed deviation 3. Change the value of F5-
setting and time are too 16 and F5-17.
small.
The controller
1. Check whether this can run properly
switch is installed. If not, based on the
This signal is not detected cancel the input signal encoder signals.
Door close setting.
during door close when The controller
Er33 limit switch
the limit switch is used in 2. Check whether wiring of can reset
abnormal
distance control mode. the switch is correct. automatically
3. Check whether the if the switch
switch is damaged becomes
normal.
- 95 -
Chapter 7 Maintenance and Troubleshooting NICE900 User Manual
- 96 -
Warranty Agreement
1. The warranty period of the product is 18 months from date of manufacturing. During the
warranty period, if the product fails or is damaged under the condition of normal use by
following the instructions, Inovance will be responsible for free maintenance.
2. Within the warranty period, maintenance will be charged for the damages caused by the
following reasons:
a. Improper use or repair/modification without prior permission
b. Fire, flood, abnormal voltage, other disasters and secondary disaster
c. Hardware damage caused by dropping or transportation after procurement
d. Improper operation
e. Damage out of the equipment (for example, external device)
3. If there is any failure or damage to the product, please correctly fill out the Product
Warranty Card in detail.
4. The maintenance fee is charged according to the latest Maintenance Price List of
Monarch.
5. The Product Warranty Card is not re-issued. Please keep the card and present it to the
maintenance personnel when asking for maintenance.
6. If there is any problem during the service, contact Monarch's agent or Monarch directly.
7. This agreement shall be interpreted by Suzhou MONARCH Control Technology Co., Ltd.
Customer
information
Company name: Contact person:
Tel. or Email:
P.C.:
Product model:
Product
information Series No. (Attach here):
Name of supplier:
Failure
information
(eg. fault
code)
Maintenance person:
NICE900
NICE900
User Manual