Allen-Bradley: SLC500 Series (DF1)
Allen-Bradley: SLC500 Series (DF1)
Compatible PLCs
Family Model
SLC500 Series SLC5/01, SLC5/02, SLC5/03, SLC5/04, SLC5/05
Communications Cable
For the SLC5/01 and SLC5/02 the Maple OIT should be connected to:
• the DF1 port on the 1747-KE or 1770-KF3 module;
for the SLC5/03, SLC5/04 and SLC5/05 the Maple OIT should be connected to:
• the Channel 0 (RS232) Port on the PLC.
1033-0001, Rev. 07
PLC Settings
Full Duplex Operation must be set.
No Hardware Handshaking must be set.
The Checksum must be set to CRC (this is the Default).
The following table lists the PLC’s register memory ranges that the Maple OITs are able to access.
Please note that your PLC’s memory range may be smaller or larger than that supported by these OITs.
The following register memory can be displayed in 16, 32, or 64 bit format on the Maple OIT.
1
NOTE: The device type of Ffn allows access to any data file (fff) and address (nnn) in the Floating
Point (F) memory area. Likewise, the device type of Nfn allows access to any data file (fff) and address
(nnn) in the Integer (N) memory area. fff specifies the data file 000-254, and nnn specifies the data
address 000-254. For example, to specify Integer data file 97, address 45 (N97:45), select device type
as Nfn and enter 097045 into the device address field. Ensure that the data file and data address are
entered using leading zeroes when necessary.
Maple Systems, Inc. · 808 134th Street SW, Suite 120 · Everett, WA 98204-7333 · USA
Page 2 1033-0001, Rev. 07
Discrete Memory
The following table lists the PLC’s discrete memory ranges that the Maple OITs are able to access.
Please note that your PLC’s memory range may be smaller or larger than that supported by these OITs.
The following discrete memory is displayable in single-bit format on the Maple OIT.
NOTE 2: When accessing bit data, use the following syntax in the Device Address field:
<word>.<bit>
The bit value must contain the leading 0. For example, to address bit 8 in word 5, the Device Address
field would contain:
5.08
NOTE 3: The Bfin and Nfn Bit devices allow access to bits in any bit data file and any word data file
respectively. In the former, fff refers to the data file (000-254), nnn refers to the data address
(000-254), and bb refers to the bit number (00-15). For example, Nfn bit 01110702 refers to
N11:107.2. Note that the leading zeroes are required in all three fields.
NOTE: Although the tables list data files 10 - 13 as both Bit and Integer, a PLC Data File can exist only
as one data type.
The following PLC memory areas are not currently supported by the Maple OITs:
NOTE: Although input files (I1) and output files (O0) are listed in EZwar, these are only supported for
Allen-Bradley MicroLogix PLCs.
If your PLC’s memory range is smaller than the range supported by the Maple OITs, it is possible to
configure the OIT to monitor a PLC memory address which does not exist. Since this can cause
unpredictable results, when you configure the OIT please ensure that all selected PLC memory
addresses are valid for your PLC model.
Do not configure the OIT to write to any PLC memory address which should only be written to by
the PLC.
Maple Systems, Inc. · 808 134th Street SW, Suite 120 · Everett, WA 98204-7333 · USA
Page 4 1033-0001, Rev. 07
EZware Settings
The following table lists the communications settings that must be configured in EZware. These settings
can be found in the Edit-Set System Parameters menu under the PLC tab. Please note:
• the Recommended Settings column provides the recommended setting based upon the default
settings most commonly used in the Allen-Bradley SLC500 PLC
• the Options column lists EZware’s options; your PLC may not support every option
Recommended
Name Options Important Notes
Settings
AB DF1
PLC type: MicroLogix,
SLC500, PLC5
Serial port I/F: RS232 RS232, RS485
Data Bits: 8 7 or 8 Must match the DF1 port setting.
Stop Bits: 1 1 or 2 Must match the DF1 port setting.
9600,19200, Must match the DF1 port setting.
Baud Rate: 19200 38400,57600, Use the fastest baud rate supported
115200 by the PLC.
Parity: None Even, Odd, None Must match the DF1 port setting.
Must match the address assigned to
HMI station No.: 0 0-31
the DF1 port.
Must match the node address
PLC station No.: 1 0-31 assigned on the Data Highway
network.
Disable, Master,
Multiple HMI: Disable use for multiple OITs
Slave
HMI-HMI link
38400 38400, 115200 use for multiple OITs
speed:
PLC time out
3.0 1.5 to 5.0 adjust if longer timeout is required
constant (sec)
see Silver Series Installation and
PLC block pack: 0 0-10
Operation Manual