0% found this document useful (0 votes)
227 views2 pages

Power Factor Controller

This document provides specifications for an electrical component called PFR1ELCO0001 that monitors electrical parameters such as voltage, current, power factor, and temperature. It can operate with single or three-phase power from 230VAC to 400VAC at 50 or 60Hz. The device has LED displays, adjustable sensitivity settings, and alarm functions. It measures RMS values and has a compact DIN rail housing.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
227 views2 pages

Power Factor Controller

This document provides specifications for an electrical component called PFR1ELCO0001 that monitors electrical parameters such as voltage, current, power factor, and temperature. It can operate with single or three-phase power from 230VAC to 400VAC at 50 or 60Hz. The device has LED displays, adjustable sensitivity settings, and alarm functions. It measures RMS values and has a compact DIN rail housing.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

ELECTRICAL COMPONENTS SDN BHD

The First Choice in Energy Efficiency

PFR1ELCO0001
Supply Voltage Device From 230vac - 50/60hz DIMENSIONS (mm)
- Single-phase: 230 Vac - 1ph Mode (L+n) SIDE VIEW
- Three-phase: 3 X 400 Vac - 1ph Mode (L1 Or L2 Or L3+n)
- Three-phase: 3 X 230 Vac - 3ph Mode (L1+l2)
Monitoring:
- Cos Inductive & Capacitive
- Neutral To Phase Voltage & Current

90
- Sensitivity
- Alarms
Manual or Automatic Operation
Sensitivity Adjustable
SPECIFICATIONS UNIT PFR1ELCO0001
SupplyVoltage VAC 230
64
OperatingLimits (Ue) % -15 to +10
RatedFrequency Hz 50 or 60 FRONT VIEW
Power Consumption L/N - 230VAC VA 3.0
ImmunityTime For Microbreakings ms <6
DisplayType - 4 x LED Red
RatedCurrent A 5
VoltageReading Limits ( N/Lx ) VAC 196 to 253
CurrentReading Limits A 0.125 to 5.5

90
MeasuringValues RMS Real Effective Value
PowerFactor Adj. - 0.91 Ind. - 0.96 Cap
Numberof Output Relay 1
Contact Capacity - 5A - 250VAC (AC1)
Working temperature °C -10 /+50
Storage temperature °C -30 /+70
Electrical Insulation kV 4
Protection degree IP 41 Front - 20 Terminal Block
36
Relative Humidity w/o condensation RH% 95
BoxType mm 2M - DIN module

PFRAELCOU485 Dimensions
Weight
mm
g
90 x 36 x 64
140

TTL-USB Adapter DIMENSIONS (mm)


USB And RS-485 Serial Interface With Cables
Surge Protection On RS-485 Line
Connect Remote Serial Device To A PC
One Serial Server Creates One Virtual Com-port On A PC PW

Power And Data Flow Indicator For Troubleshooting TX

The RS-485 Standard Supports Half-duplex (2 Wire) RX


90

Real Time Transfer Ascii Protocol T


T
Compact Size - 2 Module - 35mm + 5V L

Easy To Setup And Install Din Rail

WIRING DIAGRAM
35,70

N LCB A

PFR2 - 3 SERIES
RS485
T
T 8

L 7
6
5
C 1 2 3 4 5 6 7
4
3

U 2
1
TTL - Max. 3mt
TTL WARNING

S T - THIS EQUIPMENT MUST BE INSTALLED BY TRAINED PERSONNEL


ON - READ THE TECHNICAL MANUAL BEFORE THE INSTALLATION

T - DISCONNECT THE LINE AND THE SUPPLY VOLTAGE WHEN

B
OPERATING ON THE TERMINALS CONNECTION OF EQUIPMENT

L
AND/OR PFC CAPACITORS.

Ue = -15% +10% Hz = 47-63


C = 10A MAX AC1 8A 250VAC
.../5A
SCUSB485 S1
Ue
415V 230V M 0V
MADE IN ITALY

USB - Max. 3mt

63,40

Excellence through Continuous Improvements


ELECTRICAL COMPONENTS SDN BHD
The First Choice in Energy Efficiency

PFR2ELCO0004 / PFR2ELCO0006
PFR2ELCO0004 / PFR2ELCO0006
PFR3ELCO0008 / PFR3ELCO0012
Measurement
- Cos Inductive & Capacitive
- Phase To Phase Voltage & Current
- Reactive Power Needed
- Cos Desired
- Total Harmonic Distorsion
- Sensitivity
- Ambient Temperature
Autorecognized Capacitor Bank
Anti-hunting Function
Fixed Step Programmable
Function & Alarm Relay Programmable
Fan Relay Programmable
RJ11 - Ttl Standard - Serial Interface (Optional)
- Owner / Modbus RTU Communication Protocol

DIMENSIONS (mm)
FRONT VIEW SIDE VIEW

96

96
PFR2 Series

96 74

FRONT VIEW SIDE VIEW

PFR3 Series
149

149

PFR3ELCO0008 / PFR3ELCO0012 149 60

SPECIFICATIONS UNIT PFR2ELCO0004 PFR2ELCO0006 PFR3ELCO0008 PFR3ELCO0012


SupplyVoltage VAC 220 to 440 220 to 440
OperatingLimits (Ue) % -15 to +10 -15 to +10
RatedFrequency Hz 50 or 60 50 or 60
Power Consumption L/L - 400VAC VA 5.8 6.1
ImmunityTime For Microbreakings ms <6 <6
DisplayType - 1 Display - 3 Digit - 7 Segment 1 Display - 3 Digit - 7 Segment
RatedCurrent ( CT ) A 5 5
VoltageReading Limits ( Lx/Lx ) VAC 180 to 485 195 to 460
CurrentReading Limits ( CT ) A 0.125 to 5.5 0.125 to 5.5
MeasuringValues TRMS True Real Effective Value True Real Effective Value
PowerFactor Adj. - 0.85 Inductive - 0.95 Capacitive 0.85 Inductive - 0.95 Capacitive
FFT - Harmonic Spectrum THD% 64 st 64 st
Numberof Output Relay 4 6 8 12
Serial Interface - TTL - standard TTL - standard
Communication Protocol - Owner - Modbus RTU Owner - Modbus RTU
Connector Type - RJ11 RJ11
Working temperature °C -10 /+50 -10 /+50
Storage temperature °C -30 /+70 -30 /+70
Electrical Insulation kV 4 4
Protection degree IP 41 Front Cover - 20 Terminal Block Connections 41 Front Cover - 20 Terminal Block Connections
Relative Humidity w/o condensation RH% 95 95
BoxType mm Flush Mount Flush Mount
Dimensions mm 96 x 96 x 74 149 x 149 x 60
Weight g 350 370 650 700

Excellence through Continuous Improvements