8350 FCM2041-U3 Cerberus PRO Modular Operator Interface

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Cerberus® PRO

Modular system
Operator Interface
Model FCM2041-U3

Architect & Engineer Specifications Product Overview


 Main-operator interface with user- The Operator Interface (OI), Model FCM2041-U3, is the central processor and user
prompted lighted, large buttons for interface for each Cerberus PRO Modular system. Model FCM2041-U3 provides
system control, operating sequence
straightforward, front-end access for an end-user to perform system tasks, such as:
 Large, 6-inch (15.2 cm) color display acknowledge events; control addressable points (e.g. – intelligent detectors |
notification appliance circuits [NACs]), and reset the system.
 Touch-screen driven,
system-control menus In terms of hardware used for Cerberus PRO Modular, Model FCM2041-U3 Operator
- Context-sensitive `Help’ button Interfaces can be mounted in full-size CAB1 | CAB2 | CAB3 enclosures.
- Navigation buttons and `More Info’ Additionally, remote, multi-module-mounted enclosures for Cerberus PRO Modular,
- Additional tabs , including queues Models REMBOX2 and REMBOX4, can each house one (1) Model FCM2041-U3 OI.
for mass notification (MNS)
It is through the custom-configuration software tool, Zeus-C, that Model
 Go-to-beginning; FCM2041-U3 OIs are able to provide programmed logic and panel supervision.
go-to-end queue buttons

 Front-end light-emitting diodes (LEDs)


for `Alarm’ | `Supervisory’ Specifications
| `Trouble’ commands Each Cerberus PRO Modular Operator Interface contains a full liquid-crystal display
- Partial-system disable LED (LCD) at the front end. An audible sounds from a Model FCM2041-U3 operating
- Audible Status LEDs unit when there are unacknowledged events. The display is surrounded by keys that
(ON and Silenced)
are used to control the displayed information and to navigate through these
 Global annunciation screens. Keys are also readily available in order for the end user to obtain help
and control capability information, as well as to enter into the menu features of a Model FCM2041-U3 OI.
 Integrated slots for switch-control
Additional diagnostic displays can
(Model SCM-8) and LED-control
(Model LCM-8) modules be found at the back end of each
Model FCM2041-U3 to provide
 Mounts in any of one (1) of efficiency to the end-user in
the following enclosures: troubleshooting the Cerberus
- Model CAB1 (smallest cabinet)
PRO Modular fire-alarm control
- Model CAB2 (medium cabinet)
panel (FACP).
- Model CAB3 (largest cabinet)
- Model REMBOX2
A 40-inch (1.02m) long 60-pin
(two-module remote enclosure) wire cable, P/N 555-133743, is
- Model REMBOX4 used to connect a Cerberus PRO
- (four-module remote enclosure) Modular Operator Interface,
Model FCM2041-U3 to the
 40 software-programmable
`User Macro’ switches
Siemens five-slot card cage,
Model CC-5.
 UL864 & CAN / ULC-S576 Listed
Slide-in labels are orderable
- File S24304, Vol. 3
under a single part number for
applications that require
French (Canadian) | Spanish |
Portuguese-Brazilian text.
Model FCM2041-U3
NOTE: Alternate-language labels Operator Interface Unit
are ordered separately. mounted in a Model CAB1 enclosure

Siemens Data Sheet 8350


Building Technologies Division usa.siemens.com/cerberus-pro
Slide-in tab to apply
corresponding label
(for non-English text)

Slide-in tab to apply


corresponding label
(for non-English text)

NOTE: Alternate-language labels are orderable


under a single part number, S54430-C16-A1.

Model FCM2041-U3
Cerberus PRO Modular Operator Interface

Operation
In normal | standby condition, a Model FCM2041-U3 OI displays the site-specific,
customized message; the time and date, and a rundown of the system status.
When an event occurs in the system, the display enters the `Alert’ mode. The event is displayed, the local audible
sounds, and the tab on the display for the corresponding event queue flashes. If the system-event type is `Alarm’ |
`Trouble’ | `Supervisory’, the appropriate LED blinks. If the event caused notification appliances to sound the
`Audibles On’ indicator illuminates. At the bottom of the screen, an `Acknowledge’ button is subsequently displayed.
Pressing this button acknowledges the event and silences the local audible. Once all events are acknowledged,
a reset button becomes available in the lower right side of the display. If notification appliances are active,
two (2) additional buttons appear at the bottom of the screen.
These buttons subsequently allow the operator to silence or unsilence the notification appliances.
When the notification appliances are silenced, the `Audibles Silenced’ LED illuminates.
The system can only be reset with the notification appliances silenced.
If more events are present in the system than can be displayed on a single screen a scroll bar appears to
the right of the event list. Pressing the up-and-down navigation buttons found at the right of the LCD
allows the operator to easily scroll through the list. The selected event is highlighted in the display.
Pressing the `More Info’ button will display a screen showing details relating to the selected event.
Other buttons also appear at the bottom of this screen. There is an expanded text message available,
as well as a selection to show all of the devices associated with the event that are active.
The operator can return to the previous screen by pressing the ESC button.
NOTE: Refer to installation manual: P/N – A6V11231629 for the
most detailed information on the Cerberus PRO Modular Operator Interface.

Siemens
Building Technologies Division –2– usa.siemens.com/cerberus-pro
Temperature and Humidity Range Details for Ordering
Cerberus PRO Modular Operator Interfaces are UL Listed MODEL PART
PRODUCT
| ULC Listed. Environmental operating conditions for each Model OR TYPE NUMBER
FCM2041-U3 operator interface is 32ºF (0ºC) to 120ºF (49ºC) Cerberus PRO
with a relative humidity of no greater than 95%, non-condensing. FCM2041-U3 S54430-C18-A1 Modular Operator
Interface

Electrical Ratings
24V Back Plane Current 195μA
Screw Terminal
INPUT 0
24V Current
POWER: 6.2V Back Plane Current 0
24V Standby Current 125μA
S

8V
Each HNET / XNET peak-to-peak, max.
OUTPUT
- and - 75μA, max.
POWER: CAN Network Pair
(during message
transmission)

Siemens
Building Technologies Division –3– usa.siemens.com/cerberus-pro
NOTICE – The information contained in this data-sheet document is intended only
as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install-type, instruction sheets – as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire-safety professional before specifying or using the product.

Any further questions or assistance concerning


particular problems that might arise, relative to the
proper functioning of the equipment, please contact
Cerberus® PRO
Siemens Industry, Inc.
the Manufacturer.
Building Technologies Division
8 Fernwood Road • Florham Park, NJ 07932
Tel: (973) 593-2600
September 2017 ─ New Issue
(Rev. 0)

You might also like