8350 FCM2041-U3 Cerberus PRO Modular Operator Interface
8350 FCM2041-U3 Cerberus PRO Modular Operator Interface
8350 FCM2041-U3 Cerberus PRO Modular Operator Interface
Modular system
Operator Interface
Model FCM2041-U3
Model FCM2041-U3
Cerberus PRO Modular Operator Interface
Operation
In normal | standby condition, a Model FCM2041-U3 OI displays the site-specific,
customized message; the time and date, and a rundown of the system status.
When an event occurs in the system, the display enters the `Alert’ mode. The event is displayed, the local audible
sounds, and the tab on the display for the corresponding event queue flashes. If the system-event type is `Alarm’ |
`Trouble’ | `Supervisory’, the appropriate LED blinks. If the event caused notification appliances to sound the
`Audibles On’ indicator illuminates. At the bottom of the screen, an `Acknowledge’ button is subsequently displayed.
Pressing this button acknowledges the event and silences the local audible. Once all events are acknowledged,
a reset button becomes available in the lower right side of the display. If notification appliances are active,
two (2) additional buttons appear at the bottom of the screen.
These buttons subsequently allow the operator to silence or unsilence the notification appliances.
When the notification appliances are silenced, the `Audibles Silenced’ LED illuminates.
The system can only be reset with the notification appliances silenced.
If more events are present in the system than can be displayed on a single screen a scroll bar appears to
the right of the event list. Pressing the up-and-down navigation buttons found at the right of the LCD
allows the operator to easily scroll through the list. The selected event is highlighted in the display.
Pressing the `More Info’ button will display a screen showing details relating to the selected event.
Other buttons also appear at the bottom of this screen. There is an expanded text message available,
as well as a selection to show all of the devices associated with the event that are active.
The operator can return to the previous screen by pressing the ESC button.
NOTE: Refer to installation manual: P/N – A6V11231629 for the
most detailed information on the Cerberus PRO Modular Operator Interface.
Siemens
Building Technologies Division –2– usa.siemens.com/cerberus-pro
Temperature and Humidity Range Details for Ordering
Cerberus PRO Modular Operator Interfaces are UL Listed MODEL PART
PRODUCT
| ULC Listed. Environmental operating conditions for each Model OR TYPE NUMBER
FCM2041-U3 operator interface is 32ºF (0ºC) to 120ºF (49ºC) Cerberus PRO
with a relative humidity of no greater than 95%, non-condensing. FCM2041-U3 S54430-C18-A1 Modular Operator
Interface
Electrical Ratings
24V Back Plane Current 195μA
Screw Terminal
INPUT 0
24V Current
POWER: 6.2V Back Plane Current 0
24V Standby Current 125μA
S
8V
Each HNET / XNET peak-to-peak, max.
OUTPUT
- and - 75μA, max.
POWER: CAN Network Pair
(during message
transmission)
Siemens
Building Technologies Division –3– usa.siemens.com/cerberus-pro
NOTICE – The information contained in this data-sheet document is intended only
as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install-type, instruction sheets – as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire-safety professional before specifying or using the product.