DCU Marine
Expandable engine controller
SW version 3.0.0
1 Document information 5
2 System overview 7
3 Application overview 24
4 Installation and wiring 38
5 Controller setup 78
6 Communication 95
7 Technical data 99
8 Appendix 103
2 System overview 7
2.1 Operator Interface 7
2.1.1 Controller screens 8
2.1.2 Display menu 14
2.1.3 Functions available from ID-DCU MARINE front panel keys 14
2.1.4 How to change controller language? 15
2.1.5 How to change the display backlight intensity? 15
2.1.6 How to change the display contrast? 15
2.1.7 How to check the serial number and software revision? 15
2.1.8 How to find active alarms? 16
2.1.9 How to select engine mode? 16
2.1.10 How to view and edit setpoints? 16
2.1.11 How to view measured data? 16
2.1.12 How to view the History menu? 17
2.1.13 Main screen indication 17
2.2 Controller configuration and monitoring 17
2.2.1 AirGate connection to the PC 18
2.2.2 Configuration steps 18
2.2.3 Direct conection to the PC 19
2.2.4 DriveConfig 20
2.2.5 Modbus protocol 21
2.2.6 Password protection 21
2.2.7 WebSupervisor 22
2.3 List of supported modules 23
3 Application overview 24
3.1 ID-DCU MARINE functions 24
3.1.1 Default archives 24
3.1.2 Function description details 24
3.1.3 Operational modes 30
3.1.4 Universal states 31
3.2 ID-RPU 33
5 Controller setup 78
5.1 PLC - programmable functions 78
5.1.1 General specification 78
5.1.2 List of available PLC functions 79
5.1.3 PLC configuration example 82
5.2 Shared IO and Virtual IO 89
5.2.1 Virtual Binary Outputs (VBOUT) module 89
5.2.2 Shared virtual inputs and outputs 89
5.2.3 Distributed binary inputs and outputs 91
5.3 Multiple ECU modules support 92
5.3.1 Multi ECU Configuration with DriveConfig 92
6 Communication 95
6.1 InteliDrive - Engine ECU communication 95
6.1.1 Example of standard J1939 engine 95
6.1.2 Tier 4 Final 95
7 Technical data 99
7.1 ID-DCU MARINE 99
7.2 CAN bus interface 101
8 Appendix 103
8.1 Controller objects 104
8.1.1 List of controller objects types 104
8.1.2 Setpoints 104
8.1.3 Binary Inputs 173
8.1.4 Binary outputs 195
8.1.5 Analog Inputs 241
8.1.6 Values 261
IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
Example: This type of paragraph contains information that is used to illustrate how a specific function
works.
Cycle forward through engine operation modes: OFF -> AUX / EME / HRB / PRP.
Cycle backward through engine operation modes: OFF <- AUX / EME / HRB / PRP.
Stops the engine in AUX, EME, HRB, PRP mode (hold time =1 sec).
Select the set point, select the screen or increase set point value.
Select the set point, select the screen or decrease set point value.
Note:
Stop button hold time is 1 sec. to avoid unwanted engine stop.
The 2nd (1 sec) push of the Stop button cancels the ‘cooling state’ of the engine and stops the engine
immediately. To avoid the cancel of the ‘cooling state’ by the 2nd push of the Stop button, use LBI card of the
DriveConfig tool and make the association of Access Lock to the Cooling logical binary output of the ‘Source’
column. It causes locking of the front panel buttons during the Cooling state.
Screen Content
Hidden, but available by Key combination, see Functions available from ID-DCU MARINE front panel
keys (page 14)
Info screen: Fw and App. version, s.n., .. Language list and switch.
Language screen
Fast edit screen
Available using ↑ or ↓ front panel keys
ECU diagnostics code list
Alarm list
1 = Main screen ID Mode, RPM1, Engine state, Oil Pressure and Coolant
Alarm indication
Possible Alarm list and History record prefixes
Prefix Meaning
Wrn Warning
Sd Shutdown
Cd Cooldown
Bw Broken wire
Fls Sensor fail
E n g O i l P r e s s W R N
B o o s t P r e s s F L S
E n g O i l T e m p W R N
6 2 9 F L S
> E n g C o o l T e m p F L S
S P 1 1 0 O C 7 F M 3 E 1 0
SP SPN number (Suspect Parameter Number) is a particular code for each fault
OC OC number (Occurrence Count) is ECU internal counter for each combination of SPN and FMI
FM FMI number (Failure Mode Identifier) is a particular code for each cause of fault
E Module index of ECU module, which transmits a fault
Info screen
Info Comment
InteliDrive Product type
ComAp 2018 Company name
ID Controller type
Serial: 0200FFFF Controller serial number
Sw ver: 3.0.0 Software version
Appl: AUX Application
Branch: DCU Marine Firmware branch
Statistic values
It is calculated:
1 Run Hours Each finished 60 minutes when engine is running.
Each successful start (starter is switched off due to RPM> Starting RPM) is
2 NumSuccStarts calculated.
Each external (manual) engine start.
Each finished unsuccessful cranking - MaxCrank time is over and engine is not
3 NumUnscStarts
started.
4 Service Time It is decreased each finished 60 minutes when engine is running.
5 DayCons Daily fuel consumption, every liter of fuel is calculated.
6 TripCons Trip fuel consumption, every liter of fuel is calculated.
Note: Statistic values can be adjusted from InteliMonitor, password 3 level protected by default.
History records
Following table does not contain Wrn, Sd and Fls messages from external units.
Note: Value name can’t exceed 11 characters to be recorded to History file with prefix (Wrn, Fls etc.). Longer
names characters are canceled.
Corresponding Sd BINx, Sd BOUTx or Sd AINx is indicated in Alarm list and history record when
communication with any extension units (IS-BIN, IS-AIN, IGS-PTM) is interrupted.
Example: When IS-BIN16/8 is configured for addresses: Binary inputs = BIN1, BIN2 and Binary outputs =
BOUT1, then three messages Sd BIN1, Sd BIN2, Sd BOUT1 are indicated after communication is
interrupted.
Note: Any “State” information can be configured to any binary output by DriveConfig software.
Note: If the configuration table has a code page that is not supported in the display processor, “Unsupported
code page” message appears on the ID-DCU MARINE screen. Press Page to return back to Language
selection.
Note: The Fast Edit function is available only in case of accessible parameter, i.e. if entered password level on
ID-DCU MARINE corresponds to protected level of parameter associated to Fast Edit function.
Available mode
RPM indication
Note: InternetBridge-NT (IB-NT) connection into Internet network can be done via Ethernet or Cellular
connection. The Ethernet connection can be realized by direct access using fixed and public IP address as well
as by private network access using dynamic non-public IP address (behind Firewall, NAT, DHCP server etc. –
situation illustrated in the picture above).
Note: AirGate ID needed as parameter for connection creation is assigned to InternetBridge-NT (IB-NT)
module. Second parameter for connection to a particular controller is controller’s address (there can be
connected up to 8 ID-DCU Marine controllers via CAN2 bus to one IB-NT module).
Translator
The Translator enables to translate all or some texts to up 5 languages that could be available in controller.
Controller language can be changed from panel buttons. It is possible to operate different languages on each ID-
DCU MARINE, Remote panel and InteliMonitor.
Note: Check all screens if some texts are not shortened.
Delivered controller contains firmware and default configuration. Any Application file can be modified by
customer using DriveConfig PC software. It is possible to download Application file from the controller, modify it
and download back. There must be corresponding version of Application file with firmware in controller.
Note: Configuration aid file does not contain the History record when had been read from the InteliDrive
controller by DriveConfig.
Note: To load History file from InteliDrive use InteliMonitor software only.
DriveConfig functions
Tool for ID-DCU MARINE controller and extension modules configuration
Extension modules addressing
All I/O function or protection configuration
Setpoints adjusting
Sensor characteristics modification
History record modification
Password level protection modification (password value must be changed in InteliMonitor)
Additional PLC logic creating
InteliVision displays screens modification
ECU Fault codes management
Controller firmware (mhx file) upgrade
Controller application file Up/Down load
Language translator enables (not available in version 1.0)
Create Dictionary between two languages (Dictionary can be used repeatedly)
Translate current text in Controller (in any language)
2.2.7 WebSupervisor
WebSupervisor is web based system designed for monitoring and controlling ComAp controllers via the
Internet. This system offers a number of beneficial features that help optimize revenue for machinery fleets, as
each piece of equipment can be individually monitored for all important operation values.
You can get more information on wiring of standard extension modules in the chapter Extension modules
(page 69).
6 back to System overview
Protections
Note: There are visible only the first two bar graph marks for protection limits indication on ID-DCU MARINE
screen !!!
3. Add another protections in EXPERT window. There can be set the same delay for all four limits.
Idle Offset [RPM] = Idle RPM [RPM] + (Idle Offset [%] / 100) x (Nominal RPM [RPM] – Idle RPM [RPM])
Note: Set Engine Params: Idle offset = 0% and Engine Protect: OverloadSpLim = 100% to disable Overload
protection functionality, i.e. if the protection is not requested by an application.
OFF mode
All ID-DCU MARINE controller and ID-RPU binary outputs are switched off. Engine can’t be started or running
engine is stopped, prelubrication function is not active. Firmware and controller configuration can be changed in
OFF mode only. OFF mode is available in all applications – AUX, EME, CMB and PRP.
Other functions
Controller (except OFF mode) accepts when engine is started outside controller (by hand) or when controller
power supply is switched-on on already running engine.
Watchdog
ID-DCU MARINE periodically (~ 0.2s) sends an impulse to the ID-RPU. ID-RPU backup mode is activated
after 1s without watchdog pulse.
Required CtrlHeartBeat rate is 100ms : 100ms
ID-RPU is switched to Emergency mode after power-on reset without ID-DCU MARINE.
Table 1
X range C Prefix
2016 to 8128 32 1000
504 to 2032 8 0100
126 to 508 2 0010
1 to 127 0,5 0001
4.1.3 ECU
Electronic Control Unit is kind of extension module connected to CAN1 bus or serial line and communicating via
electronic signal (J1939 or Modbus protocol). Generally can read binary and analog values from engine (inputs)
and transmit binary outputs (e.g. Start, Stop commands) and analog outputs (e.g. Speed request). ECU size
(count of input and output resources) are configurable and depends on controller possibilities.
The only one low temperature sensitive part is the controller display.
ID-DCU -LT version contains a preheating foil on the display activated below +5°C (measured on the PCB).
Heating is switched off when controller power supply is below 10VDC (together with display backlight).
Inputs
RPM1, RPM2: Two inputs for frequency (e.g. flow) measuring. Expected sensor is magnetic pickup – with
maximal frequency range up to 8 kHz. The output values SCM Freq1, SCM Freq2 calculation use setpoints
SCM unit: FreqRate1 and FreqRate2 - see below.
Closed jumper divides input frequency by 16 - recommended for higher frequency (>1000Hz) measuring.
Jumper position does not influence output value range.
IMP1, IMP2: Two impulse inputs for integral (e.g. consumption) measuring. It is expected NPN – open collector
(active) impulse sensor with maximal frequency range up to 60 Hz. Minimal pulse duration is 1ms. The output
values SCM Imp1, SCM Imp2 calculation use setpoints SCM unit: TransferRate1 and TransferRate2 - see
below.
ID-SCM inputs wiring example
Outputs
4.1.10 ID-SCM1
Technical data
Power supply: internal supply from ID-DCU MARINE (8 to 36 VDC)
Operating temperature range: -40°C to +70°C
Number of analog outputs: 1, no galvanic separation
Configuration in DriveConfig
Module = SCM
I/O – Analog outputs – SCM - AOUT1 (only)
Source
Low convert limit
Hi convert limit
Description
ID-SCM1 can only be configured as ID-SCM.
ID-SCM1 has only 1 analog output unlike ID-SCM which has 3 AOUTs (plus 4 values and 4 setpoints).
Control value Speed Governor is send on ID-SCM1 AOUT - equivalent output on ID-SCM is 3rd AOUT
(with PWM)
Invalid values are shown in SCM values
SCM setpoints are not used (sepoints not affects the function)
1 GND 5 UBatt
2 A/B IN 6 CAN-L
3 BO-A 7 COM
4 BO-B 8 CAN-H
Note: It is possible to connect up to five InteliVision 5 CAN or four InteliVision 8 displays to common CAN2
bus. The display addresses must be different in this case.
CAN2
Inter-controller CAN for multiple engines applications. ID-COM module is necessary. It is possible to connect
ID-DCU MARINE controllers and/or
IG-MU (Direct cable, analog modem or GSM modem interface) and/or
IG-IB (Internet interface) and/or
IB-NT and/or
The data rate is selectable in two levels: 250 kBd for 200 meters line and 50 kBd for 900 meters line.
1. Configure I-CB using I-CBEdit software. Configured I-CB behaves like fictive IS-AIN and IS-BIN units. I-CB
configuration associates selected values (from ECU database) received from Engine Control Unit to
selected CAN addressees (fictive IS-AIN, IS-BIN inputs and outputs).
2. Configure corresponding CONTROLLER CAN addresses in PC configuration tool.
3. Configure separate inputs and outputs in corresponding Analog, Binary inputs, outputs in PC configuration
tool.
Note: In case of CAT engines, there is RS232 connection between I-CB and CCM.
Note:
BW protection of the ID-RPU outputs Fuel solenoid and Stop solenoid is active in open state only.
To avoid BW detection configure not wired inputs or outputs of ID-RPU as Not used by DriveConfig sw.
Battery minus terminals are separated.
See also Recommended wiring acording to DNV rules (page 53).
Note: Emergency stop button contacts type NC (Normally Closed) can be directly incorporated into circuit
controlling ID RPU / EM. STOP input. It is also acceptable to use relay NC contacts in the circuit connected to
ID RPU / EM. STOP input (relay coil is controlled by emergency stop circuit) in case of NO (Normally Opened)
emergency stop circuit type, if it is required by application.
General
To ensure proper function:
Use grounding terminals. The InteliDrive DCU Marine power feeding input is galvanically isolated from
controller body, use the grounding terminal for proper grounding.
Wiring for binary inputs and analog inputs must not be lead parallel with high voltage/current cables.
Analog and binary inputs should be provided with shielded cables, especially when length >3m.
Grounding
To ensure proper function:
The shortest possible piece of wire should be used when grounding the controller.
Use cable min. 2,5mm2 .
The “-“ terminal of the battery has to be properly grounded.
Magnetic pick-up
To ensure proper function use a shielded cable.
Be aware of interference signal from Speed governor when one speed pick-up is used.
Power supply
Use min. power supply cable of 1.5 mm2 to ensure proper function.
Maximum continuous DC power supply voltage is 36VDC.
Maximum allowable power supply voltage is 39VDC – see chapter Technical data.
Note: For redundancy power supply use ID-RPU module – see chapter Recommended wiring.
Note:
The InteliDrive DCU Marine controller should be grounded properly in order to protect against atmospheric
discharges!
Install separate conductors for signal and power inputs. Allow for conductor voltage drop when determining
conductor size. All power supplies must have common ground.
When there is a potential risk of the controller being subjected to conditions outside its capabilities - an outside
protection device should be used.
Primary Converted
0 0
1000 1
Note:
* IGS-PTM has hardware range 0-20mA but offered sensor in DriveConfig is ±20mA
** IGS-PTM has hardware range 0-250Ω only - DriveConfig offers correct sensor for I/O configuration but for
User define input curve only sensor 0-2400Ω.
Note: Fahrenheit sensors are supported from IS-AIN8 of sw version 2.2 only.
To ensure a proper function use shielded cables, especially for length over >3 m.
Current
Measurement
- Jumper on pins 1-2.
Resistance measurement
- Jumper on pins 3-4.
Note: Maximal voltage on controller Differential analog inputs AI5 to AI8 is in the range –2 to +5 VDC against
minus power supply terminal!
Note: ID-DCU MARINE hardware jumper must correspond with software configuration.
Configuration
See drawing above
Property Value
Value name is displayed on the screens and in the Alarm list and History record.
Enter up to 14 ASCII characters.
Name
Name is automatically set to Function name if function is selected from the Logical function
list see Function item.
Dim Dimension is displayed on the screens. Select dimension from the list or add a new one.
Select sensor from the list or create a customer sensor characteristics in User sensor
Sensor window. There must be corresponding analog input hardware jumper setting in InteliDrive
controller. See Sensor availability in table below.
Output value (reading) resolution. DriveConfig indicates when Resolution is out of the value
Resolution
range.
Sensor Full output value (reading) range for 20 mA (current), 250 Ω, 2400 Ω (resistive), 1 V, 4V, 5V,
range 100 mV (voltage) sensor.
Select from the list. Configure two protection levels as standard or more levels (window)
Protection
protection in Expert mode.
Configure direction Over or Under limit when protection is activated. Options "Under
Active limit+Fls" and "Over limit+Fls" means that the protection is activated in case of Analog Input
when value is Under/Over the protection limit or in case that non valid value (####) is indicated on
the Analog Input.
Configure protection activity: All the time or Engine running with three different adjustable
Block type
delays when protectioln is active after engine start (RPM > Starting RPM).
Bargraph
Bargraph starting value.
0%
Note: Some configuration items (e.g. Protection) stay without change when Property - Sensor is changed to
None.
Sensors availability
Configuration examples
Conversion from 4-20 mA to 6.0 Bar Oil pressure sensor (Wrn+Sd protection and Oil press function)
Note:
HW configuration: CU 0-1 V can be used for characteristics ±1 V, but this ± characteristics can be configured to
AI5 to AI8 inputs only!
Sensor range (gray background) automatically follows the User sensor characteristics (zero value at the above
picture is not important).
Availability Configuration
0 - 20mA / 600
AI1 to AI4
AI5 to AI8
Analog input
jumper = 1-2
(current)
4 - 20mA / 100,0
AI1 to AI4
AI5 to AI8
AI5 to AI8
Analog input
jumper = 2-3
(voltage)
0 - 100mV / 100,00
AI5 to AI8
0 - 1200 Ω / 100
AI1 to AI4
AI5 to AI8
Analog input
jumper = 3-4
(resistance)
Note:
It is possible to set up to 30 points non-linear sensor characteristics.
Connect external resistors (voltage divider) to extend input voltage range.
Inteli AIN8 unit can be mounted on DIN rail (35 mm). All dimensions are in mm.
Inteli AIN8TC unit can be mounted on DIN rail (35 mm). All dimensions are in mm.
Inteli IO8/8 unti can be mounted on DIN rail (35 mm). All dimensions are in mm.
IS-BIN 16/8 unit can be mounted on DIN rail (35 mm). All dimensions are in mm.
Inteli AIO9/1unit can be mounted on DIN rail (35 mm). All dimensions are in mm.
4.4.6 IS-AIN8
IS-AIN8 unit can be mounted on DIN rail (35 mm). All dimensions are in mm.
Inteli AIN8 unit can be mounted on DIN rail (35 mm). All dimensions are in mm.
4.4.10 I-AOUT8
General Description
I-AOUT8 is an extension unit with 8 Analog outputs. Each analog output can be switched by jumper for.
I 0 to 20 mA
U 0 to 10 VDC
LED Indication
Green LED is located near the power supply connector.
PLC values
List contains 128 internal binary values (bits) PLC Bout 1.1 to PLC BOUT 16.8 that
can be configured as any PLC function binary input or output.
Binary Only used PLC Bout x.x can be configured to ID-DCU MARINE controller or external
modules physical terminals.
Used values are visible at controller screen.
There are available 96 internal analog values PLC Aout 1 to PLC Aout 96 that can be
configured as any PLC function input or output.
Analog
Any used PLC Aout x can be configured as physical analog output.Used values are
visible at controller screen.
Unsigned value that is automatically used for Counter and Timer functions, 16 PLC
PLC resource resources are available.
Values are visible in InteliMonitor only.
IMPORTANT: Logic for controlling the motor can't be locked in PLC. Certification authority can ask
for access to the content locked this way.
PLC Function Selection Available Number of available blocks in ID-DCU Marine 3.0.0
OR/AND 128x
XOR/RS 128x
Comp Time 8x
Math Fc 16x
Ext Math Fc 8x
Interpol Fc 'B' 8x
Nonlin I Fc 4x
Math AxB/C 8x
PID Bin 4x
PID Ana C 8x
Ramp 4x
Up/Down 4x
Inc/Dec 2x
Mov Avg 4x
Timer 4x
Delay 16x
Delay B 8x
Force Hist 4x
Jump 8x
Mux Const. 4x
Counter 16x
Decomp 8x
Convert 16x
3D Map 2x
Required function
Based on adjustable pressure limits ID controller switch the engine between RPM1 to RPM2. When Pressure
drops below Pressure ON limit engine increases from RPM1 to RPM2 and after Pressure increases above
Press OFF limit goes back to RPM1.
Configuration steps
1. Start DriveConfig and open default archive ID-DCU-X.aid.
2. Pressure measuring: configure pressure sensor characteristic – suppose range 0 to 10,0 Bars on ID-DCU
MARINE Analog input 4. Wrn and Sd protection limits should be adjusted over Pressure OFF limit.
4. Configure Comparator Input: click on button and select input value from the list.
7. Drag & drop PLC functional block Ana Switch, configure Input 1 and Input 2 as PLC setpoints and edit the
setpoint names to RPM 1 and RPM 2.
10. Go to I/O window and configure analog SCM AOUT1 as RPM out. Then configure output convert Low limit
(0 RPM ~ 0.00V output) and High output convert limit (2000 RPM ~ 10.00V output).
New button on PLC toolbar to access password settings and login/logout. Button has 3 different colours:
All existing passwords are entered (all PLC sheets with password are unlocked)
Any (but not all) existing passwords are entered (any, but not all PLC sheets with password
are unlocked)
No existing password is entered or no password exists (all PLC sheets with passwords are
locked)
To assign password to the PLC sheet, click on assign icon in title of PLC sheet:
IMPORTANT: Very important parts of the control algorithm must not be locked in PLC sheets.
Certification authorities may request their unlocking if necessary.
Shared Binary Inputs and Outputs may be used exactly in the same way as standard physical Inputs and
Outputs. If SHBIN or SHAIN modules are configured, at least one corresponding module of SHBOUT or
SHAOUT (respectively) is needed. If it is not configured, corresponding protection appears because SHBIN or
SHAIN will be missing. See the figure below for more information.
IMPORTANT: For proper function of Shared Binary and Analog Inputs and Outputs, only one
source of Shared Binary or Analog Outputs must be configured (i.e. it is not possible to configure
in one controller SHBOUT1 and to another one as well SHBOUT1).
Note: Controller sends Shared Binary Outputs each 100ms if there are any changes in any bit position. If there
are no changes, controller sends the information with period 1s.
A protection upon module failure can be configured in GenConfig. See the schematic below.
Note: Controller sends Distributed Binary Outputs each 100ms if there are any changes in any bit position. If
there are no changes, controller sends the information with period 1s.
IMPORTANT: Be aware that it is necessary to use ECU list, which enables use of multiple ECU
modules. Check and select used ECU list using this option:
Module type - type of configured module (e.g. Standard J1939 engine support, ECON-4 speed governor
support etc.)
Module index – module identification number. It is used to associate alarms in alarm list and controller
history with a particular ECU module.
Module name - user adjustable string with up to 10 characters. Default values are ECU, ECU-1 to ECU-9,
depending on order in which are modules added.
Module address – user adjustable number from 0 to 255, which defines address of configured module.
Default option is Default (X), X stands for actual address value, which comes from ESC and is assigned to
module when the default option is used. It is recommended to use this option and use different setting only if
the default one does not work.
Example: Set Module address to 5, if engine CAN1 address is 5.
Controller address – user adjustable number from 0 to 255, which defines address used by controller for
communication with the module. Controller can use different address for communication with different
modules. Default option is Default (X), X stands for actual address value, which comes from ESC and is
used by controller interface for communication with module, when the default option is used. N/A is
displayed as Controller address, if Modbus is used for communication with a module.
Note: Do not confuse Controller address with Comms settings: Contr.address, which is different parameter
with independent functionality.
Note: ESC is Engine Specific Code, it contains all necessary information about transmitted values, commands
and diagnostic messages.
Protection upon module failure – use it to select type of alarm, which is issued if communication with
module fails
Add screens – use it to display/hide module related screens
Display data as – information how are analog values displayed
Analog inputs – Number of analog input values available with module.
Note: Total number of available analog input values is limited to 160 with all configured modules (e.g. 4
modules with 40 inputs would use all available inputs).
Note: Total number of available analog output values is limited to 40 with all configured modules (e.g. 5
modules with 8 outputs would use all available outputs).
Note: Total number of available binary input values is limited to 160 with all configured modules (e.g. 4 modules
with 40 inputs would use all available inputs).
Note: Total number of available binary output values is limited to 160 with all configured modules (e.g. 4
modules with 40 outputs would use all available outputs).
Analog inputs (4B) – Number of 4B analog input values available with module.
Note: Total number of available 4B analog input values is limited to 20 with all configured modules (e.g. 5
modules with 4 inputs would use all available inputs).
Name Unit
Engine speed RPM
Actual torque %
Demand torque %
Coolant temp °C
EngineOil temp °C
Boost Pressure bar
Intake Manifold Temp °C
Air Intake pressure bar
Exhaust Gas Temp °C
Accelerator Pedal position %
Percent Load %
Fuel Rate L/h
EngOil Filter Diff.Press bar
Battery Potential (Voltage) V
Fuel Delivery Pressure bar
Engine Oil level %
Crankcase Pressure bar
Coolant Pressure bar
Coolant Level %
Fault reset = accepts (confirms) diagnostic message = removes inactive message form ECU Alarm list only
when ECU Alarm list is visible.
Note: Fault reset button is “screen sensitive”. It is active only on selected actual controller screen.
After-Treatment screen
This screen is shown with configured ECU which supports Tier 4 Final. After-Treatment screen is automatically
shown, once any of selected lamps gets active or change status. Deactivating of the lamp will not trigger
showing the screen. The screen is then shown until operator switch it to another one. Alarmlist screen has lower
priority so even new alarm appears, After-treatment screen is still displayed. To avoid displaying blank screen,
inactive lamps are represented by "dotted" icons. For no active lamp the screen shows all dotted icons. Please
see examples below:
Note: Lamp icon blinking is defined as displaying active lamp icon and inverse colored active lamp icon in
required frequency.
6 back to Communication
Operating conditions
Operating temperature ID-DCU MARINE -20 to +70 °C
Operating temperature ID-DCU-LT -40 to +70 °C
Storage temperature -30 to +80 °C
Humidity 95 % without condensation
Flash memory data retention time 10 years
Protection front panel IP65
Standard conformity
Low Voltage Directive EN 61010-1:95 +A1:97
EN 61000-6-2, October 2001
Electromagnetic Compatibility EN 61000-6-4, October 2001
IEC 60533, Ed. 2; 1999-11
5 – 25 Hz, ±1.6mm
Vibration
25 – 100 Hz, a = 4 g
Shocks a = 200 m/s2
Heat radiation 9W
D+ function
Max. D+ output current 300 mA
Guaranteed level for signal Charging OK 80 % of supply voltage
Note: The maximal input voltage offset is in the range from –2 to +5 VDC against controller minus power supply
when AI5 to AI8 is used for differential voltage measuring.
± 0 – 20 mA active
Maximal current range
0 – 20 mA passive
Input impedance 50 Ω for mA measuring
Input impedance >100 kΩ for V measuring
Resistance measurement tolerance ± 0.5 % ± 2 Ω out of measured value
Voltage measurement tolerance ± 0.5 % ± 1 mV out of measured value
Current measurement tolerance ± 0.5 % ± 0.5 mA out of measured value
RS232 interface
Maximal distance 10 m
Speed 19.2 kBd
6 back to Appendix
8.1.2 Setpoints
What setpoints are:
Setpoints are analog, binary or special data objects which are used for adjusting the controller to the specific
environment. Setpoints are organized into groups according to their meaning. Setpoints can be adjusted from
the controller front panel, PC, MODBUS, etc.
Each setpoint can be protected by a password against unauthorized changes. Password protection can be
assigned to the setpoints during the configuration procedure.
IMPORTANT: Do not perform repeated writing of setpoints (e.g. do NOT have a MODBUS
’watchdog’ system where PLC periodically writes down a figure into register and then reads the
figure). The setpoints are stored in EEPROM memory, which can be overwritten up to 100 000 times
without risk of damage or data loss, however it may become damaged, when allowed number of
writing cycles is exceeded!
The issue with EEPROM memory limit is resolved from ID-DCU MARINE firmware version 2.2,
setpoint registers were moved into another memory part of the controller.
Group of setpoints:
Act. Calls/SMS
Group of setpoints:
Date/Time
Time 167
Date 167
Time Stamp Per 167
SummerTimeMod 168
EnTimeSync 168
Group of setpoints:
DetCon20
DelayLoadRed 170
DecreaseRamp 171
IgnRedLimit 171
ImmStopLimit 171
TimingRedGain 172
6 back to Controller
objects
Note: The asterisk mark “*” appears before a setpoint name (on controller screen) if the setpoint is password
protected.
The asterisk mark is removed only when the password is set from controller’s front panel.
The asterisk mark is still visible on controller screen even if the password is set from InteliMonitor.
Note: Even though one level may have been set from the front panel, the affected setpoints are not accessible
from InteliMonitor (direct or Modem) until this level is set in InteliMonitor (direct or Modem). Setpoints opened
from front panel are automatically closed 15 minutes after the last key has been depressed or when wrong value
of setpoint is set.
Note: It is possible to protect remote Start, Stop commands from InteliMonitor as well. This three level
command protection can be configured from DriveConfig.
EnterPassword
Password is a four-digit number. Only setpoints associated with the entered password level can be modified.
Use ↑ or ↓ to select the desired password and then hit enter.
ChangePassword 1
ChangePassword 2
ChangePassword 3
Note:
Any password can be changed once that level password or higher has been entered if the change is
made from InteliMonitor PC tool.
Password level 3 must be entered at first to change any password if the change is made by controller
front panel buttons.
Access code
Can be changed from InteliMonitor software only (Monitor – Change Access code).
Has to be set before remote modem or SMS connection is opened.
Can be up to 16 ASCII characters
At first Password 3 has to be entered before the new Access code can be changed.
Note: All setpoints below can be modified from Remote panel or InteliMonitor as well.
Mode ID
Setpoint group Basic settings Related FW 3.0.0
Range [units] [-]
Default value OFF
Step [-]
Comm object 8315 Related applications All
Config level Standard
Setpoint visibility Always
Description
Mode ID [ OFF, AUX ]
Mode ID [ OFF, EME ]
Mode ID [ OFF, EME, HRB ]
Mode ID [ OFF, PRP ]
Equivalent to Controller mode changes by Mode→ or ←Mode buttons.
RPU Gear Teeth
Setpoint group Basic settings Related FW 3.0.0
Range [units] 1 .. 500 [-]
Default value 120
Step 1
Comm object 10920 Related applications All
Config level Standard
Setpoint visibility Always
Description
Number of teeth on the engines flywheel for the pick-up connected to ID-RPU.
Nominal RPM
Setpoint group Basic settings Related FW 3.0.0
Range [units] 30 .. 4000 [RPM]
Default value 1500
Step 1
Comm object 8253 Related applications All
Config level Standard
Setpoint visibility Always
Description
Nominal engine speed, base for Overspeed protection limit and Engine Values: Speed Request percentage
calculation.
Note: Nominal RPM must correspond to 100% Throttle position in ECU for correct Load sharing function
in PRP application.
Idle/Nominal
Setpoint group Basic settings Related FW 3.0.0
Range [units] [IDLE, NOMINAL, BIN.INPUT]
Default value IDLE
Step [-]
Comm object 10336 Related applications All
Config level Standard
Setpoint visibility Always
Description
Activates/deactivates the logical binary output Nominal Sw, that can be configured as J1939 output to
switch ECU.
BIN.INPUT: IDLE/NOMINAL mode is switched via Binary input BI Nominal (NOMINAL when closed).
Note: Basic setting: Nominal RPM must correspond to ECU Nominal RPM for 100% Throttle position in
PRP and 50% in AUX.
RunHourSource
Setpoint group Basic settings Related FW 3.0.0
Range [units] [AUTO, INTERNAL, ECU]
Default value AUTO
Step [-]
Comm object 8630 Related applications All
Config level Standard
Setpoint visibility Always
Description
AUTO – controller displays valid running hours value received from any ECU module. In case of erratic
reading use option ECU and parameter RHS Index to define module, which is source of running hours.
Running hours value calculated by controller is used, if no valid value is received.
INTERNAL – ID-DCU MARINE running hours statistical value is used
ECU – controller reads running hours from selected ECU module. Parameter RHS Index is used to select
index of module, from which controller reads running hours.
In case no ECU support is configured, internal running hours value is used despite RunHoursSource setting.
LightTimeOff
Setpoint group Basic settings Related FW 3.0.0
Range [units] 0 .. 250 [min]
Default value 0
Step 1
Comm object 10121 Related applications All
Config level Standard
Setpoint visibility Always
Description
Timeout for ID display backlight automatic switch off. Zero setting disables display backlight switch off.
Backlight is automatically switched on after any key press or Alarm activation.
Note: LightTimerOff setpoint influences the Remote panel not master controller when changed on
Remote panel.
Timer ON
Setpoint group Basic settings Related FW 3.0.0
Range [units] [hh:mm:ss]
Default value 0:00:00
Step [-]
Comm object 10042 Related applications All
Config level Standard
Setpoint visibility Always
Description
See Timer Repeat (page 115) description.
Timer Repeat
Setpoint group Basic settings Related FW 3.0.0
Range [units] [Never, Mon-Fri, Mon-Sat, Mon-Sun, Sat-Sun ]
Default value NEVER
Step [-]
Comm object 10045 Related applications All
Config level Standard
Setpoint visibility Always
Description
Logical binary output Timer Active is closed when actual time is over the Timer ON and opened when actual
time is over Timer OFF. The function depends on Timer Repeat settings. The output is closed when
controller is switched On and Timer settings corresponds to closed state.
ECU Diag
Setpoint group Comms Settings Related FW 3.0.0
Range [units] [ENABLED, DISABLED, EXTERNAL]
Default value ENABLED
Step [-]
Comm object 10353 Related applications All
Config level Standard
Setpoint visibility Always
Description
This setpoint is used to disable reading of diagnostic codes from ECU if an external diagnostic tool is
connected to engine.
Message ECU Diag disabled is displayed in the alarm list while ECU diagnostics is disabled.
The ECU Diagnostic is disabled/enabled using LBI:ECU DiagBlck binary input in case of setting to
EXTERNAL.
Note: The terminal is disconnected automatically after 5 min of inactivity and next communication
request from the same terminal is considered as a new connection. When logging is enabled in certain
conditions the history may be filled up with large number of records related to the communication and
important records may be overwritten quite fast.
RS232 MBCSpd
Setpoint group Comms Settings Related FW 3.0.0
Range [units] [9600, 19200, 38400, 57600, 115200] [bps]
Default value 9600
Step [-]
Comm object 24477 Related applications All
Config level Standard
Setpoint visibility Always
Description
The setpoint adjusts communication speed of the RS232 interface when RS232 Mode (page 119) is set to
MODBUS.
Note: Detailed description of Modbus protocol include some examples, see in InteliGen Communication
guide.
RS232 TermCSpd
Setpoint group Comms Settings Related FW 3.0.0
Range [units] [19200, 38400, 57600, 115200] [bps]
Default value 38400
Step [-]
Comm object 24341 Related applications All
Config level Standard
Setpoint visibility Always
Description
The setpoint adjusts communication speed of the RS232 interface when RS232 Mode (page 119) is set to
STANDARD.
RS485 MBCSpd
Setpoint group Comms Settings Related FW 3.0.0
Range [units] [9600, 19200, 38400, 57600, 115200] [bps]
Default value 9600
Step [-]
Comm object 24420 Related applications All
Config level Standard
Setpoint visibility Always
Description
The setpoint adjusts communication speed of the RS485 interface when RS485 Mode (page 120) is set to
MODBUS.
RS485 TermCSpd
Setpoint group Comms Settings Related FW 3.0.0
Range [units] [19200, 38400, 57600, 115200] [bps]
Default value 38400 bps
Step [-]
Comm object 24340 Related applications All
Config level Standard
Setpoint visibility Always
Description
The setpoint adjusts communication speed of the RS485 interface when RS485 Mode (page 120) is set to
STANDARD.
Note: In certain situations multiple sites with bus tie breakers may need to have more shared outputs
sources as the CAN bus line is in some points interrupted according to bus tie breakers position.
Normally a collision would be indicated if there were more sources on the bus and this setpoint can be
used to disable the evaluation of collisions in this special case.
Note: Step, Range and dimension depend on corresponding Analog input sensor characteristic.
StartPCoolant
Setpoint group Engine params Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 10,0
Step 0,1
Comm object 10138 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Coolant pressure limit = one of the engine running indications. To activate this function any Analog input
must be configured to Analog logical input Coolant press.
Note: PRP only
Note: Step, Range and dimension depend on corresponding Analog input sensor characteristic.
MaxCrank Time
Setpoint group Engine params Related FW 3.0.0
Range [units] 1 .. 200 [s]
Default value 8
Step 1
Comm object 8234 Related applications All
Config level Standard
Setpoint visibility Always
Description
Amount of time the controller will crank the engine in an attempt to start.
CrankFailPause
Setpoint group Engine params Related FW 3.0.0
Range [units] CMB, EME: 3 ..200 [s], AUX, PRP: 0 .. 200 [-]
Default value 8
Step 1
Comm object 8257 Related applications All
Config level Standard
Setpoint visibility Always
Description
Pause between cranking attempts.
Together with request of unlimited start attempts was created LBI PrestartOverride - activation means
immediate transition from state Prestart to Cranking.
Same function was applied to second push of START button. First press of START button activates state
Prestart, second press of START button skips prestart period.
Idle RPM
Setpoint group Engine params Related FW 3.0.0
Range [units] Starting RPM.. Nominal RPM [RPM]
Default value 500
Step 1
Comm object 9946 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Default Idle speed (should be the same as Idle speed set with engine ECU).
Idle Time
Setpoint group Engine params Related FW 3.0.0
Range [units] 0 .. 600 [s]
Default value 10
Step 1
Comm object 9097 Related applications All
Config level Standard
Setpoint visibility Always
Description
Idle time delay starts when RPM exceeds Starting RPM.
During the Idle time the Binary output Idle/Nominal is opened and after then it is closed. Binary output
Idle/Nominal opens during Cooling period (Cooling Time) again.
PrelubrPause
Setpoint group Engine params Related FW 3.0.0
Range [units] 1 .. 4000 [min]
Default value 1
Step 1
Comm object 8781 Related applications All
Config level Standard
Setpoint visibility Always
Description
Time interval between prelubrication cycles –PrelubrTime (page 127).
Note: To use Prelubrication, configure Binary output Prelubrication at first.
Prelubrication is disabled in controller OFF mode or when PrelubrTime is set to zero.
When engine is running Prelubrication binary output is opened.
Prelubrication starts PrelubrPause after engine stops. Prelubrication starts immediately when:
- controller power supply turns on
- mode changes from OFF to another
- Emergency Stop is released
Cooling Time
Setpoint group Engine params Related FW 3.0.0
Range [units] 0 .. 600 [s]
Default value 30
Step 1
Comm object 8258 Related applications All
Config level Standard
Setpoint visibility Always
Description
Runtime of unloaded engine to cool down engine before stopping.
AfterCoolTime
Setpoint group Engine params Related FW 3.0.0
Range [units] 0 .. 600 [s]
Default value 120
Step 1
Comm object 8662 Related applications All
Config level Standard
Setpoint visibility Always
Description
Binary output Cooling Pump is closed when engine starts and opens with AfterCoolTime delay after engine
stopping.
FireAlarmSpeed
Setpoint group Engine params Related FW 3.0.0
Range [units] 0,0 .. 100,0 [%]
Default value 50,0
Step 0,1 % of Requested RPM range.
Comm object 10008 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
When Binary input Fire Speed is closed the binary output Clutch Connect opens (this action deactivates
loadsharing mode if it was activated before) and Loadsharing: ThrottlePos is set to Engine params:
FireAlarmSpeed value.
EnLocalSpeed
Setpoint group Engine params Related FW 3.0.0
Range [units] [ENABLED, DISABLED]
Default value DISABLED
Step [-]
Comm object 10098 Related applications All
Config level Standard
Setpoint visibility Always
Description
ENABLED: Engine Values: Speed Request is defined by Engine params: Local speed setpoint that can
be modified by Fast edit function from front panel (4 sec Enter, / ¯, Enter).
DISABLED: Engine Values: Speed Request is changed via Binary inputs Speed Up, Speed Down or via
Logical Analog input Requested RPM.see
Speed Request (page 265) t charts for (page 266) and (page 266) modes.
RunOnlyBlkDel1
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0 .. 60 [s]
Default value 10
Step 1
Comm object 10023 Related applications All
Config level Standard
Setpoint visibility Always
Description
This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel1 (i.e. "running
only", group #1) are started to be evaluated. The "running only" alarms are not beeing evaluated while the
engine is not running or then, after start, while the adjusted delay is running.
For details see drawing, which is part of RunOnlyBlkDel3 (page 135) description.
Note:
Engine running state =
RPM > Engine params: Starting RPM or
Analog input Oil Press > Engine params: Starting Poil or
Analog input Coolant Press > Engine params: StartPCoolant (PRP only) or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3.
BinInp Delay 2
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0 .. 60 [s]
Default value 5
Step 1
Comm object 10132 Related applications All
Config level Standard
Setpoint visibility Always
Description
Binary input protection is activated when input is closed for longer time than BinInp delay 2. To use this filter,
binary input protection Delay must be configured in DriveConfig to BinInp delay 2. For details see BinInp
Delay 3 (page 137) description.
ForceBlockDel2
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0 .. 60 [s]
Default value 0
Step 1
Comm object 10570 Related applications All
Config level Standard
Setpoint visibility Always
Description
Delay for Force block protection activation after binary input Force Block 2 is opened. Protection
deactivation is without delay. Protection is activated/deactivated independent on engine running or not
running state.
Overspeed
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0 .. 200 [%]
Default value 110
Step 1% of Nominal RPM
Comm object 8263 Related applications All
Config level Standard
Setpoint visibility Always
Description
Threshold for engine overspeed protection.
MinLoadSpeed
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0 .. Nominal RPM [RPM]
Default value 500
Step 1
Comm object 10139 Related applications All
Config level Standard
Setpoint visibility Always
Description
Binary output Ready to load is closed if RPM > MinLoadSpeed and engine is in Running state. Use this
output to enable/disable connecting of engine load. MinLoadSpeed is a condition to close BO Close Load
when panel I/0 button is used to connect load to engine.
Batt > V
Setpoint group Engine protect Related FW 3.0.0
Range [units] Batt <V.. 40,0 [V]
Default value 30,0
Step 0,1
Comm object 9587 Related applications All
Config level Standard
Setpoint visibility Always
Description
Warning level for battery over voltage.
OverloadSpLim
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0,0 .. 100,0 [%]
Default value 20,0
Step 0,1
Comm object 9950 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Engine overload protection limit. See Requested RPM, Overload protection (PRP only) (page 27)
Service Time
Setpoint group Engine protect Related FW 3.0.0
Range [units] 0 .. 65535 [h]
Default value 65535
Step 1
Comm object 9648 Related applications All
Config level Standard
Setpoint visibility Always
Description
Running hours count down counter is decremented when engine is running. Service alarm is indicated in
Alarm list and History record is done when counter reaches zero. Service time setpoint is initial counter
value and it is gradually decrement when engine runs.
Note: Once the service time has elapsed the Service time will have to be adjusted to non-zero value to
clear the alarm and begin a new countdown.
ECUAlarmMode
Setpoint group Engine protect Related FW 3.0.0
Range [units] [DEFAULT, ALARM ONLY]
Default value DEFAULT
Step [-]
Comm object 15813 Related applications All
Config level Standard
Setpoint visibility Always
Description
DEFAULT: LBO: Common Wrn is activated , if ECU alarm is received by controller.
ALARM ONLY: LBO: Common Wrn is not activated, if ECU alarm is received by controller.
RPM dependent Oil pressure and Coolant pressure protections are available in PRP (propulsion) application
only. Both protections are by default set to Protection block type = RunOnlyBlkDel1 (Engine running - block
delay 1).
There are two setpoints for linear Warning limit, two for Shutdown limit and one for delay. Setpoints adjusting
step and range depends on corresponding sensor characteristics.
Note: The particular RPM dependent protection is fully disabled if both xxxIdlexxx and xxxNomxxx parameters
are set to value 0,0. I.e. the protection is not activated even if measured value is negative (e.g. when there is a
wrong sensor calibration).
OPIdleRPMWrn
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 0,0
Step 0,1
Comm object 10140 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Linear Warning characteristic is defined by two points for Idle RPM and Nominal RPM.OPIdleRPMWrn
defines oil pressure warning level at idle speed.
OPIdleRPMSd
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 0,0
Step 0,1
Comm object 10142 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Linear Shutdown characteristic is defined by two points for Idle RPM and Nominal RPM.OPIdleRPMSd
defines oil pressure shutdown level at idle speed. For details see OilPrRPMdel (page 145) description.
OPNomRPMSd
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 0,0 YES
Step 0,1
Comm object 10143 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Linear Shutdown characteristic is defined by two points for Idle RPM and Nominal RPM.OPNomRPMSd
defines oil pressure shutdown level at nominal speed. For details see OilPrRPMdel (page 145) description.
To activate RPM dependent oil pressure protection any analog value has to be linked with LAI: Oil Press.
Note: RPM dependent oil pressure protection is fix configured Protection block type = Engine running
only with RunOnlyBlkDel1 delay.
CPIdleRPMWrn
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 0,0 YES
Step 0,1
Comm object 10144 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Linear Warning characteristic is defined by two points for Idle RPM and Nominal RPM.CPIdleRPMWrn
defines coolant pressure warning level at idle speed. For details see CoolPrRPMdel (page 147) description.
CPIdleRPMSd
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 0,0
Step 0,1
Comm object 10146 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Linear Shutdown characteristic is defined by two points for Idle RPM and Nominal RPM.CPIdleRPMSd
defines coolant pressure shutdown level at idle speed. For details see CoolPrRPMdel (page 147) description.
CPNomRPMSd
Setpoint group RPMdep Protect Related FW 3.0.0
Range [units] 0,0 .. 10,0 [Bar]
Default value 0,0
Step 0,1
Comm object 10147 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Linear Shutdown characteristic is defined by two points for Idle RPM and Nominal RPM.CPNomRPMSd
defines coolant pressure shutdown level at nominal speed. For details see CoolPrRPMdel (page 147)
description.
To activate RPM dependent coolant pressure protection any analog value has to be linked with LAI: Coolant
Press.
Note: RPM dependent coolant pressure protection is fix configured Protection block type = Engine
running only with RunOnlyBlkDel1 delay.
Load Int
Setpoint group Load sharing Related FW 3.0.0
Range [units] 0,0 .. 100,0 [%]
Default value 10,0
Step 0,1
Comm object 8713 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Relative Integration factor of the load sharing loop.
RQSP Aver
Setpoint group Load sharing Related FW 3.0.0
Range [units] 0 .. 1000 [%]
Default value 5
Step 1
Comm object 10136 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Average value calculated from all Speed Request values of controllers running in Loadsharing mode together
(on the same CAN2 bus). See Load sharing block diagram (page 150).
ID-DCU
Value Description Dimension InteliMonitor MARINE
display
Loadsharing group
Average of Requested RPM values
RQSP aver calculated from all controllers participating % YES YES
in loadsharing
RQSP RQSP aver value after ramp specified by
% YES YES
ramp Loadsharing: RQSP Ramp setpoint
ThrottlePos Throttle position % YES YES
Engine values group
Speed
Speed request % YES NO
Request
Note: The maximal ThrottlePos difference between parallel operating engines (due to Load sharing
function) is 1,5%.
ThrottlePos output (request to EMS) is switched to be equal to the Engine Values: Speed request after
other engines clutches are disconnected (no load sharing, only one engine powers the shaft).
Note: The Loadsharing state can be activated from Running state and if both following conditions are
met:
Actual Engine speed is in range specified by setpoints Loadsharing: ClutchMinSpeed and
ClutchMaxSpeed
Logical Binary input Rem Clutch is active (or I/0 front panel button is pressed)
There is loadsharing activation delay specified by setpoint Loadsharing: Clutch Del to postpone
loadsharing regulation after transient events after engine mechanical connection to gear-box.
Note: It is essential requirement to configure engine load information (ECU value “actual load”, physical
analog input reading actuator position feedback or boost pressure etc.) into Logical Analog input Engine
Torque for loadsharing functionality.
Note: All ID-DCU Marine controllers working in the same loadsharing group have to be interconnected
on CAN2 bus, controllers must have different controller addresses.
Note: Loadsharing state - the Loadsharing: Back Up Speed value is taken into account instead of Engine
Values: Speed Request if the Logical Analog input Requested RPM indicates Sensor Fail (#####) and
Logical Binary input Back Up Speed is active.
Clutch Del
Setpoint group Load sharing Related FW 3.0.0
Range [units] 0,0 .. 60,0 [s]
Default value 5
Step 0,1
Comm object 9949 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Time between the clutch is switched on/off and the load sharing function is activated.
ClutchMaxSpeed
Setpoint group Load sharing Related FW 3.0.0
Range [units] ClutchMinSpeed .. 100,0 [%]
Default value 100,0
Step 0,1
Comm object 10097 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Clutch can be switched on if ClutchMinSpeed < RPM < ClutchMaxSpeed. Limits are in % of Requested
speed. See Requested RPM, Overload protection (PRP only) (page 27)
Note: 0,0% corresponds to (Idle speed + Idle offset) value, 100,0% corresponds to Nominal speed.
MaxClStrtPer
Setpoint group Load sharing Related FW 3.0.0
Range [units] 0 .. 600 [s]
Default value 60
Step 1
Comm object 10102 Related applications PRP
Config level Standard
Setpoint visibility Always
Description
Engine clutch start protection. Start fail alarm is activated, if engine running condition is not detected during
MaxClStrPer delay time after Binary output Clutch Connect is closed.
AIN2 Offset
Setpoint group Analog Inputs Related FW 3.0.0
Range [units] -32767 .. 32767 [-]
Default value 0
Step [-]
Comm object 8407 Related applications
Config level Standard
Setpoint visibility Always
Description
Adjustable offset for AIN2 for calibrating purposes.
AIN3 Offset
Setpoint group Analog Inputs Related FW 3.0.0
Range [units] -32767 .. 32767 [-]
Default value 0
Step [-]
Comm object 8467 Related applications
Config level Standard
Setpoint visibility Always
Description
Adjustable offset for AIN3 for calibrating purposes.
AIN5 Offset
Setpoint group Analog Inputs Related FW 3.0.0
Range [units] -32767 .. 32767 [-]
Default value 0
Step [-]
Comm object 8794 Related applications
Config level Standard
Setpoint visibility Always
Description
Adjustable offset for AIN5s for calibrating purposes.
AIN6 Offset
Setpoint group Analog Inputs Related FW 3.0.0
Range [units] -32767 .. 32767 [-]
Default value 0
Step [-]
Comm object 8795 Related applications
Config level Standard
Setpoint visibility Always
Description
Adjustable offset for AIN6 for calibrating purposes.
AIN8 Offset
Setpoint group Analog Inputs Related FW 3.0.0
Range [units] -32767 .. 32767 [-]
Default value 0
Step [-]
Comm object 11599 Related applications
Config level Standard
Setpoint visibility Always
Description
Adjustable offset for AIN8 for calibrating purposes.
Note: Both SMS and E-MAIL active call types are supported in conjunction with InternetBridge-NT, if
cellular interface is used (WAN connection mode = Cellular). E-MAIL only is supported, if Ethernet
interface is used (WAN connection mode = Ethernet).
Note: To receive DATA active call run InteliMonitor – Type of connection = Active call. InteliMonitor
Active call window contains list of received AID files. Each list item contains Engine name, Date, Time,
ID serial number.
Note: Both SMS and E-MAIL active call types are supported in conjunction with InternetBridge-NT, if
cellular interface is used (WAN connection mode = Cellular). E-MAIL only is supported, if Ethernet
interface is used (WAN connection mode = Ethernet).
Note: To receive DATA active call run InteliMonitor – Type of connection = Active call. InteliMonitor
Active call window contains list of received AID files. Each list item contains Engine name, Date, Time,
ID serial number.
Note: Both SMS and E-MAIL active call types are supported in conjunction with InternetBridge-NT, if
cellular interface is used (WAN connection mode = Cellular). E-MAIL only is supported, if Ethernet
interface is used (WAN connection mode = Ethernet).
Note: To receive DATA active call run InteliMonitor – Type of connection = Active call. InteliMonitor
Active call window contains list of received AID files. Each list item contains Engine name, Date, Time,
ID serial number.
AcallCH3-Addr
Setpoint group Act. Calls/SMS Related FW 3.0.0
Range [units] [-]
Default value 0
Step [-]
Comm object 9599 Related applications All
Config level Standard
Setpoint visibility Always
Description
Address for channel 3 active call. Each above message type has either phone number or e-mail address
associated with it.
Num Rings AA
Setpoint group Act. Calls/SMS Related FW 3.0.0
Range [units] 1 .. 30 [-]
Default value 3
Step 1
Comm object 24512 Related applications All
Config level Standard
Setpoint visibility Always
Description
Number of rings prior to open modem connection from PC to controller.
Note: Num Rings AA change is not accepted immediately, but only after controller is switched on or
when modem is connected to controller.
Date
Setpoint group Date/Time Related FW 3.0.0
Range [units] [DD:MM:YY]
Default value 8.6.2006
Step [-]
Comm object 24553 Related applications All
Config level Standard
Setpoint visibility Always
Description
Actual date adjustment
DISABLED The automatic change to daylight saving time and back is disabled.
The automatic change is enabled, the current season is winter and the controller is
WINTER
located in the northern hemisphere.
The automatic change is enabled, the current season is summer and the controller is
SUMMER
located in the northern hemisphere.
The automatic change is enabled, the current season is winter and the controller is
WINTER-S
located in the southern hemisphere.
The automatic change is enabled, the current season is summer and the controller is
SUMMER-S
located in the southern hemisphere.
EnTimeSync
Setpoint group Date/Time Related FW 3.0.0
Range [units] [DISABLED, ENABLED]
Default value DISABLED
Step [-]
Comm object 24217 Related applications All
Config level Standard
Setpoint visibility Always
Description
The setpoint is used to enable Time synchronization function with InteliGen-NT and InteliSys-NT
controllers over CAN2 bus.
The synchronization is just unidirectional from InteliGen-NT or InteliSys-NT controller into InteliDrive-
DCU Marine, not vice versa.
FreqRate1
Setpoint group SCM unit Related FW 3.0.0
Range [units] 0 .. 500 [-]
Default value 0
Step 1
Comm object 10902 Related applications All
Config level Standard
Setpoint visibility Always
Description
Conversion constant (number of pulses for one RPM) for ID-SCM RPM1 frequency input - SCM Freq1
value. Frequency range max. 8 kHz.
FreqRate2
Setpoint group SCM unit Related FW 3.0.0
Range [units] 0 .. 500 [-]
Default value 0
Step 1
Comm object 10903 Related applications All
Config level Standard
Setpoint visibility Always
Description
Conversion constant (number of pulses for one RPM) for ID-SCM RPM2 frequency input - SCM Freq2
value. Frequency range max. 8 kHz.
TransferRate1
Setpoint group SCM unit Related FW 3.0.0
Range [units] 0 .. 500 [-]
Default value 0
Step 1
Comm object 10906 Related applications All
Config level Standard
Setpoint visibility Always
Description
Conversion ratio (number of pulses for increase by 1) for ID-SCM IMP 1 impulse input / SCM Imp1 value.
Frequency range max. 60 Hz.
Example: To measure actual water flow in liters (or cubic meters) per minute set FreqRate = 10 [ ]
when sensor gives 10 pulses per liter (or cubic meters).
Example: To measure total water consumption in liters (or cubic meters) set TransferRate = 100 [ ]
when sensor gives 100 pulses per 1liter (or cubic meter).
DetCon20
DelayLoadRed
Setpoint group DetCon20 Related FW 3.0.0
Range [units] 0,0 .. 25,4 [s]
Default value 1,0 s YES
Step 0,1 s
Comm object 10303 Related applications All
Config level Standard
Setpoint visibility DetCon20 support configured
Description
Delay after load reduction defines delay of timing signal reduction process after knocking level drops below
the IgnRedLimit.
IgnRedLimit
Setpoint group DetCon20 Related FW 3.0.0
Range [units] 0 .. 255 [-]
Default value 10 YES
Step 1
Comm object 10299 Related applications All
Config level Standard
Setpoint visibility DetCon20 support configured
Description
Ignition reduction limit is knocking value above which the engine is considered to be knocking. If the value is
exceeded, DetCon20 binary output ENGINE KNOCKING is activated and the values assigned to the timing
reduction are altered.
ImmStopLimit
Setpoint group DetCon20 Related FW 3.0.0
Range [units] 0 .. 255 [-]
Default value 40 YES
Step 1
Comm object 10304 Related applications All
Config level Standard
Setpoint visibility DetCon20 support configured
Description
Immediate stop limit is knocking value above which DetCon20 binary output TRIP is activated. This causes
engine to shut down if properly wired.
StartBlocking3 183
StartBlocking4 183
StartBlocking5 183
Load Blocking 183
RunIndication1 184
RunIndication2 184
RunIndication3 184
Nominal Speed 185
Loaded 185
Emerg. Manual 185
EnClutchStart 185
Sd Override 186
Speed Down 186
Low Brightness
Related FW 3.0.0 Related applications All
Comm object 5
Description
Active Binary input switches ID-DCU MARINE display backlight between two adjustable intensity levels.
Alternative intensity of the backlight can be set independently by ID-DCU MARINE panel buttons:
1. Hold Enter and press Page to switch to ID Info screen (from any measure screen)
2. Hold Enter and pres / ¯ arrow key to increase/decrease display brightness
The adjusted intensity is stored in non-volatile memory.
Note: Both backlight levels are default (from production) set to maximum.
Force Block 1
Related FW 3.0.0 Related applications All
Comm object 16
Description
Active input blocks protections that are configured as “Force Block 1” Prot. block type. Corresponding
setpoint is ForceBlockDel1.
Force Block 2
Related FW 3.0.0 Related applications All
Comm object 17
Description
Active input blocks protections that are configured as “Force Block 2” Prot. block type. Corresponding
setpoint is ForceBlockDel2.
Force Block 3
Related FW 3.0.0 Related applications All
Comm object 18
Description
Active input blocks protections that are configured as “Force Block 3” Prot. block type. Corresponding
setpoint is ForceBlockDel3.
Horn Reset
Related FW 3.0.0 Related applications All
Comm object 153
Description
Binary input Horn Reset is level sensitive.
Remote OFF
Related FW 3.0.0 Related applications All
Comm object 12
Description
Controller is switched to OFF mode if input is closed and back to previous mode after is opened. Input is not
active in LOC (Local) mode. Active binary input Remote OFF is indicated by “L” character in the right upper
corner on ID-DCU MARINE screen.
Note: Remote OFF will switch controller to OFF mode even if the Access Lock or Remote Lock is active
or Controller mode is password protected.
Remote HRB
Related FW 3.0.0 Related applications All
Comm object 14
Description
Controller is switched to HRB mode if closed and back to previous mode if opened. Input is not active in
LOC (Local) mode.
Remote On/Off
Related FW 3.0.0 Related applications All
Comm object 161
Description
Binary output Close load is closed/opened depends on the state of Remote On/Off binary input when engine
RPM is over Engine protection: MinLoadSpeed. Remote On/Off is not active in LOC mode.
EmergencyStop1
Related FW 3.0.0 Related applications All
Comm object 927
Description
If the input is activated, engine shutdown is immediately performed. However, the controller behavior is
slightly different compared to other shutdown alarms:
Outputs Cooling pump and Prelubrication are deactivated as well.
This input cannot be overriden with the input Sd override.
Note: Because of safety reasons it is recommended to configure this input as Normally closed and use a
NC switch.
EmergencyStop2
Related FW 3.0.0 Related applications All
Comm object 928
Description
If the input is activated, engine shutdown is immediately performed. However, the controller behavior is
slightly different compared to other shutdown alarms:
Outputs Cooling pump and Prelubrication are deactivated as well.
This input cannot be overriden with the input Sd override.
Note: Because of safety reasons it is recommended to configure this input as Normally closed and use a
NC switch.
Remote Stop
Related FW 3.0.0 Related applications All
Comm object 157
Description
Engine “edge sensitive” stop request. The first edge changes engine state from running to cooling, the
second edge stops engine (skip the rest of cooling). Binary input is inactive in LOC (Local) mode.
Remote Stop signal is equivalent to ID-DCU MARINE front panel Stop button.
Note: Binary inputs Remote Start and Remote Stop are edge (not level) sensitive. Minimal pulse
duration to safely detect the edge is at least the 120 ms (binary input sampling rate is 100 ms).
Reg Inhib
Related FW 3.0.0 Related applications All
Comm object 837
Description
Active signal inhibits automatic DPF filter regeneration.
RegenForce
Related FW 3.0.0 Related applications All
Comm object 836
Description
Active signal inhibits automatic DPF filter regeneration.
Note: The setpoint Crank Attempts is not followed if Sd Override is active, crank attempts number is
then unlimited in case of Blackout Start.
Fire Speed
Related FW 3.0.0 Related applications All
Comm object 160
Description
If active, clutch is disconnected and Loadsharing: ThrottlePos is set to Engine params: FireAlarmSpeed, the
ThrottlePos value change is influenced by ramp specified by Loadsharing: RQSP Ramp.
Rem Clutch
Related FW 3.0.0 Related applications PRP
Comm object 183
Description
If active closes binary output Clutch Connect – see CLUTCH CONNECT (PRP ONLY) (PAGE 201)
StartBlocking1
Related FW 3.0.0 Related applications All
Comm object 68
Description
OR logical function of all StartBlocking Logical Binary inputs forces controller NotReady state ( i.e. disables
engine start). It is active in LOC (Local) mode as well.
StartBlocking3
Related FW 3.0.0 Related applications All
Comm object 581
Description
OR logical function of all StartBlocking Logical Binary inputs forces controller NotReady state ( i.e. disables
engine start). It is active in LOC (Local) mode as well.
StartBlocking4
Related FW 3.0.0 Related applications All
Comm object 582
Description
OR logical function of all StartBlocking Logical Binary inputs forces controller NotReady state ( i.e. disables
engine start). It is active in LOC (Local) mode as well.
StartBlocking5
Related FW 3.0.0 Related applications All
Comm object 583
Description
OR logical function of all StartBlocking Logical Binary inputs forces controller NotReady state ( i.e. disables
engine start). It is active in LOC (Local) mode as well.
Load Blocking
Related FW 3.0.0 Related applications All
Comm object 182
Description
Active input disables the Close load function. No influence when Binary output Close load is closed.
RunIndication2
Related FW 3.0.0 Related applications All
Comm object 47
Description
Binary input can be used for engine running indication e.g. via Oil pressure contact. Active Running
indication blocks engine start (to avoid starter damage).
Engine running state = RPM > Engine params: Starting RPM or
Analog input Oil pressure > Engine params: Starting Poil or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3.
RunIndication3
Related FW 3.0.0 Related applications All
Comm object 48
Description
Binary input can be used for engine running indication e.g. via Oil pressure contact. Active Running
indication blocks engine start (to avoid starter damage).
Engine running state = RPM > Engine params: Starting RPM or
Analog input Oil pressure > Engine params: Starting Poil or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3.
Loaded
Related FW 3.0.0 Related applications All
Comm object 162
Description
Binary input function for loaded engine indication.
Emerg. Manual
Related FW 3.0.0 Related applications All
Comm object 45
Description
This input is designed to allow the engine to be controlled externally, not by the controller. This feature is
especially designed for marine gen-sets, which are supposed to be started manually as the controller has no
power supply before the gen-set is started. It may be also useful in case of testing the gen-set or in case of a
failure, which does not allow the gen-set to be controlled by the controller, but the gen-set itself is stays
operational.
The controller behaves following way:
Shows the text EmergMan in the engine status on the main screen.
Stops all functions regarding the engine control, deactivates all outputs related to it except Fuel
Solenoid.
Stop Fail alarm is not being evaluated and Stop Solenoid is not activated if nonzero speed is
detected.
When the input is deactivated, the controller takes control over the engine according to the situation
in which the gen-set was in the moment of deactivation. I.e. the engine remains running if it was
running in the moment the input was deactivated.
EnClutchStart
Related FW 3.0.0 Related applications PRP
Comm object 163
Description
Binary input activates Engine start via clutch. Engine is started by the other running engine via closed clutch
- binary output Clutch Connect. See MaxClStrtPer (page 155) protection setpoint.
Note: The setpoint Crank Attempts is not followed if Sd Override is active, crank attempts number is
then unlimited in case of Blackout Start.
Speed Down
Related FW 3.0.0 Related applications All
Comm object 164
Description
The Engine Values: Speed Request is decreased / increased when the binary input is closed. Speed Down
has higher priority when both Up and Down inputs are active. RPM inc/dec rate is defined by setpoint Engine
params: BI Speed ramp.
Engine speed can be set by Logical Analog Input Requested RPM or by BI Speed Up and Speed Down.
Following Speed Request initialization is valid when Analog input Requested RPM is not configured.
Speed Request (Idle) = 0,0%. Inputs are active in LOC (Local) mode.
Speed Request (Running) = 50,0% for AUX (ECU 50% = Nominal RPM).
Speed Request (Running) = 0,0% for PRP.
See Engine Values: (page 266) and (page 266) modes.
Note: Minimal Speed Up and Speed Down pulse duration is 110ms to be accepted by controller.
Note: Minimal Speed Up and Speed Down pulse duration is 110ms to be accepted by controller.
ECU FltReset
Related FW 3.0.0 Related applications All
Comm object 166
Description
Binary input for ECU Alarm acknowledge (level sensitive) has the same function as controller front panel
Fault reset button (screen sensitive - active only in ECU Alarm list screen).
Note: Activation of ECU Fault reset will affect InteliDrive DCU Marine controller only, no reset request
is sent to ECU. There is separated acknowledge input for Alarms – see Binary input FAULT RESET
(PAGE 178).
BI Second RPM
Related FW 3.0.0 Related applications All
Comm object 168
Description
This input changes state of logical binary output Second RPM Sw that can be configured as J1939 output to
change ECU mode. Input is active only when Basic setting: Speed Select = BIN.INPUT.
BI Idle
Related FW 3.0.0 Related applications All
Comm object 169
Description
This input changes state of logical binary output Idle/Nominal that can be configured as J1939 output to
change ECU mode. Input is active only when Basic setting: Idle/Nominal = BIN.INPUT.
Rem Start/Stop
Related FW 3.0.0 Related applications All
Comm object 172
Description
Rem Start/Stop is level signal that activates engine start when closed and stop after is opened. It is inactive
in LOC (Local) mode.
It is not possible to stop engine by panel Stop button and by Binary input Remote Stop when Rem Start/Stop
is active. Rem Start/Stop input can be configured to Binary output Timer active to enable engine automatic
start/stop function – see Basic settings / Timer setpoints.
Note: Engine “Start fail” is Warning (level 1) protection and does not block another start when Rem
Start/Stop is still closed. To prevent unlimited number of starts – configure on LBO Start fail Sd
protection.
Note: Engine stays running when Rem Start/Stop is opened in controller LOC (Local) mode.
ClutchBlocking
Related FW 3.0.0 Related applications PRP
Comm object 182
Description
ClutchBlocking can block the LBO Clutch Connect. Active input is indicated in Alarm list as “Clutch
Blocking” message.
ModeL Button
Related FW 3.0.0 Related applications All
Comm object 200
Description
Input simulates the panel ← Mode button
ModeR Button
Related FW 3.0.0 Related applications All
Comm object 201
Description
Input simulates the panel Mode → button.
Page Button
Related FW 3.0.0 Related applications All
Comm object 202
Description
Input simulates the panel Page button.
Up Button
Related FW 3.0.0 Related applications All
Comm object 204
Description
Input simulates the panel ↑-button.
Down Button
Related FW 3.0.0 Related applications All
Comm object 205
Description
Input simulates the panel ↓ button.
ECU DiagBlck
Related FW 3.0.0 Related applications All
Comm object 269
Description
Input controls ECU Diagnostic functionality in case of setting ECU Diag = EXTERNAL.
Clear DayCons
Related FW 3.0.0 Related applications All
Comm object 220
Description
Rising edge clears Day consumption counter.
Memo1 Trigger
Related FW 3.0.0 Related applications All
Comm object 584
Description
Rising edge forces to fill register Statistics: Memo1 by Logical Analog Input: Memory1 actual value.
Memo1 Statistics value can be set or resetted by InteliMonitor command.
Memo2 Trigger
Related FW 3.0.0 Related applications All
Comm object 585
Description
Rising edge forces to fill register Statistics: Memo2 by Logical Analog Input: Memory2 actual value. Memo2
Statistics value can be set or resetted by InteliMonitor command.
User Mask 1
Related FW 3.0.0 Related applications All
Comm object 567
Description
This input allows user to activate chosen function in ScreenEditor (tool inside DriveConfig) for particular
screen instrument. User may choose from the following functions:
Note: This function can be used to "swap" between two different screen instruments when certain
conditions are fulfilled. Logical binary inputs Mask 1..4 can be used to define any custom condition for
this "swapping" function.
User Mask 2
Related FW 3.0.0 Related applications All
Comm object 568
Description
This input allows user to activate chosen function in ScreenEditor (tool inside DriveConfig) for particular
screen instrument. User may choose from the following functions:
Note: This function can be used to "swap" between two different screen instruments when certain
conditions are fulfilled. Logical binary inputs Mask 1..4 can be used to define any custom condition for
this "swapping" function.
Note: This function can be used to "swap" between two different screen instruments when certain
conditions are fulfilled. Logical binary inputs Mask 1..4 can be used to define any custom condition for
this "swapping" function.
User Mask 4
Related FW 3.0.0 Related applications All
Comm object 570
Description
This input allows user to activate chosen function in ScreenEditor (tool inside DriveConfig) for particular
screen instrument. User may choose from the following functions:
Note: This function can be used to "swap" between two different screen instruments when certain
conditions are fulfilled. Logical binary inputs Mask 1..4 can be used to define any custom condition for
this "swapping" function.
Aftertreatment
Related FW 3.0.0 Related applications All
Comm object 1842
Description
Indicates that Aftertreatment control is available with configured engine support.
DPF Lamp
Related FW 3.0.0 Related applications All
Comm object 1831
Description
Active signal indicates that DPF (Diesel Particulate Filter) is starting to overfill with soot because the
system is unable to undertake an automatic active regeneration. It starts flashing when the DPF is nearly
full, engine power may be reduced.
HEST Lamp
Related FW 3.0.0 Related applications All
Comm object 1373
Description
Indicates High Exhaust System Temperature (HEST). It may be active during DPF regeneration to indicate
higher than normal exhaust temperatures.
Horn
Related FW 3.0.0 Related applications All
Comm object 1
Description
Binary output for Horn, Buzzer alarm acoustic indication. Output is automatically switched off after Engine
protection: Horn timeout. Horn is active unlimited time (until Fault reset) when Horn timeout = 0.
Common Alarm
Related FW 3.0.0 Related applications All
Comm object 256
Description
The output closes if any Wrn, Sd, Cd, Fls, alarm is active and stays closed until all alarms disappear and
Fault reset is pressed = output is opened when Alarm list is empty.
Common Wrn
Related FW 3.0.0 Related applications All
Comm object 3
Description
The output closes when any Warning alarm is active. Output opens when all Wrn alarms disappear and Fault
reset is pressed (no Wrn alarm in Alarm list).
Common Sd
Related FW 3.0.0 Related applications All
Comm object 4
Description
The output closes when any Shut-down alarm is active. Output opens when all Sd alarms disappear and
Fault reset is pressed (no Sd alarm in Alarm list).
Common Cd
Related FW 3.0.0 Related applications All
Comm object 257
Description
The output closes when any Cool-down alarm is active. Output opens when all Cd alarms disappear and
Fault reset is pressed (no Cd alarm in Alarm list).
CMD RegInhOn
Related FW 3.0.0 Related applications All
Comm object 1942
Description
Provides feedback information that command (LBI function) REGENINHIBIT (PAGE 216) is active
OFF Mode
Related FW 3.0.0 Related applications All
Comm object 17
Description
TThe output is closed in controller OFF mode.
DPF Lamp
Related FW 3.0.0 Related applications All
Comm object 1831
Description
Active signal indicates that DPF (Diesel Particulate Filter) is starting to overfill with soot because the
system is unable to undertake an automatic active regeneration. It starts flashing when the DPF is nearly
full, engine power may be reduced.
Controller mode
Related FW 3.0.0 Related applications PRP, AUX, HRB
Comm object 9887
Description
PRP Mode (PRP only) The output is closed in controller PRP mode.
AUX Mode (AUX only) The output is closed in controller AUX mode.
HRB Mode (CMB only) The output is closed in controller HRB mode.
In LOC
Related FW 3.0.0 Related applications All
Comm object 259
Description
The output is closed, if LOC (Local) mode is selected.
CPU Ready
Related FW 3.0.0 Related applications All
Comm object 260
Description
CPU indication – output is closed when CPU is ready.
Idle/Nominal
Related FW 3.0.0 Related applications All
Comm object 39
Description
The output closes during engine start, after Idle time setpoint elapses. The output opens again after Cooling
time is finished. The opposite logic output Nominal/Idle is available as well.
Note: Connect Binary output Idle/Nominal to electronic speed governor to switch the speed: opened =
IDLE, closed=RATED.
HEST Lamp
Related FW 3.0.0 Related applications All
Comm object 1373
Description
Indicates High Exhaust System Temperature (HEST). It may be active during DPF regeneration to indicate
higher than normal exhaust temperatures.
Starter
Related FW 3.0.0 Related applications All
Comm object 24
Description
Closed output energizes the engine starter.
Stop Solenoid
Related FW 3.0.0 Related applications All
Comm object 23
Description
Output is closed during engine stopping procedure.
Prestart
Related FW 3.0.0 Related applications All
Comm object 36
Description
Periodic prelubrication function – see Engine params: PrelubrTime (page 127) and PrelubrPause (page 127).
Ready To Start
Related FW 3.0.0 Related applications All
Comm object 262
Description
Engine ready for start indication: no start blocking alarm is active. Output is active in LOC (Local) mode as
well (even if can’t be started by binary inputs).
Ready To Load
Related FW 3.0.0 Related applications All
Comm object 67
Description
Output closes if the engine is in Running state and can be loaded. Opens in Cooling state. Active only if
RPM > MinLoadSpeed.
RedStopLamp
Related FW 3.0.0 Related applications All
Comm object 1829
Description
Active when continued operation could result in damage to exhaust system, but actual reason of the alarm
may not be exhasut system related.
Ignition
Related FW 3.0.0 Related applications All
Comm object 37
Description
Ignition system activation/deactivation during start - stop procedure.
The output becomes active during cranking if RPM > 30, becomes inactive during cranking pause and after
stop of the engine (RPM = 0).
Unload
Related FW 3.0.0 Related applications All
Comm object 264
Description
1 sec (fix) pulse prior to transfer from Running to Cooling state.
Cooling
Related FW 3.0.0 Related applications All
Comm object 74
Description
Closes in cooling state, opens after engine stop.
Fuel Solenoid
Related FW 3.0.0 Related applications All
Comm object 22
Description
Closed output opens the fuel solenoid. Adjustable to DIESEL or GAS. See also the Fuel Solenoid (page 130)
setpoint description.
Watchdog
Related FW 3.0.0 Related applications All
Comm object 81
Description
Indicates correctly running firmware when cycling on/off with 0,5s period.
Close Load
Related FW 3.0.0 Related applications All
Comm object 755
Description
Output is closed when panel 0/1 (On/Off) button is pressed or Binary input Remote On/Off is closed and
engine RPM is over Engine protection: MinLoadSpeed.
Output opens when RPM is bellow MinLoadSpeed. Close load can´t be opened by button when Binary input
Remote On/Off (level sensitive) is closed.
Droop Sw
Related FW 3.0.0 Related applications All
Comm object 266
Description
The output is closed when setpoint Basic setting: Governor Mode = DROOP or Governor Mode =
BIN.INPUT and corresponding Binary input BI Droop is closed. This logical output (Source) can be
configured to corresponding J1939 output (e.g. Governor Mode in Volvo-IndustrialD12 Aux).
Example:
Nominal speed at full load: 1500 rpm
Min offset: -50 rpm
Max offset: +50 rpm
"Nominal speed offset" = 0 × 3A = 58 % => speed offset = +8 rpm
Referens speed to govenor at full load = 1500 + 8 = 1508 rpm
DEF LowLvlamp
Related FW 3.0.0 Related applications All
Comm object 1833
Description
Active signal indicates low level of Diesel Exhaust Fluid (DEF). It starts flashing when the DEF tank is
nearly empty (e.g. when the level is 10%), engine power may be reduced.
Alarm Blink
Related FW 3.0.0 Related applications All
Comm object 275
Description
Function is based on Binary output Common Alarm - stays closed when any alarm is active (at least one
item in Alarm list) and opens for 2 sec when any new Alarm is activated. The first activation is delayed 2 sec.
No Fault reset influence when at least one alarm is active. Output opens when Alarm list is empty.
Idle Sw
Related FW 3.0.0 Related applications All
Comm object 276
Description
The output is closed when setpoint Basic setting: Idle/Nominal = NOMINAL or Idle/Nominal = BIN.INPUT
and corresponding Binary input BI Nominal is closed. This logical output (Source) can be configured to
corresponding J1939 output (e.g. Idle Speed Select in Volvo-IndustrialD12 Aux).
Logical 0
Related FW 3.0.0 Related applications All
Comm object 26
Description
Constant value that can be configured to any output (e.g. CurrentGear in Volvo-PRP).
Logical 1
Related FW 3.0.0 Related applications All
Comm object 27
Description
Constant value that can be configured to any output (e.g. CurrentGear in Volvo-PRP).
Timer Active
Related FW 3.0.0 Related applications All
Comm object 277
Description
Binary output Timer Active is closed and opened according to Timer setpoints setting. Engine starts and
stops when this output is connected (configured) to Binary input Rem Start/Stop. Timer is active in all
controller modes include OFF mode.
Alarm BlinkAct
Related FW 3.0.0 Related applications All
Comm object 278
Description
It follows the panel Red LED. Starts blink after any (Wrn, Sd) Alarm is activated, light after Fault reset,
disappear after Fault reset when no alarm is active.
Common SdO
Related FW 3.0.0 Related applications All
Comm object 251
Description
Indicates any active protection configured as Shut down Override.
Derating Alarm
Related FW 3.0.0 Related applications All
Comm object 279
Description
Power derating indication, information received from communication bus.
ECU PowerRelay
Related FW 3.0.0 Related applications All
Comm object 116
Description
The output closes at the beginning of prestart and opens if the engine shall be stopped.This output can be
used to indicate when the ECU should be powered up i.e. only while the engine is running.
This output also influences evaluation of communication failure with ECU and related FLS alarms from
analog inputs read from the ECU. If the output is configured (which means configured on physical binary
output or VBOUT output), the issuing of communication error is blocked during Prestart and Stopping
procedure as shown in the picture.
Note: The input must be configured on physical binary output or VBOUT output. It is not enough to
configure it as a PLC input for example.
StartButtEcho
Related FW 3.0.0 Related applications All
Comm object 281
Description
1 sec pulse is generated after panel Start button is pressed.
FltResButtEcho
Related FW 3.0.0 Related applications All
Comm object 283
Description
1 sec pulse is generated after panel Fault reset button is pressed. The pulse is generated only in case that
Alarm List screen is displayed on the controller, i.e. in the time of possibility to acknowledge alarms.
HrnResButtEcho
Related FW 3.0.0 Related applications All
Comm object 284
Description
1 sec pulse is generated after panel Horn reset button is pressed.
ClutchButtEcho
Related FW 3.0.0 Related applications All
Comm object 285
Description
1 sec pulse is generated after panel I/0 button is pressed.
Note: Horn reset function works for remote acces from DriveMonitor, Modbus, Modem, ... as well
MalfunctLamp
Related FW 3.0.0 Related applications All
Comm object 1832
Description
Indicates that emissions related engine fault code is active.
ActLoadShar
Related FW 3.0.0 Related applications All
Comm object 449
Description
Indication of active Load sharing.
AirFlaps
Related FW 3.0.0 Related applications All
Comm object 620
Description
AirFlaps output is activated with engine starting (when controller enters state Cranking) and it is deactivated
5s after engine stopping.
User Button 1
Related FW 3.0.0 Related applications All
Comm object 726
Description
InteliVision function buttons can be assigned to these LBOs User Button 1 .. 16. The configuration of
button’s functionality is done via Screen Editor feature in DriveConfig PC application.
User Button 2
Related FW 3.0.0 Related applications All
Comm object 727
Description
InteliVision function buttons can be assigned to these LBOs User Button 1 .. 16. The configuration of
button’s functionality is done via Screen Editor feature in DriveConfig PC application.
User Button 3
Related FW 3.0.0 Related applications All
Comm object 728
Description
InteliVision function buttons can be assigned to these LBOs User Button 1 .. 16. The configuration of
button’s functionality is done via Screen Editor feature in DriveConfig PC application.
User Button 4
Related FW 3.0.0 Related applications All
Comm object 729
Description
InteliVision function buttons can be assigned to these LBOs User Button 1 .. 16. The configuration of
button’s functionality is done via Screen Editor feature in DriveConfig PC application.
User Button 6
Related FW 3.0.0 Related applications All
Comm object 751
Description
InteliVision function buttons can be assigned to these LBOs User Button 1 .. 16. The configuration of
button’s functionality is done via Screen Editor feature in DriveConfig PC application.
User Button 7
Related FW 3.0.0 Related applications All
Comm object 752
Description
InteliVision function buttons can be assigned to these LBOs User Button 1 .. 16. The configuration of
button’s functionality is done via Screen Editor feature in DriveConfig PC application.
User Button 8
Related FW 3.0.0 Related applications All
Comm object 1087
Description
InteliVision function buttons can be assigned to these LBOs User Button 1 .. 16. The configuration of
button’s functionality is done via Screen Editor feature in DriveConfig PC application.
User Button 9
Related FW 3.0.0 Related applications All
Comm object 1088
Description
InteliVision function buttons can be assigned to these LBOs User Button 1 .. 16. The configuration of
button’s functionality is done via Screen Editor feature in DriveConfig PC application.
User Button 11
Related FW 3.0.0 Related applications All
Comm object 1090
Description
InteliVision function buttons can be assigned to these LBOs User Button 1 .. 16. The configuration of
button’s functionality is done via Screen Editor feature in DriveConfig PC application.
User Button 12
Related FW 3.0.0 Related applications All
Comm object 1091
Description
InteliVision function buttons can be assigned to these LBOs User Button 1 .. 16. The configuration of
button’s functionality is done via Screen Editor feature in DriveConfig PC application.
User Button 13
Related FW 3.0.0 Related applications All
Comm object 1092
Description
InteliVision function buttons can be assigned to these LBOs User Button 1 .. 16. The configuration of
button’s functionality is done via Screen Editor feature in DriveConfig PC application.
User Button 14
Related FW 3.0.0 Related applications All
Comm object 1093
Description
InteliVision function buttons can be assigned to these LBOs User Button 1 .. 16. The configuration of
button’s functionality is done via Screen Editor feature in DriveConfig PC application.
User Button 16
Related FW 3.0.0 Related applications All
Comm object 1095
Description
InteliVision function buttons can be assigned to these LBOs User Button 1 .. 16. The configuration of
button’s functionality is done via Screen Editor feature in DriveConfig PC application.
RegenInhibit
Related FW 3.0.0 Related applications All
Comm object 960
Description
Indicates that automatic DPF filter regeneration is inhibited using REG INHIB (PAGE 180).
RegenInhibLamp
Related FW 3.0.0 Related applications All
Comm object 1834
Description
Indicates that diesel particulate filter regeneration is inhibited.
RegenForce
Related FW 3.0.0 Related applications All
Comm object 961
Description
Indicates that automatic DPF filter regeneration is forced using REGENFORCE (PAGE 180).
RemoteControl1
Related FW 3.0.0 Related applications All
Comm object 141
Description
Those eight LBOs can be handled from InteliMonitor Remote switch window. This way can operator directly
handle controller binary outputs or other e.g. PLC functions.
RemoteControl2
Related FW 3.0.0 Related applications All
Comm object 142
Description
Those eight LBOs can be handled from InteliMonitor Remote switch window. This way can operator directly
handle controller binary outputs or other e.g. PLC functions.
RemoteControl3
Related FW 3.0.0 Related applications All
Comm object 143
Description
Those eight LBOs can be handled from InteliMonitor Remote switch window. This way can operator directly
handle controller binary outputs or other e.g. PLC functions.
RemoteControl4
Related FW 3.0.0 Related applications All
Comm object 144
Description
Those eight LBOs can be handled from InteliMonitor Remote switch window. This way can operator directly
handle controller binary outputs or other e.g. PLC functions.
RemoteControl6
Related FW 3.0.0 Related applications All
Comm object 146
Description
Those eight LBOs can be handled from InteliMonitor Remote switch window. This way can operator directly
handle controller binary outputs or other e.g. PLC functions.
RemoteControl7
Related FW 3.0.0 Related applications All
Comm object 147
Description
Those eight LBOs can be handled from InteliMonitor Remote switch window. This way can operator directly
handle controller binary outputs or other e.g. PLC functions.
RemoteControl8
Related FW 3.0.0 Related applications All
Comm object 148
Description
Those eight LBOs can be handled from InteliMonitor Remote switch window. This way can operator directly
handle controller binary outputs or other e.g. PLC functions.
FS-Status
Related FW 3.0.0 Related applications RPU
Comm object 10213
Description
Binary output Fuel solenoid (FS) status when output is opened:
0 OK
1 Fail: Broken wire (BW)
FS-Load
Related FW 3.0.0 Related applications RPU
Comm object 10213
Description
Binary output Fuel solenoid (FS) status when output is opened:
0 OK
1 Fail: Broken wire (BW)
SS-Status
Related FW 3.0.0 Related applications RPU
Comm object 10213
Description
Binary output Stop solenoid (SS) status when output is closed – see FS-Status (page 219)
FS / SS -Status FS / SS -Load
FS / SS is closed, normal operation 1 No meaning
FS / SS is closed, HC or OT 0 No meaning
FS / SS is opened, normal operation No meaning 0
FS / SS is opened, BW No meaning 1
BinOut Power
Related FW 3.0.0 Related applications RPU
Comm object 10213
Description
Status of ID-RPU Fuel solenoid and Stop solenoid power supply terminal. Active when Power supply is
NOT connected.
Battery Fail
Related FW 3.0.0 Related applications RPU
Comm object 10213
Description
Indicates that system is switched to Battery B.
RPU control
Related FW 3.0.0 Related applications RPU
Comm object 10213
Description
When closed ID-RPU module is active (after ID-DCU MARINE fail) for engine Sd and Overspeed
protection.
CommError 10
Related FW 3.0.0 Related applications All
Comm object 2007
Description
J1939 communication fail indication.
Bw RPU StopSol
Related FW 3.0.0 Related applications All
Comm object 324
Description
ID-RPU Binary output Stop solenoid - Broken wire indication.
Note: Binary output Stop solenoid and Fuel solenoid broken wire is indicated in open state.
ECU AlarmList
Related FW 3.0.0 Related applications All
Comm object 303
Description
Output is closed when at least one item is in ECU Alarm list.
UnivState 1
Related FW 3.0.0 Related applications All
Comm object 185
Description
Universal states 1 to Universal states 7 indication. See Universal states (page 31) description.
UnivState 2
Related FW 3.0.0 Related applications All
Comm object 186
Description
Universal states 1 to Universal states 7 indication. See Universal states (page 31) description.
UnivState 3
Related FW 3.0.0 Related applications All
Comm object 187
Description
Universal states 1 to Universal states 7 indication. See Universal states (page 31) description.
UnivState 5
Related FW 3.0.0 Related applications All
Comm object 189
Description
Universal states 1 to Universal states 7 indication. See Universal states (page 31) description.
UnivState 6
Related FW 3.0.0 Related applications All
Comm object 190
Description
Universal states 1 to Universal states 7 indication. See Universal states (page 31) description.
UnivState 7
Related FW 3.0.0 Related applications All
Comm object 191
Description
Universal states 1 to Universal states 7 indication. See Universal states (page 31) description.
EcuDiagBlocked
Related FW 3.0.0 Related applications All
Comm object
Description
Output is closed when Basic setting: ECU Diag = DISABLED.
PLC Message 1
Related FW 3.0.0 Related applications All
Comm object 181
Description
The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list.
PLC Message 3
Related FW 3.0.0 Related applications All
Comm object 183
Description
The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list.
PLC Message 4
Related FW 3.0.0 Related applications All
Comm object 184
Description
The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list.
PLC Message 5
Related FW 3.0.0 Related applications All
Comm object 372
Description
The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list.
PLC Message 6
Related FW 3.0.0 Related applications All
Comm object 373
Description
The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list.
PLC Message 7
Related FW 3.0.0 Related applications All
Comm object 374
Description
The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list.
PLC Message 9
Related FW 3.0.0 Related applications All
Comm object 530
Description
The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list.
PLC Message 10
Related FW 3.0.0 Related applications All
Comm object 531
Description
The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list.
PLC Message 11
Related FW 3.0.0 Related applications All
Comm object 532
Description
The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list.
PLC Message 12
Related FW 3.0.0 Related applications All
Comm object 533
Description
The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list.
PLC Message 13
Related FW 3.0.0 Related applications All
Comm object 534
Description
The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list.
PLC Message 15
Related FW 3.0.0 Related applications All
Comm object 792
Description
The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list.
PLC Message 16
Related FW 3.0.0 Related applications All
Comm object 793
Description
The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list.
Emergency Stop
Related FW 3.0.0 Related applications All
Comm object 260
Description
Indication of Emergency Stop input.
Engine RPM
Related FW 3.0.0 Related applications All
Comm object
Description
Engine speed state indication. Output is closed when no RPM is received from J1939 (sensor fail) or
Overspeed or Under speed is detected.
Overload
Related FW 3.0.0 Related applications All
Comm object
Description
Active overload protection activation.
ChrgAlternFail
Related FW 3.0.0 Related applications All
Comm object
Description
Charger fail detection. D+ output current is limited to cca 300 mA.
Guaranteed level for signal Charging OK = 90% of supply voltage.
There are three possible conditions for stop engine cranking: Starting RPM, StartingPOil and D+ function
(when ENABLED). Starter goes off when any of these conditions becomes valid.
Stop Fail
Related FW 3.0.0 Related applications All
Comm object
Description
Engine stop fail indication. Stop fail: engine does not reach 0 RPM after stop command within Engine
params: Stop time.
Overspeed
Related FW 3.0.0 Related applications All
Comm object 779
Description
Engine overspeed indication.
Underspeed
Related FW 3.0.0 Related applications All
Comm object
Description
Under speed indication.
Battery Flat
Related FW 3.0.0 Related applications All
Comm object
Description
ID-DCU MARINE controller reset during Cranking state.
Battery Volt
Related FW 3.0.0 Related applications All
Comm object 1293
Description
Indication when battery voltage (ID-DCU MARINE power supply) is out of Engine protect: Batt <V and Batt
>V limits.
WrnService Time
Related FW 3.0.0 Related applications All
Comm object
Description
Output is closed when Service time (count down) = 0.
Note: History record and Alarm list indication is activated as well.
Not Lubricated
Related FW 3.0.0 Related applications All
Comm object
Description
The lubrication cycle (PrelubrTime) is not finished after controller Switch on or return from OFF mode.
OP RPMdep
Related FW 3.0.0 Related applications All
Comm object
Description
Out of Oil pressure RPM dependent limit indication.
CP RPMdep
Related FW 3.0.0 Related applications All
Comm object
Description
Out of Cooling pressure RPM dependent limit indication.
Battery A volt
Related FW 3.0.0 Related applications All
Comm object
Description
It is closed when the battery A voltage of RPU is out of limits: Engine protection: Batt >V, Batt <V, Batt V
del.
Battery B volt
Related FW 3.0.0 Related applications All
Comm object
Description
It is closed when the battery B voltage of RPU is out of limits: Engine protection: Batt >V, Batt <V, Batt V
del.
Start Blocking
Related FW 3.0.0 Related applications All
Comm object
Description
Start blocking indication.
ClutchBlocking
Related FW 3.0.0 Related applications All
Comm object
Description
Clutch blocking indication.
Running
Engine running state indication.
Overspeed
Engine overspeed indication.
OilPress
Oil pressure out of limit indication.
OilTemp
Oil temperature out of limit indication.
CoolantTemp
Coolant temperature out of limit indication.
Coolant Level
Coolant level out of limit indication.
Running
Related FW 3.0.0 Related applications All
Comm object 67
Description
Engine running state indication.
Overspeed
Related FW 3.0.0 Related applications All
Comm object 779
Description
Engine overspeed indication.
OilPress
Related FW 3.0.0 Related applications All
Comm object 521
Description
Oil pressure out of limit indication.
CoolantLevel
Related FW 3.0.0 Related applications All
Comm object
Description
Coolant level out of limit indication.
6 back to Controller
objects
Engine Speed
Related FW 3.0.0 Related applications All
Comm object 8
Description
RPM value from ECU - J1939.
Oil Press
Related FW 3.0.0 Related applications All
Comm object 9
Description
Engine oil pressure, which is displayed at the first controller screen.
Note: Configure Oil Press logical analog input (LAI card in DriveConfig) to display the value at the first
controller screen.
Coolant Temp
Related FW 3.0.0 Related applications All
Comm object 67
Description
Engine coolant temperature, which is displayed at the first controller screen.
Note: Configure Coolant Temp logical analog input (LAI card in DriveConfig) to display the value at the
first controller screen.
Fuel ConsAct
Related FW 3.0.0 Related applications All
Comm object 82
Description
There are two cumulative Statistics registers - values TripCons and DayCons. Those statistic values
increment value based on sampling of Logical Analog Input Fuel ConsAct. LAI can be sourced from ECU
Fuel Rate [ l/h ] or separate Actual Fuel consumption sensor connected to physical Analog input.
Both statistics values is possible to modify in InteliMonitor – Set Statistics command or clear by Logical
Binary Inputs ClearDayCons or ClearTripCons.
BoatSpeed
Related FW 3.0.0 Related applications All
Comm object 117
Description
Analog input for boat speed value [kts], which is used for MomAvgFlCon L (page 281) calculation
1. Default configuration
ID / AIN_Function = Oil Press; MainScrAna1
ID / AIN2_Function = Coolant Temp; MainScrAna2
2. To display e.g. value from AIN3 “AirTemp1” instead “OilPress” (the first position) and AIN4
“AirTemp2” instead “CoolTemp” value:
a. Select AIN3 Property Function = MainScrAna1
b. Select AIN4 Property Function = MainScrAna2
c. Create new language (in DriveConfig Languages) based on English
d. Rename (in DriveConfig Translator / Other texts) text “OilPress” to “AirTemp1” in the newly
created language
e. Rename (in DriveConfig Translator / Other texts) text “CoolTemp” (no space between) to
“AirTemp2” in the newly created language
f. Switch the ID-DCU Marine controller into newly created and modificated language (Enter +
Page, Page, select the new language by up/down arrows, Enter)
Note: Translate text “OilPress” and “CoolTemp” - no space between words because of similar texts (e.g.
Coolant Temp, etc. are located on other screens).
1. Default configuration
ID / AIN_Function = Oil Press; MainScrAna1
ID / AIN2_Function = Coolant Temp; MainScrAna2
2. To display e.g. value from AIN3 “AirTemp1” instead “OilPress” (the first position) and AIN4
“AirTemp2” instead “CoolTemp” value:
a. Select AIN3 Property Function = MainScrAna1
b. Select AIN4 Property Function = MainScrAna2
c. Create new language (in DriveConfig Languages) based on English
d. Rename (in DriveConfig Translator / Other texts) text “OilPress” to “AirTemp1” in the newly
created language
e. Rename (in DriveConfig Translator / Other texts) text “CoolTemp” (no space between) to
“AirTemp2” in the newly created language
f. Switch the ID-DCU Marine controller into newly created and modificated language (Enter +
Page, Page, select the new language by up/down arrows, Enter)
Note: Translate text “OilPress” and “CoolTemp” - no space between words because of similar texts (e.g.
Coolant Temp, etc. are located on other screens).
Cold Temp 1
Related FW 3.0.0 Related applications All
Comm object 56
Description
If there is an additional terminal board between a thermocouple sensor and the IS-AIN8 (TC) module and
there is a significant temperature difference between this terminal board and the module, it is necessary to
measure the temperature at this terminal board and use this temperature for the thermocouple compensation
instead of the internal temperature of the module.
Cold Temp 1 Logical Analog input is intended for measurement of this thermocouple compensation
temperature for the IS-AIN8 (TC) module with index #1, Cold Temp 2 corresponds to IS-AIN8 (TC) module
with index #2 etc.
Note: Thermocouples without internal compensation "Thermo(nc)..." must be used for this case.
Cold Temp 3
Related FW 3.0.0 Related applications All
Comm object 58
Description
If there is an additional terminal board between a thermocouple sensor and the IS-AIN8 (TC) module and
there is a significant temperature difference between this terminal board and the module, it is necessary to
measure the temperature at this terminal board and use this temperature for the thermocouple compensation
instead of the internal temperature of the module.
Cold Temp 1 Logical Analog input is intended for measurement of this thermocouple compensation
temperature for the IS-AIN8 (TC) module with index #1, Cold Temp 2 corresponds to IS-AIN8 (TC) module
with index #2 etc.
Note: Thermocouples without internal compensation "Thermo(nc)..." must be used for this case.
Cold Temp 4
Related FW 3.0.0 Related applications All
Comm object 59
Description
If there is an additional terminal board between a thermocouple sensor and the IS-AIN8 (TC) module and
there is a significant temperature difference between this terminal board and the module, it is necessary to
measure the temperature at this terminal board and use this temperature for the thermocouple compensation
instead of the internal temperature of the module.
Cold Temp 1 Logical Analog input is intended for measurement of this thermocouple compensation
temperature for the IS-AIN8 (TC) module with index #1, Cold Temp 2 corresponds to IS-AIN8 (TC) module
with index #2 etc.
Note: Thermocouples without internal compensation "Thermo(nc)..." must be used for this case.
Cyl Temp 2
Related FW 3.0.0 Related applications All
Comm object 18
Description
Analog inputs for engine Cylinder temperature measuring.
Cyl Temp 3
Related FW 3.0.0 Related applications All
Comm object 19
Description
Analog inputs for engine Cylinder temperature measuring.
Cyl Temp 4
Related FW 3.0.0 Related applications All
Comm object 20
Description
Analog inputs for engine Cylinder temperature measuring.
Cyl Temp 5
Related FW 3.0.0 Related applications All
Comm object 21
Description
Analog inputs for engine Cylinder temperature measuring.
Cyl Temp 6
Related FW 3.0.0 Related applications All
Comm object 22
Description
Analog inputs for engine Cylinder temperature measuring.
Cyl Temp 8
Related FW 3.0.0 Related applications All
Comm object 24
Description
Analog inputs for engine Cylinder temperature measuring.
Cyl Temp 9
Related FW 3.0.0 Related applications All
Comm object 25
Description
Analog inputs for engine Cylinder temperature measuring.
Cyl Temp 10
Related FW 3.0.0 Related applications All
Comm object 26
Description
Analog inputs for engine Cylinder temperature measuring.
Cyl Temp 11
Related FW 3.0.0 Related applications All
Comm object 27
Description
Analog inputs for engine Cylinder temperature measuring.
Cyl Temp 12
Related FW 3.0.0 Related applications All
Comm object 28
Description
Analog inputs for engine Cylinder temperature measuring.
Cyl Temp 14
Related FW 3.0.0 Related applications All
Comm object 30
Description
Analog inputs for engine Cylinder temperature measuring.
Cyl Temp 15
Related FW 3.0.0 Related applications All
Comm object 31
Description
Analog inputs for engine Cylinder temperature measuring.
Cyl Temp 16
Related FW 3.0.0 Related applications All
Comm object 32
Description
Analog inputs for engine Cylinder temperature measuring.
Expert field is now empty. This field is visible in Expert mode only.
4. Above step configured protection are now visible in Expert field and corresponding limits as well.
5. Add the third protection: “+” button, and edit Property (e.g. Wrn, Under, ….) Any protection limit/delay can be
set to Constant (then value is fixed, specified in line below) and can not be changed by customer (not
included in setpoint list) … or …
Use “+” button to add Delay setpoint and set/change name value and limits.
Note: Configure this UnivState to some Binary output and modify Bin output Name.
Oil pressure and Water temperature on the first ID controller screen indication
1. Reading from ID-DCU MARINE analog inputs
logical function
8.1.6 Values
EngRPMfiltered
Value group Basic settings Related FW 3.0.0
Resolution [units] 1 [RPM]
Comm object 11401 Related applications All
Description
Filtered current engine speed for nice displaying without nozzle oscillations.
Note: limit is defined by the value of the communication object of specified number
Mode Loc
Value group Basic settings Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 10135 Related applications All
Description
Text string value containing "LOC" or empty text string depending on Activated or Deactivated LOC mode.
SpeedReq RPM
Value group Engine values Related FW 3.0.0
Resolution [units] 1 [RPM]
Comm object 10006 Related applications All
Description
application PROP conversion 0,0% = 0.3 * NominalRPM, 100,0% = 1.1 * NominalRPM
application AUX/CMB/EME conversion 0,0% = 0.9 * NominalRPM, 100,0% = 1.1 * NominalRPM
In the case of sensor fail (out of range) is Sped request = 0 for PRP and 50% (=Nominal RPM) for AUX
configuration.
T Cyl Max
Value group Engine values Related FW 3.0.0
Resolution [units] 1 [°C]
Comm object 10526 Related applications All
Description
Detected maximal temperature value from Logical Analog inputs Cyl Temp 1 .. Cyl Temp 16.
T Cyl Min
Value group Engine values Related FW 3.0.0
Resolution [units] 1 [°C]
Comm object 10527 Related applications All
Description
Detected minimal temperature value from Logical Analog inputs Cyl Temp 1 .. Cyl Temp 16.
Oil Press
Value group Engine values Related FW 3.0.0
Resolution [units] 1 [Bar]
Comm object 10268 Related applications All
Description
Internal value corresponding to Logical Analog input Oil Press.
Cool Temp
Value group Engine values Related FW 3.0.0
Resolution [units] 1 [°C]
Comm object 10267 Related applications All
Description
Internal value corresponding to Logical Analog input Coolant Temp
CPU Temp
Value group Analog CU Related FW 3.0.0
Resolution [units] 1 [°C]
Comm object 10124 Related applications All
Description
Internal Temperature measured on controller board.
D+
Value group Analog CU Related FW 3.0.0
Resolution [units] 1 [V]
Comm object 10603 Related applications All
Description
Engine alternator output voltage detected at D+ controller terminal.
Oil Press
Value group Analog CU Related FW 3.0.0
Resolution [units] 1 [Bar]
Comm object 9155 Related applications All
Description
AIN CU 2
Value group Analog CU Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 9156 Related applications All
Description
Analog input value corresponding to analog input located directly on ID-DCU controller.
Note: The name "Ain CU 2" is just default value which can be changed in analog input Property: Name.
AIN CU 4
Value group Analog CU Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 9158 Related applications All
Description
Analog input value corresponding to analog input located directly on ID-DCU controller.
Note: The name "Ain CU 4" is just default value which can be changed in analog input Property: Name.
AIN CU 5
Value group Analog CU Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 9159 Related applications All
Description
Analog input value corresponding to analog input located directly on ID-DCU controller.
Note: The name "Ain CU 5" is just default value which can be changed in analog input Property: Name.
AIN CU 6
Value group Analog CU Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 9160 Related applications All
Description
Analog input value corresponding to analog input located directly on ID-DCU controller.
Note: The name "Ain CU 6" is just default value which can be changed in analog input Property: Name.
AIN CU 8
Value group Analog CU Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 9162 Related applications All
Description
Analog input value corresponding to analog input located directly on ID-DCU controller.
Note: The name "Ain CU 8" is just default value which can be changed in analog input Property: Name.
ID BOUT
Value group Binary CU Related FW 3.0.0
Resolution [units] [-]
Comm object 8239 Related applications All
Description
Controller binary outputs state indication.
LogBout 2
Value group LogBout Related FW 3.0.0
Resolution [units] [-]
Comm object 9144 Related applications All
Description
List of logical binary outpus.
LogBout 3
Value group LogBout Related FW 3.0.0
Resolution [units] [-]
Comm object 9145 Related applications All
Description
List of logical binary outpus.
LogBout 4
Value group LogBout Related FW 3.0.0
Resolution [units] [-]
Comm object 9146 Related applications All
Description
List of logical binary outpus.
LogBout 5
Value group LogBout Related FW 3.0.0
Resolution [units] [-]
Comm object 9147 Related applications All
Description
List of logical binary outpus.
LogBout 7
Value group LogBout Related FW 3.0.0
Resolution [units] [-]
Comm object 9149 Related applications All
Description
List of logical binary outpus.
RemoteControl
Value group LogBout Related FW 3.0.0
Resolution [units] [-]
Comm object 10627 Related applications All
Description
List of logical binary outpus, which can be closed and opened remotely, e.g. from InteliMonitor using the
"Remote switches" tool or using MODBUS communication.
PasswordDecode
Value group Info Related FW 3.0.0
Resolution [units] [-]
Comm object 9090 Related applications All
Description
This value contains encrypted serial number of the controller and administrator password and is intended for
retrieving of the lost password. Send this number together with controller serial number to your distributor if
you need to retrieve your password.
Build date
Value group Info Related FW 3.0.0
Resolution [units] [-]
Comm object 24211 Related applications All
Description
Date of controller fimrware creation.
SW version
Value group Info Related FW 3.0.0
Resolution [units] [-]
Comm object 24339 Related applications
Description
Major and minor firmware version number. E.g. value "2,2" means version 2.2. Release version number is
not included.
SW Branch
Value group Info Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 8707 Related applications
Description
Firmware branch code. Contains 1 in case of standard branches.
Mode ID
Value group Info Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 9887 Related applications
Description
This value contains actual controller mode. The controller mode is selected by the setpoint Basic Settings:
Mode ID but the setpoint can be overridden by Logical Binary input Remote OFF.
Timer Text
Value group Info Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 10040 Related applications
Description
Code of the currently running system process timer. The text representation of each code can be obtained by
the procedure described at the value Engine state.
Timer Val
Value group Info Related FW 3.0.0
Resolution [units] 1 [s]
Comm object 8955 Related applications
Description
The value contains remaining time of the currently running system process timer.
Note: Alarm linked with a specific bit is defined in ESC (Engine Specific Code) and is not user
configurable.
ECU Alarms 2
Value group Info Related FW 3.0.0
Resolution [units] [-]
Comm object 10917 Related applications All
Description
States of predefined ECU alarms, which are available with Modbus reading.
Note: Alarm linked with a specific bit is defined in ESC (Engine Specific Code) and is not user
configurable.
ECU Alarms 3
Value group Info Related FW 3.0.0
Resolution [units] [-]
Comm object 10918 Related applications All
Description
States of predefined ECU alarms, which are available with Modbus reading.
Note: Alarm linked with a specific bit is defined in ESC (Engine Specific Code) and is not user
configurable.
ECU Alarms 4
Value group Info Related FW 3.0.0
Resolution [units] [-]
Comm object 10919 Related applications All
Description
States of predefined ECU alarms, which are available with Modbus reading.
Note: Alarm linked with a specific bit is defined in ESC (Engine Specific Code) and is not user
configurable.
Latitude
Value group Info Related FW 3.0.0
Resolution [units] [-]
Comm object 11678 Related applications All
Description
GPS coordinate received from InternetBridge-NT (IB-NT).
Longitude
Value group Info Related FW 3.0.0
Resolution [units] [-]
Comm object 11679 Related applications All
Description
GPS coordinate received from InternetBridge-NT (IB-NT).
GPS Speed
Value group Info Related FW 3.0.0
Resolution [units] 0,1 [kts]
Comm object 12165 Related applications All
Description
Speed in knots received from IB-NT (1 knot = 1,852 km/h).
NumSuccStarts
Value group Statistics Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 8207 Related applications All
Description
Successful engine start number counter. The counter is increased by 1 even if the particular start command
will take more than one attempt.
Note: The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set statistics.
NumUnscStarts
Value group Statistics Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 10149 Related applications All
Description
Unsuccessful starts counter. The counter is incremented always when Start fail alarm is issued.
Note: The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set statistics.
Service Time
Value group Statistics Related FW 3.0.0
Resolution [units] 1[-]
Comm object 9648 Related applications All
Description
This is maintenance countdown timer. The timer is located in setpoints group Engine protect as well as in
Statistics values. Adjust the timer to the requested maintenance interval. It will be decremented while the
engine is running. The alarm WrnServiceTime is issued as soon as the timer counts down to zero.
TripCons
Value group Statistics Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 9817 Related applications All
Description
Trip fuel consumption calculated by controller from LAI: Fuel ConsAct.
Memo1
Value group Statistics Related FW 3.0.0
Resolution [units] 1 [-]
Comm object 8230 Related applications All
Description
There are two Statistics registers Memo1 and Memo2. Those statistic values are based on Logical Analog
Input Memory1 or Memory2 value in the time of Logical Binary input Memo1 Trigger or Memo2 Trigger
rising edge. Both statistics values is possible to modify in InteliMonitor – Set Statistics command.
MomAvgFlCon L
Value group Statistics Related FW 3.0.0
Resolution [units] 0,1 [/nm]
Comm object 11321 Related applications All
Description
Momentary average fuel consumption per nautical mile. It is available, if both LAI: FuelConsump and LAI:
BoatSpeed are configured.
DEF Level
Value group Aftertreatment Related FW 3.0.0
Resolution [units] 1 [%]
Comm object 14522 Related applications All
Description
Indicates aftertreatment Diesel Exhaust Fluid tank level in percent.
Following are examples of transfer characteristics 0 - 100% to 4 – 20mA. The first case is transfer
characteristics -25 - 100% to 0 – 20mA, it contains the needed conversion to 4 – 20mA.