Chiller Plant Calculation & Raw Data Required

The document outlines formulas to calculate: 1) Heat rejected by each cooling tower and total heat rejected based on flow rate, specific heat of water, and temperature differences. 2) Cooling load of each chiller and total cooling load using similar parameters. 3) Power consumption and efficiencies of chillers, pumps, cooling towers, and heat exchangers. 4) Total system efficiency, component efficiencies, and percent heat balance are also defined. Raw data needed from logging includes flow rates, temperatures and power readings over 7 days at 1 minute intervals.

Uploaded by

Budi Iswahyudi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
681 views1 page

Chiller Plant Calculation & Raw Data Required

The document outlines formulas to calculate: 1) Heat rejected by each cooling tower and total heat rejected based on flow rate, specific heat of water, and temperature differences. 2) Cooling load of each chiller and total cooling load using similar parameters. 3) Power consumption and efficiencies of chillers, pumps, cooling towers, and heat exchangers. 4) Total system efficiency, component efficiencies, and percent heat balance are also defined. Raw data needed from logging includes flow rates, temperatures and power readings over 7 days at 1 minute intervals.

Uploaded by

Budi Iswahyudi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Calculation Formula

Heat Rejected (kW)


Cooling Tower 1 HR = CWRF1 (L/s) x 4.19 (kJ/kg oC) x [CWTR1 - CWTS1] ( oC)
Cooling Tower 2 HR = CWRF2 (L/s) x 4.19 (kJ/kg oC) x [CWTR2 - CWTS2] ( oC)
Cooling Tower 3 HR = CWRF3 (L/s) x 4.19 (kJ/kg oC) x [CWTR3 - CWTS3] ( oC)

Total Heat Rejected (kW)


= Cooling Tower 1 HR + Cooling Tower 2 HR + Cooling Tower 3 HR
= [ CWRF1 x 4.19 x (CWTR1 - CWTS1) ] + [ CWRF2 x 4.19 x (CWTR2 - CWTS2) ] + [ CWRF3 x 4.19 x (CWTR3 - CWTS3) ]

Cooling Load (kW)


Chiller 1 CL = CHWRF1 (L/s) x 4.19 (kJ/kg oC) x [CHWTR1 - CHWTS1] ( oC)
Chiller 2 CL = CHWRF2 (L/s) x 4.19 (kJ/kg oC) x [CHWTR2 - CHWTS2] ( oC)
Chiller 3 CL = CHWRF3 (L/s) x 4.19 (kJ/kg oC) x [CHWTR3 - CHWTS3] ( oC)
Chiller 4 CL = CHWRF4 (L/s) x 4.19 (kJ/kg oC) x [CHWTR4 - CHWTS4] ( oC)

Total Cooling Load (kW)


= Chiller 1 CL + Chiller 2 CL + Chiller 3 CL + Chiller 4 CL
= [CHWRF1 x 4.19 x (CHWTR1 - CHWTS1)] + [CHWRF2 x 4.19 x (CHWTR2 - CHWTS2)] + [CHWRF3 x 4.19 x (CHWTR3 - CHWTS3)]
+ [CHWRF4 x 4.19 x (CHWTR4 - CHWTS4)]

Total Cooling Load (RT)


= Total Cooling Load (kW)
3.517

Power Consumption by component (kW)


Chillers Power = PM (Chillers_kW)
Chilled Water Pumps Power = PM (CHWPs_kW)
Condenser Water Pumps Power = PM (CWPs_kW)
Cooling Towers Power = PM (CTs_kW)
Heat Exchamger Pumps Power = PM (HXP35s_kW) + PM (HXP11s_kW)

Total Power Consumption (kW)


= Chillers Power + Chilled Water Pumps Power + Condenser Water Pumps Power + Cooling Towers Power + Heat Exchanger Pumps Power
= PM (Chillers_kW) + PM (CHWPs_kW) + PM (CWPs_kW) + PM (CTs_kW) + [PM (HXP35s_kW) + PM (HXP11s_kW)]

Total System Efficiency (kW/RT)


= Total Power Consumption (kW)
Total Cooling Load (RT)
≤ 0.66 kWRT

Component Efficiency (kW/RT)


Chiller Eff = Chillers Power (kW)
Total Cooling Load (RT)

CHWP Eff = CHWPs Power (kW) + HXPs Power (kW)


Total Cooling Load (RT)

CWP Eff = CWPs Power (kW)


Total Cooling Load (RT)

CT Eff = CTs Power (kW)


Total Cooling Load (RT)

Percent Heat Balance


% HB = [Total Cooling Load (kW) + Chillers Power (kW)] - Total Heat Rejected (kW) x 100%
≤ 5%
Total Heat Rejected (kW)

Raw Data Required from the Logging System


7 days @ 1 minute Interval
- dd/mm/yyyy hh:mm Date & Time (1 Parameters)
- CHWRF1 (L/s) - CHWTS1 (oC) - CHWTR1 (oC) Chilled Water (Flow, Suply and Return Temp) For Each Chiller
- CHWRF2 (L/s) - CHWTS2 (oC) - CHWTR2 (oC) (12 Parameters)
o
- CHWRF3 (L/s) - CHWTS3 ( C) - CHWTR3 (oC)
- CHWRF4 (L/s) - CHWTS4 (oC) - CHWTR4 (oC)

- CWRF1 (L/s) - CWTS1 (oC) - CWTR1 (oC) Condenser Water (Flow, Suply and Return Temp) For Each Cooling Tower
- CWRF2 (L/s) - CWTS2 (oC) - CWTR2 (oC) (9 Parameters)
- CWRF3 (L/s) - CWTS3 (oC) - CWTR3 (oC)

- PM (Chillers_kW) Power for Each Components


- PM (CHWPs_kW) (6 Parameters)
- PM (CWPs_kW)
- PM (CTs_kW)
- PM (HXP35s_kW)
- PM (HXP11s_kW)