P7650A/B/U: Differential Pressure Sensors
P7650A/B/U: Differential Pressure Sensors
P7650A/B/U: Differential Pressure Sensors
SPECIFICATION DATA
FEATURES
• Reduce field failures
• Excellent tolerance to overpressure & vibration
reduces field failures
APPLICATION • Reduce setup
• Selectable ranges and scales reduce setup time
The P7650 sensor can measure either air pressure or and number of models to stock
velocity. Measuring air velocity requires the use of the • High accuracy
P7650L velocity pick-up probe. The P7650 is available in • High accuracy digital sensor with seven
three installation configurations: duct, panel or universal. selectable sub-ranges maintains calibration
Duct and panel models have two pressure and velocity and reduces callbacks
options: 0-1” WC / 0-3,000 FPM or 1-10” WC / 3,000-
6,000 FPM with four field-selectable sub-ranges. • Water-resistant housing
• IP65/NEMA 4 housing allows for mounting in
The universal model comes in one pressure/velocity wash-down locations
range: 0-10” WC / 0-7,000 FPM with seven field- • Maintenance free
selectable sub-ranges. All variants are available with and
without display. The P7650 has an IP65/NEMA 4 • High reliability sensor technology for long-term,
environmental rating and a 5-year limited warranty. maintenance-free operation
• Circuit protection
• Circuit protection avoids damage due to
incorrect input wiring
PRODUCT IDENTIFICATION
Selectable w.c. Pressure Range, Supply
New Part Number Mounting Uni or Bi-Directional Velocity Mode Display Output Voltage
P7650A1000 +/-0-.1", 0-.25", 0-.5", 0-1" w.c. or 500/1,000/2,000/3,000 FPM Yes
P7650A1018 +/-25, 50, 100, 250 Pa Selectable 2.5/5/10/15MS No
P7650A1026 Panel +/-0-1", 0-2", 0-5", 0-10" or Yes
3,000/4,000/5,000/6,000 FPM
+/-0.250, 0.500, 1.00, 2.50 kPa
P7650A1034 15/20/25/30MS No
Selectable
P7650B1008 +/-0-.1", 0-.25", 0-.5", 0-1" w.c. or 500/1,000/2,000/3,000 FPM Yes
0-10Vdc, 0-5Vdc,
P7650B1016 +/-25, 50, 100, 250 Pa Selectable 2.5/5/10/15MS No 12-30Vdc
and 4-20mA
Duct or 24Vac
P7650B1024 +/-0-1", 0-2", 0-5", 0-10" or Yes Selectable
3,000/4,000/5,000/6,000 FPM
+/-0.250, 0.500, 1.00, 2.50 kPa
P7650B1032 15/20/25/30MS No
Selectable
P7650U1040 +/-0-.1", 0-.25", 0-.5", 0-1", 0-2", 0-5", No
500/1,000/2,000/3,000/4,000/
0-10" in. w.c. or
Universal 5,000/6,000/7,000 FPM
P7650U1052 +/-0.25, 0.5, 1.0, 2.5 kPa; or
2.5/5/10/15/20/25/30/35 MS Yes
+/-25, 50, 100, 250 Pa Selectable
50
31-00139-02
P7650A/B/U
31-00139—02 2
P7650A/B/U
WIRING DIAGRAMS
7 0
7 0 ZERO
1 2
ZERO
5 6
1 2
5 6
3
4
3 4
1.000
DIGITAL
OUTPUT
DIGITAL
1.000
{
CONTROL RMT. ZERO
{
RMT. V IN
ZERO –
DIGITAL
V+/PWR
V-/GND
VOUT
OUTPUT POWER –
PWR
mA RTN
DIGITAL SOURCE
CONTROL 24 VAC/DC
RETURN +
V+ M37263
M37262
Fig. 1. 2-wire, 4-20 mA Current Loop Output. Fig. 2. 3-wire, 0-5 V/0-10 V Voltage Output.
DIMENSIONS
1-19/32
(42)
3-1/2 (88)
3-3/32
(78)
19/64
4-13/32
(7)
(112)
7-13/32 (188)
M37264
3 31-00139—02
P7650A/B/U
REGULATORY INFORMATION
FCC REGULATIONS Operation is subject to the following two conditions:
1. This device may not cause interference; and
§ 15.19 (a)(3) 2. This device must accept any interference, including
interference that may cause undesired operation of
This device complies with part 15 of the FCC Rules.
the device.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
Le présent appareil est conforme aux CNR d’Industrie
2. This device must accept any interference received,
Canada applicables aux appareils radio exempts de
including interference that may cause undesired
licence. L’exploitation est autorisée aux deux conditions
operation.
suivantes :
1. l’appareil ne doit pas produire de brouillage;
IC REGULATIONS 2. l’utilisateur de l’appareil doit accepter tout brouil-
lage radioélectrique subi, même si le brouillage est
RSS-GEN susceptible d’en compromettre le fonctionnement.
This device complies with Industry Canada’s license-
exempt RSSs. FCC Warning (Part 15.21) (USA
only)
Changes or modifications not expressly approved by the
party responsible for compliance could void the user’s
authority to operate the equipment.
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or
modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any
liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.