Teleprotection: Features and Applications
Teleprotection: Features and Applications
Teleprotection: Features and Applications
TELEPROTECTION
Design production and maintenance of telecontrol equipments, special communications devices and industrial automation systems. Products built/customized
upon customer requests. Specific devices for smart grids.
www.tesmec.com PICTURES & DRAWINGS CAN BE DIFFERENT ACCORDING TO TECHNICAL SPECIFICATIONS - UPDATING PROGRAMME VARIATIONS WITHOUT NOTICE ARE POSSIBLE 01.16
BTP-1000 TECHNICAL SPECIFICATIONS
Other Features
• Analog interfaces: up to 4 independent commands in any combination • Single or redundant power supply;
or up to 16 commands with priority; • Alarms and events logging with time synchronization;
• Digital interfaces: up to 8 independent commands in any combination • Integrated trip counters;
or up to 256 commands with priority; • SNMP agent with standard and private MIBs;
• High programmability of commands parameters; • Secure management access;
• Set-reset commands (continuous commands); • Human Machine Interface (HMI) with built-in functions for easy
• Comprehensive self-test diagnostics; commissioning and maintenance.
Technical Specifications
Power supply 24/48/110/220 Vdc, ±20%, redundancy (as option)
Weight and Dimensions Up to 8 kg, 19-inch subrack, height: 6U
Standards compliance IEC 60834-1, IEC 61000-6-2, IEC 61000-6-4, IEC 60255-27
Analog interfaces: up to 4 independent commands in any combination or up to 16 commands with priority
Number of commands Digital interfaces: up to 8 independent commands in any combination or up to 256 commands with priority
Number of command cards Up to 8
Number of command inputs/ 4 command inputs + 8 command outputs + 1 alarm, inputs/outputs completely programmable
outputs for each card
Command inputs characteristics Opto-isolated contacts, nominal voltage from 24 Vdc to 250 Vdc, electrically isolated, polarity independence
Solid state relays, nominal voltage from 24 Vdc to 250 Vdc, maximum current up to 6 A (different mounted
Command outputs characteristics relays), electrically isolated
IEC 61850 support GOOSE interface to the protection, RJ45 electrical ethernet ports or SFP optical ethernet port
V.11 (32/64 kbps), G.703 (64 kbps co-directional), E1 (2 Mbps), SFP optical fibers (850/1310/1550 nm, MM/
Digital lines SM), optical IEEE C37.94
Analog lines 2/4-wire 600 Ω or high impedance, APLC/DPLC (embedded in BUPL-1000 PLC equipment)
Number of line interfaces Up to 2, simultaneously or in “hot back-up”
Dependability and security According to IEC 60834-1
Electro-mechanical relays, maximum current up to 5 A, normally closed and/or normally open free contacts,
Alarms
configurable alarm sources
Time synchronization NTP, IEEE 1588, IRIG-B
Events/alarms logging > 10000 events, non-volatile memory, trip counters
Management HMI, Web browser, SNMP, EOC, display (as option)
Applications
BTP-1000 collects vital information for
the protection of the electric power
grid and communicates to a remote
teleprotection equipment in order to
coordinate the protection devices for
fault location, transformers and other
items of electrical substations of high-
voltage transmission lines.
www.tesmec.com PICTURES & DRAWINGS CAN BE DIFFERENT ACCORDING TO TECHNICAL SPECIFICATIONS - UPDATING PROGRAMME VARIATIONS WITHOUT NOTICE ARE POSSIBLE 01.16