Building Service Project 1
Building Service Project 1
Project 1:
Case Study of Building Services in Multi-Storey Buildings Involving Public Use
1
TABLE OF CONTENTS
ACKNOWLEDGEMENT 5
ABSTRACT 6
INTRODUCTION 7
1.1 Introduction
1.2 Systems
1.2.1 Fire detection devices
- Smoke detector
- Heat detector
- Flame detector
1.2.2 Alarm
- Manual call points
- Fireman intercom
- Motorized bell
- Wall mounted horns
1.4 Conclusion
1.5 References
2.1 Introduction
2.2 Systems
2.2.1 Passive containment
- Compartmentation
- Smoke control
- Fire resistant elements
2.2.2 Means of escape
- escape routes
- Place of assembly
2.2.3 Fire fighting access
- Fire appliance access
2.4 Conclusion
2.5 References
2
TABLE OF CONTENTS
3.1 Introduction
3.2 Types of Mechanical Ventilation Systems
3.2.1 Mechanical Extract System
3.2.2 Mechanical Supply System
3.2.3 Combined Mechanical Extract & Supply
3.6 Conclusion
3.7 References
4.1 Introduction
4.2 Types of Air cycles
4.2.1 Refrigerant cycle
4.2.2 Air cycle
4.6 Conclusion
4.7 References
3
TABLE OF CONTENTS
5.1 Introduction
5.2 Elevators
5.2.1 Introduction of elevators
5.2.1.1 Specification of an elevator
5.2.1.2 Factors to determine the number of lifts
5.2.1.3 Location of lift
5.2.1.4 Criteria of elevator system
5.7 Conclusion
5.8 References
4
ACKNOWLEDGEMENT
5
ABSTRACT
6
INTRODUCTION
7
1.0 ACTIVE FIRE
PROTECTION
1.1 iNTRODUCTIONS
1.2 SYSTEMS
1.2.1 Fire detection devices
1.2.2 Alarm
1.2.3 Water Based
1.2.4 Non-Water Based
1.4 CONCLUSION
1.5 REFERENCES
8
1.0 ACTIVE FIRE PROTECTION
1.1 INTRODUCTION
1.2 SYSTEMS
1. Smoke Detectors
2. Heat Detectors
10
1.0 ACTIVE FIRE PROTECTION
2. Flame Detectors
a) Fire telephone
3. Motorized bells
13
1.0 ACTIVE FIRE PROTECTION
1. Sprinklers
14
1.0 ACTIVE FIRE PROTECTION
2. Dry Risers
15
1.0 ACTIVE FIRE PROTECTION
16
1.0 ACTIVE FIRE PROTECTION
3. Hose reels
17
1.0 ACTIVE FIRE PROTECTION
1. INERTEC system
18
1.0 ACTIVE FIRE PROTECTION
2. Fire Extinguishers
19
1.0 ACTIVE FIRE PROTECTION
Water Extinguishers
Label : Cream
20
1.0 ACTIVE FIRE PROTECTION
Dry powder extinguishers basically cuts Figure 1.25 Dry Powder extinguisher.
off the oxygen supply to the fuel.
Label : Black
21
1.0 ACTIVE FIRE PROTECTION
Label : Yellow
22
1.0 ACTIVE FIRE PROTECTION
23
1.0 ACTIVE FIRE PROTECTION
1. Smoke Detectors
2. Heat Detectors
24
1.0 ACTIVE FIRE PROTECTION
4. Fire Telephones
The fire telephones are located at the end
of each fire escape staircase.
25
1.0 ACTIVE FIRE PROTECTION
27
1.0 ACTIVE FIRE PROTECTION
28
1.0 ACTIVE FIRE PROTECTION
29
1.0 ACTIVE FIRE PROTECTION
1. Sprinklers
a) Pendent type
b) Upright type
Figure 1.44 Pendent type sprinkler.
Pendent fire sprinklers are used in the
office areas as they provide the most
coverage due to the shape of the deflector
as it is curved downwards, which helps
direct the water flow into a cone shape.
This provides maximum coverage over an
area. Other than that, they are smaller and
sleeker, and are easily installed into
ceilings without disrupting the aesthetics.
30
1.0 ACTIVE FIRE PROTECTION
1. Sprinklers (cont.)
a) 1 duty pump
b) 1 standby pump
c) 1 jockey pump
Figure 1.46 Duty pump.
The sprinklers used in the building are
designed to operate automatically and
independently in the event of fire. The
activated sprinklers will activated the
installed sprinkler system flow switch,
which will send an audible and visual
signal to the fire control panel and directly
to the nearest fire brigade. Activation of
the sprinklers also will activate the
Sprinkler Alarm Valve, which is used to
actuate an alarm when more than one
sprinkler is activated. .
Figure 1.47 Domestic water tank.
Due to the drop in water pressure once the
sprinklers are activated, this prompts the
activation of the Fire Water Pump system,
which then must be switched off manually
after the fire has been extinguished
completely. This pumpset does not
operate full time, and only functions in the
event of an emergency.
31
1.0 ACTIVE FIRE PROTECTION
2. Dry risers
The dry risers are situated outside and
inside the building, at easily accessible
points which are the;
32
1.0 ACTIVE FIRE PROTECTION
3. Hose reel
Fire hose reels serve as the first frontline
fire fighting method, which can be done by
the occupants themselves. Water flow
from the hose can be activated via the
valve. The discharge of water is
approximately 6 metres far. According to
BS 5306 Part 1: 1976, hose reels are to be
installed in recesses so that they do not
form obstructions on a route of escape. A
hose reel can be operated by turning on
the valve (located at the connection on the
pipe), reeling out the hose and directing
the nozzle at the flame base and then
turning on the nozzle.
33
1.0 ACTIVE FIRE PROTECTION
35
1.0 ACTIVE FIRE PROTECTION
36
1.0 ACTIVE FIRE PROTECTION
37
1.0 ACTIVE FIRE PROTECTION
1. INERTEC system
2. Fire Extinguishers
38
1.0 ACTIVE FIRE PROTECTION
39
1.0 ACTIVE FIRE PROTECTION
1.4 CONCLUSION
40
1.0 ACTIVE FIRE PROTECTION
1.5 REFERENCES
http://www.janusfiresystems.com/products
/water-systems/
41
2.0 PASSIVE FIRE
PROTECTION
2.1 INTRODUCTION
2.4 CONCLUSION
2.5 REFERENCES
42
2.0 PASSIVE FIRE PROTECTION
2.1 INTRODUCTION
2.2 SYSTEMS
1. Passive containment
2. Means of escape
3. Fire fighting access
a) Compartmentation
b) Staircase and lobby enclosure
c) Smoke control system
d) Flame containments on material and
construction
e) Fire resistance for wall, structural member
and height
43
2.0 PASSIVE FIRE PROTECTION
44
2.0 PASSIVE FIRE PROTECTION
a) Fire-rated door
45
2.0 PASSIVE FIRE PROTECTION
This uses positive pressurisation of all stairwells Figure 2.5 Smoke spill
in the structure. This positive pressurisation is
obtained through mechanical fans that inject
outside air into the stairwell. The purpose of
maintaining this pressure it to keep the stairwell
clear of smoke and toxic fumes. Smoke travels
from high to low pressure, the fans help create a
slightly higher pressure to control/stop the flow.
46
Figure 2.7 concrete structure
2.0 PASSIVE FIRE PROTECTION
a) Escape routes
i) Vertical exits (staircases)
47
2.0 PASSIVE FIRE PROTECTION
b) Assembly point
48
2.0 PASSIVE FIRE PROTECTION
49
2.0 PASSIVE FIRE PROTECTION
a) External access
Water outlet
50
2.0 PASSIVE FIRE PROTECTION
2.4 CONCLUSION
2,5 REFERENCES
51
3.0 MECHANICAL
VENTILATION
3.0 INTRODUCTION
3.4 CONCLUSION
3.5 REFERENCES
52
3.0 MECHANICAL VENTILATION
3.1 INTRODUCTION
53
3.0 MECHANICAL VENTILATION
Commonly found in :-
● Cinemas
● Offices
● Lecture theatres 54
● Sports centers Figure 3.4 Ventilation of
● Department stores department stores
3.0 MECHANICAL VENTILATION
- Allow - Increase in
dehumidification of heating/cooling costs
outdoor air
- May cause moisture
- Suitable for warm or problems in colder
four season climates countries
- Unable to remove
moisture from incoming
air
Table 3.1 Table of comparison
55
3.0 MECHANICAL VENTILATION
3.4.1 Fans
A ) Propeller Fan
Heavy duty
56
3.0 MECHANICAL VENTILATION
E ) Centrifugal Fan
57
Figure 3.13 Exploded diagram
of fan
3.0 MECHANICAL VENTILATION
There are five types of air filters:- Figure 3.14 varieties of air filters
A ) Dry Filters
B ) Vicious Filters
.They have high retention capacity to dust and Figure 3.15 Dry filter panel
are often used for industrial applications.It has
close spaced corrugated metal plates that is
coated in non-flammable oil..A rotating variation
has filter plates hung from chains.In
sequence,the plates would remove attached
contaminant by washing through oil
Figure 3.16 Diagram of a cell
panel
58
Figure 3.18 Oil-sprayed filter
3.0 MECHANICAL VENTILATION
C ) Bag Filter
60
3.0 MECHANICAL VENTILATION
61
3.0 MECHANICAL VENTILATION
d) Ventilation Grilles
○ Found on the most top floor of the
stairwell. Used to prevent over
pressurization of air in the stairwell,
otherwise, doors will be difficult to
open due to the over pressurization.
Which may result to difficulty in
evacuation.
(a) Where the air capacity of the fan shall be sufficient to maintain an air flow of
not less than 60 meters per minute through the doors which are deemed to be
open;
(b) Where the number of doors which are deemed to be opened at the one time
shall be 10% of the total number of door opening into the staircase with a
minimum number of two doors open;
(c) Where with all the doors closed the air pressure differential between the
staircases and the area served by it shall not exceed 5 millimeters water
gauge;
(d) Where the mechanical system to prevent smoke from entering the staircase
shall be automatically activated by a suitable heat detecting service, manual
or automatic alarm or automatic wet pipe sprinkle system;
(e) Which meets the functional requirements as may be agreed with the D.G.F.S. 63
3.0 MECHANICAL VENTILATION
a) Inlet Diffuser
○ Commonly seen type of diffusers to
supply air throughout the offices of
the building are louvre faced.
○ Reasoning:
■ Variety of air patterns.
■ Multi-directional.
■ Uniform with ceiling layout.
■ Ease of maintenance with
regards to replacements and
availability of replacements.
b) Natural Outlet Grille
○ Air outlets to allow air flow from the
interior offices spaces outwards
from the building.
○ This helps to gradually depressurize
the offices spaces, but at same time
maintaining a general positive
pressure.
○ Due to less outlet grilles compared
to the mechanical inlets.
64
3.0 MECHANICAL VENTILATION
a) Grilles
○ Located on the toilet ceilings,
extracting air from the toilets and
expelling them out from the
building.
Disclaimer*
Duct works are covered by the ceiling.
Figure 3.33 Toilet Grille
a) Exhaust System
○ Located in the elevator machine
room on the 8th floor of Block C.
○ This room uses two sets of regular
exhaust systems that utilise
propeller fans to ventilate the space
.
MS 1525:2014
8.4 Controls
8.4.2 Humidity control
In a system requiring moisture removal to maintain specific selected relative
humidity in spaces or zones, no new source of energy (such as electric reheat)
should be used to produce a space relative humidity below 70 % for comfort cooling 65
purposes.
3.0 MECHANICAL VENTILATION
3.6 CONCLUSION
3.7 REFERENCES
4.0
AIR CONDITIONING
SYSTEM
4.1 INTRODUCTION
4.6 CONCLUSION
67
4.7 REFERENCES
4.0 AIR CONDITIONING SYSTEMS
4.1 INTRODUCTION
Air conditioning also known as A.C system is the
process of altering the state of an occupied
interior space air to achieve a more favorable
environment despite changes in the external
weather conditions or internal head loads.
Generally, these modifications to the internal
space by air conditioning systems are made
through technological means. Air conditioners
are commonly used devices that serve this
purpose by replacing the internal heat with fresh
air and cooling is achieved by means of a
refrigerant cycle.
Factors for using Air- conditioning:
1. Comfort
2. Performance of workers and machinery
3. Equipment
4. Health
4.2.2 REFRIGERANTS
69
4.0 AIR CONDITIONING SYSTEMS
71
4.0 AIR CONDITIONING SYSTEMS
72
4.0 AIR CONDITIONING SYSTEMS
73
4.0 AIR CONDITIONING SYSTEMS
Figure 4.13 Floor plan of the 8th floor showing the location
of the plant room and the Cooling tower.
Liquid pumps
74
Figure 4.14 Plant room with the chiller system and the
water pumps
4.0 AIR CONDITIONING SYSTEMS
1. Cooling Tower
75
4.0 AIR CONDITIONING SYSTEMS
76
4.0 AIR CONDITIONING SYSTEMS
A. Compressor
The compressor pumps the refrigerant
through the system at a designated flow
rate and pressure to the condenser. The
refrigerant enters the compressor from the
suction side in vapour state and
compresses it as it is being pumped
through causing an increase in the
temperature and the pressure.
Figure 4.20 Picture showing the side
view of one chiller comprised of the
B. Condenser compressor and evaporator
The condenser acts as a heat exchanger,
removing the heat from the refrigerant
picked up in the evaporator. The
refrigerant condenses as it passes its heat
to the cooling water. The high pressure
refrigerant then enters the expansion
valve.
C. Expansion Valve
The expansion valve lowers the pressure
and increase the volume of the refrigerant
before it flows to the evaporator, allowing
it to pick up unwanted heat from the
evaporator.
D. Evaporator
The evaporator also works as a heat
exchanger between the water and the
refrigerant. The water flowing from its
respective coil cools as the heat is
extracted by the refrigerant. This chilled 77
water is then pumped to the AHU to
provide air conditioning.
4.0 AIR CONDITIONING SYSTEMS
78
4.0 AIR CONDITIONING SYSTEMS
1. Air filter
The treated air in the AHU passes through the air
filters where dust particles and other
contaminants are collected ensuring the quality
Figure 4.22 Diagram showing the air
of the air before being passed to the ductwork filter placement in AHU
for distribution throughout the building. Air filters
also ensure the overall life of an AHU,
2. Centrifugal fan
The blower performs the function of creating the
current of the air. The air collected by the blower
is conditioned and then released into the
building via the ductwork. Centrifugal fan is
facilitated by a motor to provide high efficiency
Figure 4. 23 Centrifugal fan and motor
over a wide operating rate and is quieter than
inside the AHU compartment
most motors.
3. Cooling Coil
The cooling coils work to remove heat from the
refrigerant. They are made of copper and coiled
to increase the surface area for heat exchange,
cooling the air before being passed into the
Figure 4. 24 Diagram showing cooling
ductwork. coil in AHU
4. Humidifier
A humidifier is placed in the AHU to control and
set the humidity of the air and provide a
comfortable and healthy environment in the
space the conditioning works for. In the absence
of this component, air maybe too dry due to the Figure 4. 25 Diagram showing
constant heating. humidifier placement in AHU
79
4.0 AIR CONDITIONING SYSTEMS
4.5.5 DIFFUSERS
4.6 CONCLUSION
81
4.0 AIR CONDITIONING SYSTEMS
4.7 REFERENCES
82
5.0 MECHANICAL TRANSPORTATION
5.0
MECHANICAL
TRANSPORTATION
5.1 INTRODUCTION
5.2 ELEVATORS
5.2.1 Introduction of elevators
5.2.2 Types of elevator systems
5.7 CONCLUSION 83
5.8 REFERENCES
5.0 MECHANICAL TRANSPORTATION
5.1 INTRODUCTION
Location of lift
Figure 5.2 shows an elevator sign
Elevator signs call out emergency
The position of the lift should be at a location precautions as well as help visitors
which provide easy means of access for the and workers find their way around
building users. your facility.
Source:https://mbtskoudsalg.com/ima
ges/elevator-vector-symbol-3.png
84
5.0 MECHANICAL TRANSPORTATION
● Office
● Apartment
● Hotel
Office
An elevator to every 250 persons, i.e if the
building occupancy is 1000 persons, the number
of elevators required will be 1000/250 = 4
(elevators).
Speed of the elevator shall be selected by
multiplying the number of storey of the building
by 10, i.e speed of elevators shall be 15x10 = 150
(mpm).
Capacity of the elevator for small office buildings
can be either 13 or 15 persons while larger
building requires 17 persons or more.
Apartment
An elevator to every 500 occupants. Speed of
the elevator can be half of the speed for office
building. Usually smaller capacity elevator is
used. However 15 persons capacity stretcher
type elevator is the popular choice.
Hotel
An elevator to every 150 guest. Speed of
elevator is 7.5 times the number of storey of the
building
Depending on the type of building, one can
choose something close to the above by going 1
or 2 notch lower or 1 notch higher.
85
5.0 MECHANICAL TRANSPORTATION
Source:http://astepaboveelevator.co
m/elevators101.html
87
5.0 MECHANICAL TRANSPORTATION
● Control system
● Electric Motor
Figure 5.7 show the passenger
● Hoistway elevator
● Lift car
1. CONTROL SYSTEM
2. ELECTRIC MOTOR
3. HOISTWAY
4. LIFT CAR
90
5.0 MECHANICAL TRANSPORTATION
● Automatic
Response to one call from either lift car or
landing. No further calls are accepted until the
car is at rest. Only suited to light occupancy and
low-rise buildings up to five floors.
● Call Button
A call button is located at each landing entrance Figure 5.14 shows Multi-Beam Door
and a set of buttons in the car corresponds to Sensor
Source:https://www.slideshare.net/ar
each floor. Landing calls are stored and
kam_slideshare/transportation-syste
answered in sequence as the lift car descends. In ms-in-buildings
upward direction, passengers are distributed in
floor sequence by selection within the car.
● Group collective
Applied where groups of lifts occur in large
buildings, using an interconnected collective
stored control system This permits the closest lift
traveling in the desired direction to respond,
rather than passengers waiting for one specific
lift or having to press every lift’s button.
● Programmed control
This is an improvement of the group collective
system, incorporating time-controlled functions,
where demand is known to be particularly high
on some floors at certain times. Figure 5.15 shows a standard elevator
button panel
Source:http://www.electrical-knowho
● Breakdown w.com/2012/04/elevator-control-syst
In case of breakdown, the elevator company, the em-part-two.html
MS Elevators Engineering Sdn Bhd will be
contacted. A 24 hours hotline number is assigned
for the call centre. All incoming complaints or
break down will be handled by the engineer.
Upon receiving any breakdown call, the engineer
will immediately contact the technicians at
respective zones. Man-trapped and emergency
cases will be attended within 30 to 45 minutes
and normal breakdown cases will be attended to
within two (2) hours barring any unforeseen
circumstances.
Block C, 2 Passenger
Elevators
Elevators
93
5.0 MECHANICAL TRANSPORTATION
Elevators
94
5.0 MECHANICAL TRANSPORTATION
Elevators
95
5.0 MECHANICAL TRANSPORTATION
96
5.0 MECHANICAL TRANSPORTATION
97
5.0 MECHANICAL TRANSPORTATION
5.6.1 Lift
98
5.0 MECHANICAL TRANSPORTATION
99
5.0 MECHANICAL TRANSPORTATION
5.6.5 Handrails
5.7 CONCLUSION
5.8 REFERENCES
101