New Toilet Exhaust Fan Static Pressure Calculation3.12.2018

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 4

(TOILET SITE : KSA, ALRYADH Date :

MOLD EXHAUST
FAN) Zone G.F Revision :
GENERAL DATA
DUCT MATERIAL : GI DUCT
ROUGHNESS COEF. : 0.93
SHEET THICKNESS : 6 / 10° mm
ALTITUDE :
ALTITUDE COEF. : 0.000
AIR DENSITY : 1.09 Kg/m3 1.18 @ 22or 24 &50%
DUCTS PRESSURE LOSSES BOARD
A-B B-C C-D D-E E-F F-G G-H H-I I-J
SECTION 1 2 3 4 5 6 7 8 9 10 11 12
FLOW CFM 300 225 150 75
FLOW M3/H 510 382.5 255 127.5
LENGTH M 43.5 1.7 2 1
DIAM. mm 188.85 133.2 133.2 109.32
DIAM. EQUIV. 188.85 133.2 133.2 109.32
WIDTH mm 200 150 150 100
HEIGHT mm 150 100 100 100
AREA M2 0.03 0.01 0.01 0.01
VELOCITY M/S 5.06 7.62 5.08 3.77
PD per Meter Pa 1.92 6.19 2.96 2.19
PD x LENGTH Pa 83.35 10.527 5.9211 2.1909 0

KSI 1 2 3 4 5 6 7 8 9 10 11 12
ELBOW 30° 0.18
ELBOW 45° 0.24
ELBOW 90° 0.4
TEE 45° 0.3
TEE 90° 1 1
END TEE 1.5
BRANCH TEE 0.05 1 1
TRANSITION 0.25
CONTRACTION 0.05
AIR OUTLET 1.1
GRILLE 0.44 1
TOTAL KSI 1.00 0.05 0.05 0.44 0.00 0.00
DUCTS PD Pa 13.94 1.58 0.70 3.41 0.00 0.00
PRESSURE DROP Pa 97.29 12.11 6.63 5.61 0.00 0.00

SPECIAL FITTING PRESSURE DROPS

DESIGNATION PD (PA) QTY TOTAL


FIRE DAMPER 10 0 STATIC PRESSURE AT 100%
DAMPER 10 1 10 FLOW AT 100%
SUPPLY GRILLE 15 0 * DUCTS PRESSURE DROP :
RETURN GRILLE 10 0 * FITTING PRESSURE DROP :
FRESH AIR GRILLE 20 0
REJECT AIR GRILLE 15 0 STATIC PRESSURE AT 110%
PLANE FILTER 80 0 FLOW AT 110%
OIL BATH FILTER 150 0 * DUCTS PRESSURE DROP :
HOOD FILTER 100 0 * FITTING PRESSURE DROP :
PRIMARY HEATING COIL 5 0
DISC EXHAUST VALVE 70 1 70 STATIC PRESSURE AT 120%
FLEXIBLE CONNECTION 15 1 15 FLOW AT 120%
SOUND ATTENUATOR 40 0 * DUCTS PRESSURE DROP :
TOTAL 95 Pa * FITTING PRESSURE DROP :

where : 1 inWG = 249.1 Pa

therefore : 142 Pa = 0.57 inWG


3/12/18
00-01

13 14 15 TOTAL

48.2 ml

101.99 Pa

13 14 15 TOTAL

1.54
19.64 Pa
121.63 Pa

217 Pa
510 m³/h
122 Pa
95 Pa

238 Pa
561 m³/h
134 Pa
105 Pa
260 Pa
612 m³/h
146 Pa
114 Pa