Dräger Flame 2700

Flame Detection

Working in areas with combustible gases, vapours or materials requires


fire/flame detection as a life-saving necessity. The best solutions must
combine state-of-the-art technology with rugged durability and be ready to
reliably work in any situation. Dräger offers a wide variety of high-quality
flame-detectors that fulfil these requirements.
02 | Dräger Flame 2700

Benefits

Reliability You Can Count On

The Dräger Flame 2700 is a Multi IR Flame Detector and is specifically designed to detect hydrocarbon and
hydrogen flames at long distances. Its high immunity to false alarms and superior performance features makes it
ideal for a large number of applications.

Built To Resist

As one of the most weather resistant detector currently on the market, the Flame 2700 comes with features
for various extremes such as a heated window against icing and up to 95 % non-condensation during humid
phases.

A Sharp Eye For Greater Safety

With the ability to detect a 0.1 m2 gasoline pan fire at 65 m or a hydrogen flame at 30 m in less than
5 seconds, the Flame 2700 offers the best in reliability. Additionally, its MTBF minimum of 150,000 hours
ensures a longer and hassle-free operating period – a big plus for the safety of your workers and operations.

Intelligent Design

The Flame 2700 is also built with operating convenience in mind. This can be seen in its lower power
requirements and a compact, lighter design that makes installation and maintenance easier.

Reliability

Functional safety is a concept applicable across all industry sectors. It is fundamental to enabling complex
technology used for safety-related systems. It provides assurance that the safety-related systems will offer
necessary risk reduction. The Dräger Flame 2700 is highly reliable and complies with the IEC 61508 Safety
Integrity Requirements of SIL2.

Automatic and manual optics checks (BIT)

Automatic checks of the detector electronics and optics help to ensure that no fault goes undetected.
Additionally the test can be triggered manually at any time.

Easily visible status LED

A tri-colored LED which is visible at the front of the detector provides a simple status indication to personnel in
close proximity to the detector. Green indicates normal operation; yellow indicates a fault and red indicates the
presence from radiation a fire.
Dräger Flame 2700 | 03

Benefits

Simple installation and commissioning

Installation is simple! The detector is easily installed with a stainless steel tilt mount which enables the detector
to be rotated up to 60° in all directions to position the detector in relation to the potential fire source.

Further benefits and features:

‒ Multi spectrum design – for long distance detection and high false alarm immunity
‒ Advanced Digital Processing of the Dynamic Characteristics of Fire (flickering, threshold correlation and
ratio)
‒ Sensitivity selection – to ensure no zone crossover detection
‒ Automatic and Manual Built-In-Test (BIT) – to assure continued reliable operation
‒ Heated window – for operation in harsh weather conditions (snow, ice, condensation)
‒ Multiple output options for maximum flexibility and compatibility
‒ 3 Relays for Alarm, Fault and Auxiliary
‒ 0-20 mA (stepped)
‒ HART® Protocol for maintenance and asset management
‒ RS-485, Modbus compatible
‒ Approved to Safety Integrity Level 2 (SIL2 – TÜV)
‒ Ex approvals for worldwide application: ATEX, IECEx, FM/FMC, CSA

System Components

Dräger REGARD® 3900

The Dräger REGARD® 3900 is a standalone, self contained control


system for the detection of Toxic, Oxygen and Ex hazards. The control
system is fully configurable between 1 and 16 channels, depending upon
the type and quantity of input/output boards installed.
D-27777-2009
04 | Dräger Flame 2700

Accessories

Flame Simulator

The Flame Simulator emits radiation in a unique sequential pattern


corresponding to and recognizable by the detector as fire. This allows
the detectors to be tested under simulated fire conditions without the
associated risks of an open flame.
D-51319-2015

Weather Cover

The Weather Cover protects the detector from different weather


conditions, such as snow or rain.
D-5921-2016

Laser Pointer

Does the detector cover the area that needs protection? Is it located
correctly and does the detector’s cone of vision cover the most
dangerous spot? This accessory enables the installer to optimize
detector location and its actual detection area coverage.
D-5925-2016
Dräger Flame 2700 | 05

Related Products

Dräger Flame 2000

Working in areas with combustible gases, vapours or materials requires


fire/flame detection as a life-saving necessity. The best solutions must
combine state-of-the-art technology with rugged durability and be ready
to reliably work in any situation. Dräger offers a wide variety of high-
quality flame-detectors that fulfil these requirements.
D-5904-2016

Dräger Flame 2100

Working in areas with combustible gases, vapours or materials requires


fire/flame detection as a life-saving necessity. The best solutions must
combine state-of-the-art technology with rugged durability and be ready
to reliably work in any situation. Dräger offers a wide variety of high-
quality flame-detectors that fulfil these requirements.
D-9307-2014

Dräger Flame 2350

Working in areas with combustible gases, vapours or materials requires


fire/flame detection as a life-saving necessity. The best solutions must
combine state-of-the-art technology with rugged durability and be ready
to reliably work in any situation. Dräger offers a wide variety of high-
quality flame-detectors that fulfil these requirements.
D-9289-2014

Dräger Flame 2370

Working in areas with combustible gases, vapours or materials requires


fire/flame detection as a life-saving necessity. The best solutions must
combine state-of-the-art technology with rugged durability and be ready
to reliably work in any situation. Dräger offers a wide variety of high-
quality flame-detectors that fulfil these requirements.
D-9288-2014
06 | Dräger Flame 2700

Related Products

Dräger Flame 2500

Working in areas with combustible gases, vapours or materials requires


fire/flame detection as a life-saving necessity. The best solutions must
combine state-of-the-art technology with rugged durability and be ready
to reliably work in any situation. Dräger offers a wide variety of high-
quality flame-detectors that fulfil these requirements and more.
D-9272-2014
Dräger Flame 2700 | 07

Technical Data

Type Explosion proof IR flame detector for hydrocarbon and hydrogen based fires
Spectral Response Multi IR Bands 2 to 5 μm
Measuring Performance Field of view Horizontal 67°; Vertical 70° for Gasoline
Horizontal 80°; Vertical 80° for Hydrogen
Response Time Typically 5 seconds
Sensitivity Ranges 4 Sensitive ranges for 1 ft2 (0.1 m2)
n-Heptane pan fire from 50 ft (15 m)
to 215 ft (65 m)
Detection Range Fuel ft / m
(at highest Sensitivity Setting n-Heptane / Gasoline 215 / 65
for 1 ft2 (0.1 m2) pan fire) Diesel Fuel / JP5 / Kerosene 150 / 45
Ethanol 95 % 135 / 40
Methanol 115 / 35
IPA (Isopropyl Alcohol) 135 / 40
Hydrogen* 125 / 38
Methane / LPG* 150 / 45
Polypropylene Pellets 115 / 35
Ammonia** 60 / 18
Silane** 7/2
Office Paper 82 / 25
* 30''(0.75 m) high, 10'' (0.25 m) width plume fire; ** 20'' (0.5 m) high, 8'' (0.2 m) width plume fire

Electrical Data
Output Signals 0 – 20 mA (stepped), HART®
Fault Signal 0 + 1 mA
BIT Fault Signal 2 mA ±10 %
Normal Signal 4 mA ±10 %
Warning Signal 16 mA ±5 %
Alarm Signal 20 mA ±5 %
Relays Alarm, Fault and Auxiliary
SPST volt-free contacts rated 2 A at 30 VDC
RS485 Modbus compatible communication link
Power Supply 24 VDC nominal (18 – 32 VDC)
Power Consumption Standby: max. 90 mA (110 mA with heated window)
Alarm: max. 130 mA (160 mA with heated window)

Ambient Conditions
Temperature -55 to +75 °C / -67 to +167 °F (operating)
-55 to +85 °C / -67 to +185 °F (option and storage)
Humidity Up to 95 % non-condensing
(withstands up to 100 % RH for short periods)

Enclosure
Material Stainless steel SS 316L
Connecting Thread 2 x 3/4" – 14NPT or 2 × M25 × 1.5 mm
Weight Detector SS 316L 2.8 kg
Tilt mount 1.0 kg
Dimensions Detector 101.6 × 117 × 157 mm
Ingress Protection IP66 and IP67, NEMA 250 6P

Approvals
ATEX and IECEx Ex II 2 G D
Ex d e IIC T5 Gb Ex d e IIC T4 Gb Ex d e mb IIC T4 Gb
08 | Dräger Flame 2700

Technical Data

Ex tb IIIC T96°C Db Ex tb IIIC T106°C Db Ex tb IIIC T98°C Db


(-55 °C ≤ Ta ≤ +75 °C) (-55 °C ≤ Ta ≤ +85 °C) (Ta = -55 °C to +75 °C)
FM/FMC/CSA Class I Div. 1, Groups B, C & D
Class II/III Div. 1, Groups E, F & G
Safety Integrity Level SIL2 certified by TÜV (EN61508)
Performance Approval EN54-10 (VdS)
FM3260
CE marking EMI/RFI protected to EN61326-3 and EN61000-6-3

Ordering Information
Dräger Flame 2700 (M-111SC) 68 13 916
Dräger Flame 2700 (M-211SC) 68 13 917
Dräger Flame 2700 (M-311SC) 68 13 918

91 01 995 | 16.06-1 | HQ | PP | Subject to modifications | © 2016 Drägerwerk AG & Co. KGaA


Dräger Flame 2700 (M-112SF) 68 13 956
Dräger Flame 2700 (M-212SF) 68 13 957
Dräger Flame 2700 (M-222SF) 68 13 958
Dräger Flame 2700 (M-312SF) 68 13 959

Accessories
Flame Simulator FS-1400 (M) 68 13 976
Dräger Flame 2xx0 Duct Mount 68 13 978
Tilt Mount Flame Detector 68 13 979
Weather cover Flame Detector (SS) 68 13 189
Weather cover Flame Detector (ABS) 68 13 190
Dräger Flame 2xx0 Laser Pointer 68 13 890
Dräger Flame Pole Mount 3" 68 13 323
Dräger Flame Pole Mount 2" 68 13 322
Dräger Flame USB RS-485 Kit 68 13 994
Battery Pack for Flame Simulator FS1x00 68 13 889
HART® is a registered trademark of the HART® Communication Foundation

CORPORATE HEADQUARTERS REGION DACH REGION MIDDLE EAST, AFRICA REGION CENTRAL
Drägerwerk AG & Co. KGaA Dräger Safety AG & Co. KGaA Dräger Safety AG & Co. KGaA AND SOUTH AMERICA
Moislinger Allee 53–55 Revalstraße 1 Branch Office Dräger Panama S. de R.L.
23558 Lübeck, Germany 23560 Lübeck, Germany P.O. Box 505108 Complejo Business Park,
www.draeger.com Tel +49 451 882 0 Dubai, United Arab Emirates V tower, 10th floor
Fax +49 451 882 2080 Tel +971 4 4294 600 Panama City
[email protected] Fax +971 4 4294 699 Tel +507 377 9100
. [email protected] Fax +507 377 9130
REGION EUROPE . [email protected]
Dräger Safety AG & Co. KGaA REGION ASIA PACIFIC .
Revalstraße 1 Draeger Safety Asia Pte Ltd REGION NORTH AMERICA
23560 Lübeck, Germany 25 International Business Park Draeger, Inc.
Tel +49 451 882 0 #04-20/21 German Centre 3135 Quarry Road
Fax +49 451 882 2080 Singapore 609916 Telford, PA 18969
[email protected] Tel +65 6308 9400 Tel +1 800 4DRAGER
. Fax +65 6308 9401 (+1 800 437 2437)
asia.pacifi[email protected] Fax +1 215 723 5935
. [email protected]
.
Locate your Regional Sales
Representative at:
www.draeger.com/contact

You might also like