Design, Operation and Maintenance of Lact Units
Design, Operation and Maintenance of Lact Units
Design, Operation and Maintenance of Lact Units
Class LM 2090
Ben Stubblefield
Meter Check
P.O. Box 7736
Moore, Ok 73153-1736
The sampling system is very important to the The check valve is also needed downstream of the
operation of a LACT. Sampler locations and flow at Back pressure valve on a LACT unit so fluid cannot
the sampling point are critical and should refer to flow back from the pipeline.
API MPMS Chapter 8.2 for details. The sample
probe can also be placed downstream of a static Pressure gauges
mixer. Samplers should be paced by the Meter and
inject a common sample of 1.5 CC per stroke into Pressure gauges are needed on pump discharge
the sample container. The size of a sample also down and up stream of air eliminator / strainer
container is determined by thru-put of LACT. The and at the meter to check for normal operation. This
sample line from sampler to the sample container can also tell whether strainer needs cleaning or if
must be sloped downward toward sample container meter problems exist.
with no high or low points in the line. Sample
containers have a variety of features, some of which Control Panel
are listed below.
The electrical panel on LACT controls the function of
! Quick open closure for inspecting and cleaning. the unit. The control panel can be mounted on the
skid or placed off skid depending on the
! Internal coated with elliptical bottom to prevent classification of the area. All electrical equipment is
corrosion and helps with rundown and drainage. installed following applicable codes. Newer units are
being built with programmable controllers thus
! Sight glass is for visual inspection and amount eliminating relays and allowing better control of flow
of the sample collected. rate, pressure and BS&W piping.
Proving manifold ♦ Turn power off to pump and fill the unit with oil
and vent off air to prevent damage to P.D.
Downstream of the meter is a proving manifold. This Meter. Check for leaks then start pump and
manifold consists of three (3) valves. The block and slowly open block and bleed valve. The flow rate
bleed is the inline valve and must be a double block can be set by using back pressure valve.
and bleed type so it can be checked for leakage.
Proving requires no leakage through this valve. The ♦ Check the sampler to be sure it is taking a
two (2) bypass valves divert the flow thru the prover sample and storing it in the sample container
and back into the line for full flow. with no leaks.
♦ Calibrate BS&W monitor and temperature
averager following manufacturer’s instructions • The ATC or ATG if equipped needs a hot and
for calibration. cold test performed at initial proving time and
whenever a large change in meter factor occurs.
♦ Check the divert valve by simulating bad oil to
be sure it will divert on bad oil. • Block and bleed valve should be inspected at
each proving for leakage. If a leak is detected a
♦ The meter fail switch also needs to be checked. proving should not be performed until the valve
This can be done by blocking the flow causing a is repaired.
signal to be sent to the unit telling it to shut
down. High and low levels need to be set for • Pump needs to be checked for excessive
proper starting and stopping of the LACT unit. vibration or leaking seals. A drop in flow rate
may occur if the impeller is partially plugged.
♦ The unit should be proved and a meter factor
established. This factor is used to calculate • The meter factor is one of the key components
thruput of the meter. in determining if a meter needs to be repaired.
• Check the unit for leaks in meter and valve LACT units need proved to establish a meter factor.
drains. Also, seeps or drips in piping. This requires a portable meter prover or a stationary
unit attached to the LACT unit. The portable meter
• Strainer needs to be cleaned periodically to prover is more commonly used in our area. It should
maintain normal flow rate. be water drawn and sized according to API
standards.
• The BS&W monitor should be recalibrated
monthly or when a delivery is completed. Conclusion
• PD Meters require periodic maintenance of the Hopefully this paper will cover the basics of a LACT
gear train, packing gland, the counter, or right and as a guideline for those learning about LACT
angle drive. units. The use of Coriolis meters on LACT units
minimizes maintenance and cost of a LACT.