Toyo VCS

The document provides specifications for various medium voltage vacuum contactor switch models, including the VS-62, VS-64, VS-62L, VS-64L, VS-62D, VS-64D, VS-62DL, VS-64DL, VS-62DF, VS-64DF, VS-62DFL, and VS-64DFL. Key specifications listed include a rated insulation voltage of 7.2kV, rated operation voltage of 6.6kV, rated operation currents ranging from 200A to 400A depending on the model, a rated frequency of 50/60Hz, rated short-circuit breaking current of 4kA, and rated short time currents under 0.5

Uploaded by

dony ramdhani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
270 views12 pages

Toyo VCS

The document provides specifications for various medium voltage vacuum contactor switch models, including the VS-62, VS-64, VS-62L, VS-64L, VS-62D, VS-64D, VS-62DL, VS-64DL, VS-62DF, VS-64DF, VS-62DFL, and VS-64DFL. Key specifications listed include a rated insulation voltage of 7.2kV, rated operation voltage of 6.6kV, rated operation currents ranging from 200A to 400A depending on the model, a rated frequency of 50/60Hz, rated short-circuit breaking current of 4kA, and rated short time currents under 0.5

Uploaded by

dony ramdhani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

■ SURGE ABSORBER (mm)

VACUUM
• ZnO Type

2-M10 Stud Bolt - Stainless Steel


4-M10 Nut - Stainless Steel
TOYO CONTACTOR SWITCH
4-Terminal Clamp 4-M10 P/W - Stainless Steel
Stainless Steel
Stainless Steel Cap of the Arrester

8/20μs Maximum Residual Voltage


Epoxy-Fiberglass Wrap Rated MCOV Discharge (kV) at Switching Dimension
(mm) Weight
Type Voltage (kV) Voltage (kV) 30/75μs
ØD (kg)
(kV) (rms)
5kA 10kA 250A 500A H x øD L
TOSA - 3H 3 2.55 – 9.88 6.8 7.0 264 x 109 113.5 1.22
Silicone Rubber TOSA -4.5H 4.5 3.83 – 14.82 10.2 10.5 264 x 109 113.5 1.42
Housing
TOSA - 6H 6 5.10 – 19.76 13.6 14.0 264 x 109 113.5 1.92
H Zinc Metal Oxide TOSA - 3N 3 2.55 10.61 – 6.8 7.0 264 x 99 113.5 0.80
(ZnO) Block
20

TOSA -4.5N 4.5 3.83 15.42 – 10.2 10.5 264 x 99 113.5 0.92
TOSA - 6N 6 5.10 20.22 – 13.6 14.0 264 x 99 113.5 1.10
Aluminum (Al) Alloy Block

L
13
Ø
64

• Capacitor Type

Caution P. Connection Terminal Details


No Overturn P.
400 M12 Bolt
115

39

Torque P. 465
3

25±3 N・m 500

Terminal Cap
140 140 Connecting Cable 5.5~38mm2
No Overturn P.
2-15×20 Slots
Caution P.
N.P.
450

Caution P.
250
170

Caution P.
Earthing
Terminal 80
15

M8 Screw
t3.2

440 110
470
4-12×16 Slots

Rated Voltage Insulation Withstand Rated Capacitance Series Resistor Weight


Type
(V) (kV) (μF) (Ω) (kg)
NV2-045T10 3300/√3 16/45 0.1 x 3 100 15
NV2-060T10 6600/√3 22/60 0.1 x 3 100 15

總 公 司: 台北市內湖區行愛路 68 號 6 樓 台中辦事處: 台中市文心路四段 200 號 10 樓之2


電 話: (02)8791-8588 傳 真:(02)8791-9588 電 話: (04)2296-9388 傳 真:(04)2296-9386
電 子 郵 件: [email protected] 高雄辦事處: 高雄市民生一路56號15樓之6
網 址: www.toyotech.com.tw 電 話: (07)227-2133 傳 真:(07)227-2173
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Jan.2016
■ SPECIFICATIONS

Classification
MEDIUM VOLTAGE VACUUM CONTACTOR SWITCH
Item

Type VS-62 VS-64 VS-62L VS-64L VS-62D VS-64D VS-62DL VS-64DL VS-62DF VS-64DF VS-62DFL VS-64DFL

Normal Normal Normal


Operation System Latched Latched Latched
Excitation Excitation Excitation

Rated Insulation Voltage 7.2 KV

Rated Operation Voltage 6.6 KV

Rated Operation Current 200A 400A 200A 400A 200A 400A 200A 400A 200A 400A 200A 400A

Rated Frequency 50 / 60 Hz

Rated short-circuit
4 KA
Breaking Current

2 sec. 4 KA
Rated Short
Time Current
0.5 cycle 40 KA 50 KA 40 KA 50 KA 40 KA 50 KA 40 KA 50 KA 40 KA 50 KA 40 KA 50 KA

Dielectric Strength Grade 6A

Power Frequency Withstand 20 KV

Lightning Impulse Withstand 60 KV

Switching Frequency Closing, Breaking Capacity: Closing 10In, Breaking 8In

Operating Cycles/hr (AC-4) 1200 300 1200 300 1200 300

Closing, Breaking Capacity: Closing 6In, Breaking 1In


Operating Life Electrical
(AC-3 million 2.5 2.5 2.5 2.5 2.5 2.5
operations)
Mechanical 0.25 0.25 0.25 0.25 0.25 0.25

Closing coil AC 100/110V , DC 110/125V , AC 200/220V


Control Voltage
Tripping coil AC 100/110V , DC 110/125V , AC 200/220V (Latched Type)

Auxiliary Contacts 2a2b

Fuse Melting Detector — 1C Contact Mounted

750 1500 750 1500 750 1500 750 1500 750 1500 750 1500
Maximum Motor (KW)
(1500) (3000) (1500) (3000) (1500) (3000) (1500) (3000) (1500) (3000) (1500) (3000)
Application
Capacity
TR. (KVA)
3.3KV 1000 2000 1000 2000 1000 2000 1000 2000 1000 2000 1000 2000
(6.6KV) (2000) (4000) (2000) (4000) (2000) (4000) (2000) (4000) (2000) (4000) (2000) (4000)
SC. (KVAR)

Weight (kg) 23 24 58 60 78 79

Application Standards IEC 60470 , BS-775 , JEM 1167

–1–
■ TIME-CURRENT CHARACTERISTIC for SIBA HHD-B ■ VS-62 / VS-64 (Fixed Type, Normal Excitation)

• AC CONTROL

6/12 kV “e” = 292 mm P


U MCX
Connection on
OFF MCX Connectors
MC
U V P

V
V
C A3 B3 A1 B1
10 4 Sn C N A1
Time-current ON MCX
characteristic H00413-30_1 SI-RF MCH MCC
A2 A3 A4

DC
AC
B1 B2 B3
MCX MC A4 B4 A2 B2 B4
10 3
V N

10 2
• DC CONTROL
Virtual Pre-arcing time

200R 25 A
160R

250R 25 A
31,5 A

125 A
100 A
6,3 A

80 A
25 A
20 A
10 A

16 A

40 A

50 A
63 A

C1
C140
C1
P

A
MCX

OFF MCX MC
10 1 Connection on
Connectors

V
MC
C
A3 B3 A1 B1
ON MCX
C N A1
MCH MCC
A2 A3 A4

DC
10 0
MC B1 B2 B3
MCX
A4 B4 A2 B2 B4
N
N

10 -1
8
6
5
4
3

■ VS-62L / VS-64L (Fixed Type, Latched)


10 -2
RMS Prospective
current
• AC CONTROL
10 1 2 3 4 5 6 8 10 2 2 3 4 5 6 8 10 3 2 3 4 5 6 8 10 4 A 2 3 4 5 6 8 10 5
Connection on
10 3 Connectors
Cut-off current
H00413-40_1 MCX U P U V P
MCX OFF
kA ON
C N A1
MCX
MC A2 A3 A4

V
A3 B3 A1 B1 B1 B2 B3
M1 SA T1
C
MC B4
10 2 M2 SI-RF MC

AC
T1 T2
MCC MCT A4 B4 A2 B2
MCX
M1 M2
250RC140 A T2
200RC125 A
V
160RC125 A N
125 A
peak

100 A
80 A
63 A
10 1
50 A
Cut-off current

40 A

25 A
31,5 A • DC CONTROL
20 A
Connection on
16 A
P Connectors
10 A MCX OFF
6,3 A ON MCX
MCX C N A1
MC
10 0
A2 A3 A4

V
8 A3 B3 A1 B1
M1 C T1
6 B1 B2 B3
MC
4 B4
M2 MC
DC

2
MCC MCT A4 B4 A2 B2 T1 T2
MCX
T2 M1 M2
N
10 -1 2 3 4 6 8
10 0 10 1 10 2 kA 10 3 N

Prospective short-circuit-current (Sym. r.m.s.)

–9– –2–
■ VS-62D / VS-64D (Draw-out Type, Normal Excitation) ■ MV-FUSE LINKS for motor-current-circuits (SIBA HHD-B)

• AC CONTROL

P
6/12 kV “e” = 292 mm
OFF U MCX
Connection on
MCX Connectors
ON MCX MC
U V P
V
C A3 B3 A1 B1
SA C N A1
L1
SI-RF MCH MCC
A2 A3 A4 Variant dimension
LS
AC

B1 B2 B3
L2
MC A4 B4 A2 B2 B4 L1 L2 Application
MCX Air and gas insulated switchgear / Motor current circuit
V N
Indoor and outdoor use

Packing stuck / 1 piece


• DC CONTROL

P
MCX
OFF Class IEC 60282-1 VDE 0670-4
ON MCX
MCX
MC
Connection on Back-up DIN 43 625
Connectors
V

C A3 B3 A1 B1

L1 C N A1
MCH MCC A2 A3 A4
LS Article Rated Current Length “e” Diameter D
DC

L2 B1 B2 B3
MC
A4 B4 A2 B2 B4 L1 L2 A mm mm
MCX
N 30 004 13 6,3 - 50 53
N
30 012 13 63 - 125 67
6/12 292
30 020 13 160RC125 85
30 020 14 200RC125 - 250RC140 85

■ VS-62DL / VS-64DL (Draw-out Type, Latched)

• AC CONTROL
Connection on
MCX U P Connectors
ON MCX OFF
U V P
MCX C N A1
Rated Weight Pre-Arcing 2 Power Cold
M1
MC t-Value
A3 B3 A1 B1
A2 A3 A4 Current Current - I 1 Current - I I2t-Value Loss Resistance
min max
V

MC SA C T1 n n
B1 B2 B3
M2
SI-RF MC
B4 L1 L2 A kg/1 KA A A2s A2s A2s W mΩ
L1
6,3 30 004 13.6,3 1,6 63 22 45 210 360 10 178
AC

LS MCC MCT A4 B4 A2 B2 T1 T2 10 30 004 13.10 1,6 63 34 75 350 560 17 113


L2 T2
M1 M2 16 30 004 13.16 1,6 63 56 250 1.100 2.000 17 50
N
MCX 20 30 004 13.20 1,6 63 70 640 2.900 4.800 13 27
V
25 30 004 13.25 1,6 63 90 1.050 4.700 7.500 16 21
31,5 30 004 13.31,5 1,6 63 110 1.700 6.600 12.000 21 17
• DC CONTROL 40 30 004 13.40 1,6 63 140 2.900 12.000 19.000 27 13
50 30 004 13.50 1,6 63 170 5.700 20.000 33.000 30 9,3
P Connection on
MCX MCX OFF Connectors 63 30 012 13.63 2,0 63 210 10.700 40.000 66.000 34 6,8
ON
MCX
80 30 012 13.80 2,0 63 280 21.000 78.000 140.000 47 4,8
MC C N A1
M1 100 30 012 13.100 2,0 63 320 33.000 130.000 210.000 58 3,8
A3 B3 A1 B1 A2 A3 A4 125 30 012 13.125 2,0 63 390 47.000 180.000 390.000 98 3,3
V

MC C T1
M2 B1 B2 B3
160RC125 30 020 13.160 3,8 63 600 90.000 330.000 570.000 103 2,5
MC B4 L1 L2
L1 200RC125 30 020 14.200 3,8 50 800 230.000 480.000 704.000 74 2,1
DC

LS MCC MCT
250RC140 30 020 14.250 3,8 50 1.000 371.000 750.000 1.100.000 77 1,7
A4 B4 A2 B2 T1 T2
L2 —— — — — — — — — —
M1 M2
—— — — — — — — — —
MCX N T2

–3– –8–
■ DIMENSIONS (mm) ■ VS-62DF / VS-64DF (Draw-out Type with Fuse, Normal Excitation)

• Fixed Type with Mechanical Interlock • AC CONTROL


R S T
CN2 FC1 CN3 Connection on
PF CN2 FC3 PT Connection Connectors
PF CN2 FC2
U V U V P
F PT CN3 F(10A)
C N A1
U P MCX
OFF
A2 A3 A4
VC CN3 MCX B1 B2 B3
ON MCX MC
FOR 1 PT
U V W SA C A3 B3 A1 B1 B4 L1 L2
L1
SI-RF MCH MCC
LS FC1 FC2 FC3
L2
MC
A4 B4 A2 B2
MCX
V N

• DC CONTROL
Connection on
P
Connectors
OFF MCX

MCX C N A1
ON MCX MC
A2 A3 A4

V
C A3 B3 A1 B1
B1 B2 B3
L1
MCH MCC B4 L1 L2
LS

DC
L2 MC FC1 FC2 FC3
A4 B4 A2 B2
MCX
N
N

■ VS-62DFL / VS-64DFL (Draw-out Type with Fuse, Latched)

• VS-62DF(L) / VS-64DF(L) Draw-out Type Cradle • AC CONTROL


R S T
CN2 FC1 CN3 Connection on
PF CN2 FC3 PT Connection Connectors
PF CN2 FC2
U V U V P
F PT CN3 F(10A)
MCX P C N A1
U MCX OFF
ON
A2 A3 A4
VC CN3 MCX
MC
M1 B1 B2 B3
FOR 1 PT
A3 B3 A1 B1
U V W MC SA C T1 B4 L1 L2
M2
SI-RF MC
L1
T1 T2
LS MCC MCT A4 B4 A2 B2
T2
M1 M2
L2
N FC1 FC2 FC3
MCX
V

• DC CONTROL
Connection on
P Connectors
ON MCX MCX OFF

MCX C N A1
MC
M1
A3 B3 A1 B1 A2 A3 A4

V
MC C T1
M2 B1 B2 B3
MC B4 L1 L2
L1
DC

LS A4 B4 A2 B2
MCC MCT
L2 T1 T2
M1 M2
MCX N T2
FC1 FC2 FC3
N

–7– –4–
■ DIMENSIONS (mm)

• VS-62(L) / VS-64(L) Fixed Type

• VS-62D(L) / VS-64D(L) Draw-out Type Cradle

OPTIONAL PARTS
1 POSITION DETECTOR
2 SURGE ABSORBER
3 SHUTTER
4 CONDENSER TRIP DEVICE
(CTD)

–5–
■ DIMENSIONS (mm) ■ DIMENSIONS (mm)

• VS-62(L) / VS-64(L) Fixed Type • VS-62D(L) / VS-64D(L) Draw-out Type Body

• VS-62D(L) / VS-64D(L) Draw-out Type Cradle • VS-62DF(L) / VS-64DF(L) Draw-out Type Body

–5– –6–
■ DIMENSIONS (mm)

• Fixed Type with Mechanical Interlock

• VS-62DF(L) / VS-64DF(L) Draw-out Type Cradle

OPTIONAL PARTS
1 POSITION DETECTOR
2 SURGE ABSORBER
3 SHUTTER
4 CONDENSER TRIP DEVICE
(CTD)

–7–
■ VS-62D / VS-64D (Draw-out Type, Normal Excitation) ■ MV-FUSE LINKS for motor-current-circuits (SIBA HHD-B)

• AC CONTROL

P
6/12 kV “e” = 292 mm
OFF U MCX
Connection on
MCX Connectors
ON MCX MC
U V P
V
C A3 B3 A1 B1
SA C N A1
L1
SI-RF MCH MCC
A2 A3 A4 Variant dimension
LS
AC

B1 B2 B3
L2
MC A4 B4 A2 B2 B4 L1 L2 Application
MCX Air and gas insulated switchgear / Motor current circuit
V N
Indoor and outdoor use

Packing stuck / 1 piece


• DC CONTROL

P
MCX
OFF Class IEC 60282-1 VDE 0670-4
ON MCX
MCX
MC
Connection on Back-up DIN 43 625
Connectors
V

C A3 B3 A1 B1

L1 C N A1
MCH MCC A2 A3 A4
LS Article Rated Current Length “e” Diameter D
DC

L2 B1 B2 B3
MC
A4 B4 A2 B2 B4 L1 L2 A mm mm
MCX
N 30 004 13 6,3 - 50 53
N
30 012 13 63 - 125 67
6/12 292
30 020 13 160RC125 85
30 020 14 200RC125 - 250RC140 85

■ VS-62DL / VS-64DL (Draw-out Type, Latched)

• AC CONTROL
Connection on
MCX U P Connectors
ON MCX OFF
U V P
MCX C N A1
Rated Weight Pre-Arcing 2 Power Cold
M1
MC t-Value
A3 B3 A1 B1
A2 A3 A4 Current Current - I 1 Current - I I2t-Value Loss Resistance
min max
V

MC SA C T1 n n
B1 B2 B3
M2
SI-RF MC
B4 L1 L2 A kg/1 KA A A2s A2s A2s W mΩ
L1
6,3 30 004 13.6,3 1,6 63 22 45 210 360 10 178
AC

LS MCC MCT A4 B4 A2 B2 T1 T2 10 30 004 13.10 1,6 63 34 75 350 560 17 113


L2 T2
M1 M2 16 30 004 13.16 1,6 63 56 250 1.100 2.000 17 50
N
MCX 20 30 004 13.20 1,6 63 70 640 2.900 4.800 13 27
V
25 30 004 13.25 1,6 63 90 1.050 4.700 7.500 16 21
31,5 30 004 13.31,5 1,6 63 110 1.700 6.600 12.000 21 17
• DC CONTROL 40 30 004 13.40 1,6 63 140 2.900 12.000 19.000 27 13
50 30 004 13.50 1,6 63 170 5.700 20.000 33.000 30 9,3
P Connection on
MCX MCX OFF Connectors 63 30 012 13.63 2,0 63 210 10.700 40.000 66.000 34 6,8
ON
MCX
80 30 012 13.80 2,0 63 280 21.000 78.000 140.000 47 4,8
MC C N A1
M1 100 30 012 13.100 2,0 63 320 33.000 130.000 210.000 58 3,8
A3 B3 A1 B1 A2 A3 A4 125 30 012 13.125 2,0 63 390 47.000 180.000 390.000 98 3,3
V

MC C T1
M2 B1 B2 B3
160RC125 30 020 13.160 3,8 63 600 90.000 330.000 570.000 103 2,5
MC B4 L1 L2
L1 200RC125 30 020 14.200 3,8 50 800 230.000 480.000 704.000 74 2,1
DC

LS MCC MCT
250RC140 30 020 14.250 3,8 50 1.000 371.000 750.000 1.100.000 77 1,7
A4 B4 A2 B2 T1 T2
L2 —— — — — — — — — —
M1 M2
—— — — — — — — — —
MCX N T2

–3– –8–
■ TIME-CURRENT CHARACTERISTIC for SIBA HHD-B ■ VS-62 / VS-64 (Fixed Type, Normal Excitation)

• AC CONTROL

6/12 kV “e” = 292 mm P


U MCX
Connection on
OFF MCX Connectors
MC
U V P

V
V
C A3 B3 A1 B1
10 4 Sn C N A1
Time-current ON MCX
characteristic H00413-30_1 SI-RF MCH MCC
A2 A3 A4

DC
AC
B1 B2 B3
MCX MC A4 B4 A2 B2 B4
10 3
V N

10 2
• DC CONTROL
Virtual Pre-arcing time

200R 25 A
160R

250R 25 A
31,5 A

125 A
100 A
6,3 A

80 A
25 A
20 A
10 A

16 A

40 A

50 A
63 A

C1
C140
C1
P

A
MCX

OFF MCX MC
10 1 Connection on
Connectors

V
MC
C
A3 B3 A1 B1
ON MCX
C N A1
MCH MCC
A2 A3 A4

DC
10 0
MC B1 B2 B3
MCX
A4 B4 A2 B2 B4
N
N

10 -1
8
6
5
4
3

■ VS-62L / VS-64L (Fixed Type, Latched)


10 -2
RMS Prospective
current
• AC CONTROL
10 1 2 3 4 5 6 8 10 2 2 3 4 5 6 8 10 3 2 3 4 5 6 8 10 4 A 2 3 4 5 6 8 10 5
Connection on
10 3 Connectors
Cut-off current
H00413-40_1 MCX U P U V P
MCX OFF
kA ON
C N A1
MCX
MC A2 A3 A4

V
A3 B3 A1 B1 B1 B2 B3
M1 SA T1
C
MC B4
10 2 M2 SI-RF MC

AC
T1 T2
MCC MCT A4 B4 A2 B2
MCX
M1 M2
250RC140 A T2
200RC125 A
V
160RC125 A N
125 A
peak

100 A
80 A
63 A
10 1
50 A
Cut-off current

40 A

25 A
31,5 A • DC CONTROL
20 A
Connection on
16 A
P Connectors
10 A MCX OFF
6,3 A ON MCX
MCX C N A1
MC
10 0
A2 A3 A4

V
8 A3 B3 A1 B1
M1 C T1
6 B1 B2 B3
MC
4 B4
M2 MC
DC

2
MCC MCT A4 B4 A2 B2 T1 T2
MCX
T2 M1 M2
N
10 -1 2 3 4 6 8
10 0 10 1 10 2 kA 10 3 N

Prospective short-circuit-current (Sym. r.m.s.)

–9– –2–
■ SPECIFICATIONS ■ EXAMPLE for Motor Protection Fuse Selection

Classification
• It is recommended to select a motor protection fuse rating by the following steps:
MEDIUM VOLTAGE VACUUM CONTACTOR SWITCH  decide the motor starting current, draw a line towards the right to intersect with the chosen
morot starting time.
Item  draw a vertical line upwardly to intersect with the chosen number of starts per hour of the motor.
 draw a line towards the left to get the suggested fuse rating.
Type VS-62 VS-64 VS-62L VS-64L VS-62D VS-64D VS-62DL VS-64DL VS-62DF VS-64DF VS-62DFL VS-64DFL 3216 8 4 2 Motor Starts / h

Normal Normal Normal


Operation System Latched Latched Latched
Excitation Excitation Excitation

2 x 315 A
Rated Insulation Voltage 7.2 KV
500 A
400 A
Rated Operation Voltage 6.6 KV
355 A

Rated Operation Current 200A 400A 200A 400A 200A 400A 200A 400A 200A 400A 200A 400A 315 A

250 A
Rated Frequency 50 / 60 Hz
200 A

Rated short-circuit
160 A

Rated Current of Fuse Link [A]


4 KA
Breaking Current
125 A

2 sec. 4 KA 100 A
Rated Short
Time Current 80 A
0.5 cycle 40 KA 50 KA 40 KA 50 KA 40 KA 50 KA 40 KA 50 KA 40 KA 50 KA 40 KA 50 KA
63 A

Dielectric Strength Grade 6A 50 A

Power Frequency Withstand 20 KV

Lightning Impulse Withstand 60 KV 2


10

Switching Frequency
1200 300 1200 300 1200 300 1,5
Operating Cycles/hr (AC3)

2
Electrical 2.5 2.5 2.5 2.5 2.5 2.5

Motor - Starting Current [A]


Operating Life
(million operations)
Mechanical 0.25 0.25 0.25 0.25 0.25 0.25 3

400A 4
Closing coil AC 100/110V , DC 110/125V , AC 200/220V
Control Voltage 5
Tripping coil AC 100/110V , DC 110/125V , AC 200/220V (Latched Type) 6
7
Auxiliary Contacts 2a2b 8
9
3
10
750 1500 750 1500 750 1500 750 1500 750 1500 750 1500
Maximum Motor (KW)
(1500) (3000) (1500) (3000) (1500) (3000) (1500) (3000) (1500) (3000) (1500) (3000)
Application 1,5
Capacity

Motor Starting Time


TR. (KVA) 2 60 s
3.3KV 1000 2000 1000 2000 1000 2000 1000 2000 1000 2000 1000 2000 30 s
(6.6KV) (2000) (4000) (2000) (4000) (2000) (4000) (2000) (4000) (2000) (4000) (2000) (4000) 15 s
SC. (KVAR)
3 6s

Weight (kg) 23 24 58 60 78 79
4

Application Standards IEC 60470 , BS-775 , JEM 1167 5

–1– – 10 –
■ SURGE ABSORBER (mm)

• ZnO Type

3/8-16 STUD 8/20μs Maximum Residual Voltage


Dimension
HEX NUT & Rated MCOV Discharge (kV) at Switching
(mm) Weight
WIRE CLAMP Type Voltage (kV) Voltage (kV) 30/75μs
(kg)
PROTECTIVE CAP (kV) (rms)
5kA 10kA 500A H x øD
(OPTION)
TOSA - 6D100
TO 6 5.1 18 22.3 15.3 194 x 105 2.7
33.3mm

105mm DIA
14mm DIA HOLE
H 127mm

66.8mm 14mm
25.4mm

RATED VOLTAGE RECOMMENDED TIGHTENING TORQUES FOR


STAMP TOSA-D100 ARRESTER FASTENERS
3/8-16 STUD
WIRE CLAMP, Fastener
Faste Recommended
RETAINER, Tightening Torque
FLATWASHER 3⁄
& HEX NUT 8 inch line terminal
inc 20 foot pounds
3⁄
8 inch ground terminal 20 foot pounds
1⁄
2 inch fastener connecting 20 foot pounds
base bracket to crossarm or
transformer sidewall bracket

• Capacitor Type

Caution P. Connection Terminal Details


No Overturn P.
400 M12 Bolt
115

39

Torque P. 465
3

25±3 N・m 500

Terminal Cap
140 140 Connecting Cable 5.5~38mm2
No Overturn P.
2-15×20 Slots
Caution P.
N.P.
450

Caution P.
250
170

Caution P.
Earthing
Terminal 80
15

M8 Screw
t3.2

440 110
470
4-12×16 Slots

Rated Voltage Insulation Withstand Rated Capacitance Series Resistor Weight


Type
(V) (kV) (μF) (Ω) (kg)
NV2-045T10RE 3300/√3 16/45 0.1 x 3 100 15
NV2-060T10RE 6600/√3 22/60 0.1 x 3 100 15

總 公 司: 台北市內湖區行愛路 68 號 6 樓 台中辦事處: 台中市文心路四段 200 號 10 樓之2


電 話: (02)8791-8588 傳 真:(02)8791-9588 電 話: (04)2296-9388 傳 真:(04)2296-9386
電子郵 件: [email protected] 高雄辦事處: 高雄市民生一路56號15樓之6
網 址: www.toyotech.com.tw 電 話: (07)227-2133 傳 真:(07)227-2173
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Aug.2017

You might also like