FOUNDATIONTM Fieldbus H1,

physical layer products


from MTL and Relcom
for DCS

TM Solutions inc

September, 2003

Copyright © 2003 by MTL Instruments and Relcom Inc


Fieldbus Terminology

Splice <1m Segment

Trunk
Terminator
Spurs
Terminator

Copyright © 2003 by MTL Instruments and Relcom Inc


Topology

Control Network

Junction
Box

Chicken Foot
Point-to-Point Bus with Spurs Daisy-Chain
or Tree

Copyright © 2003 by MTL Instruments and Relcom Inc


Spur Lengths

In General, Keep as Short as Practical

uSegmentDevices Maximum Spur Length


u 1-12 120 m
u 13-14 90 m
u 15-16 60 m

These numbers Assume 1 Device per Spur

Remember, These are Recommendations

Copyright © 2003 by MTL Instruments and Relcom Inc


Fieldbus Cable
u Shielded Twisted Pair (18 Ga.) is most commonly used.
u Type A Fieldbus Cable (eg. Belden 3076F) is preferred.

Cable Distance Characteristic Resistnce Atten.


Type meters Impedance Ohm/km dB/km Description
Type A 1900 100 22 3 18 AWG Each Twisted
Pair is Shielded
Type B 1200 100 56 5 22 AWG Multiple
Twisted Pair, one Shield

Type C 400 unknown 132 8 26 AWG Multiple


Twisted Pair, no Shield
Type D 200 unknown 20 8 16 AWG Multi-core, no
Twist, no Shield

Copyright © 2003 by MTL Instruments and Relcom Inc


Fieldbus Electrical Circuit Diagram

Near-End Far-End
Power Conditioner Terminator Terminator

Field Devices

100 Ω 100 Ω
Signal
+ Isolation
9-32V 1 µF 1 µF
- Inductors

1900M Max.

To H1
Interface
Card
Copyright © 2003 by MTL Instruments and Relcom Inc
Physical layer components
Safe or Zone/Division 2 hazardous area
Host
Link Active Scheduler
DCS / PLC
• Up to 32 devices/link
T Terminator
1 2 3

– Most hosts limited to Fieldbus Power Supply


16 devices MTL5995

• Devices MTL / Relcom


Wiring Components
– 9-32V required + short circuit protection
– 13 - 30mA/device FCS-MBx-SG

(typically 20 mA)
• MTL5995
– 19V Normally non-arcing
spur live disconnect
– 350mA Trunk MTL951
Spur
– Switchable terminator

T Terminator:
FBT1, FCS-MBT

Copyright © 2003 by MTL Instruments and Relcom Inc


Isolated power conditioners

To more power conditioners

Segment 2
PC

Note:
Terminators Segment 1
and host connection PC
not shown

Isolation
Bulk Power Bulk Power
Supply A Supply B Power
PC Conditioner

Protects against cross talk


and multi segment failure from multiple earth faults
Copyright © 2003 by MTL Instruments and Relcom Inc
Crosstalk

To more power conditioners

Segment 2
PC

Note:
Terminators Segment 1
and host connection PC
not shown

Bulk Power Bulk Power


Supply A Supply B Power
PC Conditioner

Copyright © 2003 by MTL Instruments and Relcom Inc


Earth faults

To more power conditioners

Segment 2
PC

Note:
Terminators Segment 1
and host connection PC
not shown

Bulk Power Bulk Power


Supply A Supply B Power
PC Conditioner

With 2 earth faults, all segments fail

Copyright © 2003 by MTL Instruments and Relcom Inc


MTL5995 Power Supply

Isolation and 19V,350mA output


power conditioning

Zone 2 and Division 2


mounting Market leader

Copyright © 2003 by MTL Instruments and Relcom Inc


Power supplies: redundant power
conditioners

To more backplanes

Note:
PC Segment
Alarm circuitry
terminators
and host connection PC Power Supply
not shown Backplane
Power Supply
Module
Bulk Power Bulk Power
Supply A Supply B Isolation
Power
PC Conditioner

Alarm
Copyright © 2003 by MTL Instruments and Relcom Inc
Redundant Power System

Reduced wiring Redundant isolated


power conditioning

Alarm circuitry

Replace power
Redundant DC modules without
power inputs resetting fieldbus

25V, 350mA output

Copyright © 2003 by MTL Instruments and Relcom Inc


Redundant Power System

Copyright © 2003 by MTL Instruments and Relcom Inc


Custom Redundant Power System
Replace power Redundant isolated
modules without power conditioning
resetting fieldbus

Connection to
redundant 4ch H1
Integrated cards
terminator

Redundant 24Vdc
power inputs
4 segments
25V, 350mA output Alarm module

Copyright © 2003 by MTL Instruments and Relcom Inc


Power supplies: single power conditioner

To more backplanes

Note:
Alarm circuitry Segment
terminators PC
and host connection
not shown

Bulk Power Bulk Power isolation


Supply A Supply B Power
PC Conditioner

• Ideal passive power conditioner: 5mH inductor + 50Ω


resistor
• But: voltage load dependant 14.5-32V+ 6W power
dissipation
Copyright © 2003 by MTL Instruments and Relcom Inc
Wiring Using a Traditional Junction Box

Interconnects between
spurs

Junction box has to be


drawn and documented

Any wiring errors cost


commissioning time

Copyright © 2003 by MTL Instruments and Relcom Inc


Megablock Series
SpurGuardTM option
Power LED >9V -short circuit protection
-visual indication of fault

Securable, pluggable
connectors

2, 4 and 8 drop versions Overvoltage protection

Copyright © 2003 by MTL Instruments and Relcom Inc


F118 Customize 10-way Megablock
SpurGuardTM option
-short circuit protection Connector
Power LED >9V -visual indication of fault

Switch selectable
Terminator
Over voltage protection

Copyright © 2003 by MTL Instruments and Relcom Inc


Megablock Junction Box Options

Copyright © 2003 by MTL Instruments and Relcom Inc


Fieldbus Device Commissioning and
Maintenance Tools
Basic life support: bus powered
>9V 3, signal 3, polarity 3

Signal generator for wire testing

Fieldbus monitor: bus powered


measures: DC volts, signal, noise
device count, new device
communication errors

Copyright © 2003 by MTL Instruments and Relcom Inc


Hazardous Areas
• Fieldbus H1 can be used in hazardous areas with
any of these protection techniques
Area Protection Technique Live working *
Zone/ normally non-arcing 7
Division 2 non-incendive 3
Zone/ increased safety/flameproof/explosionproof 7
Division 1 intrinsic safety 3
– *Live working without a gas clearance certificate

• Techniques allowing live working preferred


• Live connection/disconnection helps commissioning,
maintenance and expansions

Copyright © 2003 by MTL Instruments and Relcom Inc


Hazardous Areas
Safe or Zone/Division 2
Hazardous area

RP302 RP302 RP302


Repeater

1 2 3 1 2 3
1 2 3 1 2 3

IS fieldbus isolator MTL5053


Up to max. 4 isolator per H1 card
T T T T

Safe or Zone/Division 1
Hazardous area

Max. up to 4 IS fieldbus
device per isolator
T Terminator
FBT1, FCS-MBT
T T T

Copyright © 2003 by MTL Instruments and Relcom Inc


Non-incendive protection
All Gas Groups
350mA, typically 16 devices

No
No live
live working
working

OR

Live
Live connection/
connection/ Division 2 or Zone 2 Hazardous Area
disconnection
disconnection
Copyright © 2003 by MTL Instruments and Relcom Inc
NET9000 Series
• Designed for the harshest
process environment
• -40 to +70 deg C
• 5g vibration
• 30g shock
• G3 corrosive resistance
• IP65 in enclosure
• Zone 2 and Class I Div 2
mounting

Copyright © 2003 by MTL Instruments and Relcom Inc


Non-incendive protection
Live
Live connection/disconnection
connection/disconnection
trunk,
trunk,spurs
spursand
anddevices
devices
Gas Group C,D; IIB 330mA, typically 16 devices

Non
Non incendive
incendive or
or IS
IScertifed
certifed field
field devices
devices
Gas Group A,B; IIC: 120mA, typically 6 devices

Division 2 or Zone 2 Hazardous Area

Copyright © 2003 by MTL Instruments and Relcom Inc


Intrinsically safe protection - FISCO
Live
Live connection/disconnection
connection/disconnection
trunk,
trunk,spurs
spursand
anddevices
devices
Gas Group C,D; IIB 250mA, typically 12 devices

Gas Group A,B; IIC: 110mA, typically 5-6 devices

Safe Area
Div 2 or Zone 2 Division1 or Zone 1 Hazardous Area
Hazardous Area
Copyright © 2003 by MTL Instruments and Relcom Inc
912x-IS FISCO power supplies
• Fieldbus repeater for
multidrop power supplies
• Power, fault and comms
LEDs
• Switch selectable
terminator for host, fixed IS
terminator
• Switch selectable power
for host H1 card
• 250V ac DC power/host/IS
fieldbus isolation

Copyright © 2003 by MTL Instruments and Relcom Inc


Fantastic FISCO

• Engineer an IS fieldbus the same as general purpose


fieldbus

– Voltage from power supply


– Current required by devices
– Ohm’s law - resistance of cabling
– Require >9V at devices

Copyright © 2003 by MTL Instruments and Relcom Inc


Is that all there is to FISCO?
• Formerly IS installations done using IEC/EN60079-14
‘Entity’ required:
– calculation of cable parameters
– comparison of safety descriptions
– creation of descriptive system document
• Now IEC TS 60079-27 FISCO Technical
Specification
– Eliminates need to calculate cable parameters
– Reduces safety documentation to a list of devices
– Allows addition of devices without a review of safety
documentation

Copyright © 2003 by MTL Instruments and Relcom Inc


Fieldbus Intrinsically Safe COncept

• Field cables must conform to the following specification:


– Loop resistance must be between 15 and 150 ohms / km
– Loop inductance must be between 0.4 and 1 mH / km
– Loop capacitance must be between 80 and 200 nF / km
– Maximum length of each spur cable is 30m in IIC and IIB
– Maximum length of each trunk cable is 1 km in IIC or 5 km in IIB
• The limits are not restrictive
– typical Fieldbus cable has parameters of 50ohms/km, 0.8mH/km and
120nF/km

Copyright © 2003 by MTL Instruments and Relcom Inc


FISCO Safety Descriptions

Entity FISCO
Ui 24V 17.5V
Ii 250mA 380mA
Pi 1.2W 5.32W
Ci 5nF 5nF
Li 20µH 10µH

Copyright © 2003 by MTL Instruments and Relcom Inc


FISCO power supply -with entity devices
Safe or Zone/Division 2
hazardous area

FISCO
power supply

Zone/Division 1 hazardous area


Entity certified
IIC/A,B,C,D FISCO
Entity spur device
certified
connector
devices

Copyright © 2003 by MTL Instruments and Relcom Inc


932X-SC Spur Connectors

• 9321-SC connects FF816 entity


certified devices to FISCO power
supply segment.
• 9322-SC connects devices located
in Zone 0 to EEx ib fieldbus trunk
• DIN rail mounting

Copyright © 2003 by MTL Instruments and Relcom Inc


MTL Relcom – Non-arcing + Flameproof
FOUNDATION Fieldbus Solution
All Gas Groups

Live
Live connection/
connection/
disconnection
disconnection

OR

Zone 1 or 2 Hazardous Area

Copyright © 2003 by MTL Instruments and Relcom Inc


MTL951 live disconnect for zones 1 & 2
• Ideal for
– EEx nA normally non-sparking
– EEx d flameproof
– EEx e increased
• Fieldbus signal and 110/230V
ac power versions
• BASEEFA certified EEx de IIC
T4
• Simple and Inexpensive

Copyright © 2003 by MTL Instruments and Relcom Inc


Surge protection
MA-4000 Power Supply Protection FP32 Segment Protection

TP32 Instrument Protection

Copyright © 2003 by MTL Instruments and Relcom Inc


Surge protection

Copyright © 2003 by MTL Instruments and Relcom Inc


Surge protection

Copyright © 2003 by MTL Instruments and Relcom Inc


Surge protection

Copyright © 2003 by MTL Instruments and Relcom Inc


Surge protection

TP32

Copyright © 2003 by MTL Instruments and Relcom Inc


MTL/Relcom power supply/
wiring component users
• Shell Malampaya • Shell Deer Park
• Shell Athabasca • Shell Brent Alpha
• Arco/Philips Alaska • Suncor
• Syncrude • Gulf Petroleum Indonesia
• Anheuser Busch • Merisol
• BP Amoco Lima • Rutgers Organics
• Corning • Petronas Malaysia
• Exxon Mobil • Baxter
• Abbott Laboratories • Degussa
• Scanraff • Pertamina Dumai Indonesia
• Bayer • Conoco
• BASF • Citgo
• NPC • Genzyme

Copyright © 2003 by MTL Instruments and Relcom Inc