Manual ET200pro Motor Starter
Manual ET200pro Motor Starter
Manual ET200pro Motor Starter
Table of contents
Description 1
Brief instructions 2
SIMATIC
Installation 3
ET 200pro Commissioning 4
and diagnostics
Motor starters
General technical 5
specifications
Appendix
Order numbers A
Dimensioned drawings B
Applications C
Data formats and data records D
Glossary, Index
Release 06/2015
NEB950566102000/RS-AA/007
Safety guidelines
This manual contains notices which you should observe to ensure your own personal safety, as well as to protect
the product and connected equipment. The information regarding your personal safety is indicated by a warning
triangle, while information regarding only property damage does not have a warning triangle. According to the
warning level, the warnings are shown in decreasing order as follows:
Safety note
Contains important information for the acceptance test and the safety-related use of the product.
Danger
Indicates that death or severe personal injury will result if proper precautions are not taken.
Warning
Indicates that death or severe personal injury can result if proper precautions are not taken.
Caution
With a warning triangle, this indicates that minor personal injury can result if proper precautions are not taken.
Caution
Without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
Attention
Indicates that an undesired result or state can occur if the corresponding notice is not observed.
Qualified personnel
The corresponding device / system must only be set up and operated in connection with this documentation.
Commissioning and operating of a device / system may only be carried out by qualified personnel.
Qualified personnel within the scope of the safety-related notices of this documentation are persons who
have the authorization to commission, earth, and label devices, systems, and power circuits according to
the standards of safety technology.
Correct usage
Note the following:
Warning
This device may only be used for the applications described in the catalog or the technical descriptions
and only in connection with devices or components from other manufacturers which have been approved
or recommended by Siemens.
This product can only function correctly and safely if it is transported, stored, set up, and installed correctly,
and operated and maintained as recommended.
Brands
All designations labelled with a trademark symbol ® are registered trademarks of Siemens AG. Some other
designations used in these documents are also brands; the owner's rights may be violated if they are used
by third parties for their own purposes.
Technical Assistance: Telephone: +49 (911) 895-5900 (8 am - 5:00 pm CET) Fax: +49 (911) 895-5907
E-mail: [email protected]
Internet: www.siemens.com/sirius/technical-assistance
Siemens AG
Automation and Drives
Postfach 4848, 90327 Nürnberg, Germany Siemens AG 2005
Technical data subject to change without notice.
Siemens Aktiengesellschaft
Preface
Target group
This manual describes the ET 200pro motor starter hardware. It is aimed
at configuration engineers, commissioning engineers and maintenance
personnel.
Scope of validity
This manual is valid for the ET 200pro motor starters. It contains a
description of the components that were valid at the time the manual was
published. We reserve the right to enclose a product information document
containing up-to-date information about new components and new versions
of components.
Guide
You can find specific information in the manual quickly by using the
following aids:
• At the start of the manual is a table of contents as well as lists of figures and tables
included in the manual.
• A glossary explaining the key terms, and an index, can be found at the end of
the manual.
Disclaimer of liability
The products described in this manual were developed to discharge safety-
oriented functions as part of a higher-order system or machine. A complete
safety system generally comprises sensors, analyzers, signalling devices
and concepts for safe shutdowns. The manufacturer of the system or
machine is responsible for ensuring correct overall functioning. Siemens AG,
its subsidiaries and its affiliated companies (hereinafter referred to as
"Siemens") are not in a position to guarantee all features of a higher-order
system or machine not designed by Siemens.
Siemens also refuses to accept liability for recommendations, express or
implicit, in the subsequent description. No warranty, guarantee or liability
claims above and beyond the General Terms and Conditions of Supply and
Sale of Siemens can be derived from the subsequent description.
Note
This is a product for environment A. This equipment may cause undesirable
radio interference in household environments.
In this case, you are required to complete appropriate measures.
Note
A list of the contents of the SIMATIC ET 200pro manuals can be found in
chapter 1.5 of this manual.
Abbreviated designations
The following abbreviated designations are used for motor starters and
special modules:
3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
6.1 Rear wall bus modules for special modules and motor starters. . . . . 6-1
6.1.1 Technical specifications. . . . . . . . . . . . . . . . . . . . . . . . . 6-2
9 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
C Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Gl-1
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . In-1
OFF
motor starters
… lockable disconnection function for
the main circuit
… for short-circuit protection
(see chapter 7.2).
1.1.4 Accessories
Terminating module
module switch module High feature Standard High feature
ON
O
OFF
ON
O
OFF
Terminating module
module repair switch down module Standard High feature
module
ON
OFF
Parts list
The parts list below gives a list of all components required for an ET 200pro
sample configuration with motor starters (see figure 1-3).
— 3RK1922-2BA00 Rear wall bus module for special modules and motor starters
— 3RK1922-2BA01 Rear wall bus module for safety local repair switch module
— 3RK1911-2BE10 Plug set for power infeed (X1) for 4 mm2 HAN Q4/2
— 3RK1902-0CE00 Plug set for motor connection (X2) for 1.5 mm2 HAN Q8/0
The table below shows the number of parameters of the individual modules in bytes:
Module PAA/PAE
(bytes)
• The following table shows you the maximum current-carrying capacity of the modules
to take into consideration:
Maximum
Component current-carrying Modules that can be connected
capacity
1.4 PROFIenergy
What is PROFIenergy
PROFIenergy is a manufacturer-independent profile on PROFINET. The profile
supports the shutdown in idle times (energy-saving function), measurement of
the energy flow (measurement function) and the status function that is used
to export the current status conditions and other information on PROFIenergy.
PROFIenergy uses field-tested PROFINET mechanisms ensuring rapid and
simple implementation
Origination
Both standards and regulations are increasingly focussing on environmental
protection and energy management as well as the desire to save energy costs
in a production plant and thus secure a sustainable competitive advantage.
As a result, the aim of industry is to save energy and to actively reduce CO2
emissions. The careful use of valuable resources means that the manufacturer-
nonspecific PROFIenergy profile defined on PROFINET makes an active
contribution to environmental protection.
O
ON
ET 200pro Distributed I/O Device
+
OFF
Essential steps
The essential steps with ET 200pro are always:
• Mounting of ET 200S components and the external wiring of control elements
(buttons) and actuators (e.g. motors)
• Configuration with STEP 7
• Integration into the user program
• Activation of the ET 200pro
• Evaluation of the diagnostics
2.3 Requirements
The requirements for the example are as follows:
• You have set up an S7 station, consisting of a power supply module and a DPV1
compatible master (e.g. CPU 315-2 DP(1), order number: 6ES7315-2AG10-0AB0).
For this example, a CPU 315-2 DP(1) was used as the DP master.
Every other DPV1 master (IEC 61784-1:2002 Ed1 CP 3/1 standard) can also be used,
of course.
• On your PG, STEP 7 (from V 5.3 with SP2) is fully installed. You have STEP 7
knowledge.
• The PG is connected to the DP master.
Note
Information regarding the operation of STEP 7 can be found in the online help.
2.4 Installation
Warning
Dangerous electrical voltage! This can lead to electrical shock and burns.
Before starting work, de-energize the plant and device.
Unused connections must be sealed using standard accessory components.
The following image shows you in which order you should mount the ET 200pro
components onto the module carrier.
A1 A2 A3 A4 A5
Terminating module
ON
O
OFF
Infeed Cap
Cap Motor connection
Module carrier, wide Energy jumper plug
Figure 2-1: Components and setup for the example
Mounting order
A precise mounting description can be found for the following:
• IM 154 Installation of DP High Feature and digital modules in the manual
’ET 200pro Distributed I/O Device’
• Installation of rear wall bus modules in chapter 3.4
• Installation of repair switch modules and motor starters in chapter 3.5
64
32
16 Coding switch under screw cover
8 on the front side
4
PROFIBUS address 6 2
1
The following image shows the circuitry of the main circuit and the control
circuit for the example.
PROFIBUS-DP
1L+
2L+
1M
2M
Terminating module
Bus module Bus module Bus module
A1 7 7 7
IM 154
A2 A3 A4
IN1
IN2
IN3
IN4
Q1
Q1
DI 8 Logic
L1
L3
L1
L3
L1
L3
PE
PE
PE
PE
PE
PE
L2
L2
L1
L3
L2
L2
L1
L3
L2
L2
A4
1 1
ON 13 DC 21
24V OFF
M 2 2
3~ 14 22
DI0 4 4 DI1
L1 IN1 IN2
L2 3 3
L3
PE 1M
5 5
FE
Caution
Provide sufficient short circuit and overload protection for the entire setup.
2. Cable the ET 200pro as shown in figure 2-3. Only the external lines shown in
bold should be connected. The functions are:
– 400 V AC and PE (power supply) on connection X1 of the repair switch
module
– Consumer (motor) on connection X2 of the motor starter
– Energy jumper plug between connection X3 of the repair switch
and connection X1 of the motor starter
– both switches for ON (NO contact) and OFF (NC contact) on
electronics module 8 DI 24V DC
3. Seal the connection X2 of the repair switch module with a cap
4. Seal the connection X3 on the motor starter using a cap
5. Connect the DP Master to the ET 200pro using the PROFIBUS bus
connection cable. The PROFIBUS DP interface is on the
IM 154-. DP High Feature.
6. Switch on the voltage supply for the DP master.
7. Observe the status LEDs on the DP master.
CPU 315-2 DP:
- 5 V DC green
- SF DP off
- BUSF flashes red
2.6 Configuration
1. Start the SIMATIC Manager and create a new project with a DP master
(e.g. CPU315-2 DP) (see figure 2-4).
2. Generate the PROFIBUS subnet.
3. Insert the ET 200pro on the PROFIBUS from the hardware catalog.
4. Set the PROFIBUS address 6 for ET 200pro.
5. If not already carried out, update your software (see chapter 4.2 - ’Updating
the software’), so that the ET 200pro modules are visible. Drag the individual
ET 200pro modules from the hardware catalog into the configuration table
(see figure 2-4).
6. For complete display of the parameter set for motor starters, in the screen
for the module IM 154-. under ’Operating parameters’, set the DP Alarm
Mode of ’DPV0’ (=preset) on ’DPV1’. If this is not possible, the CPU used
is not suitable for DPV1.
7. Parameterize the ’Response to residual current detection’ for the motor
starter for this example to "warning".
Module / Order number Input Output Comment
DP code address address
2 3RK1304-0HS00-8AA0 0.0 - 0.7 Disconnecting
module
3 3RK1304-5xS40-4AA01) 1.0 - 1.3 0.0 - 0.3 DSe motor starter
4 6ES7141-4BF00-0AA0 3.0 - 3.7 Electronics module
8 DI 24V DC
1) x = The current range should be selected according to your connected load
2.8 Activation
1. Switch on the following voltage supplies on ET 200pro.
- 1L+ and 2L+ via the IM 154-. module
- Do not switch on the 400 V AC power supply!
2. Observe the status LEDs on the DP master and ET 200pro
- CPU 315-2 DP:
5V DC: Lights up
SF DP: off
BF: Off
3. Observe the status LEDs on the IM 154-. DP high feature.
- SF off
- BF off
- ON green
- 24 V DC green
4. Observe the status LEDs on the 8 DI 24V DC
- DI0 off
- DI1 green
- DI2 off
- DI3 off
5. Observe the status LEDs on the DSe motor starter
- SF off
- STATE off
- DEVICE green
Danger
Make sure that no dangerous live parts can be touched.
Warning
Make sure that the actuators connected to the motor starters do not present
a danger (e.g. uncontrolled rotary movements of the motor).
1. Open the ’HW Config’ window in the SIMATIC Manager on your computer
or programming device.
2. Open the "Online" station.
3. Simulate various windows and observe the messages in the ’DP Slave
Diagnostics’ status window, for example:
- Shut down the voltages 1L+ and / or 2L+
In the image below, for example, a motor starter is diagnosed on slot 2 and 3.
2.10 Help
If you have problems or questions, please contact:
Technical Assistance: Telephone: +49 (911) 895-5900 (8 am - 5:00 pm CET) Fax: +49 (911) 895-5907
E-mail: [email protected]
Internet: www.siemens.com/sirius/technical-assistance
Easy installation
The ET 200pro distributed I/O device is designed for simple installation.
ET 200pro motor starters are designed as a complete device together with
a rear wall bus module (110 mm) on a module carrier, wide (press-drawn
section).
First fit the ET 200pro interface module IM 154-. onto the module carrier.
Then fit required rear wall bus modules in succession onto the right-hand side
of interface module IM 154-.
The function modules are fitted onto the rear wall bus modules in stages by
fitting them onto the right-hand side of the interface module IM 154-. or the
preceding module by fitting them on and then screwing them on using 3 Phillips
bolts.
Installation position
The distributed I/O device is suitable for the following installations on a vertical
wall:
ON
ON
OFF
O
OFF
vertical horizontal
Figure 3-1: Installation position
Please note:
During configuration, please observe the following points:
Measurements Module mm
Installation Rear wall bus module for motor starters and special modules 110
width
Installation On module carrier, wide, with rear wall bus module for:
depth • Special modules
- Repair switch module 190
- Safety local repair switch module 190
- 400V shutdown module 170
• Motor starter; standard 170
• Motor starter high feature with sensor cables 180
3.3 Derating
3.3.1 What is derating?
In the case of the ET 200pro special modules and motor starters, the following
factors must be taken into account and balanced against one another when
used in challenging ambient conditions:
• Ambient temperature Tu:
The ambient temperature Tu is the temperature surrounding the housing of
a special module and motor starter.
The lower the maximum ambient temperature Tu, the higher the current load
in the special modules and motor starters can be.
• Absolute current load Ie:
The lower the current through a special module and motor starter, the lower
the heat loss (= heat) within the device. If the device does not generate much
heat, the ambient temperature Tu can be higher.
ON
OFF
O
Ie [A] Ie [A]
RSM ASM 400V
O
ON
RSM
OFF
30 30
ON
OFF
O
ASM 400V
25 25
ON
O
OFF
20 F-RSM 20
F-RSM
15 15
ON
OFF
O
10 10
DSe, RSe
5 5 DSe, RSe
0 0
10 20 30 40 50 60 10 20 30 40 50 60
ϑu [°C] ϑu [°C]
+RUL]RQWDODVVHPEO\ 9HUWLFDODVVHPEO\
sDSSte / sDSte sDSSte / sDSte
,H>$@ ,H>$@
sRSSte / sRSte sRSSte / sRSte
$ :LWKE\SDVV$GHYLFH $ :LWKE\SDVV$GHYLFH
$ $ $
$ $
$ 'LUHFWVWDUWXSWR&ODVV$GHYLFH $ 'LUHFWVWDUWXSWR&ODVV$GHYLFH
$ $
$ :LWKRXWE\SDVV$GHYLFH $
$ $ :LWKRXWE\SDVV$GHYLFH
$
$ $ $ $
$
$ $
$ $
$ :LWKRXWE\SDVV$GHYLFH $ :LWKRXWE\SDVV$GHYLFH
$ $
˽>r&@ ˽>r&@
< 8-fold Ie 2A 12 A 12 A
9-fold Ie 1,7 A 10 A 8A
10-fold Ie 1,5 A 9A 7A
Site altitude
If site altitude is above 1000 m, the following are necessary:
• A reduction in the rated current for thermal reasons
• A reduction in rated voltage on account of the diminished dielectric strength
The diagram below plots the reductions in rated current and rated operating
voltage as a function of site altitude:
105
100 Ue reduction
95 Ie reduction
90
85
80
75
70
0 500 1000 1500 2000 2500 3000 3500 4000
Site altitude in m
Requirements
Space is left for the IM 154 interface module.
Installing rear wall bus module for special modules and motor starters
The example below shows the installation of a rear wall bus module.
Drawing Procedure
3
1
5
Table 3-2: Rear wall bus module installation
Caution
Ensure that the seal is securely seated and observe the tightening torque of
the Phillips bolts of 1.5 Nm to ensure that the construction is fully sealed.
3 x 1.5 Nm 2
3 x 2)
1
1
1
4 3
Caution
The plug insert on the X1 connection of the repair switch is installed rotated
180° against the plug insert on the X1 connection of a motor starter.
This prevents an X1 connection cable for the repair switch being inserted
onto a motor starter.
3
3
4 5
Caution
If you remove more than one module from the ET 200pro, the station switches
to STOP.
The table below describes how to remove motor starters using the example
of a direct starter.
4
Table 3-7:Removing motor starters
8
8
Note
It is advisable to inform maintenance and service personnel in detail about
correct handling of the motor starters before the system is handed over to
ensure that the advantages of ET 200pro can be deployed from the start.
Attention
It is essential that the voltage tolerance for the 2L+ load power supply
(contactor and power electronics) is observed up to 55 °C: 20.4 V to 28.8 V.
Current set
With all motor starters you parameterize the current set via the relevant
configuration and parameterization tool (e.g. GSD file, HW config, motor starter
ES, TIA portal, etc.).
Safety note
External short-circuit protection
If the short-circuit current at the installation position of the motor starter, can
exceed the rated short-circuit breaking capacity (100 kA/400 V) of the integrated
fuses, you must provide additional external short-circuit protection (fuse or
circuit breaker), see also chapter 7.4.
Caution
A reset is only accepted if the parameterized recovery time previously set is not
reached.
• Repair switch module or local safety module with integrated power switch of
size Ie 25 A.
Actuation value of the short-circuit protection at 13 x Ie.
Reset by pressing the rotary switch.
Caution
Unplugging or plugging in a consumer during ongoing operation (i.e. under load)
is not permitted.
Reversing starters
Use the user program to ensure before a change of direction that the drive
is switched to "STOP" mode and remains in stop until the motor has stopped
turning.
4.2 Configuration
Configuring means configuring and parameterizing the ET 200pro.
More information can be found in chapter 5 of the manual ’SIMATIC ET 200pro
Distributed I/O Device’.
The table below shows which STEP 7 version is required for operating
the modules.
STEP 7
Product label Order number Product brief version
from
Caution
If during the configuration process, the interface module IM 154-. and
the ET 200pro motor starters are not visible, a software update is required.
Software update
To update your software via the internet, proceed as follows:
1. Open the STEP 7 software ’HW config’
2. Open the menu option ’Tools’ > ’Install HW Updates’
3. In the screen that is opened, activate the ’Download from the internet’ option
(ensure that there is an active connection to the internet)
4. In the table, select the required updates or click the ’Select all’ button
5. Click ’Run’
6. The updates will be installed
4.3 Diagnostics
4.3.1 Diagnostics and monitoring through the user program
Diagnostics and monitoring for ET 200pro take place via the user program and/
or the diagnostics channel of the PROFIBUS DP.
Any group faults (DI 0.2=1) and group warnings (DI 0.3=1) are sent to the input
process image.
For comprehensive diagnostic analysis and demo programs using STEP 5 and
STEP 7 see manual ’SIMATIC ET 200pro Distributed I/O Device’.
The S7 blocks FB125 and FC125 are available for diagnostic analysis in the user
program. The S7 blocks and the accompanying descriptions are available as free
downloads from the following addresses:
http://support.automation.siemens.com/WW/view/de/387257
http://support.automation.siemens.com/WW/view/de/5362473
In the following tables you will find the respective fault types and their
meanings as a supplement to the channel-based diagnostics.
Direct starter 00100: • Thermal motor model • Allow the motor to cool down
DSe, sDSSte / Overload overload • Check the motor's current
sDSte (F4) consumption
• Check the set current limits
00111: • Ie upper current limit
Reversing starter
Upper limit violated
RSe, sRSSte /
violated
sRSte
(F7)
01000: • Ie lower current limit
Lower limit violated
violated
(F8)
01001: • Internal failure/device Switch the 1L+ supply voltage
Fault fault on and off, if fault continues,
(F9) • Switching element replace motor starter.
defective
11000: • Asymmetry Check phases L1 to L3.
Actuator shutdown • Motor blocked Clear stalled rotor.
(F24) • Residual current Check main phases L1 to L3
detected for interruption.
• Or in conjunction
with another type
of fault in this table
11010: • Input tripping Eliminate the external fault
External fault • Input tripping limit (withdraw from limit position,
(F26) position for example)
00101 • Thermal motor model Check plant configuration
Overload is at >178% load.
switching element Shutdown as device
(F5) protection if "Thermal
motor model"
parameter setting =
warning.
10001: • Switching element Check 2L+
(F17) power supply missing
Table 4-3: Fault types for motor starters
LED
Status / cause of fault
SF1)
Operating status
Red Device fault (device diagnostics from interface module IM 154-. detected)
1) Status of the LEDs in this form only when group diagnostics activated
1) Status of the LEDs in this form only when group diagnostics activated
2) Flashes after starting operation for approx. 7 s due to self-test, change of the connection assignment in operation
or fault in the electronics
LED
Status / cause of fault
SF1)
Operating status
1) Status of the LEDs in this form only when group diagnostics activated
4.4.4 DSe, sDSSte / sDSte, RSe, sRSSte / sRSte motor starter diagnostics
LEDs
Status / cause of fault
SF STATE Device
Off Green Green Motor on; no fault (cw or ccw with RSe)
Table 4-4: Status and fault displays via LEDs for DSe, sDSSte / sDSte, RSe, sRSSte / sRSte
LEDs
Status / cause of fault
SF STATE Device
Device fault
(fault sets group fault)
Input signals
Repair switch Safety Local repair 400V shutdown
module switch module module
DI 0.0 Module status: Module status: Module status:
0 ON ON OFF
1 OFF OFF ON
DI 0.1 Status of the safety Status of the safety
bar bar
0 Not used Bar not powered Bar not powered
1 Bar powered Bar powered
DI 0.2
0
1
DI 0.3
0
1
DI 0.4
0
1
Not used Not used Not used
DI 0.5
0
1
DI 0.6
0
1
DI 0.7
0
1
Input signals
DI 0.0 Ready (automatic) DI 1.0 Motor current Iact2)
0 Starter not ready via host / Bit 0
PLC
1 Starter can be operated
by host
DI 0.1 Motor on1) DI 1.1 Motor current Iact2)
0 Off Bit 1
1 On (clockwise/
counterclockwise rotation)
DI 0.2 Group fault DI 1.2 Motor current Iact2)
(short-circuit / overload)
(If one or more faults Bit 2
described in table 4-6 occur,
"Group fault" is reported
irrespective of whether the
"Group diagnosis" parameter
(see chapter 7.6.1 and
chapter 8.2.4) is set to
"Disable" or "Enable").
0 No faults
1 Fault
DI 0.3 General warning DI 1.3 Motor current Iact2)
0 No warning Bit 3
1 Warning
DI 0.4 Input 1 DI 1.4 Motor current Iact2)
0 Not active Bit 4
1 Active
DI 0.5 Input 2 DI 1.5 Motor current Iact2)
0 Not active Bit 5
1 Active
DI 0.6 Input 3 DI 1.6 Manual local operating mode
0 Not active 0 Not active
1 Active 1 Manual operation local
DI 0.7 Input 4 DI 1.7 Ramp operation
(for soft starter)
0 Not active 0 Not active
1 Active 1 Active
1) Signal is 1 if the motor current is >18.75% of the set rated current
2) See chapter 10.3.1
For a description of the parameters, see chapter 10.3
Output signals
The 3 log books are organized as a ring buffer each of 126 bytes. The entries are
made together with the corresponding current operating hours of the device.
For each entry, 6 bytes are required, meaning that the last 20 entries remain
legible.
Format of the entries:
Byte Meaning
With all ET 200pro motor starters, the operating hours are secured if the voltage fails
(a maximum of 6 minutes is lost). Statistics data can be exported via ’ES Motor Starter’
or via PLC DPV-1 with SFC59 or SFB 53.
System diagnostics (see also manual ’ET 200pro Distributed I/O Device’)
In diagnostics-compatible ET 200pro devices, device-specific diagnostics are
recorded via assigned PROFIBUS fault numbers. The relevant fault number
is issued to the ET 200pro interface module IM 154-. .
The system diagnostics show if there is a channel fault. Information on whether
or not channel-related information is present is also provided.
In the diagnostics data record (see manual "ET 200pro Distributed I/O Device“),
the channel-related diagnostics start from byte 19.
For each channel-related diagnostics, 3 bytes are always inserted. The
associated DP fault number (= fault type) is binary-coded, inserted in each case
in the third byte on bit positions 0 … 4.
The stored values are extracted by the starter from the diagnostics recorded
in data record 92. As there are insufficient uniquely defined DP fault numbers
for the starters, different DS92 diagnostics must be mapped to one and
the same number (= multiple assignment; see table).
Supported by ET 200pro
Channel-specific diagnostics DP DS92:
motor starters /
Single fault Fault no. Byte no.
DS92 meaning
Reserved
Short-circuit 1 22 Temperature sensor short-circuit
power switch tripped (repair
32 switch module)
Overload 4 23 Thermal motor model overload
3
Excess temperature 5 0 Overload switching element
Upper limit exceeded 7 42 Ie limit exceeded
3
Lower limit violated 8 4 Ie limit value violated
4
Fault 9 0 Switching element defective
1
Parameterization fault 16 8 Invalid parameter value
82 Parameter change in ON status
not permissible
Transmitter or load voltage not present 17 10 Switching element power supply
missing
Actuator shutdown 24 24 Overload shutdown
41 Asymmetry shutdown
44 Ie limit value shutdown
46 Zero current shutdown
47 Motor blocking shutdown
External fault 26 33 Current limitation active
(sDSSte / sDSte and sRSSte /
54 sRSte)
55 Input tripping
Shutdown input
57 (ccw end position)
Shutdown input
(cw end position)
Table 4-6: System diagnostics
Device diagnostics
In the input process image for the starters, the current group fault (DI 0.2)
and group warning messages (DI 0.3) are sent cyclically where necessary.
More in-depth information on the fault type are accessible where necessary
via a diagnostics call (V1-system diagnostics).
All device-specific diagnostics are summarized in the data record 92 (29 bytes).
The content of DS 92 can be exported using ’ES Motor Starter via the device
interface or online via DP V1 using the ’Read data record’ function.
Application
The ’ES Motor Starter’ diagnostic and commissioning tool is suitable for
the following motor starters:
• DSe, RSe
• High feature DSe, sDSSte / sDSte, RSe, sRSSte / sRSte
The connection between the PC or programming device and the motor starter
is set up using an infrared RS232 PC cable.
Caution
To ensure fault-free data transfer, ensure that the infrared interface is clean.
You can find additional information on the software in the online help.
Order Numbers
The order numbers for the RS232 interface cable, USB cable, the ES Motor
Starter software can be found in the appendix under Components for ET 200pro
motor starters.
Temperature -25 to 55 °C
Snap-in nose
Data bus
Snap-in nose
Snap-in nose
7.1 Overview
The following special modules are available:
• Repair switch module (RSM) (see chapter 7.2)
• Safety local repair switch module (F-RSM) (see chapter 7.3)
• 400V shutdown module (ASM-400V) (see chapter 7.4)
Parameters and technical specifications for the special modules, see chapter 7.6.
The repair switch module is designed for the following individual functions:
• Disconnect the downstream starters from the power supply
• Start lockout via a padlock on the rotary element
• Shortcircuit protection for series-connected consumers with 25 A power
switch
≤8 mm
Labelling field
Data bus
1L+
1M
L1 1 7
L2 2
L3 3
PE
X1)
Logic
12 3 X2) 1 2 3 X3)
PE
PE
L1
L2
L3
L1
L2
L3
1 2 3 4 3 4
11 12 11 12 11 12
3 4 1 2 1 2
Figure 7-3: Assignment of the main power connections on the repair switch module
Safety note
The module should be tested during commissioning and then every 12 months.
For the test, proceed as follows:
- Press the emergency stop switch
- Check that the OUT output has been switched off
- Check that the 400 V AC has been switched off
- Release the emergency stop switch
- With a monitored start, check that the OUT output and the 400 V are still
switched off; then press the START button
Repeat the test with the next emergency stop switch until all emergency stop
switches have been pressed.
The module with local safety function is designed for the following individual
functions:
• Has the same functions as a repair switch module
• 2 safe inputs for:
– Emergency stop / emergency off or safety door contacts, 2-channel
– Monitored start-up
• 2 safe outputs, incl.:
– 1 output on the front
– 1 output on the back with power infeed on 1 safety RW channel
• 2 sliding switches for setting the basic functions
– 1-channel / 2-channel
– Autostart / monitored start
• Low-demand and high-demand operating mode
• Use up to safety category 4 conforming to EN 954-1 or SIL 3 conforming
to IEC 61508
Caution
The safety local repair switch module can only be installed on the rear wall
bus module 3RK1922-2BA01.
7.3.2 Description
The safety local repair switch module includes a 3TK2841 module and is
equipped with M12 connections for connecting external safety components.
Either 1-channel or 2-channel emergency stop / emergency shutdown circuits or
safety door circuits can be connected to connection 1 (IN 1 / IN 2).
Both mechanical switches and electronic sensors can be connected. Electronic
sensors must be operated in the "1-channel mode" operating mode.
An external switch (NO contact) for monitored START can be connected (START)
on connection 2. The connected switch must not be pressed when switching
on or enabling the emergency stop / emergency shutdown function. The OUT
output or F0 bar is activated when the switch is released. The length of pressing
the switch should be in the range 200 ms … 5 s, otherwise this start command
is not accepted.
There is a safe output for connecting a door tumbler available (OUT) on
connection 3.
The required safety function can be set via 2 sliding switches located
underneath the left-hand M12 opening.
The safe inputs are assigned to connection numbers 2 and 4.
The safe outputs are supplied with voltage via the rear wall bus module.
An output is looped through on the front and can be used to actuate a door
tumbler, for example (OUT).
The 2nd output switches the supply to the contactor coils (2L+) for the
downstream motor starters via the rear wall bus module (F0).
Caution
The door tumbler above is only a simple mechanical lock, in other words this
door tumbler does not conform to the safety applications of category 4
conforming to EN 954-1, as a feedback of the mechanical lock bolts is not
possible.
When connecting an electronic sensor with two outputs, ensure that the cross-
circuit detection is realized in the sensor.
The electronic sensor and the ET 200pro station must be supplied from
the same power supply unit.
≤8 mm
Rotary element for
power switch with
ON
start lockout via
padlock
O Fault
OFF
RUN
LED group fault
POWER
1-channel
Labelling field 2-channel
Connection 2 (START)
Connection 1 (IN1, IN2) with status display
Sliding switch for
Connection 3 (OUT)
function selection
with status display
Plug-in connector
for outfeed of the Padlock bolt
main power (X2)
Data bus
1L+
2L+
1M
2M
F0
L1 1 7
L2 2
L3 3
PE
X1)
IN 3 monitored START
OUT
12 3 X2) 1 2 3 X3)
PE
PE
L1
L2
L3
L1
L2
L3
Figure 7-5: Circuit diagram for safety local repair switch module
1 2 3 4 3 4
11 12 11 12 11 12
3 4 1 2 1 2
4 3
Figure 7-7: Assignment of the auxiliary circuits on the safety local repair switch module
Configuration
Sliding switch
S1 S2
1—
1 2-channel operation autostart;
0—
0 1-channel operation Monitored START
S1 S2
Figure 7-8: Configuration of the safety local repair switch module
Safety note
The set configuration should be checked with the ’1-channel’ and ’2-channel’
displays. One of these two displays should always be lit.
If both are lit at the same time or are off at the same time, the device is no
longer ready for operation and should be replaced immediately.
Caution
Configuration changes must be carried out with the 2L+ power supply switched
off.
Changes with 2L+ power supply present result in a fault message and to shut
down the outputs. To reset the fault message and to transfer the changed
configuration, the 2L+ power supply must be switched off and back on again.
Electronic sensors must be operated in the "1-channel mode" operating mode.
With an internal or external fault (e.g. cross-circuit of the emergency stop lines),
the outputs are shut down and the fault is signalled via the ’FAULT’ LED.
With an external fault, the ’FAULT’ LED is on continuously. After the fault has
been corrected (e.g. enable emergency stop), the module can be operated
again.
With an internal fault, the ’FAULT’ LED flashes. If the fault cannot be resolved
by switching on and off, e.g. when changing the configuration in operation,
the module must be replaced.
Safety note
The module should be tested on commissioning and after that,
every 12 months.
For the test, proceed as follows:
- The safety module supplying the F0 bar should be shut down.
- Check that the 400 V has been shut off.
- The safety module supplying the F0 bar should be switched on.
The 400V shutdown module is designed for the following individual functions:
• 2-way shutdown of the main circuit supply (category 4)
• Return message of the module functional status via bus
• Return message of the switching status of the contactor via bus
7.4.2 Description
The 400V shutdown module must only be used in combination with the safety
local repair switch module for local safety applications. It includes 2 series-
connected contactors for the safety-oriented shutdown of the main supply
circuit. The operational switching of the connected consumer must be carried
out via a downstream motor starter. The auxiliary circuit supply of the device is
provided via a safety bar in the rear wall bus module.
The 400V shutdown module can be used in combination with the safety local
repair switch module for safety applications up to category 4 conforming to
EN 954-1 or SIL 3 conforming to IEC 61508.
The operating mode is low-demand and high-demand.
Caution
The aggregate current via the 400V shutdown module must be max. 25 A.
Warning
With a load-side short-circuit (power switch on the F-RSM has tripped), there
is a risk of both contactors being welded in the ASM.
After a short-circuit shutdown, the ASM must therefore be checked for correct
functioning.
In switched off status, there must be no electrically conductive connection
between pins 1, 2 and 3 on the X1 connection and sockets 1, 2 and 3 on X2
connection.
Welding the contactors in the event of a short-circuit must be avoided via an
additional protection in the energy infeed with fuses (max. 16 A gL/gG NH
type 3NA, DIAZED type 5SB or NEOZED type 5SE).
Labelling field
Plug-in connector
for forwarding of
Plug-in connector the main power (X2)
for infeed of the
main power (X1)
Padlock bolt
OUT 2
1L+
1M
2M
L1 1 7
L2 2
L3 3
PE
X1)
Q1
DI 0.0 Module status
DI 0.1 Safety bar status
Logic
Q2
Q1 Q2
123 X2)
PE
L1
L2
L3
4 3 3 4
12 11 11 12
2 1 1 2
X1) X2)
If an internal fault occurs, the outputs remain without power and the fault
is signalled with the ’SF’ LED and notified via bus as diagnostics alarm.
In this case, the faulty module must be replaced.
L1
L2 T1 T1
L3 T2 T2
T3 T3
Infeed
To load
To load
Jumper plug
Warning
With special modules and with motor starters, unused connections with caps
do not need to be sealed to protect open contacts against dirt and to seal
the ET 200pro securely in line with IP65.
Action,
Parameters Factory setting Applicability
value range
Module-specific data
Safety guidelines
T1 — 10 years 10 years
B10 — — 6 x 105
Control circuit
Main circuit
Insulation resistance
Protective separation between main and auxiliary 400 V, conforming to DIN EN 61140
circuits
Circuits with rated voltage Ue against other Test voltage conforming to IEC 61131, Part 2
circuits or earth 500 V DC
• 0 V < Ue < 50 V 2.6 kV DC to ground
• 300 V < Ue < 600 V
1)
These values apply in combination with the F-RSM module
Table 7-2: Technical specifications for the special modules (Contd.)
Due to the integrated electronic overload protection, a cover of the power range up
to 12 A with only two device versions is possible. The ET 200pro motor starters can
be parameterized and permit access to comprehensive diagnostic and statistics
data. The PC configuration tool ’ES motor starters’ is available for this purpose from
version 2006.
A connection to the motor starters can be established in two ways:
1. Locally on-site via the optical device interface of the motor starter
2. Remote on PROFIBUS DP via DPV1
Caution
Due to the operation of star-connected three-phase motors, high EMC
interference may occur. Interference above the IEC limit values can lead to an
impairment of functions or failure of the electronics. In case of high EMC
interference, we recommend the use of motors with EMC protection circuits.
(Exception: electronic starters may not be operated with a EMC protection
circuit).
The best filtering effect is achieved with three-phase RC interference inversion
modules.
Varistor interference inversion modules should not be used since they only
insufficiently filter out fast transients.
The ET 200pro motor starters are offered as direct (DSe) and reversing starters
(RSe) each in two versions:
• Standard series (code: DSe, RSe
– either with control for externally supplied brake with 400 V
– without digital inputs
• High feature range (short name for direct starters: DSe, RSe
– either with control for externally supplied brake with 400 V
– with 4 digital inputs
– with advanced parameterization options
The ET 200pro electronics starters are available as direct (sDSSte / sDSte) and
reversing starters (sRSSte / sRSte) in the high feature version with the following
equipment.
• 4 digital inputs
• with soft start and soft coasting-down function
• with deactivated soft start function as electronic starter for applications with
high switching frequency
• either with control for externally supplied brake with 400 V
• with advanced parameterization options
The table below provides an overview of the various properties of the motor
starters.
• DSe ST are motor starters for a direction of rotation that can be used in
the ET 200pro distributed I/O device
• RSe ST are motor starters for two directions of rotation with mechanical lock
on cw and ccw motion that can be used in the ET 200pro distributed I/O
device
• Are suitable for switching and protecting three-phase loads up to 5.5 kW
at 400 V AC
• Are available in setting ranges of 0.15 - 2 A and 1.5 - 12 A
• are equipped with SIRIUS contactors
• Have parameterizable electronic overload protection
• Integrated residual current detection
• Asymmetry detection integrated (fixed limit value 30 % Ie)
• The as-is current is measured and the information transmitted to analyzers
• Detection of the switching status of the contactor
• Available diagnostic information of the motor starter (see chapter 4.3)
• Integrated log book functions with 3 device log books
• Integrated statistics data memory
• Circuit state and motor-starter status are indicated by LEDs
• Available either with control for externally supplied brake with 400 V AC
• Short-circuit protection via 3 fuses, meaning they can only be operated
without repair switch module / external short-circuit protection
• Separate supply voltage for
– Bus interface, electronics
– Contactor coils
• Manual control and local parameterization possible via optical device interface
• The power infeed, energy forwarding via a loop and load branch is provided
via power plug-in connector with padlock
• Firmware update via the optical device interface possible via specialist
personnel
• Have the same basic properties as the DSe ST and RSe ST motor starters
• Also have 4 digital inputs for 2-wire and 3-wire sensors with LED display.
The inputs can also be used for parameterized local control functions
• Have advanced parameterization options
• Upper and lower current limits can be defined and monitored for system and
process supervision
• Have the same basic properties as the DSe HF and RSe HF motor starters
• Also have soft start and coasting down functions
• With the soft start function deactivated, the motor starter can be used as
an electronic direct and reversing starter
• Current limitation function
• Thermistor motor protection
8.2.4 View of DSe and RSe motor starters; Standard and high feature
Inputs IN 1 to IN 4
with status display
(only with high feature)
Plug-in connector
for forwarding of
Plug-in connector the main power (X3)
for infeed of the
main power (X1)
Padlock bolt
Plug-in connector
for consumer connection (X2)
Figure 8-1: View of DSe and RSe motor starters; Standard and high feature
Inputs IN 1 to IN 4
with status display
Figure 8-2: View of electronic sDSSte / sDSte und sRSSte / sRSte starters
4 3 3 4
6 47 8 5
12 11 11 12
1 2 3
2 1 1 2
Figure 8-3: Assignment of the main power connections on the motor starter
Auxiliary circuits
There are the following auxiliary circuits on a ET 200pro motor starter:
• 1L+ Electronic voltage supply via the rear wall bus module to supply
electronics and connected sensors on inputs IN 1 to IN 4.
• 2L+ Load power supply ( 24 V DC) via the rear wall bus module for actuation
of the contactor.
• Sensor supply via M12 plug-in connector. Connections 2 and 4 are bridged.
Connection 5 is inside the device connection to functional earth.
The image below shows the assignment
1 2
+24 V DI x
DI x 0V
4 3
5 FE (functional earth)
Figure 8-4: Assignment of the M12 plug-in connector on the motor starter
Diagram for DSe (ST and HF) direct starters and electron. sDSSte / sDSte starters
Data bus
1L+
2L+
1M
2M
7
L1 1 1 L1
L2 2 2 L2
L3 3 3 L3
PE
X1) X3) PE
Input 12)
DI 0.4
Input 22)
DI 0.5
Logic Input 32)
DI 0.6
Input 42)
DI 0.7
DO 0.0 Motor cw
DO 0.2 Brake
DO 0.5 Self-test
Auxiliary switch
Q1
1) Brake control only with order number suffix … AA3
Br.
L1
L3
L2
Figure 8-5: Circuit diagram - DSe direct starter; Standard and high feature
Diagram for rev.-starter RSe (ST and HF) and electron. rev.-starter sRSSte / sRSte
Data bus
1L+
2L+
1M
2M
7
L1 1 1 L1
L2 2 2 L2
L3 3 3 L3
PE
X1) X3) PE
DI 0.4
Input 22)
DI 0.5
Logic Input 32)
DI 0.6
Input 42)
DI 0.7
DO 0.0 Motor cw
DO 0.2 Brake
DO 0.5 Self-test
Q1 Q2
Q1 Q2 Auxiliary switch
1) Brake control only with order number suffix … AA3
Br.
PE
L1
L3
L2
Figure 8-6: Circuit diagram - RSe reversing starter; Standard and high feature
Danger
Hazardous voltage. Danger of death or risk of serious injury.
Before starting work, de-energize the plant and device.
Phase L1 is not run via the semiconductor in the sDSSte / sDSte and sRSSte /
sRSte.
8.2.7 Parameters
Group diagnosis:
This parameter enables diagnosis messaging (fault types are listed in
chapter 4.3).
Note
The "Disable group diagnostics" parameter is also used to suppress the SF-LED
displays of faults set by the header. The changed fault detection and display via
SF-LED remains active.
Note
For electronic starters sDSSte / sDSte, sRSSte / sRSte, the following applies:
With the brake delay activated, the brake delay must be greater than the
coasting time when the coasting time is set.
Note
This is a product for environment A (industrial area). This equipment may cause
undesirable radio interference in household environments. In this case, the user
may be required to complete appropriate measures.
Caution
The brake actuation and the motor control are laid in the same cable. Non-
permissibly high levels of induction voltages can arise when the motor is
switched off, and these are coupled to the brake actuation in the motor cable
and in this way can result in electrical component faults in the starter.
Brake motors controlled via starter …AA3, should therefore always be fitted
with suppressors (e.g. RC combinations) for the main circuit (exception:
Electronic starters must not be operated with an EMC protective circuit).
107
8
6
4
Operating cycles at 400 V
106
8
6
4
2
105
8 Ia = Breaking current
6
4 Ie = Rated operating current
2
104
8 PN = Rated power of three-phase
6
4 motors at 400 V
2
103
2 3 4 5 6 10 20 30 40 50 60 80 100 200 Ia(A) 400
9 12 Ie(A)
4 5,5 PN (kW)
Starting current
Rotary current asynchronous motors have a high switch-on current I(Anlauf).
This inrush current can be between three and fifteen times as high as the rated
operating current, depending on the type of motor. A figure between seven and
eight times the rated operating current can be postulated as typical.
I
Istartup
Irated
I0 (idle)
nrated nsyn n
Mpull-out
M
Mmotor
Mstartup
Mload
Mdip
Maccel
Mrated
Mmotor
Mload
nrated nsyn n
Figure 8-8: Typical current and torque curve of a three-phase asynchronous motor
I Starting current in d M
IAd
MAd Mmotor at d
Mload
Starting current
for * / d start
IA*=
1/3 IA d Mmotor at*
=1/3 MAd MA*
n n
n nsyn n nsyn
*nrated *nrated
UL1- L3
α α
α α ϕ
L2
UL2- L3
M L1
3~
L3
G1
Figure 8-10: Phase firing of the supply voltage by semiconductor elements in the sDSSte / sRSSte
soft starters
Example:
Starting voltage 50 % of Ue => starting current equals 50 % of the motor
starting current for direct-on-line starting.
A soft starter also reduces motor torque. This is the reason why a soft-started
motor does not jerk into action.
The relationship is as follows: motor torque is proportional to the square of
motor voltage.
Example:
Starting voltage 50 % of Ue => starting torque 25 % of the starting torque for
direct-on-line starting.
Advantages:
• Less space needed in the control cabinet
• No protective circuitry (e.g. filter elements) needed for compliance with radio
interference suppression requirements
• Lower installation costs
• Straightforward system startup
• Only 3 motor feeder cables, half as many as are needed for a star delta
starter
• Local adjustments make the unit easy to configure in accordance with system
requirements.
Disadvantages:
• Long-term speed settings not possible.
• Lower torque at reduced voltage
I M
100 % Usystem
Istartup
100 % Usystem
Istartup Mstartup
0.7 x 70 % Usystem
Istartup 70 % Usystem
0.5 x 50 % Usystem
Mstartup
0.49 x 50 % Usystem
Mstartup
0.25 x
nsyn n nsyn n
Figure 8-11: Current and torque curves for a soft starter
Applications
Typical applications include, for example:
Conveyor belts, conveyor systems:
• smooth starting
• smooth slowing,
• high switching frequency
Rotary pumps, piston-type pumps:
• avoidance of pressure surges
• service life of the piping system is extended
Agitators, mixers:
• reduced starting current
Fans:
• less strain on gearing and drive belts
8.3.3 Features
Danger
Hazardous voltage. Danger of death or risk of serious injury.
Before starting work, de-energize the plant and device.
Phase L1 is not run via the semiconductor in the sDSSte / sDSte and sRSSte /
sRSte.
Warning
Following a shutdown function with a motor brake, the soft coasting down and
time delay work against the halted motor.
time ramp
The graphic below shows the time ramp of sDSSte / sDSte, sRSSte / sRSte with
parameterized ramp operation (DI 1.7 = 1):
U
UN
Us
t
tR on tR off
Figure 8-12: Time ramp / time diagram, sDSSte / sDSte, sRSSte / sRSte
Starting voltage
The start voltage should be parameterized so that the motor starts running rapidly.
Stop voltage
The "Stop voltage" parameter is used to set the voltage value where this is
cancelled with the "voltage ramp" coasting down type, i.e. switched off.
In this formula:
• CD cyclic duration factor [%]
• ts starting time [s]
• tb operating time [s]
• tp idle time [s]
t
ts tb tp
Switching frequency
It is essential to comply with the maximum permissible switching frequency
in order to avoid exposing the devices to thermal overload. To do this, the
"Response to overload - thermal motor model" parameter must be deactivated
(shutdown without restart). It is also necessary to deactivate the idle time for
cooling in the thermal motor model by selecting the default = 0 = deactivated
(see chapter 8.2.7, "Idle time parameters").
The tables below provide an overview of the switching frequencies/hour
according to the influencing factors.
3RK1304-5KS70-…… (0.15 A to 2 A)
CLASS 10A
Device orientation vertical horizontal
Rated current Ie 2A 2A 2A 2A 2A 2A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/1 s 250 910 250 910 250 910 250 910 250 910 250 910
CD = 70 %, start 4xIe/1 s 150 460 150 460 150 460 150 460 150 460 150 460
CD = 30 %, start 4xIe/2 s 120 420 120 420 120 420 120 420 120 420 120 420
CD = 70 %, start 4xIe/2 s 70 210 70 210 70 210 70 210 70 210 70 210
Class 10
Device orientation vertical horizontal
Rated current Ie 2A 2A 2A 2A 2A 2A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/1 s 120 450 120 450 120 450 120 450 120 450 120 450
CD = 70 %, start 4xIe/1 s 70 230 70 230 70 230 70 230 70 230 70 230
Class 15
Device orientation vertical horizontal
Rated current Ie 2A 2A 2A 2A 2A 2A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/1 s 80 300 120 450 120 450 120 450 120 450 120 450
CD = 70 %, start 4xIe/1 s 50 150 70 230 70 230 70 230 70 230 70 230
Class 20
Device orientation vertical horizontal
Rated current Ie 2A 2A 2A 2A 2A 2A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/1 s 60 220 60 220 60 220 60 220 60 220 60 220
CD = 70 %, start 4xIe/1 s 37 110 37 110 37 110 37 110 37 110 37 110
1) Load cycle current effective value corresponds to 1.15 x Ie => motor protection
2) Load cycle limit for motor starter. The motor should be protected against overload here using thermistors
Table 8-6: Switching frequencies with activated soft start function
3RK1304-5LS70-…… (1.5 A to 12 A)
CLASS 10A
Device orientation vertical horizontal
Rated current Ie 5A 5A 5A 5A 5A 4.5 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/1 s 250 910 250 780 250 650 250 860 250 650 250 650
CD = 70 %, start 4xIe/1 s 150 460 150 400 150 300 150 460 150 280 150 280
CD = 30 %, start 4xIe/2 s 120 420 120 370 120 320 120 420 120 320 120 320
CD = 70 %, start 4xIe/2 s 70 210 70 190 70 150 70 210 70 140 70 140
Class 10
Device orientation vertical horizontal
Rated current Ie 5A 5A 5A 5A 5A 4.5 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/2 s 120 450 120 380 120 320 120 430 120 320 120 320
CD = 70 %, start 4xIe/2 s 70 230 70 180 70 130 70 230 70 140 70 140
Class 15
Device orientation vertical horizontal
Rated current Ie 5A 5A 5A 5A 5A 4.5 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/3 s 80 300 80 250 80 220 80 280 80 210 80 210
CD = 70 %, start 4xIe/3 s 50 150 50 130 50 100 50 150 50 95 50 95
Class 20
Device orientation vertical horizontal
Rated current Ie 5A 5A 5A 5A 5A 4.5 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/4 s 60 220 60 190 60 160 60 210 60 160 60 160
CD = 70 %, start 4xIe/4 s 37 110 37 100 37 70 37 115 37 70 37 70
1) Load cycle current effective value corresponds to 1.15 x Ie => motor protection
2) Load cycle limit for motor starter. The motor should be protected against overload here using thermistors.
Table 8-6: Switching frequencies with activated soft start function (Contd.)
3RK1304-5LS70-…… (1.5 A to 12 A)
CLASS 10A
Device orientation vertical horizontal
Rated current Ie 7A 5.8 A 5A 6A 5A 4.5 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/1 s 250 580 250 600 250 650 250 650 250 650 250 650
CD = 70 %, start 4xIe/1 s 150 260 150 260 150 300 150 280 150 280 150 280
CD = 30 %, start 4xIe/2 s 120 290 120 300 120 320 120 320 120 320 120 320
CD = 70 %, start 4xIe/2 s 70 130 70 130 70 150 70 140 70 140 70 140
Class 10
Device orientation vertical horizontal
Rated current Ie 7A 5.8 A 5A 6A 5A 4.5 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/2 s 120 290 120 300 120 320 120 320 120 320 120 320
CD = 70 %, start 4xIe/2 s 70 130 70 130 70 130 70 140 70 140 70 140
Class 15
Device orientation vertical horizontal
Rated current Ie 7A 5.8 A 5A 6A 5A 4.5 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/3 s 80 190 80 200 80 220 80 210 80 210 80 210
CD = 70 %, start 4xIe/3 s 50 85 50 85 50 100 50 95 50 95 50 95
Class 20
Device orientation vertical horizontal
Rated current Ie 7A 5.8 A 5A 6A 5A 4.5 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/4 s 60 145 60 150 60 160 60 160 60 160 60 160
CD = 70 %, start 4xIe/4 s 37 65 37 65 37 70 37 70 37 70 37 70
CD = 30 %, start 4xIe/8 s 30 72 30 75 30 80 30 80 30 80 30 80
CD = 70 %, start 4xIe/8 s 18 33 18 33 18 35 18 35 18 35 18 35
1) Load cycle current effective value corresponds to 1.15 x Ie => motor protection
2) Load cycle limit for motor starter. The motor should be protected against overload here using thermistors.
Table 8-6: Switching frequencies with activated soft start function (Contd.)
3RK1304-5LS70-…… (1.5 A to 12 A)
CLASS 10A
Device orientation vertical horizontal
Rated current Ie 9A 9A 9A 9A 9A 9A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/1 s 250 340 250 250 210 210 250 290 210 210 170 170
CD = 70 %, start 4xIe/1 s 150 290 150 200 150 160 150 240 150 170 125 125
CD = 30 %, start 4xIe/2 s 120 170 120 120 105 105 120 145 105 105 88 88
CD = 70 %, start 4xIe/2 s 70 140 70 100 70 80 70 120 70 82 63 63
Class 10
Device orientation vertical horizontal
Rated current Ie 9A 9A 9A 9A 9A 9A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/2 s 120 170 120 120 105 105 120 145 105 105 88 88
CD = 70 %, start 4xIe/2 s 70 140 70 100 70 80 70 120 70 82 63 63
CD = 30 %, start 4xIe/4 s 60 85 60 60 53 53 60 72 53 53 44 44
CD = 70 %, start 4xIe/4 s 38 72 38 50 38 38 38 60 38 41 31 31
Class 15
Device orientation vertical horizontal
Rated current Ie 9A 9A 9A 9A 9A 9A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/3 s 80 115 80 85 70 70 80 97 71 71 58 58
CD = 70 %, start 4xIe/3 s 50 95 50 65 50 52 50 80 50 55 42 42
CD = 30 %, start 4xIe/6 s 40 57 40 42 35 35 40 48 35 35 29 29
CD = 70 %, start 4xIe/6 s 26 48 26 33 26 26 25 40 25 27 21 21
Class 20
Device orientation vertical horizontal
Rated current Ie 9A 9A 9A 9A 9A 9A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/4 s 60 85 60 60 53 53 60 72 53 53 44 44
CD = 70 %, start 4xIe/4 s 38 72 38 50 38 38 38 60 38 41 31 31
CD = 30 %, start 4xIe/8 s 30 42 30 30 26 26 30 36 26 26 22 22
CD = 70 %, start 4xIe/8 s 18 36 18 25 18 18 19 30 19 20 15 15
1) Load cycle current effective value corresponds to 1.15 x Ie => motor protection
2) Load cycle limit for motor starter. The motor should be protected against overload here using thermistors.
Table 8-6: Switching frequencies with activated soft start function (Contd.)
3RK1304-5LS70-…… (1.5 A to 12 A)
CLASS 10A
Device orientation vertical horizontal
Rated current Ie 12 A 12 A 12 A 12 A 12 A 11 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/1 s 215 215 155 155 125 125 175 175 125 125 120 120
CD = 70 %, start 4xIe/1 s 150 150 100 100 70 70 125 125 70 70 70 70
Class 10
Device orientation vertical horizontal
Rated current Ie 12 A 12 A 12 A 12 A 12 A 11 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/2 s 107 107 77 77 63 63 88 88 63 63 60 60
CD = 70 %, start 4xIe/2 s 70 80 50 50 35 35 62 62 36 36 33 33
Class 15
Device orientation vertical horizontal
Rated current Ie 12 A 12 A 12 A 12 A 12 A 11 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/3 s 72 72 52 52 42 42 59 59 42 42 40 40
CD = 70 %, start 4xIe/3 s 50 54 34 34 24 24 41 41 24 24 24 24
CD = 30 %, start 4xIe/6 s 36 36 26 26 21 21 29 29 21 21 20 20
CD = 70 %, start 4xIe/6 s 25 27 17 17 12 12 20 20 12 12 12 12
Class 20
Device orientation vertical horizontal
Rated current Ie 12 A 12 A 12 A 12 A 12 A 11 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD = 30 %, start 4xIe/4 s 54 54 38 38 31 31 44 44 31 31 31 31
CD = 70 %, start 4xIe/4 s 38 40 25 25 18 18 31 31 18 18 18 18
CD = 30 %, start 4xIe/8 s 27 27 19 19 15 15 22 22 15 15 15 15
CD = 70 %, start 4xIe/8 s 18 20 12 12 9 9 15 15 9 9 9 9
1) Load cycle current effective value corresponds to 1.15 x Ie => motor protection
2) Load cycle limit for motor starter. The motor should be protected against overload here using thermistors.
Table 8-6: Switching frequencies with activated soft start function (Contd.)
3RK1304-5KS70-…… (0.15 A to 2 A)
CLASS 10A
Device orientation vertical horizontal
Rated current Ie 2A 2A 2A 2A 2A 2A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD=30 % (8xIe) / 0.2 s 300 2000 300 2000 300 2000 300 2000 300 2000 300 2000
CD=70 % (8xIe) / 0.2 s 180 1000 180 1000 180 1000 180 1000 180 1000 180 1000
CD=30 % (8xIe) / 0.4 s 150 1000 150 1000 150 1000 150 1000 150 1000 150 1000
CD=70 % (8xIe) / 0.4 s 90 520 90 520 90 520 90 520 90 520 90 520
Class 10
Device orientation vertical horizontal
Rated current Ie 2A 2A 2A 2A 2A 2A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
Direct start CD=30 % 150 1000 150 1000 150 1000 150 1000 150 1000 150 1000
(8xIe) / 0.4 s
CD=70 % (8xIe) / 0.4 s 90 500 90 500 90 500 90 500 90 500 90 500
3RK1304-5LS70-…… (1.5 A to 12 A)
CLASS 10A
Device orientation vertical horizontal
Rated current Ie 5A 5A 5A 5A 5A 4.5 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD=30 % (8xIe) / 0.25 s 240 1300 240 1000 240 800 240 1150 240 840 240 840
CD=70 % (8xIe) / 0.25 s 150 800 150 500 150 350 150 650 150 380 150 380
CD=30 % (8xIe) / 0.5 s 120 700 120 500 120 400 120 580 120 430 120 430
CD=70 % (8xIe) / 0.5 s 70 380 70 270 70 200 70 340 70 200 70 200
Class 10
Device orientation vertical horizontal
Rated current Ie 5A 5A 5A 5A 5A 4.5 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD=30 % (8xIe) / 0.5 s 120 700 120 520 120 420 120 580 120 430 120 430
CD=70 % (8xIe) / 0.5 s 70 400 70 280 70 200 70 340 70 200 70 200
3RK1304-5LS70-…… (1.5 A to 12 A)
CLASS 10A
Device orientation vertical horizontal
Rated current Ie 7A 5.8 A 5A 6A 5A 4.5 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD=30 % (8xIe) / 0.3 s 200 630 200 670 200 740 200 700 200 700 200 700
CD=70 % (8xIe) / 0.3 s 120 280 120 290 120 330 120 320 120 320 120 320
CD=30 % (8xIe) / 0.6 s 100 320 100 330 100 370 100 350 100 350 100 350
CD=70 % (8xIe) / 0.6 s 60 140 60 140 60 160 60 160 60 160 60 160
Class 10
Device orientation vertical horizontal
Rated current Ie 7A 5.8 A 5A 6A 5A 4.5 A
Ambient temperature 40 °C 50°C 55°C 40 °C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD=30 % (8xIe) / 0.6 s 100 320 100 330 100 370 100 350 100 350 100 350
CD=70 % (8xIe) / 0.6 s 60 140 60 140 60 160 60 160 60 160 60 160
3RK1304-5LS70-…… (1.5 A to 12 A)
CLASS 10A
Device orientation vertical horizontal
Rated current Ie 9A 9A 9A 9A 9A 9A
Ambient temperature 40°C 50°C 55°C 40°C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD=30 % (8xIe) / 0.35 s 170 330 170 240 170 200 170 280 170 200 170 170
CD=70 % (8xIe) / 0.35 s 100 280 100 190 100 150 100 230 100 155 100 120
Class 10
Device orientation vertical horizontal
Rated current Ie 9A 9A 9A 9A 9A 9A
Ambient temperature 40°C 50°C 55°C 40°C 50°C 55°C
Degree of protection 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
CD=30 % (8xIe) / 0.75 s 85 160 85 115 85 95 80 130 80 95 80 80
CD=70 % (8xIe) / 0.75 s 52 130 52 90 52 70 50 110 50 75 50 57
In order for a motor to reach its rated speed, motor torque at any given time
during run-up must be greater than the torque needed by the load, as otherwise
a stable operating point would be reached before the motor achieved its rated
speed (the motor would "drag to a stop"). The difference between motor torque
and load torque is the accelerating torque that is responsible for the increase in
the speed of the drive. The lower the accelerating torque, the longer is the time
the motor needs to run up to its operating speed.
Starting torque
Reducing the terminal voltage of a three-phase asynchronous motor reduces
the motor's starting current and the starting torque.
Current is directly proportional to voltage, whereas voltage is proportional to
the square root of motor torque.
Example:
Motor = 5.5 kW, rated current = 11.4 A, starting current = 6.3 x rated current,
motor torque = 36 Nm, starting torque = 2.4 x rated torque
Settings for the soft starter: Start voltage 50 % of rated voltage for motor
The reductions are thus as follows:
• Starting current is reduced to half the starting current for a direct start: 50 %
of (6.3 x 11.4 A) = 36 A
• Starting torque is reduced to 0.5 x 0.5 = 25% of the starting torque for
a direct start: 25% of 2.4 x 36 Nm = 21.6 Nm
Note
On account of the ratio between starting voltage and torque, it is important
to ensure that starting voltage is not too low. This applies particularly for
a pronounced saddle torque, the lowest motor torque that occurs during run-
up to rated speed.
Mmotor
M
Mstartup
MB
MB = accelerating
torque of the motor
Mstartup
with
SIRIUS
soft starter n
Ue
US
tR t
Figure 8-14: Load and motor torques and motor terminal voltage for operation with soft starter
Note
With the ET 200pro soft starters sDSSte / sDSte and sRSSte / sRSte, the
corresponding soft starter must be chosen according to the rated motor current
(soft starter rated current must be ≥ rated motor current).
Starting time
To achieve optimal operating conditions for the sDSSte / sRSSte soft starters,
the set startup time should be approx. 1 s longer than the resultant motor
startup time. Longer starting times increase the thermal load on the devices
and the motor unnecessarily and lead to a reduction in the permissible
switching frequency.
Danger
Ensure that the wiring is correct and carefully carried out! ET 200pro
components may otherwise be destroyed! There is a danger of death!
Shock protection
The HAN Q4/2 plug-in connectors used for power supply and HAN Q8/0 for
consumer connection have sufficient shock protection (finger-proof) in
accordance with DIN VDE 0106, Part 100.
Warning
Dangerous electrical voltage! This can lead to electrical shock and burns.
Before starting work, de-energize the plant and device.
The core cross-section of the energy lines must be modified for the relevant
ambient conditions. The key factors for the core cross-section are:
• the current set on the device,
• the installation type,
• the ambient temperature,
• the material type (PVC, rubber).
For PVC energy lines, the following maximum current loading capacity applies,
e.g. with installation in the cable duct, depending on the ambient temperature:
mm2 TU
Connect unused connections with caps; this is the only way to ensure
protection rating IP65. order number 3RK1902-0CJ00 (x 10) or 3RK1902-0CK00
(x 1).
• for assembly of the sockets and pins on the individual cores, a crimping tool
(see chapter A.2).
As well as the following accessories:
• for supply to special modules (assignment of X1, see chapter 9.2.2),
for supply to motor starters (assignment of X1, see chapter 9.2.3):
– a flexible Cu cable with 4 x 2.5 mm2 / 4 mm2 / 6 mm2 (3-core + PE)
– an energy plug-in connector HAN Q4/2 socket
- for 2.5 mm2: 3RK1911-2BE50
- for 4.0 mm2: 3RK1911-2BE10
- for 6 mm2: 3RK1911-2BE30
• for energy forwarding via a loop to the RSM and F-RSM special modules
(assignment of X2 see chapter 9.2.2):
– a flexible Cu cable with 4 x 2.5 mm2 / 4 mm2 (3-core + PE)
– an energy plug-in connector HAN Q4/2 pin
- for 2.5 mm2: 3RK1911-2BF50
- for 4.0 mm2: 3RK1911-2BF10
• for consumer connection on the motor starter (assignment of X2
see chapter 9.2.3):
– a flexible Cu cable with 1.5 mm2 or 2.5 mm2
- without brake control: 3-core + PE
- with brake control: 5-core + PE
– an energy plug-in connector HAN Q8/0 pin
- for 1.5 mm2: 3RK1902-0CE00
- for 2.5 mm2: 3RK1902-0CC00
MS MS
SF
BF
ON
DC 24V
Energy infeed
Connector set M M
7-pin (socket)
angled cable routing
MS MS
SF
BF
ON
Connector set
7-pin (socket) M M
angled cable routing
with turned socket insert
MS MS
SF
BF
ON
DC 24V
Other Station
M M
Power relaying
Figure 9-3: Example: Power forwarding
SF SF
SF
MS MS MS MS
BF
ON
DC 24V
Connector set
9-pin (pin)
angled cable routing
The X1 energy plug-in connector for infeed or X2 for forwarding via a loop to
special modules RSM and F-RSM consist of the following components:
X1 infeed HAN Q4/2 socket
Plug-in housing
2 1
Cable gland 12 PE 11
with seal insert
Contact sockets
4 3
Socket insert
Coding
Coding
Pin insert
Coding 2 1
Coding
Socket / Assignment
pin X1 and X2
1 Phase L1
2 Phase L2
3 Phase L3
4 Not used
11 Not used
12 Not used
PE (yellow / green)
Figure 9-5: Plug-in connector for RSM and F-RSM special modules
Caution
Ensure that the coding position when inserting the pin insert or socket insert
into the plug-in housing.
Caution
Ensure that the coding position when inserting the pin insert or socket insert
into the plug-in housing.
Installing and wiring the energy plug-in connectors according to the following
specifications:
Step Procedure
1 Insert the cable through the cable gland, the relevant seal insert
provided, and the plug-in housing.
The seal insert is available in the following graduations:
4 Fasten the contact sockets / contact pins on the cores via crimping using
a suitable tool (see chapter A.2) or solder.
5 Sort the contact sockets / contact pins into the socket insert / pin insert
according to the assignments as shown in chapter 9.2.2 and chapter 9.2.3.
The contact sockets / contact pins should not yet be engaged. Check the
correct assignment. Slide the contact sockets / contact pins into the socket
insert / pin insert until they engage.
Contact sockets / contact pins already fitted can be removed again using
a removal tool (see chapter A.2).
6 Ensure that the coding position is correct, pull back the cable and screw
the socket insert / pin insert into the plug-in housing using the Phillips bolts
provided.
7 Screw the cable gland tight. Ensure that the cable is not turned against
the plug-in housing.
Table 9-2: Installing and wiring energy plug-in connectors
1 1 Phase L1
2 2 Phase L2
3 3 Phase L3
4 4 Not used
PE (yellow / green)
Socket Assignment
1 +24 V
1 2 )
21 DI x
4 5 3 3 0V
41) DI x
5 FE
1) Sockets 2 and 4 are bridged inside the device
Table 9-4: M12 connection assignment
Inputs Outputs
Device parameters Measurements
Self-protection
The motor starter protects itself against destruction thanks to the thermal
motor model and temperature measurements with electronic switching
elements. If the self-protection is triggered,
• the brake output and the motor are shut down immediately
• the message ’Switching element overload’ is generated
It is not possible to switch on using ’Emergency start’
Currents
All currents (e. g. blocking current, current limit values) are percentage current
values relative to the rated operating current.
Attention
The rated operating current is the most important central parameter! The rated
operating current must be set in all cases to ensure motor protection!
Special feature:
– In the motor starter, the rated operating current is factory-set to maximum value
(For tests with commissioning without a field bus and without advance
parameterization).
– In the GSD / GSDmL / MDD and the software ’ES motor starter’, the rated
operating current is set to minimum value for safety reasons. This value must
therefore be parameterized in the configuration process. Otherwise, the motor starter
could trip due to an overload when the motor is started for the first time.
0 0 0 0 0 0 Iact = 0
1 0 0 0 0 0 Iact = Irated x 1
Load type
Here you enter whether the motor starter is to protect a 1-phase or 3-phase
consumer.
• With a 1-phase load, the asymmetry detection is deactivated!
With all mechanically switched motor starters, the 1-phase load can be
connected between any two phases.
• With a 3-phase load, the asymmetry detection is activated! The three phase
currents are compared with one another.
Note
The load type is only relevant to mechanical motor starters. Only 3-phase load
types are permitted for connection to electronic starters.
Increment: 10 mA
Rated operating current1) 2.0 A 0.15 A to 2.0 A
12.0 A 1.5 A to 12.0 A
Danger
Shutdown with restart means that if a switch-on command is pending
the motor starter switches on automatically (auto-reset).
Attention
If the thermal motor model exceeds the limit value of 178 % for the intrinsic
protection of the motor starter, a shutdown command is generated by the
motor starter itself independently of the "Response on overload - thermal
motor model" parameterization.
Tripping class (can only be parameterized with high feature motor starters)
The ’tripping class’ (CLASS) defines the maximum tripping time within which
a protective device must trip from cold at 7.2 times the setting current (motor
protection to IEC60947). The tripping characteristics plot time to
disengagement as a function of operating current.
120 120
100 100
50 50
20 20
Min.
Min.
10 10
5 5
2 CLASS 20 2 CLASS 20
1 1
50 50
20 20
15
NO:
10 s 10 15
10 10
5 CLASS 5 5
CLASS 5
2 2
tA
tA
x Ie x Ie
1 1
0.7 1 2 5 8 0.7 1 2 5 8
3-pole symmetrical load 2-pole load (failure of a phase or
current asymmetry > 40 %)
Note
The setting options for the tripping classes depend on the motor starter and
on the current range:
Recovery time (can only be parameterized with high feature motor starters)
The ’recovery time’ is the time defined for cooling after which a reset is possible
following an overload trip.
Trip reset signals received during the recovery time (DO 0.3) have no effect.
The motor starters are set to the following times:
• with DSe ST, RSe ST:
Setting fixed to 90 s.
• with DSe HF, RSe HF, sDSSte / sDSte and sRSSte / sRSte:
The recovery time after overload tripping is at least 1 minute. The recovery
time can be parameterized and can be changed between 60 seconds and
1800 seconds.
Factory setting: 90 seconds
Power failures during this time extend the time specifications accordingly
when the basic ’Non-resetting on voltage failure’ parameter is active.
Idle time (can only be parameterized with high feature motor starters)
The idle time’ is a time defined for cooling process following operational
shutdown, in other words not after overload trips.
After this time elapses, the thermal memory of the motor starter is cleared,
a cold start is possible.
This permits higher switching frequencies if the drive is of the correct size,
without the motor model trigger limit being exceeded.
Caution
Higher switching frequencies result in greater motor heating.
If the motor size (heat class) is not modified, motor protection can no longer
be guaranteed.
The diagram below shows the cooling response with and without idle time:
Motor
On
Off
t
No idle time
ϑ Tripping limit
Overload tripping
No overload trip
t
Idle time.
Thermal memory is cleared after the idle time
The device functions ’Thermal motor model’ supplies the following messages
and measurements and statistics data:
Message Action
Measurements Description
Preventative diagnostics —
Motor running at no-load, e.g. due Very low level of Residual current
to system damage! current flowing detection
(< 18.75 % of Ie)
Caution
When switching on the motor, the zero current detection is suppressed for
approx. 1 second!
Upper / lower current limit (can only be parameterized with high feature motor starters)
You can enter an upper and /or lower current limit value.
Example:
• ’Substance for mixing too thick’, i.e. current overshoots the upper current
limit.
• ’No-load operation, because drive belt broken’, i.e. current undershoots
the lower current limit.
Caution
The current limits are – for startup bridging – only active after the class time
elapses, e.g. class 10 after 10 seconds.
Blocking time (can only be parameterized with high feature motor starters)
Time for which a blockage can persist without initiating a shutdown. The motor
starter shuts down if the blockage is still present after the blocking time expires.
Range: 1 second to 5 seconds.
Blocking current (can only be parameterized with high feature motor starters)
The motor starter detects a blockage if the parameterized blocking current
is exceeded. The blocking time monitoring is started from the point when
the value is exceeded. If the blocking current flows for longer than the
parameterized blocking time, the motor starter generates the shutdown
command itself.
Caution
The motor starter shuts down if the blockage is still present after the blocking
time expires.
I Stalled rotor
Blocking
current Blocking cancelled
within blocking time
t
Blocking time
I Stalled rotor
Blocking
Blocking still present
current
after the blocking time
elapses
t
Blocking time
Figure 10-4: Principle of anti-blocking function
The ’current limit values’ device function delivers the following messages and
actions:
Message Action
Task
Temperature sensors are located directly in the motor stator winding. They are
used for direct temperature monitoring of the motor windings. This is used to
detect whether the motor is working normally or is overloaded.
Caution
Electronic starters sDSSte / sDSte and sRSSte / sRSte can evaluate one
temperature sensor circuit!
Temperature sensor
You can deactivate these parameters if there is no temperature sensor in
the motor.
You can activate this parameter if there is a temperature sensor in the motor.
Two types of temperature sensor are supported:
– Thermoclick. This is a switch that opens at a specific winding temperature
– PTC - type A. This is a PTC thermistor with defined characteristic according
to VDE 0660 Parts 302 and 303
Range:
• Deactivated
• Thermoclick (switch with fixed switch-on temperature)
• PTC - type A (PTC thermistor with fixed resistance range)
Caution
If you parameterize "Deactivated", the following parameters are ignored:
• Response to overload – temperature sensor
• Temperature sensor monitoring
Caution
Temperature sensor circuit is electrically connected to "24 V DC supply voltage
is not switched".
Caution
Restart means that with a switch-on command present, the motor starter
will automatically be re-started when the cause of the fault has been rectified
(autoreset).
The "Temperature sensor" function delivers the following messages and actions:
Message Action
10.5 Asymmetry
Description
Higher asymmetric current consumption is the reaction of a three-phase
asynchronous motor to slight asymmetry in the supply voltage. This causes an
increase in temperature in the stator and rotor windings.
Caution
When switching on the motor, the asymmetry evaluation is suppressed for
approx. 500 milliseconds
Asymmetry limit (can only be parameterized with high feature motor starters)
The ’asymmetry limit’ is a percentage by which motor current can vary in
the individual phases.
Asymmetry has occurred when the difference between the lowest and the
highest phase currents is greater than the parameterized asymmetry limit value.
The datum for evaluation is the maximum phase current in one of the three
phases.
Range: 30 % to 60 % of the rated operational current
Messages, actions
Message Action
Asymmetry detected —
Measurements
Measurements Description
10.7 Inputs (can only be parameterized with high feature motor starters)
Description
With the ’Inputs’ device function, the motor starter can run various
actions that can be parameterized. The signals at the digital inputs are evaluated
for this purpose. The inputs can be wired directly to sensors (PNP) in 2-core and
3-core technology.
The input actions of the individual digital inputs affect the motor starter
functions independently from one another (= OR operand)
n signal input
This device parameter is used to specify whether or not the input level of
the digital inputs is to be saved.
• retentive, e.g. self-holding operation
• non-retentive, i.e. inching operation.
Input n level
This parameter can be used to specify the input logic.
Range: NO contact / NC contact
Caution
With ’n input – action’: ’Emergency start’, ’Motor cw’, ’Motor ccw’ and
’Trip reset’, ’n input – level’ can only be parameterized as a NO contact!
Caution
If ’n input – level’ of normally closed and normally open contacts and the
associated ’n input – action’ are parameterized to ’Shutdown without restart’,
with an open input the ’shutdown input’ signaling bit is and shut down
accordingly due to the input signal delay!
Caution
The input level of the digital inputs is always sent to the control (PLC) as a NO
contact, regardless of parameter ’n input – level’ (process image of the inputs
in data record 69 and diagnostics in data record 92).
Input n action
A variety of actions can be triggered by an input signal. The following actions
can be parameterized, depending on ’n input – level’, ’n input – signal’ and
’Operating mode’.
Caution
When ’n input– signal’ = retentive and ’n input– action’ = motor cw / ccw, at
least one input with input action ’Shutdown …’ or ’Quick stop’ always needs
to be parameterized.
If this rule is violated, the parameters are rejected with the relevant diagnostics
message!
Quick stop
• Motor and brake output are switched off without a group fault.
• "Quick stop" has priority over "Motor cw" and "Motor ccw"
• The input action responds to the active edge of the input signal.
Deactivation with static "Quick stop" input signal present is therefore
possible.
• The input trigger is cleared by removing the "Motor cw" and "Motor ccw"
control commands or via "Lock quick stop" (in the process image).
Example 1:
Digital input 1–signal = retentive / edge-triggered
① ② ③ ④ ⑤
Motor cw signal
Digital input 1
Motor
② Motor is switched on via "Motor cw", then switched off via the rising edge on digital input 1
(parameterized on input action1 = quick stop). Removing the "Motor cw" command resets
the quick stop function.
③ Motor is switched on via "Motor cw", then switched off via the rising edge on digital input 1.
Setting lock quick stop resets the quick stop function and the motor runs "cw" again until
the "motor cw" command is cancelled.
④ Motor is switched on via "Motor cw", then switched off via the rising edge on digital input 1.
Setting lock quick stop resets the quick stop function and the motor runs "cw" again.
Although digit input 1 (DI2) is still static, the motor continues to run and is only reset after
cancelling the "motor cw" command.
Reason: The input action is edge-triggered.
⑤ Motor is switched on via "Motor cw" and continues to run uninterrupted as lock quick stop
overwrites the edges of the signals of digital input 1 (DI2).
Example 2:
Digital input 1 signal = non-retentive / level-triggered (preset)
① ② ③ ④
Motor cw signal
Digital input 1
Motor
② Motor is switched on via "Motor cw", then switched off via the level on digital input 1
(parameterized with input action1 = quick stop). The quick stop function is reset via lock
quick stop.
Motor is switched on again as "Motor cw" is still active.
③ Motor is switched off via the level on digital input 1. Setting "lock quick stop " resets the quick
stop function and as the "motor cw" level is still present, the motor continues to run "cw" until
the "lock quick stop" command is cancelled.
④ Motor is switched on via "Motor cw", then switched off via the rising edge on digital 1.
When the "quick stop" function is active, the motor remains switched off and after "quick stop"
is cancelled, runs again until "motor cw" is switched off.
Cold run
This function allows the motor starter to be switched on without main power.
The motor starter responds as if the main power is present on the system.
For example, this means that during the commissioning phase, the
corresponding control commands are accepted by the control and the
corresponding messages are delivered.
Note
If the main power is still on (current is flowing), an internal shutdown command
is generated.
Message Actions
Cold run active
Cold run shutdown Disconnect
Table 10-14: Messages and actions for cold run
The ’Inputs’ device function delivers the following messages and actions:
Message Action
Input 1 —
Input 2 —
Input 3 —
Input 4 —
Input tripping Shutdown (must be acknowledged
with trip reset)
Shutdown input - clockwise end position Shutdown (must be acknowledged
with counter-command)
Shutdown input - counterclockwise
end position
Input control —
Warning input —
Sensor supply overload Shutdown (must be acknowledged
with trip reset)
Table 10-16: Inputs – Messages and actions
Starting Stop
voltage voltage
t t
Starting time Coasting down time
Caution
With the control function deactivated, soft starters need to observe the
following derating:
Reduction in the rated operating current from 12 A to 9 A to class 10.
Caution
With the "direct" startup type, the following derating must be observed:
• Reduction in the rated operating current from 12 A to 9 A
• Only CLASS 5 or CLASS 10 possible.
Coast type
There are two ways of coasting down or stopping the motor:
• free coasting: The motor is switched on without regulation.
• Voltage ramp: The motor is shut down on a linear, negative voltage ramp.
Starting time
The motor terminal voltage is increased linearly from the start voltage to full
mains voltage during the parameterizable starting time.
Range: 0 to 30 seconds.
Starting voltage
Start value of the voltage ramp for soft starting.
Range: 20 % to 100 % of the mains voltage.
Stop voltage
End value of the voltage ramp for soft coasting down.
Range: 20 % to 90 % of the mains voltage.
Caution
At a rated operating current of > Ie = 9 A, the current limiting value is
automatically reduced to 550 % by the motor starter.
Caution
This parameter is only relevant in the ’Automatic’ operating mode.
Group diagnostics
This parameter is used to determine whether the diagnostics are to be enabled
or locked via PROFIBUS DP (fault type).
Replacement value
If the bus fails, controlled by a corresponding replacement process image of
the motor starter outputs.
Example:
Replacement value
Motor cw Reserved
Brake Reserved
Self-test Reserved
Caution
This device parameter is only relevant if you have parameterized ’Response
to CPU/master STOP’ ’Use dummy value’.
Replacement value 0 7 x (0 or 1)
Switching example
The image below shows a switching example for mechanical brake process:
L1 L2 L3
1 7 3 4 4 Brake L1 (switched)
5 Not used
6 6 Brake L3 (direct)
7 Phase L2
8 Not used
e PE (yellow / green)
Brake magnet
M
3~
Caution
Only effective with simultaneous ON switching command for brake and motor.
Caution:
• Positive time specifications: Delayed switching on of the brake output in
relation to the motor.
• Negative time specifications: Delayed switching on of the motor in relation
to the brake output.
In reversing mode, the enabling delay only starts after the interlock time
elapses.
Range: –2.5 seconds to +2.5 seconds.
Caution
Only effective with simultaneous OFF switching command for brake and
motor.
Priorities regulation
’Enable delay of the brake when starting’ has priority over ’Holding time of
the brake when stopping’. An elapsed holding time is aborted when the enable
delay is re-started (via an ON switching command for brake and motor).
10.10.3 Message
The mechanical brake process delivers the following message when the brake
output is switched on:
Message
10.11 Self-test
Description
There are 2 self-test types:
• Self-test cyclical in operation
Carried out cyclically during operation
• Self-test on command
Activated by the user via bit DO 0.5 ’self-test’ in the process image of
the outputs.
Test stages
The self-test consists of 3 test stages. The test stages are run depending on
the signal duration of the test command:
1 < 2 sec. LED test All LEDs are switched on for 2 seconds!
• Check by user, no signaling bit
2 2 … 5 sec. HW test The motor starter hardware is tested;
Current measurement with display via
’DEVICE’ LED:
• Current flowing: flashes red
• Current not flowing:flickers red
• Check by user, no signaling bit
> 5 sec. No action —
Table 10-21: Self-test – test stages
Self-test fault
In the event of a fault, the ’DEVICE’ LED is on in red.
The fault can only be acknowledged when switched on again.
If the fault is still present, the self-test will still run with a fault when switched on.
The motor starter must be replaced!
10.11.1 Messages
Messages
Self-test active
Self-test OK
Caution
Certain device components are continually monitored internally by the motor
starter and the result is signalled with the self-test messages.
The ’Fault on self-test’ message can also occur in the event of a fault with
the internal monitoring, without the self-test having been activated.
Commands
Emergency start can be controlled via the following commands:
Commands
Emergency start ON
Emergency start OFF
10.12.1 Message
Message Description
Messages
This device function delivers the following messages:
Messages Meaning
10.14 Maintenance
Description
Maintenance functions are required to prevent wear-related failures of
equipment and systems. This increases the availability of the system. The
optimal use is that the motor starter promptly signals the intrinsic possible
failure in good time or the failure of the motor in stages. This makes regular
checking by maintenance personnel as to whether or not maintenance is
required unnecessary.
Device parameters
Two maintenance timers are available that permit indirect detection of wear
across the operating time. The maintenace timer are special operating hours
counters that can be both deleted and parameterized using warning limit values.
Interlock time (can only be parameterized with high feature motor starters)
The ’interlock time’ effects the time-delayed switchover of the rotation direction.
Within the interlock time, the centrifugal mass of a drive should come to
a standstill before the next switching command can be executed.
Range: 0 to 60 seconds
Caution
An interlock time of 0 means 150 milliseconds for safety reasons.
Table 10-26: Device parameters for reversing starter control function – settings
10.15.3 Messages
Message
Motor ccw
Interlock active
Message Action
Caution
To ensure fault-free data transfer, ensure that the infrared interface is clean.
10.18 Communication
Description
The communication is a higher level function consisting of multiple sub-
functions:
• Operating type monitoring
• Rear wall bus integration
• Commands
• Plausibility check of data
• Output of messages
Data channels
ET 200pro motor starters have 3 different data channels:
The control via the corresponding data channel depends on the operating mode.
Operating modes
The following operating modes are differentiated with increasing priority:
• ’Automatic’ operating mode (lowest priority)
The motor starter can only be controlled with PLC via field bus.
• ’Manual bus’ operating mode
The motor starter can only be controlled with B&B device (e.g. PC)
via field bus.
• ’Manual local’ operating mode
Motor starter can be controlled with
– Local - control point on digital inputs (’Motor cw’, ’Motor ccw’,
e.g. with switch module from test plug set or with external switches)
Requirement: ’Manual local’ operating mode set (see below).
– B&B device (e.g. PC, hand-held controller) via
the local device interface (highest priority)
Caution
An operating mode of higher priority can override the control supremacy via
command or an input action of ’Manual’ operating mode of a lower priority
at any time , but not vice versa.
An operating mode of higher priority can only delay the control priority if with
the motor switched off the higher priority operating mode returns control priority
via the ’Automatic’ operating mode or switching off the input action ’Manual
local’ operating mode.
Using the following signaling bits in diagnostics data record DS92, it is possible
to uniquely detect which control source currently has control priority:
– ’Automatic’ operating mode
– Manual bus’ operating mode
– ’Manual local’ operating mode
– Input control
– Lost connection in manual operating mode
Connection monitoring
The connection monitoring is active with the operating modes ’Manual bus’ and
’Manual local’. At least one write data record must be sent within 5 seconds.
Otherwise the motor starter switches off with the message ’Connection lost
in manual operating mode’.
If you do not want to send any commands or control commands, you can send
an empty data record, for example.
To do this, use the empty data record 93 - ’command’. Here, only the
coordination is filled out as appropriate and the commands filled with "0".
Set manual local operating mode for a local control point on the digital inputs
The manual local operating mode can be set as follows:
• Using a B&B device (e.g. PC) via the local device interface.
Parameterize the input n -actions ’Motor cw’ and ’Motor ccw’. Then remove the B&B
device to activate the control via the digital inputs. The ’Control input’ signaling bit
is set in the process.
• Use a digital input on which you connect a switch to change over to
the ’Manual local’ operating mode.
This digital input then needs to be parameterized using ’n input – action’ ’Manual local’
operating mode.
10.18.2 Commands
Command Meaning
Trip reset • Reset and acknowledgement of fault
messages
• Clear signaling bits1) if there is no fault
message
• No effect
Clear slave pointer Clear the ’preventative diagnostics’ statistics
data
Clear log book trips Clear log book with recorded causes of fault.
Clear log book events Clear log book with recorded warning messages
and specific actions.
Factory setting All parameters have basic factory setting again
except for the communication parameters.
Only possible in ’Manual’ operating mode!
Parameterization lock CPU / Motor starter ignores parameterization
Master ON via master (PLC)
Parameterization lock CPU / Motor starter accepts parameterization
Master OFF via master (PLC)
Emergency start ON Switch on ’emergency start’ device function
Emergency start OFF Switch off ’emergency start’ device function
’Automatic’ operating mode Control via PLC;
cyclical and acyclical bus channel (C1)
’Manual’ operating mode • Control via PC; acyclical bus channel (C2)
• Control via device interface
Re-start Motor starter runs a restart (same action
as Power OFF / ON).
Only possible in ’Manual’ operating mode!
1) Signaling bits, see table on next page
Caution
Command is run immediately!
The changeover from ’Manual’ to ’Automatic’ operating mode is only possible
if the motor and brake output is switched off.
Description
The motor starter checks all incoming parameters for validity and plausibility.
In the case of incorrect parameters
• during a startup (after power ON) the messages ’Group fault’ and ’Incorrect
parameter value’ are set.
Motor and brake output remain switched off.
• in ongoing operation, the messages ’Incorrect parameter value’ or
’Parameterization in ON status not permitted’ are set. ’Group fault’ is not set.
Motor and brake output are not switched off.
Messages Meaning
General messages
Ready (automatic) Device can be operated via host (e.g. PLC)
Group fault At least 1 fault is set.
General warning At least 1 warning exists
Process image fault Process image of the outputs contains
nonallowable bit combination, e.g. ’Motor
cw’ and ’Motor ccw’ set simultaneously
Field bus connection
Bus fault Device has no rear wall bus
communication (ESSA3 interface to the
controller interrupted)
CPU/master STOP PLC program no longer being processed
Acknowledgement
Trip reset completed Trip teset accepted, i.e. fault has been
acknowledged.
Trip reset not possible Unable to acknowledge fault as the reason
for the shutdown is still present.
Operating type monitoring
Automatic operating mode Automatic (PLC control)
Manual bus operating mode Manual operation via field bus
(B&B control)
Manual local operating mode Manual operation via local device interface
(B&B control)
Lost connection in manual operating mode During manual operation, the associated
communication connection was
interrupted for longer than 5 seconds.
Table 10-32: Communication – Messages
Messages Meaning
Parameter assignment
Parameterization active Yes / no
1)
Incorrect parameter value Parameter not correct
Parameter change not permissible in ON Attempted parameter change not
status1) permissible when the motor is running.
Faulty parameter number1) Specifies the first unaccepted parameter
(ID number of the parameter).
Parameterization lock CPU / Master active Motor starter ignores parameters from the
PLC, but informs the PLC that parameters
are OK.
No external startup arameter er hold Message that after Power ON or a restart
of the motor starter, new parameters are
received by the PLC
Statistics data
Slave point cleared1) Statistics data for preventative diagnostics
have been cleared.
1) Signaling bits that can be cleared with trip reset
10.19 PROFIenergy
10.19.1 What is PROFIenergy
PROFIenergy (PE)
The ET200pro motor starter supports the "PE_power saving function" and
"PE_measurement function" for the motor current. These are referred to as
commands as they trigger responses in the ET200pro motor starter.
In addition, the ET200pro motor starter delivers other what are known as
services that provide information on the status of the motor starter, as defined
for PROFenergy. These can then be evaluated and processed in the application
program.
Commands
Control commands
Start_Pause The starter changes to energy-saving mode.
End_Pause The starter changes back to operating mode.
Status commands
PE_Identify Delivers a list with the supported PROFIenergy
commands / functions.
PEM_Status Delivers the status of the current PE mode.
Query_Modes
List_Energy_Saving_Modes Delivers a list of supported power-saving modes.
Get_Mode Delivers the paramter values with which the
PE_energy saving function works.
Query_Measurement
Get_Measurement_List Delivers a list with the supported PE_Measurements
Get_Measurement_Values Delivers the supported PE_measurements
Table 10-33: Messages and actions
For data transfer, a distinction is made between two different status conditions
with the ET200pro motor starter:
6WDUWB3DXVH! (QGB3DXVH! W
W 3DXVHBPLQ
The "Energy-saving mode active" status is displayed via the flashing device LED
(flashing sequence: 0.25 s on / 1.75 s off → unique flashing rhythm for energy-
saving mode).
Note
A fault present is not acknowledged by changing to energy-saving mode,
i.e. the fault present is stored internally and can be exported. After exiting
energy-saving mode, the fault must be corrected and acknowledged.
The status displays for the bus and the power supplies and the SF-LED are
not affected by the active energy-saving mode.
Motor shutdown via suppression (masked) of the PAA bits Motor cw,
Motor ccw, BRAKE). The other PAA bits (e.g. trip reset) are still active.
Changing to "Pause" energy-saving mode is only effective if the idle time sent is
greater than the device-specific minimum idle time. I.e. a change is only carried
out when the idle is longer than the motor starter needs to switch off the main
power for the motor.
With a soft starter, a parameterized slow-down ramp of the device-specific
minimum idle time needs to be added. The minimum idle times for DSe/RSe are
100 ms and for sDSSte/sRSSte 100 ms to 30 s depending on the parameterized
coasting down time.
The change to energy-saving mode is logged in the "Events" log book.
Entry: "Energy-saving mode active" In ES motor starter diagnostics tool,
the change is entered into the log book in energy-saving mode with the event
ID 1520.
Log books
There are 3 different log books that can be read as a data record:
• Log book - trips: Data record 73
• Log book - events Data record 75
• Log book - device faults: Data record 72
Device faults are entered.
• The "Log book – trips" is cleared using the ’Log book – clear trips’ command
Connector set for power infeed 2.5 mm2 (HAN Q4/2) 3RK1911-2BE50
(X1) 4 mm2 (HAN Q4/2) 3RK1911-2BE10
6 mm2 (HAN Q4/2) 3RK1911-2BE30
160
110 150
230
246
Caution
Due to the operation of star-connected three-phase motors (especially if
<1 kW), high EMC interference may occur. Interference above the IEC limit
values can lead to an impairment of functions or failure of the electronics.
In case of high EMC interference, we recommend the use of motors with EMC
protection circuits. (Exception: electronic starters may not be operated with
a EMC protection circuit).
The best filtering effect is achieved with three-phase RC interference inversion
modules.
Varistor interference inversion modules should not be used since they only
insufficiently filter out fast transients.
ON
Terminating module
OFF
Standard applications
Figure C-1: Design with repair switch module and ECOFAST connection
1 6ES7194-4GB10-0AA0 Module carrier, wide, 1 m
1 6ES7154-2AA00-0AB0 IM 154-2 DP interface module with terminating module
3 3RK1922-2BA00 Bus module
1 3RK1304-0HS00-7AA0 RSM repair switch module
1)
With repair switch module and ECOFAST connection
1) x = according to model
The example below shows a layout with infeed via a repair switch module into
PROFIBUS-DP
Bus module Bus module Bus module
7 7 7
154-2 DP
NEB950566102000/RS-AA/007
SIMATIC - ET 200pro motor starters
IN1 IN2 IN3 IN4
Q1 Q1 Q2
Q1
Figure C-1: (cont.) Design with repair switch module and ECOFAST connection
L1
L3
L1
L3
L1
L3
L1
L3
L1
L3
Br.
L1
L3
Br.
L2
L2
L2
L2
L2
L2
L1
L3
L1
L3
L1
L3
L2
L2
L2
PE
PE
PE
PE
PE
PE
PE
PE
PE
12 3
L1
L3
L2
PE
M M M
3~ 3~ 3~
L1
L2
L3
PE
C-3
Applications
C-4
C.1.2
Applications
Terminating module
1) x = according to model
The example below shows a layout with direct infeed into the motor starter.
PROFIBUS-DP
Bus module Bus module Bus module
7 7 7
154-2 DP
NEB950566102000/RS-AA/007
SIMATIC - ET 200pro motor starters
IN1 IN2 IN3 IN4 IN1 IN2 IN3 IN4
L1
L3
L1
L3
L1
L3
L1
L3
L1
L3
Br.
L1
L3
Br.
L2
L2
L2
L2
L2
L2
L1
L3
L1
L3
L1
L3
L2
L2
L2
PE
PE
PE
PE
PE
PE
PE
PE
PE
M M M
3~ 3~ 3~
L1
L2
L3
PE
C-5
Applications
C-6
C.1.3
Applications
motor starter. On the motor starter, every X3 connection on the energy bus
The example below shows a layout with direct infeed into each motor starter.
The direct infeed in every motor starter can be used to exchange each individual
PROFIBUS-DP
Bus module Bus module Bus module
7 7 7
154-2 DP
NEB950566102000/RS-AA/007
SIMATIC - ET 200pro motor starters
Figure C-3: (cont.) Design for hot swapping
IN1 IN2 IN3 IN4 IN1 IN2 IN3 IN4
Q1 Q1 Q1 Q2
L1
L3
L1
L3
L1
L3
L1
L3
L1
L3
L1
L3
L2
L2
L2
L2
L2
L2
L1
L3
L1
L3
L1
L3
L2
L2
L2
PE
PE
PE
PE
PE
PE
PE
PE
PE
M M M
3~ 3~ 3~
L1
L2
L3
PE
C-7
Applications
C-8
C.2
C.2.1
Safety local
Interface repair switch 400 V shut- RSe
Applications
Caution
ON
O
Safety note
Terminating module
OFF
START for category 2.
SAFETY applications
Figure C-4: Design with emergency stop 1-channel with monitored START
2 3RK1922-2BA00 Bus module
1 3RK1922-2BA01 Bus module for safety local repair switch module
1-channel emergency stop with monitored START
1)
1 3RK1304-5xS40-3AA0 RSe-HF motor starter
2 3RK1922-2BQ00 Energy jumper plug
2 3RK1902-0CK00 Cap for energy bus
1)
1 3RK1911-2BEx0 Connector set for energy supply
1)
1 3RK1902-0Cx00 Connector set for motor connection
switch module should be used in combination with a 400 V trip module.
1) x = according to model
An automatic re-start in connection with an emergency stop is not permitted.
Please ensure that both coding switches are in the correct position in line with
PROFIBUS-DP
Bus module Bus module Bus module
7 7 7
154-2 DP
NEB950566102000/RS-AA/007
1 F0
1— Q1
Q2
0— Q1 Q2
Q1
S1 S2
1-channel
Figure C-4: (cont.) Design with emergency stop 1-channel with monitored START
L1
L3
L1
L3
L1
L3
L1
L3
Br.
L1
L3
Br.
L2
L2
L1
L3
L2
L1
L3
L2
L2
L2
L2
L1
L3
L2
PE
PE
PE
PE
PE
PE
PE
PE
monitored
START
M
3~
L1
L2
L3
PE
C-9
Applications
C-10
C.2.2
Safety local
Interface repair switch 400 V shut- RSe
Applications
ON
Terminating module
OFF
START for category 4.
Figure C-5: Design with emergency stop 2-channel with monitored START
2 3RK1922-2BA00 Bus module
1 3RK1922-2BA01 Bus module for safety local repair switch module
2-channel emergency stop with monitored START
1)
1 3RK1304-5xS40-3AA0 RSe-HF motor starter
2 3RK1922-2BQ00 Energy jumper plug
2 3RK1902-0CK00 Cap for energy bus
1)
1 3RK1911-2BEx0 Connector set for energy supply
1)
1 3RK1902-0Cx00 Connector set for motor connection
1 XXX Emergency stop / emergency stop switch; 2-pole, NC contact
The example below shows a design with emergency stop with monitored
PROFIBUS-DP
Bus module Bus module Bus module
7 7 7
154-2 DP
NEB950566102000/RS-AA/007
1 F0
1— Q1
Q2
0— Q1 Q2
Q1
S1 S2
2-channel
L1
L3
L1
L3
L1
L3
L1
L3
Br.
L1
L3
Br.
L2
L2
L1
L3
L2
L1
L3
L2
L2
L2
L2
L1
L3
L2
Figure C-5: (cont.) Design with emergency stop 2-channel with monitored START
PE
PE
PE
PE
PE
PE
PE
PE
monitored
START
M
3~
L1
L2
L3
PE
C-11
Applications
C-12
C.2.3
Safety local
Interface repair switch 400 V shut- RSe High fea-
Applications
Caution
ON
Terminating module
OFF
to output OUT 1.
Figure C-6: Design for guard door monitoring 1-channel and automatic re-start
1 3RK1922-2BA01 Bus module for safety local repair switch module
1 3RK1304-0HS00-7AA0 Safety local repair switch module
1 3RK1304-0HS00-8AA0 400 V shutdown
the safety local repair switch module for your application.
1)
1 3RK1304-5xS40-3AA0 RSe-HF motor starter
Guard door monitoring 1-channel with automatic re-start
1) x = according to model
The example below shows a design with guard door monitoring with automatic
re-start in category 2. As an option, a tumbler for guard doors can be connected
PROFIBUS-DP
Bus module Bus module Bus module
7 7 7
154-2 DP
NEB950566102000/RS-AA/007
1 F0
1— Q1
Q2
0— Q1 Q2
Q1
S1 S2
1-channel
autostart
L1
L3
L1
L3
L1
L3
L1
L3
Br.
L1
L3
Br.
L2
L2
L1
L3
L2
L1
L3
L2
L2
L2
L2
L1
L3
L2
PE
PE
PE
PE
PE
PE
PE
PE
Figure C-6: (cont.) Design for guard door monitoring 1-channel and automatic re-start
M
3~
L1
L2
L3
PE
C-13
Applications
Applications
Bit 8 7 6 5 4 3 2 1 0
23 22 21 20 2-1 2-2 2-3 2-4 2-5
Description
When a data record is rejected, a fault code is sent with the negative
acknowledgement, both via the device interface and via the bus interface.
This provides information on the reason for the negative acknowledgement.
The fault codes conform to the PROFIBUS-DPV1 standard assuming they apply
to the motor starter.
Fault codes
The following fault codes are generated by the motor starter:
high low
00 H 00 H No faults —
Communication interface
80 H A0 H Negative acknowledgement with • Data record only writeable
’Read data record’
80 H A1 H Negative acknowledgement with • Data record only readable
’Write data record’
80 H A2 H Protocol fault • Layer 2 (field bus)
• Device interface
• Incorred coordination
80 H A9 H Function not supported. • DPV1 service does not
support read / write data
record
80 H B5 H Invalid status • PROFIenergy data record read
without prior writing
Access to technology
80 H B0 H Unknown data record number • DS no. in motor starter not
(DS no.) known
80 H B1 H Incorrect data record length • DS length and specified DS
during writing length do not match
80 H B2 H Incorrect slot number • Slot not 1 or 4
80 H B6 H Communication partner has • Incorrect operating mode
declined the data transfer. (automatic, manual bus,
manual local)
• Data record is only readable
• Parameter change in ON
status not permissible
80 H B8 H Invalid parameter • Invalid parameter value
Device resources
80 H C2 H Temporary resource lack in • No free reception buffer
device. • Data record currently being
updated
• Data record job currently
active on another interface
Table D-1: Fault codes
Note
SFC 58 and 59 cannot be used with PROFINET. These modules only function
with PROFIBUS.
For PROFINET, the modules SFB 52 and 53 should be used. These also function
with PROFIBUS.
Other information
Other information on the SFBs can be found
• in the reference manual ’System software for S7-300 / 400, system and
standard functions’
• in the STEP 7 online help
Byte layouts
If data that are longer than a byte are stored, the bytes have the following
layouts ("big endian"):
Byte 0 Byte 0
Byte
Byte 1 Byte 1
Note
Note that data record 68 in automatic operating mode is overwritten by the cyclical
process image
Byte Meaning
Leader
0 Coordination 0x21 writing via C1 channel (PLC)
0x31 writing via C2 channel (PC)
1 Reserved
2 Reserved
3 Reserved
Process image of the outputs
4 Process data DO 0.0 to DO 0.7, bottom table
5 Process data DO 1.0 to DO 1.7, bottom table
6 Reserved
7 Reserved
Table D-2: DS68 process image for read/write outputs
Byte Meaning
Process image for the inputs
0 Process data DI 0.0 to DI 0.7, bottom table
1 Process data DI 1.0 to DI 1.7, bottom table
2 Reserved
3 Reserved
Table D-4: DS69 process image for the read / write inputs
…
120…123 Operating hours device 1…4294967295 1s last, latest
entry
124…125 Object number 0…32767 1
This data record can take up to 21 inputs. When all positions have been written
to, the oldest entry is overwritten.
Note
The most recent entry is entered at the end of the data record. The remaining
entries are moved upwards one entry.
oldest entry
4…5 Object number 0…32767 1
…
120…123 Operating hours device 1…4294967295 1s
last, latest
124…125 Object number 0…32767 1 entry
This data record can take up to 21 inputs. When all positions have been written
to, the oldest entry is overwritten.
Note
The most recent entry is entered at the end of the data record. The remaining
entries are moved upwards one entry.
oldest entry
4…5 Object number 0…± 32767 1
..
120…123 Operating hours device 1…4294967295 1s
last, latest
124…125 Object number 0…± 32767 1 entry
* + :Incoming event
– :Outgoing event
Table D-10: DS75 – Log book – Read events
This data record can take up to 21 inputs. When all positions have been written
to, the oldest entry is overwritten.
Note
The most recent entry is entered at the end of the data record. The remaining
entries are moved upwards one entry.
Advance warnings
1419 ± Prewarning limit - time-based trigger reserve not reached 2)
1420 ± Prewarning limit - motor heating exceeded 2)
1457 ± Maintenance required 2)
Warnings
318 ± Switching element power supply missing
324 ± Temperature sensor overload 1)
325 ± Temperature sensor wire break 1)
326 ± Temperature sensor short-circuit 1)
327 ± Thermal motor model overload
334 ± Ie limit value not reached
335 ± Ie limit value exceeded
337 ± Zero current detected
340 ± Asymmetry detected
351 ± Warning input
1458 ± Maintenance request 2)
Actions
310 ± Emergency start active
357 Automatic operating mode
358 Manual bus operating mode
359 Local operating mode
360 ± Lost connection in manual operating mode
363 Slave pointer deleted
365 Invalid parameter value
366 Parameter change in ON status not permissible
368 ± Parameterization lock CPU/Master active
369 Factory setting restored
1302 Log book - trips cleared
1303 Log book - events cleared
1484 ± Temperature sensor deactivated 2)
1520 ± Energy-saving mode active
Table D-11: Messages in the log book – Events
Data record 81 has the same layout and content as data record 131.
Data record 81 delivers the default values for all parameters of DS 131.
Greyed out signalling bits are not supported by ET 200pro motor starters.
Byte Signalling bit F-no.1) Meaning / Acknowledgement
Switching / controlling:
0
0 Ready (automatic) Device can be operated via host (e.g. PLC)
—
Signalling bit is updated continuously
01 Motor cw Switching element 1 on
—
Signalling bit is updated continuously
02 Motor ccw Switching element 2 on
—
Signalling bit is updated continuously
03 Overload switching element (F5) e.g. power semiconductor too hot and shutdown
F24 Signalling bit is cleared if the shutdown cause has
been eliminated and acknowledged using trip reset
04 Switching element defective F9 e.g. contactor welded shut or power semiconductor
failed
Signalling bit can only be cleared by switching the
power supply (24 V-NS DC) off and on again once
the cause has been eliminated
05 Emergency start active Signalling bit is cleared if emergency stop is
—
deactivated
06 Group fault at least 1 fault that generates a F-no. is set.
—
Signalling bit is cleared when the shutdown cause
is eliminated and has been acknowledged with trip
reset, autoreset, OFF command
07 General warning there is at least 1 warning
—
Signalling bit is updated continuously
10 Switching element power F17, Signalling bit is cleared when the shutdown cause is
supply missing F24 eliminated 4)
Signalling bit is cleared when the shutdown cause is
eliminated and acknowledged with trip reset 5)
11 No supply voltage F17, Signalling bit is cleared when the shutdown cause
F24 is eliminated and acknowledged with trip reset
(occurs even if control voltage is missing on the
incoming or outgoing side; applies to soft starters
12 Interlock active With reversing starters
—
Signalling bit is updated continuously
Table D-12: DS92 – Read device diagnostics
37 Control input2) Motor cw, motor ccw control commands via input
—
actions
Signalling bit is updated continuously
40 Asymmetry detected Asymmetry present
—
Signalling bit is updated continuously
41 Asymmetry shutdown F24 Asymmetry present and shutdown
Signalling bit is cleared when the shutdown cause
has been eliminated and acknowledged with trip
reset
42 Ie limit value exceeded2) F7 Limit value exceeded
Signalling bit is updated continuously
43 Ie limit value not reached) F8 Limit value not reached
Signalling bit is updated continuously
44 Ie limit value shutdown2) F24 Signalling bit is cleared when the shutdown cause
has been eliminated and acknowledged with trip
reset
45 Residual current detected Zero current detected
—
Signalling bit is updated continuously
46 Zero current shutdown F24 Zero current detected and shutdown
47 Motor blocking shutdown F24 Shutdown, blocking current detected for longer than
the permitted blocking time
Signalling bit is cleared when the shutdown cause
has been eliminated and acknowledged with trip
reset
50 Input 12) Status conditions of the free inputs (with NO contact):
—
’1’ = active, HIGH level present
51 Input 22) ’0’ = inactive, LOW level present (reversed for NC
—
contact)
52 Input 32) Signalling bit is updated continuously
—
53 Input 42)
—
54 Shutdown input2) F26, Shutdown present
F24 Signalling bit is cleared when the shutdown cause
has been eliminated and acknowledged with trip
reset/autoreset
55 Shutdown F26, Shutdown present
clockwise end position F24 Signalling bit is automatically cleared when
input2) the shutdown cause is eliminated.
Counter-clockwise start possible.
56 Warning input2) Warning present
—
Signalling bit is updated continuously
57 Shutdown F26, Shutdown present
counter-clockwise end F24 Signalling bit is automatically cleared when
position input2) the shutdown cause is eliminated.
Clockwise start possible.
Table D-12: DS92 – Read device diagnostics (Contd.)
224 Manual local input control2) Manual local operating mode active,
—
+ input control active
225 Manual local B&B control Not supported
—
86 Memory submodule faulty F26 Signalling bit is always cleared when
(F24) acknowledged with trip reset.
Results in a shutdown on startup
87 Memory submodule not — Signalling bit is updated continuously
plugged in
226 Manual local - PC controlling Manual local operating mode active,
—
+ PC control active
Parameters
80 Parameterization active Signalling bit is updated continuously
—
81 Invalid parameter value F16 Signalling bit is always cleared when acknowledged
(F24) with trip reset or valid parameters have been
received.
Results in a shutdown on startup
82 Parameter change in ON Attempted parameter change with motor running or
—
status not permissible device function that caused the shutdown.
Signalling bit is always cleared when acknowledged
with trip reset or valid parameters have been
received
83 Parameterization lock CPU / Signalling bit is updated continuously
—
Master active Motor starter ignores parameters from the PLC
84 No external startup — Signalling bit is always cleared when changing from
parameter received start to normal operating condition
85 reserved = 0 —
Device function
90 Self-test active Signalling bit is updated continuously
—
91 Self-test OK Signalling bit is updated continuously
—
92 Fault during self-test F9 Signalling bit can only be cleared by switching
the supply voltage off / on (24 V-NS DC) when
the cause of fault has been eliminated.
93 Factory setting restored Signalling bit is always cleared when acknowledged
—
with ’Trip Reset’.
94…5 Memory module 00: not assigned (status after power-ON)
—
01: Programming active
10: Programming successful
11: Programming faulty F26,
(F24 only on start-up)
Signalling bit is always cleared if acknowledged
with trip reset.
Table D-12: DS92 – Read device diagnostics (Contd.)
1-byte commands
0 Reserved no function
1 Trip reset Reset and acknowledgement of fault messages
2 Emergency start ON —
3 Emergency start OFF —
4 Automatic operating Transfer to automatic operating mode (control via DP master)
mode
5 Manual operating mode Transfer to manual operating mode. In the process, the motor
- Bus starter switches over in manual bus operating mode or manual
- On-site local operating mode, depending on the interface via which the
command is received.
6 Factory setting Restore factory setting of the parameters from DS 128
7 Clear slave pointer The measurements for preventative diagnostics are cleared
(= 0).
8 Program Not supported
memory module
9 Re-start Trigger re-start (as after mains ON), e. g. after re-assignment
of the station address.
10 Parameterization lock No parameterization possible via parameterizing master,
CPU / Master ON or its parameters will be ignored
11 Parameterization lock Parameterization possible via parameterizing master
CPU / Master OFF
12 Clear memory module Not supported
Table D-14: DS93 – write command
13 Clear log book trips Clear log book with recorded causes of fault.
14 Clear log book events Clear log book with recorded warning messages and specific
actions.
15 Cold run ON Activate cold-run function
16 Cold run OFF Deactivate cold-run function
17 Clear maintenance The content of the maintenance timer statistics value is set
timer to "0".
18 Establish current limits Not supported
19 Transfer current limit Not supported
values
20 … 255 Reserved —
Table D-14: DS93 – write command (Contd.)
Measurements
0 Phase current IL1 act(%) 0…796.9 % 3.125% 8-bit current
waveform.
1 Phase current IL2 act(%) 0…796.9 % 3.125% 8-bit current
waveform.
2 Phase current IL3 act(%) 0…796.9 % 3.125% 8-bit current
waveform.
4…5 Remaining cool-down time of the motor 0 … 1800 s 0.1 s
60…6 Motor heating 0…200 % / [0…100] 2%
67 Asymmetry [0]: No asymm. Tripping limit
[1]: Asymm. (≥ 40 %) depends on
asymmetry
0 = 100 %
1 = 75
7 Asymmetry value1) 0…100 % / [0…100] 1% —
28…31 Phase current IL1(eff) ±0 … 20 A 0.01 A —
32…35 Phase current IL2(eff) ±0 … 20 A 0.01 A —
36…39 Phase current IL3(eff) ±0 … 20 A 0.01 A —
42 Heat sink temperature is evaluated with 1.5 - 12 A soft starters to protect the power module
46…47 Time-based triggering of the thermal 0…6 500 s 0.1 s FFFFH:
motor model Time infinite
1) only with HF starters
Table D-15: DS94 – Read measurements
Operating hours
The motor starter records 2 operating hour values:
The operating hours of the motor indicate how long the switching elements and therefore the motor
were switched on.
The operating hours of the equipment (motor starter) indicate how long the 24V-NS DC supply
voltage of the motor starter was switched on.
Table D-16: DS95 - Read statistics
Leader
0…3 4 Reserved
Device identification (TF)
4…11 8 … Time stamp 1)
12…31 20 Siemens AG Manufacturer
32…55 24 — MLFB number
56 1 0x01 Device range: load branch
57 1 0x01 Device sub-range: Motor starters
58 1 0x01 / 0x02 / 0x03 / 0x04 Device class: e.g. direct starters / reversing
starters / direct soft starters / reversing soft starters
59 1 0x66 System: ET200pro
60 1 0x32 /0x5A Standard starters / high feature starters
61 1 0x00 Reserved
62…77 16 — Product code
78…81 4 E… Hardware revision status (byte 0 to byte 3)
82…85 4 … ID number
86…87 2 0x00 Reserved
88…95 8 … Service number
96…99 4 0x00 Reserved
1) Time stamp: Time of the factory initialization with basic factory settings
Table D-18: DS100 – Read device identification
Bit 8 7 6 5 4 3 2 1 Note
Byte
You can store any text with up to 121 characters (max. 128 bytes),
e.g. for system documentation in the motor starter.
When using the DP V1 functions, complete data records can be exchanged with
the starters via the ET 200pro rear wall bus.
It is recommended to first export the data record 131 with the actual
parameters from the motor starter, change the relevant parameters and
then write them back to the motor starter.
Note that the coordination (byte 0) should be set to 0x21 before write data
record.
The message interchange between the interface module and the special
modules or motor starters is carried out in blocks of up to 16 bytes in length.
The entirety (block) of a data record must be sent in each case.
For advanced parameterization of the ET 200pro starters, the following
elements of the data record 131 (1st block / 62 bytes) are used:
I&M 0
The following data are prepared in data record 231:
1L+
(PWR) supply voltage for electronics.
2L+
(CON) supply voltage for contactor control.
Bypass
After the starting operation, the bypass connects the motor directly to the
power supply and thus avoids the heat loss in the integrated thyristor modules.
Direct starters
A direct starter is a → motor starter for a single direction of rotation that
switches a motor on or off directly. It consists of a circuit breaker and a
contactor.
GSD
Device master data
GSDML
The GSDML language is defined by the GSDML schema. A GSDML schema
contains validity rules permitting the syntax of a GSD file, for example. GSDML
schema (in the form of schema files) ordered by manufacturers of IO devices
of PROFIBUS International.
Load group
A group of motor starters supplied by a single power bus infeed. A load group
can be located within a → potential group or parts of two potential groups.
MS (motor starter)
Motor starter is the generic term for direct and reversing starters.
With motor starters the start-up and direction of rotation of a motor
is determined.
Reversing starters
A reversing starter is a → motor starter for two directions of rotation of a motor.
It consists of a circuit breaker and two contactors.
Numerics C
1-channel operation 7-8 Cap 9-2
1L+ Gl-1 Cap for energy bus 1-4, 3-10
2-channel operation 7-8 CLASS 10-6
2L+ Gl-1 Coast type 8-11, 10-30
400 V shutdown module 1-2 Coasting down time 8-11, 8-23, 10-30
400V shutdown module 7-10 Coasting-down time 8-23
Cold run D-17
A Cold start 10-8
Accessories 1-4 Commands 10-48
Actions 10-9 Commissioning 4-1
Actual motor current 10-3 Communication 10-45
Aggregate current 7-13 Configuration 2-7, 4-3, 7-8
Applications C-1 Configuration of an ET 200pro with motor
ASM -400 1-2, 7-10 starters 3-2
Assignment of the auxiliary circuits 7-8 Configuration options 1-6
Assignment of the inputs 8-16 Connecting the cables 3-9
Assignment of the main power Connection 9-1
connections 7-3, 7-7, 7-12, 8-6 Connection cross-section power
Asymmetrical limit value 10-18 infeed 8-13
Asymmetry 10-18 Connection monitoring 10-47
Autostart 7-8 Connection technology 7-7, 8-6
Auxiliary circuits 8-7 Control circuit 8-13
Crimping tool 1-5
B Current asymmetry limit value 8-10
Basic components 1-1 Current flow via the power bus 7-13
Basic parameters 10-2 Current formats D-1
Blocking current 10-12, 10-14 Current limit 8-11
Blocking current limit value 8-10 Current limiting value 8-24, 10-30
Blocking protection after Current limits 10-11, 10-14
acceleration 10-13 Current setting 4-1
Blocking protection during Current-carrying capacity 1-8
acceleration 10-13 Cyclic duration factor CD 8-24
Blocking time 10-12, 10-14
Blocking time limit value 8-10 D
Brake actuation 8-15 Data channels 10-45
Brake enabling delay 8-11 Data formats D-1
Brief instructions 2-1 Data record 68 D-6
Bypass Gl-1 Data record 69 D-7
Byte layouts D-5 Data record 72 D-8
Data records D-5
Derating 3-4
Device diagnostics 4-17
Name
Company / Office
Siemens AG Address
DF CP PRM IM 2
Phone
92220 Amberg
Fax