Lecture 02
Lecture 02
HVDC Principle
6-pulse bridge HVDC
power Id power
Reactive
Id Reactive
power power
DC line
I
I.sinφ
The converter operates in inverter 36
Vd Vd
Vd 0 Slope is DX Vd 0
1.0 1.0
α = 0° α = 0°
Increasing α
Increasing α
Rectifier Rectifier
α is the control
Id variable for rectifier Id
1.0 I dN and γ is the control 1.0 I dN
Increasing γ
variable for inverter.
Inverter Inverter
γ = 0°
-1.0 αmax < 180 ° -1.0
38
HVDC Principle
HVDC Principle
12-pulse bridge HVDC
Id
Y ∆ Vdr∆ Vdi∆ ∆ Y
Y Y VdrY VdiY Y Y
Id
and µ = 25°
IAY
IA∆
Y ∆ Vd∆
IA∆ Vd
IA IA Y Y VdY
IAY
40
HVDC Principle
2. HVDC Principle
½ Rd
power power
Y ∆ Id ∆ Y
power Vdr Vdi
Y Y Y Y
½ Rd
Reactive power Reactive power
αmin < α voltage γmin < γ
decreasing α
αmin = 5° - 7° γ min = 15° - 17°
Vdr
To ensure all To keep reactive
thyristor valves are Vdi power requirement
enough forward bias on inverter side as
to turn on. low as possible.
Id current
42
HVDC Principle
2. HVDC Principle
a) Earth Return
ii) Bipolar Configuration
b) Metallic Return
i) Mono-polar Configuration 43
iii) Homo-polar Configuration
HVDC Principle
2. HVDC Principle
44
Control of
the DC Transmission
46
Control of the DC Transmission
Firing Control
Function of the firing control is to convert the firing angle
order (α*) demanded fed into the valve group control system.
There might be voltage distortions due to non-characteristic
harmonics, faults and other transient disturbances such as
frequency variation. Thus, phase-locked loop (PLL) based firing
system is generally applied. θ
PI Controller vo Voltage comparator
vA verror
Phase (1 + Ts ) Controlled
vB Detector
K Oscillator comparator
Ts
…
vC
…
uA
…
sin(.) comparator
uB - ⅔π
sin(.)
uC Gate firing
sin(.) α* 47
Control of the DC Transmission
Firing Control (Continued)
uA
vA
0
time
verror
0
time
2π
θ α*
0
α time
Firing pulse of phase A
48
Control of the DC Transmission
Current Control (CC)
The firing angle is controlled with a feedback control
system as shown in figure. The dc voltage of the converter
increases (by decrease α*) or decreases (by increase α*) to adjust the
dc current to its set-point (Id*).
(1 + Ts )
K Id
Ts
Y ∆
Vdr
vA, vB , vC Y Y
αmax
id* - α* Firing 6
PI Control
6 Current
+ αmin measurement
id 49
Control of the DC Transmission
Constant Extinction Angle Control (CEA)
The firing angle of the inverter is controlled at minimum
angle (γmin) to reduce reactive power requirement. This can be
achieved by using Gamma control (γ-control).
Current
measurement
∆ Y
Vdi
Y Y
vA, vB , vC
αmax
Valve voltage 6 Firing α* γ*
-
Control PI
6
+
αmin
γ
γ measurement
50
Control of the DC Transmission
VI Characteristic of the CC and the CEA
voltage voltage
Vdr
α*
X Vdi Vdi
Vdr
γ* = γmin α*=α min γ* = γmin
AC voltage
decreasing
Id current Id current
γ*
∆ Y γ - Control
Vdi
Y Y
∆id = 0.1 to 0.15
Minimum
selection
vA, vB , vC
αmax
α* + id*
Firing
Control PI -
Current 6
αmin +
measurement
id
52
Control of the DC Transmission
VI Characteristic of CC, CEA and CMC
voltage voltage
Vdr CEA
α*
X Vdi Vdi
Vdr
γ* = γmin α*=α min X γ* = γmin
∆Id
CMC
CC AC voltage ∆Id
decreasing
Id current Id current
voltage voltage
More Weak
Vdr
α* X
Weak AC
CEA
Vdr α* γ* = γmin
Vdi X
Vdi
∆Id CEA ∆Id VC
CMC γ* = γmin CMC
γ* > γmin
Id current Id current
∆ Y
Vdi
Y Y γ*
γ - Control
Maximum
selection
vA, vB , vC αmax
Minimum
selection
vdi*
6 Firing α* PI
Control
-
6 αmin +
CMC
vdi
Voltage 55
measurement
Control of the DC Transmission
Voltage Dependent Current Limit (VDCL)
Commutation failures can occur during an AC fault on the
inverter side. It results in continue conduction of a valve beyond
its 120° conduction interval. The CC will regulate the DC current to
its rated value, but in the worst case, two inverter valves may form
DC short circuit and continue conducting for a long time, which
can cause valve damage. To prevent this problem, DC current
must be reduced. One possible to detect the AC side fault is the
lowering of the DC voltage. This voltage is typically chosen at 40%
of the rated voltage.
Id
56
Control of the DC Transmission
Voltage Dependent Current Limit (VDCL)
The VDCL is a limitation imposed by the ability of the AC
system to sustain the DC power flow when the AC voltage at the
rectifier bus is reduced due to some disturbance as well. The
VDCL characteristics is presented below.
voltage voltage
VC VC
Vdr α* Vdr α*
X
X
Vdi Vdi
CMC
VDCL CMC ∆Id VDCL ∆Id
≈ 0.4 ≈ 0.4 VDCL
VDCL Idmax
∆Id VDCL ∆Id
Id-min Idmax current Id-min Id current
57
Control of the DC Transmission
Voltage Dependent Current Limit (VDCL)
id*
Minimum
selection
Vd
vd i CC
v i
v
1
1 + Ts VDCL
vd Voltage
measurement
58
Control of the DC Transmission
Tap Change Control (TCC)
When voltage of the AC system of the rectifier and/or of the
inverter is fluctuated, transformer taps (both side) can adjust to
keep the DC voltage within desired limits or suitable operating
point. Generally, the tap will be changed when the firing angle of
the rectifier/inverter still reach its more than 10-15 minutes to
avoid interaction of other controls.
59
Control of the DC Transmission
Power Reversal
The VI characteristic of power reversion is presented below
(VDCL and VC are not included). The station 1 (rectifier) increases firing
angle (α) into the inverter region and the station 2 (inverter) decreases its
firing angle (α) into rectifier region. This can be performed without altering
the direction of current flow.
voltage voltage
V1dr α*
X γ* = γmin
V2di
Id current Id current
V1di
X
γ* = γmin
V2dr α* 60
Control of the DC Transmission
Y ∆ Id ∆ Y
Vdr Vdi
Y Y Y Y
Vd, Id,α, γ
Max.
Max.
Control
Control
α* α*
Firing
Firing
Min.
Min.
∆id
Master Control
id *
CC VDCL VDCL CC
p*/vd γmin
CAE γmin CAE
po p* Power
VC Vd* Vd* VC
order
∆p
TCC TCC
Modulation Signal 61
Control of the DC Transmission
CIGRE’s HVDC benchmark was simulated on ATP-EMTP with
the typical HVDC control schemes, which the CC mode was
employed at rectifier and VC mode was applied at inverter. All
simulation results are presented in normalized values.
Start Up HVDC 62
Control of the DC Transmission
The HVDC started at 0.1 sec. The firing angle of rectifier started at
90° while the extinction angle of inverter started at 90°.
Power Reversal 65
Control of the DC Transmission
VDCL performance during 1-phase fault at AC
network of the rectifier station.
Va Vb Vc
Vdi αr
70
Control of the DC Transmission
71
Modulation Function of EGAT-TNB HVDC
Control of the DC Transmission
74