6EP33226SB000AY0 Datasheet en PDF
6EP33226SB000AY0 Datasheet en PDF
6EP33226SB000AY0 Datasheet en PDF
LOGO!POWER 12 V/4.5 A
LOGO!POWER 12 V / 4.5 A Regulated power supply input: 100-240
V AC output: 12 V DC/ 4.5 A
Input
Input 1-phase AC or DC
Rated voltage value Vin rated 100 ... 240 V
Voltage range AC 85 ... 264 V
Input voltage
● at DC 110 ... 300 V
Wide-range input Yes
Overvoltage resistance 300 V AC for 1 s
Mains buffering at Iout rated, min. 40 ms; at Vin = 187 V
Rated line frequency 1 50 Hz
Rated line frequency 2 60 Hz
Rated line range 47 ... 63 Hz
Input current
● at rated input voltage 120 V 1.13 A
● at rated input voltage 230 V 0.61 A
Switch-on current limiting (+25 °C), max. 50 A
I²t, max. 3 A²·s
Built-in incoming fuse internal
Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 12 V
Total tolerance, static ± 3 %
Static mains compensation, approx. 0.1 %
Static load balancing, approx. 0.1 %
Residual ripple peak-peak, max. 200 mV
Residual ripple peak-peak, typ. 30 mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 300 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 50 mV
Adjustment range 10.5 ... 16.1 V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer
Status display Green LED for output voltage OK
On/off behavior No overshoot of Vout (soft start)
Startup delay, max. 0.5 s
Voltage rise, typ. 100 ms
Rated current value Iout rated 4.5 A
Current range 0 ... 4.5 A
● Note +55 ... +70 °C: Derating 2%/K
Supplied active power typical 54 W
Parallel switching for enhanced performance Yes
Numbers of parallel switchable units for enhanced 2
performance
Efficiency
Efficiency at Vout rated, Iout rated, approx. 87.1 %
Power loss at Vout rated, Iout rated, approx. 8 W
Power loss [W] during no-load operation maximum 0.3 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), 0.2 %
max.
Dynamic load smoothing (Iout: 10/90/10 %), Uout ± 4 %
typ.
Load step setting time 10 to 90%, typ. 1 ms
Load step setting time 90 to 10%, typ. 1 ms
Safety
Primary/secondary isolation Yes
Galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178
Protection class Class II (without protective conductor)
CE mark Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File
E151273, NEC class 2 (acc. to UL 1310)
Explosion protection ATEX (EX) II 3G Ex nA IIC T3; cULus Class I Div. 2 (ANSI/ISA-
12.12.01, CSA C22.2 No. 213) Group ABCD, T4, File E488866
FM approval Class I, Div. 2, Group ABCD, T4
CB approval Yes
Marine approval ABS, DNV GL
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation not applicable
Noise immunity EN 61000-6-2
Operating data
Ambient temperature
● during operation -25 ... +70 °C
— Note with natural convection
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
Humidity class according to EN 60721 Climate class 3K3, no condensation
Mechanics
Connection technology screw-type terminals
Connections
● Supply input L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely
stranded
● Output +, -: 1 screw terminal each for 0.5 ... 2.5 mm²
● Auxiliary -
Width of the enclosure 54 mm
Height of the enclosure 90 mm
Depth of the enclosure 53 mm
Required spacing