VTS Checklist

VTS Sp. z o.o. is a Polish company that provides air handling units. This document summarizes the pre-commissioning of unit number 8-142-17-3230-00001 for the Al Meera Convenience Store in Alkhor, Qatar. The unit was inspected according to the operation and maintenance manual. All installation and electrical checks were completed successfully. The air handling unit was started and ran for 30 minutes without any issues. The unit has been prepared for start-up.

Uploaded by

Mohd Haroon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
452 views1 page

VTS Checklist

VTS Sp. z o.o. is a Polish company that provides air handling units. This document summarizes the pre-commissioning of unit number 8-142-17-3230-00001 for the Al Meera Convenience Store in Alkhor, Qatar. The unit was inspected according to the operation and maintenance manual. All installation and electrical checks were completed successfully. The air handling unit was started and ran for 30 minutes without any issues. The unit has been prepared for start-up.

Uploaded by

Mohd Haroon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

VTS Sp. z o.o.

,
Al. Sikorskiego 11, 02-758 Warszawa, Poland
HQ Division
6a Łużycka Str., 81-537 Gdynia, Poland
tel. + 48 (58) 628 13 54, fax +48 (58) 628 13 22
www.vtsgroup.com; [email protected]

AIR HANDLING UNITS – START UP & PRE COMMISSIONING


PROJECT : AL MEERA CONVENIENCE STORE AT ALKHOR

UNIT SERIAL NO 8-142-17-3230-00001

UNIT REFRENCE NO AND LOCATION HRU-01,VS-230-R-F/R/E, at Roof Floor


ACTIVITY DESCRIPTION YES NO REMARKS

Installation
a. Rubber Pads Installed as per Mfr recommended. YES
b. All Access door clamps are locked YES
c. Condensate drain is unobstructed YES
Electrical
a. Power available to unit as per O & M manual. YES
b. Power available to VFD & Program acc to O & M
YES
manual.
c. Proper Fan rotation verified YES

d. In operation Motor Amps must not increase the rated


YES
value.
Coils
a. Chilled water piping properly connected YES

b. Drain Trap height as per O & M manual YES


c. Drain pan with two outlets have two separate U
NO N.A.
traps.
Filters
a. Clean Filters YES

b. Filter properly installed. YES


THE AHU HAS BEEN INSPECTED & PREPARED FOR START-UP AS PER THE VENTUS O&M MANUAL. THE
AHU STARTED AND KEPT RUNNING FOR 30 MINUTES.
REPORT

INSPECTED BY: CUSTOMER:

VTS Sp. z o.o.


Registration number KRS0000239557, registered in Warszawa District Court XIII Commercial
Division of National Court Register, Tax Identification Number NIP PL 5871599675.