<<Contents>> <<Index>>

General Model RS4E5700


Specifications FAST/TOOLS Integration
Package
GS 32P04D20-01EN

 GENERAL
This software runs on the safety engineering computer (SENG) and enables the integration between ProSafe-RS
and FAST/TOOLS. (*1) This package is used for configuring a system which monitors and controls oil wells and oil
pipe lines dotted in wide area. If this software is used, ProSafe-RS can not be integrated with CENTUM VP.
For more detail about ProSafe-RS and FAST/TOOLS integrated system, refer to the GS “ProSafe-RS Safety
Instrumented System Overview (for Vnet/IP-Upstream)” (GS 32P01B30-01EN).
*1: In an RS Project, this package cannot be used together with “CENTUM VP Integration Package” (RS4E5600).

 FUNCTION OVERVIEW
With this software, users can configure a system that integrates ProSafe-RS and FAST/TOOLS, as illustrated below.

STARDOM PRM Server/Field Domain A


Engineering Communication
FAST/TOOLS Computer Server PRM Client
SENG

Vnet/IP- Upstream

SCS SCS

SCS FCN/FCJ
L2SW
L2SW L2SW

FCN/FCJ FCN/FCJ

SENG: Safety Engineering Station SCS SCS Domain B Domain C


SCS: Safety Control Station
FAST/TOOLS: YOKOGAWA SCADA System
PRM: Plant Resource Manager
FCN/FCJ: STARDOM Controller
L2SW: Layer 2 Switch
L3SW: Layer 3 Switch

L3SW L2SW L3SW L2SW

Vnet/IP-Upstream
FCN/FCJ FCN/FCJ

F01E.ai

Figure Example of Configuration of ProSafe-RS and FAST/TOOLS Integration System


In ProSafe-RS and FAST/TOOLS integrated system, functions described below are available.
• SCS can be operated and monitored from FAST/TOOLS
- Operation and monitoring of SCS using Tag Name
- Detecting Process Alarms and System Alarms
- SCS status display
- Managing SCS annunciators (alarm and recovery)
• Dual redundant Ethernet TCP/IP communication can be configured using a pair of Vnet/IP-Upstream open networks.
• The distance between stations of the same Vnet/IP-Upstream domain can be extended by the network mode.

For the specification of FAST/TOOLS, refer to the GS of “FAST/TOOLS” (GS 50A01A10-01EN).

Yokogawa Electric Corporation GS 32P04D20-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Nov. 2015 (YK)
3rd Edition July 24, 2018 (YK)
<<Contents>> <<Index>> 2
Vnet/IP-Upstream is the control network to integrate ProSafe-RS and FAST/TOOLS with this package. The network
mode of Vnet/IP-Upstream has 3 modes, i.e. standard mode, wide-area mode, and narrowband mode. For more
detail of the network mode, refer to “ProSafe-RS Safety Instrumented System Overview (for Vnet/IP-Upstream)” (GS
32P01B30-01EN).
In addition, please be sure to separate physically Vnet/IP-Upstream system from Vnet/IP system of integration
between ProSafe-RS and CENTUM VP. The physical separation means the two networks should not be linked either
directly or through a network switch or a router.

 FUNCTION SPECIFICATION
 Package Function
FAST/TOOLS Integration Package includes functions described below.

Function Description
Domain Properties setting Setting Standard, Wide-area or Narrowband
The annunciator messages of each SCS to be shown on the FAST/TOOLS is defined on Tag
Annunciator Message definition
Name builder.
The application logic variables and function blocks of each SCS to be accessed by FAST/TOOLS
Tag Name definition
need to be defined with tag names and parameters on Tag Name builder.

The following table summarizes the maximum number of function blocks that can be operated/monitored for each
SCS in a FAST/TOOLS integrated system configuration.

Name Function Block/Element Name Maximum Number


Safety Control Station S2SC70 / SSC60 SSC50 SSC57
ANLG_S/ANLGI Analog Input Block
Total 2700 Total 1800
VEL Velocity (rate-of-change) Alarm Block Total 1800
AGA_3/AGA_7/AGA_R AGA Calculation – (*1) – (*1)
ANN/ANN_FUP Annunciator Message 2000 1000 1000

*1: These function blocks are for SSC57.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P04D20-01EN July 24, 2018-00
<<Contents>> <<Index>> 3
 Types of SCS Data and Function Blocks for which Tag Names can be assigned
The following table summarizes the types of SCS variable data and function blocks for which tag names can be
assigned.

Type Description
BOOL BOOL-type variable
DINT Integer variable
REAL Real-number variable
ANLG_S Analog Input Function Block with Data Status
ANLGI Analog Input
VEL Velocity Limit Alarm
ANN Annunciator
ANN_FUP First-up Alarm Annunciator
IO_REAL Real-number analog input variable
IO_BOOL BOOL-type contact I/O variable
ECW_B BOOL-Type Data External Communication
ECW_I INTEGER-Type Data External Communication
ECW_R REAL-Type Data External Communication
ECWR_B (*1) External communication with BOOL-type data retaining function
ECWR_I (*1) External communication with INTEGER-type data retaining function
ECWR_R (*1) External communication with REAL-type data retaining function
SCI_B BOOL-Type Subsystem Communication Input
SCI_I INTEGER-Type Subsystem Communication Input
SCI_R REAL-Type Subsystem Communication Input
SCO_B BOOL-Type Subsystem Communication Output
SCO_I INTEGER-Type Subsystem Communication Output
SCO_R REAL-Type Subsystem Communication Output
AGA_3 (*1) AGA3 calculation
AGA_7 (*1) AGA7 calculation
AGA_R (*1) Report data creation
*1: These function blocks are for SSC57.
When ProSafe-RS is integrated with FAST/TOOLS, the following Function Blocks can not be used. If any of them are
used, an error occurs during the build operation.
• Override (OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB)
• Password (PASSWD)
• Manual Operation (MOB_21, MOB_11, MOB_RS, MOA)
• Fire and Gas Communication input (PSI_I, PSI_R), PROFINET communication input (PNI_I, PNI_R)

 SYSTEM REQUIREMENTS
Refer to the GS “ProSafe-RS Safety Instrumented System Overview (for Vnet/IP-Upstream)” (32P01B30-01EN).

 MODEL AND SUFFIX CODE


Description
Model RS4E5700 FAST/TOOLS Integration Package
-V Software license
Suffix Code 1 Always 1
1 English version

 ORDERING INFORMATION
Specify the model and suffix code(s).

 TRADEMARKS
• ProSafe, CENTUM, PRM, STARDOM, FAST/TOOLS, Exaopc, FieldMate, and Vnet/IP are either registered
trademarks or trademarks of Yokogawa Electric Corporation.
• Other company and product names appearing in this document are registered trademarks or trademarks of their
respective holders.

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P04D20-01EN July 24, 2018-00
Subject to change without notice.

You might also like