Mer We Dd3320 Electricity Diagrams
Mer We Dd3320 Electricity Diagrams
Mer We Dd3320 Electricity Diagrams
diagrams
MER_WE_DD3320
list of diagrams
01 General LV Synoptic
02 Low Voltage Main Distribution Board (principles)
03 General Services distribution board
04
05 Kitchen distribution board
06 Guest rooms : principles of distribution
07 Guest rooms : distribution boards, consumer units
08 Guest rooms : details
09 External lighting
10 Earthing principles
THE DIAGRAMS INCLUDED HERE GIVE THE PRINCIPLES OF ELECTRICAL DISTRIBUTION IN MERCURE HOTELS. IT
SHALL BE THE RESPONSIBILITY OF THE VARIOUS SPECIALIST CONSULTANTS TO INTERPRET AND ADAPT
THESE DIAGRAMS TO PRODUCE PROPER WORKING DRAWINGS MEETING THE ACTUAL REQUIREMENTS OF THE
PROJECT.
SERVICE LIFT
General LV
bedroom bedroom bedroom
DISTR. BOARD
consumer unit consumer unit consumer unit Synoptic
SWIMMING POOL
FLOOR
N° date: 02/03
LAUNDRY ROOM 01 rev D
bedroom bedroom bedroom
consumer unit consumer unit consumer unit
MER_WE_DD3320
TELEPHONE
DISTR. BOARD
consumer unit consumer unit consumer unit
Principles of distribution
FLOOR
LIFT
The Mains Intake shall feed all the
bedroom bedroom bedroom sub-distribution boards in the hotel.
SMOKE EXHAUST consumer unit consumer unit consumer unit Depending on the power capacity,
this Mains Intake shall be connected
either to a transformer or directly to
INVERTER the LV public main.
bedroom bedroom bedroom
DISTR. BOARD
consumer unit consumer unit consumer unit An "emergency" diesel, feeding only
the safety equipment in the hotel,
EXTL. LIGHTING
FLOOR shall be installed if legislation
requires it.
GENERAL SERVICES A "replacement" generator, feeding
bedroom bedroom bedroom
certain electrical systems in the
consumer unit consumer unit consumer unit
hotel, shall be installed
KITCHEN - if legislation requires it
- if the reliability of the local
bedroom bedroom bedroom electricity distribution is inadequate,
DISTR. BOARD
consumer unit consumer unit consumer unit leading to frequent and/or long
power cuts.
FLOOR
computer UPS
BAR
SO (n outlets) principles shall be used as the basis for the required installation. MERCURE
B machines (n outlets)
A: Provide several outlets for lighting, a minimum of 3. Controlled from a ELECTRICITY
dimmer if required C restaurant lighting (n outlets) switch plate near the bar, certain circuits will be on dimmers.
B: provide several outlets (e.g. glass washer, coffee machine, ice maker,
RESTAURANT
D SO (n outlets) beer pump, chilled cabinet, etc.) General Services
restaurant terrace lighting C: Provide several outlets for lighting, a minimum of 3. Controlled from a distribution board
E
switch plate near the restaurant cash desk, certain circuits will be on
terrace SO (n outlets) dimmers.
N° date: 02/03
F self-service unit SOs (n outlets) D: Provide several SO outlets for cleaning and a specific outlet for the till
(there will also be SOs on the inverter circuit) 03 rev C
dimmer if required G hall lighting (n outlets) E: Any terrace accessible from the restaurant will have several lighting
and SO circuits MER_WE_DD3320
SO, general system (n outlets)
F: These are SO circuits to be used for the connection of the self-service
LOBBY
H SO, specific system (n outlets) display unit (e.g. plate warmer)
G: Provide several outlets for lighting, a minimum of 3. Controlled from a
canopy lighting switch plate in the reception back office, certain circuits will be on dimmers
K toilets H: Specific circuit: decorative point lighting, advertising panels, restaurant
menu-holder, etc. These circuits shall be switched on and off from "G". In
I multi-purpose hall addition provide outlets for the reception desk (there will also be SOs on
an inverter circuit)
meeting rooms, lighting
J I: Feeds a specific sub-distribution board, this sub-distribution board may
MEETINGS
meeting rooms, SOs also combine the outlets for the small meeting rooms
"normal" bus bars
J: Unless there are very few meeting rooms, the "meeting" functions
lighting to lounge corridor should be combined in a sub-distribution board that includes lighting, SOs,
K lounge toilets (n outlets) public address and sundry auxiliaries.
K: Provide several outlets for lighting, SOs, hand dryers, etc. (the lighting
L 32A panel multi-purpose room shall be remote controlled)
L: the multi-purpose room shall be provided with a power supply for use
office lighting (n outlets)
by clients wanting special effects
M offices SO (n outlets) M: in the offices, at each work station, provide 3 SOs installed in
prefabricated PVC trunking
NON-PUBLIC
corridor lighting (n outlets) N: for photo-copying, air conditioning (split) in some sensitive technical
ZONES
X
SO = socket outlet
B glass washer
B deep fryer
B steam cooker
SO = socket outlet
B oven
B convection oven
B
bain marie
B grill
plate warmer
hot table
microwave
salamander
percolator
SO -1
SO -n
N° date: 02/03
06 rev E
C D
MER_WE_DD3320
SUPPLY TO CONSUMER UNITS, RIGHT SIDE OF CORRIDOR
Guest room consumer unit Guest room consumer unit Guest room consumer unit E
in service duct on right side in service duct on right side in service duct on right side
of corridor. Serves 2 of corridor. Serves 2 of corridor. Serves 2
adjacent bedrooms. adjacent bedrooms. adjacent bedrooms.
Guest room consumer unit Guest room consumer unit Guest room consumer unit
in service duct on left side in service duct on left side in service duct on left side
of corridor. Serves 2 of corridor. Serves 2 of corridor. Serves 2
adjacent bedrooms. adjacent bedrooms. adjacent bedrooms.
A
Floor distribution board in room
provided for this purpose
to l.h. to r.h. to l.h. to r.h. to l.h. to r.h.
bedroom bedroom bedroom bedroom bedroom bedroom
MERCURE
bedroom consumer units, right side of corridor
"normal" bus bars
MAINS INTAKE
bedroom consumer units, left side of corridor Do not put more than 6 consumer units on
the same outlet.
GUEST ROOM
corridor lighting, circuit 1 2: the diagram shown here assumes the
distribution boards,
existence of an emergency generator.
consumer units
lighting to non-public areas This unit shall only be installed if it is a
legal obligation. If there is no generator, date: 02/03
No.
30 mA corridor SO this 2nd circuit must not be omitted: it is
essential to have 2 distinct lighting circuits 07 rev F
30 mA in the corridors.
SO in non-public rooms, linen room If there is no generator, some of the MER_WE_DD3320
riser from the mains intake
6 hours
2
BUS BARS
"NORMAL"
corridor lighting, circuit 2
emergency lighting
in next bedroom 5 transparent cover. It shall be wired from the bottom with stuffing glands.
lighting Comment: The supply to all the light
It shall be located in the service duct and shall feed 2 adjacent rooms. The principle
16 A points from the same outlet simplifies
SO for a BR shall be as follows:
6 the connection of the general switch for
- "3" : a RCD (30 mA) shall protect 2 fused outlets (lighting and SOs)
the bedroom: it is in series with the
10 A - "4": on the lighting circuit there shall be all the light points, including the SO for
fan-coil unit lighting circuit breaker "4" and therefore
the desk lamp and the anti-mist heater for the mirror turns off all the lighting in the bedroom.
30 mA - "5": on the SO circuit there shall be all the other supplies, including the hair dryer
10 A
lighting - "6": the fan-coil unit shall be on a specific fused outlet
left guestroom
L M N V O 13 U 15
NOV_WE_DF1100
standard bedroom NOVOSPACE via
Q
via
and the sets of diagrams 4 C, M
5 11 5 P 6 7 8
NOV_WE_AD1101
Q 9
R 14
V 10 F
T 12
F 1 E D
K
via
T
via B, L
3 C, M
C B A
Comments: The general switch J
does not turn off the following:
- the SOs for guests' use (he may I H G W 16 2
leave a telephone, portable via
B, L
computer, etc. on charge)
- the mini-bar TV
- the TV
- the fan-coil unit
MERCURE
ELECTRICITY
external lighting
(principles)
DESCRIPTION COMMENT
MER_WE_DD3320
comes from Mains Intake A: Contactor controlled from the panel in reception with 3 position button:
Off - On Automatic. In this case the contactor is closed by the action of a
B SO photo cell and a timer. These 2 units are wired in series.
B: 30 mA RCD. The SO shall be provided in the car park for use by
coaches.
, canopy lighting
All the contactors shall be controlled with illuminated push buttons
, menu holder
mounted on a panel in the reception back office. NOTE: this panel may be
an integral part of the Mains Intake. The number of outlets shall be
A adapted to suit actual requirements. Each neon sign shall be fitted with a
statutory fireman's switch.
,
, car park lighting
, floodlighting 1
, floodlighting 2
, garden lighting
, sign 1
sign n
> 50 cm
C DETAIL OF THE EARTHING BAR "D" N° date: 02/03
LOCATION : TRANSFORMER STATION
11 rev D
F
MER_WE_DD3320
1
NOTE: All underground connections, connections to the slab reinforcement, etc. shall be
made using thermit welding. Minimum depth of cover = 60 cm.
> 50 cm
"goose foot" ground
rod