Make Your Settings Only Into White Boxes Corresponding To Desired Standard Curve!
Make Your Settings Only Into White Boxes Corresponding To Desired Standard Curve!
1. Make your settings only into white boxes corresponding to desired standard curve!
IEC Curve A
SETTINGS: INJECTED: Time to Operate Time to Reset SETTINGS:
PKP TDM Multple of PKP PKP
0.42 10 16.7 18.32 seconds 0.06 seconds 1
IEC Curve B
SETTINGS: INJECTED: Time to Operate Time to Reset
PKP TDM Multple of PKP SETTINGS:
0.1 0.09 1.69 0.08 seconds 0.01 seconds PKP
1
IEC Curve C
SETTINGS: INJECTED: Time to Operate Time to Reset
PKP TDM Multple of PKP
0.015 1 0.02 102.86 seconds 74.83 seconds SETTINGS:
PKP
IEC Short Inverse 1
SETTINGS: INJECTED: Time to Operate Time to Reset
PKP TDM Multple of PKP
0.015 1 0.02 4.32 seconds 0.64 seconds
A
IAC Long Inverse 0.243
SETTINGS: INJECTED: Time to Operate Time to Reset
PKP TDM
1 2 5 6.67 seconds 0.02 seconds
I/Ipkp =
IAC Inverse
SETTINGS: INJECTED: Time to Operate Time to Reset
TDM Multple of PKP
1 0.5 -14.52 seconds -1.32 seconds
I2t Curves
SETTINGS: INJECTED: Time to Operate Time to Reset
TDM Multple of PKP
1 0.5 400.00 seconds 25.00 seconds
FlexCurve A or B
SETTINGS: INJECTED: Time to Operate Time to Reset
TDM Multple of PKP to be calculated to be calculated
1 1.5 seconds seconds
B P Q K
0 0.04 1 0
D= 2
T= 7.3088265642