0% found this document useful (0 votes)
176 views4 pages

APPENDIXE - 1 STR-1386-tests PDF

The document outlines the required tests for switchgear and its components according to various IEC standards. It lists over 20 different type and routine tests for switchgear, circuit breakers, disconnectors, and earthing switches. The tests include power frequency withstand voltage tests, lightning impulse withstand voltage tests, temperature rise tests, short-time withstand current tests, mechanical operation tests, and dielectric tests to verify components meet standards. It provides the test designation, applicable standard, subclause, and required test values for each test.

Uploaded by

hansamv
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
176 views4 pages

APPENDIXE - 1 STR-1386-tests PDF

The document outlines the required tests for switchgear and its components according to various IEC standards. It lists over 20 different type and routine tests for switchgear, circuit breakers, disconnectors, and earthing switches. The tests include power frequency withstand voltage tests, lightning impulse withstand voltage tests, temperature rise tests, short-time withstand current tests, mechanical operation tests, and dielectric tests to verify components meet standards. It provides the test designation, applicable standard, subclause, and required test values for each test.

Uploaded by

hansamv
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

THE ISRAEL ELECTRIC CORPORATION LTD

ENGINEERING DIVISION SPEC: STR-1386


SUBSTATION PLANNING SECTOR Appendix № 1

REQUIRED TESTS FOR SWITCHGEAR AND IT'S


COMPONENTS

№ Test denomination Standard Sub Value


clause
1. SWITCHGEAR
1.1. Type tests IEC 62271-200 Clause 6
1.1.1. Power frequency withstand voltage IEC 62271-200 6.2.6
test according to ……………………..
Value of test voltage-common value
(kV r.m.s./min) ……………………… 50/1

1.1.2. Lightning impulse withstand voltage IEC 62271-200 6.2.6


test according to ……………………..
Value of test voltage-common value
(kV peak) ……………………………. 125

1.1.3. Power frequency withstand voltage IEC 62271-200 6.2.10


test on auxiliary and control circuits
according to ………………………….
Value of test voltage (kV r.m.s./min): 2/1

1.1.4. Measurement of the resistance of IEC 62271-200 6.4


the main circuit according to ……….

1.1.5. Temperature rise tests (contacts, IEC 62271-200 6.5


terminals, auxiliary and control
equipment etc.) ……………………..

1.1.6. Short-time withstand current test …. IEC 62271-200 6.6


Value of test current (kA r.m.s./sec) 1.5/5

1.1.7. Verification of the IP coding ……… IEC 62271-200 6.7.1

1.1.8. Tightness test ……………………… IEC 62271-200 6.8

Page 1 of 4
THE ISRAEL ELECTRIC CORPORATION LTD
ENGINEERING DIVISION SPEC: STR-1386
SUBSTATION PLANNING SECTOR Appendix № 1

1. REQUIRED TESTS FOR SWITCHGEAR (cont.)

№ Test denomination Standard Sub Value


clause

1.1.9. Electromagnetic compatibility IEC 62271-200 6.9


(EMC) test …………………………

1.1.10 Verification of making and breaking IEC 62271-200 6.101


capacities …………………………

1.1.11 Mechanical operation test ……… IEC 62271-200 6.102

1.2. Routine tests IEC 62271-200 Clause 7


1.2.1. Dielectric test on the main circuit IEC 62271-200 7.1
according to ………………………..
Value of test voltage: 50/1
(kV r.m.s./min) …………………….

1.2.2. Tests
. on auxiliary and control IEC 62271-200 7.2
circuits
2 according to ………………

1.2.3. Tightness test ……………………… IEC 60694 7.4

1.2.4. Design and visual checks ………… IEC 62271-200 7.5

1.2.5 Mechanical operation test ……….. IEC 62271-200 7.102

1.3 Special tests


1.3.1 Seismic qualification dynamic IEEE Std Moderate
analysis ……………………………. 693-2005 Level

Page 2 of 4
THE ISRAEL ELECTRIC CORPORATION LTD
ENGINEERING DIVISION SPEC: STR-1386
SUBSTATION PLANNING SECTOR Appendix № 1
2. REQUIRED TESTS FOR CIRCUIT BREAKER

№ Test denomination Standard Sub Value


clause
2 CIRCUIT BREAKER
2.1. Type tests IEC 62271-100 Table 7

2.1.1. Dielectric tests as follows: IEC 62271-100 6.2


a. Power frequency voltage test ……. IEC 62271-100 6.2.6.1

b. Lightning impulse voltage test ……. IEC 62271-100 6.2.6.2

2.1.2. Measurement
. of the resistance of the IEC 62271-100 6.4
main2 circuit …………………………….
2.1.3. Temperature rise tests ………………. IEC 62271-100 6.5
2.1.4. Short-time withstand current and peak IEC 62271-100 6.6
withstand current test ………………..
2.1.5. Additional tests on auxiliary and IEC 62271-100 6.10
control circuits …………………………
2.1.6. Mechanical operation test at ambient IEC 62271-100 6.101.2
air temperature ………………………. class M2
2.1.7. Short circuit current making and IEC 62271-100 6.102
breaking test ………………………… 6.106

2.2. Routine tests IEC 62271-100 7

2.2.1. Dielectric test on main circuit IEC 62271-100 7.1

2.2.2. Tests on auxiliary and control circuits IEC 62271-100 7.2

2.2.3. Measurement of the resistance of the IEC 62271-100 7.3


main circuit

2.2.4. Design and visual checks IEC 62271-100 7.5

2.2.5. Mechanical operating tests IEC 62271-100 7.101

Page 3 of 4
THE ISRAEL ELECTRIC CORPORATION LTD
ENGINEERING DIVISION SPEC: STR-1386
SUBSTATION PLANNING SECTOR Appendix № 1

3. REQUIRED TESTS FOR DISCONNECTORS AND


EARTHING SWITCHES

№ Test denomination Standard Sub Value


clause
3 DISCONNECTORS AND EARTHING SWITCHES
3.1. Type tests IEC 62271-102 Clause 6
3.1.1. Dielectric tests IEC 62271-102 6.2

3.1.2. Measurement of the resistance of the IEC 62271-102 6.4


main circuit

3.1.3. Temperature rise tests (contacts, IEC 62271-102 6.5


terminals, auxiliary and control
equipment etc.)

3.1.4. Short-time withstand current and peak IEC 62271-102 6.6


withstand current test

3.1.5. Test to prove the short-circuit making IEC 62271-102 6.101


performance of earthing switch class E2

3.1.6. Mechanical operation test at ambient IEC 62271-102 6.102


air temperature class M2

3.2. Routine tests IEC 62271-102 Clause 7


3.2.1. Dielectric test on the main circuit IEC 62271-102 7.1

3.2.2. Measurement of the resistance of the IEC 62271-102 7.3


main circuit

3.2.3. Mechanical operating test IEC 62271-102 7.101

Page 4 of 4