Series of Pressure Relief Device For Transformers User's Manual
Series of Pressure Relief Device For Transformers User's Manual
Series of Pressure Relief Device For Transformers User's Manual
!1
Application
●The products comprise of directional oil-gushing to prevents contaminated from the transformer oil, and
protect environment.
●The products that coupled with electrical alarm signal realize remote control.
●The products are apt for electrical equipments such as gas or liquid insulate transformer, instrument
transformers, on-load tap-changer, high voltage switch etc.
●Once there’s something wrong in such electrical equipments, valve open and relieve the pressure to avoid
oil basin from metamorphose and blowout.
●With the pressure reduced the valve automatically closed to prevent water and impurity got in from
outside.
Working conditions and install mode Model Specification
● Environment temperature
- 30℃~40℃.
● Installation site
a)Install in the oil basin
to cover
b)Install in the oil basin
to sidepiece upside
c)Install in lift pedestal
What the letter mean:
K: electrical alarm signal;J: machinery alarm signal; B: with locking devices;
TH: Humid Tropics ;TA:Dry Tropics ;T: Humid and Dry Tropics
For example 1: YSF8-55/130KJBTH
Namely, fuel injection caliber Φ130 mm, opening pressure of 55 kPa, with machinery, electrical alarm
signal, humid tropics applicable, with locking devices, 8th design , model II registered mark of the
pressure release valve.
For example 2: YSF8-55/80KJBTH
Namely, fuel injection caliber Φ80 mm, opening pressure of 55 kPa, with machinery, electrical alarm
signal, with locking devices, humid tropics applicable, the 8th design directional injection pressure release
valve.
The product specification and basic parameter
Effective caliber of oil- Opening Tolerance of Closing Sealed
gushing pressure Opening pressure Pressure Pressure
(mm) (k Pa) (k Pa) (k Pa) (k Pa)
35 19 21
55 29.5 33
Φ50
Φ80 70 ±5 37.5 42
Φ130
85 45.5 51
135 72 80
Selection of pressure relief device
● selection of effective caliber
Total weight of oil(t) ∠1.5~4.5 4.5~11.5 11.5~23
Effective caliber of oil-
Φ50 Φ80 Φ130
gushing valve (mm)
!2
Attention: When total oil weight more than 23 tons,
The quantity of release valve that chooses should be:
Total oil weight(tons) /23=Φ130 calibers of pressure release valve quantity(decimal fraction up to integer)
● selection of opening pressure
a)The opening pressure of pressure release valve should be equal to or slightly less than 0.6~0.7 safe
pressure in oil tank;
b)Use product specification and basic parameter to assure the opening pressure.
Configuration and installation dimensions
YSF9-/80 and 130 series pressures release valve figure and configuration chart.
φ50 φ74 φ83.5 φ130 φ150 φ56 φ88 178 70 84.5 M12×4 M6×4
φ80 φ122 φ133 φ170 φ200 φ100 φ144 210 104 140 M12×6 M10×6
φ130 φ172 φ181 φ235 φ260 φ148 φ200 253 134 179.5 M16×6 M10×6
!3
Outletbox
terminal fig basic fig of
electric switch
Basic
parameter of electric
switch
Working current
electrical
Wo r k i n g
source
voltage
sort Resistance Reactance(A)
Alternating
5(A) 3(cosΦ=0.4)
current (AC)
220(V)
Direct current.
0.3(A) 0.05(T=7ms)
(DC)
Install 、Using、Debugging
● Install: Pressure releasing valve and tank connect with the stud bolt
Attention:
1)The bottom of pressure releasing valve assemble to seal well;
2)When connect the pressure releasing valve and tank, tighten the bolts equality, avoid that valve
pedestal rupture.
●Using: With latching that must be removed before equipment circulate, insure the normal work of the
pressure releases valve.
●Debugging: Electric alarm switch,should manual debug deferent signal of switch whether exactitude、
sensitive,before the equipments circulate .
Method :1)Measure export signal of switch when pressure releasing valve actionless by multimeter to
see whether in accordance with the signal mark of the switch.
Viz.: (a) “Common” towards “Normal open” normal open.
(b) “Common” towards “Normal closed” normal closed.
2)Experiment of simulate releasing valve’s action,checkout whether inching switch accurate export
behavioural signal.
Method: Raise the small red hat of the pressure releasing valve,then releasing valve turn on, check
!4
whether the switch measure of the electric signal change.
Viz.: (a) “Common” of switch towards “Normal open”: “Normal open” should turn to “Normal
closed”;
(b) “Common” of switch towards “Normal closed”: “Normal closed” should turn to “Normal open”;
(c) Examine the signal switch and control circuit connect whether right and good.
Attention: The small red hat must be replacement after test over, insure that the pressure releasing valve
normal working and warning.
Product malfunction analysis
malfunction
Reason Solution method
phenomena
c)Oil basin and valve have leaky Check oil basin and valve whether
place. pressurize good.
Crucial hint
●Latching should operate strictly according to caution requirement, insure that the pressure releasing valve
normal working.
●When install, accessory、 parts of the pressure releasing valve shouldn’t be arbitrium teardown.
●When equipment run, as if releasing valve turn on result in the instruction pole up, replace the instruction
pole by hand before find out reason, unchain warning alarm.
Maintenance and Inspection
!5
Make use of the power-off time during maintenance of the pressure releasing valve:
●If turn on action sensitive? If there is block or stop up should eliminate.
●If the sealing gaskets are aged or deformed or damaged?
●If accessory、 parts whether metamorphose or wear off?
●If the signal switch whether operate sensitive?
How to Make Order
●The customer should be appropriate prepare several pressure releasing valve to switchover during
maintenance.
●Product every examine and repair, after teardown should change new sealing element,the sealing after
teardown do not suitable continue to use.
●Please specify the model, opening pressure, caliber of oil-gushing, mode of signal, using environment,
quantity and switch down-lead length(If no indication, then no down-lead.)
Spare parts and maintenance are available, also special designs asked and manufactures.
!6