Contactor Finder

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

22 SERIES 22

Modular contactors 25 - 40 - 63 A SERIES

25 A modular contactor - 2 pole 22.32.0.xxx.1xx0 22.32.0.xxx.4xx0


• 17.5 mm wide
• NO contact gap ≥ 3 mm, double break
• Continuous duty for the coil and contacts
• AC/DC silent coil (with varistor protection)
• Protective separation (reinforced insulation)
between coil and contacts
• Mechanical and LED indicators as standard
• Auto-On-Off selector version available
• AgNi and AgSnO2 contact versions available
• Compliant with EN 61095: 2009
• Auxiliary contact module available,
quick-assembly with the main contactor
(1 NO + 1 NC and 2 NO versions) • AgNi contacts, specifically • AgSnO2 contacts, specifically
• For railway applications; materials compliant intended for resistive and intended for lamp loads and
with fire and smoke characteristics slightly inductive loads as for high inrush current loads
(EN 45545-2:2013) well as for motor loads
• 35 mm rail (EN 60715) mount
22.32…1xx0/22.32…4xx0
Screw terminal

2 NO 1 NO + 1 NC 2 NC
(x3x0) (x5x0) (x4x0)
For outline drawings see page 8
Contact specification
• Contact gap ≥ 3 mm for NO
Contact configuration 2 NO, 3 mm* (or 1 NO + 1 NC or 2 NC) contacts only;
Rated current/Maximum peak current A 25/80 25/120 NC contacts ≥ 1.5 mm
Rated voltage V AC 250/440 250/440
Rated load AC1 / AC-7a (per pole @ 250 V)  VA 6250 6250
Rated current AC3 / AC-7b A 10 10
Rated load AC15 (per pole @ 230 V) VA 1800 1800
Single-phase motor rating (230 V AC) kW 1 1
Rated load AC5a (per pole @ 250 V) A 15 15
Rated current AC-7c A — 10
Nominal lamp rating:
230 V incandescent/halogen W 800 2000
fluorescent tubes with
electronic ballast W 300 800
fluorescent tubes with
electromechanical ballast W 200 500
CFL W 100 200
230 V LED W 100 200
LV halogen or LED with
electronic ballast W 100 200
LV halogen or LED with
electromechanical ballast W 300 800
Breaking capacity DC1: 30/110/220 V A 25/5/1 25/5/1
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10)
Contact material AgNi AgSnO2
Coil specification
Nominal voltage (UN) V DC/AC (50/60 Hz) 12 - 24 - 48 - 60 - 120 - 230 12 - 24 - 48 - 60 - 120 - 230
Rated power AC/DC VA (50 Hz)/W 2/2.2 2/2.2
Operating range DC/AC (50/60 Hz) (0.8…1.1)UN (0.8…1.1)UN
Holding voltage DC/AC (50/60 Hz) 0.4 UN 0.4 UN
Must drop-out voltage DC/AC (50/60 Hz) 0.1 UN 0.1 UN L
Technical data
Mechanical life AC/DC cycles 2 · 106 2 · 106
Electrical life at rated load AC-7a cycles 70 · 103 30 · 103
Operate/release time  ms 30/20 30/20
XI-2016, www.findernet.com

Insulation between coil


and contacts (1.2/50 µs) kV 6 6
Ambient temperature range °C –20…+50 –20…+50
Protection category IP 20 IP 20
Approvals (according to type)

1
22 22 SERIES
SERIES Modular contactors 25 - 40 - 63 A

25 A modular contactor - 4 pole 22.34.0.xxx.1xx0 22.34.0.xxx.4xx0


• 35 mm wide
• NO contact gap ≥ 3 mm, double break
• Continuous duty for the coil and contacts
• AC/DC silent coil (with varistor protection)
• Protective separation (reinforced insulation)
between coil and contacts
• Mechanical and LED indicators as standard
• Auto-On-Off selector version available
• AgNi and AgSnO2 contact versions available
• Compliant with EN 61095: 2009
• Auxiliary contact module available,
quick-assembly with the main contactor
(1 NO + 1 NC and 2 NO versions) • AgNi contacts, specifically • AgSnO2 contacts, specifically
• For railway applications; materials compliant intended for resistive and intended for lamp loads and
with fire and smoke characteristics slightly inductive loads as well for high inrush current loads
(EN 45545-2:2013) as for motor loads
• 35 mm rail (EN 60715) mount
22.34…1xx0/22.34…4xx0
Screw terminal

4 NO 3 NO + 1 NC 2 NO + 2 NC
(x3x0) (x7x0) (x6x0)
For outline drawings see page 8
Contact specification • Contact gap ≥ 3 mm for NO
Contact configuration 4 NO, 3 mm* (or 3NO + 1NC or 2NO + 2NC) contacts only;
Rated current/Maximum peak current A 25/80 25/120 NC contacts ≥ 1.5 mm
Rated voltage V AC 250/440 250/440
Rated load AC1/AC-7a (per pole @ 250 V)  VA 6250 6250
Rated current AC3/AC-7b A 10 10
Rated load AC15 (per pole @ 230 V) VA 1800 1800
Three-phase motor rating (400 - 440 V AC) kW 4 4
Rated load AC5a (per pole @ 250 V) A 15 15
Rated current AC-7c A — 10
Nominal lamp rating:
230 V incandescent/halogen W 800 2000
fluorescent tubes with
electronic ballast W 300 800
fluorescent tubes with
electromechanical ballast W 200 500
CFL W 100 200
230 V LED W 100 200
LV halogen or LED with
electronic ballast W 100 200
LV halogen or LED with
electromechanical ballast W 300 800
Breaking capacity DC1: 30/110/220 V A 25/5/1 25/5/1
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10)
Contact material AgNi AgSnO2
Coil specification
Nominal voltage (UN) V DC/AC (50/60 Hz) 12 - 24 - 48 - 60 - 120 - 230 12 - 24 - 48 - 60 - 120 - 230
Rated power AC/DC VA (50 Hz)/W 2/2.2 2/2.2
Operating range DC/AC (50/60 Hz) (0.8…1.1)UN (0.8…1.1)UN
Holding voltage DC/AC (50/60 Hz) 0.4  UN 0.4 UN
L Must drop-out voltage DC/AC (50/60 Hz) 0.1 UN 0.1 UN
Technical data
Mechanical life AC/DC cycles 2 · 106 2 · 106
Electrical life at rated load AC-7a cycles 150 · 10 3
30 · 103
Operate/release time  ms 18/40 18/40
XI-2016, www.findernet.com

Insulation between coil


and contacts (1.2/50 µs) kV 6 6
Ambient temperature range °C –20…+50 –20…+50
Protection category IP 20 IP 20
Approvals (according to type)

2
22 SERIES 22
Modular contactors 25 - 40 - 63 A SERIES

40 - 63 A modular contactor - 4 pole 22.44.0.xxx.4xx0 22.64.0.xxx.4xx0


• NO and NC contact gap ≥ 3 mm, double break
• Continuous duty for the coil and contacts
• AC/DC silent coil (with varistor protection)
• Protective separation (reinforced insulation)
between coil and contacts
• Mechanical indicator as standard
• AgSnO2 contacts
• Compliant with EN 61095: 2009 and with
• EN 60947-4-1: 2009
• 35 mm rail (EN 60715) mount
• For high inrush current loads • Specifically intended:
22.44…/22.64… 176 A for high inrush current loads
Screw terminal • Contact material AgSnO2 240 A
• Contact material AgSnO2

4 NO 3 NO + 1 NC 2 NO + 2 NC
For outline drawings see page 8 (4310) (4710) (4610)
Contact specification
Contact configuration 4 NO, (or 3NO + 1NC or 2NO + 2NC) ≥ 3 mm
Rated current/Maximum peak current A 40/176 63/240
Rated voltage V AC 400/440 400/440
Rated load AC1 / AC-7a (per pole @ 400 V)  VA 16000 24000
Rated current AC3 / AC-7b (400 V) A 22 30
Rated load AC15 (per pole @ 230 V) VA — —
Three-phase motor rating (400 - 440 V AC) kW 11 15
Rated load AC5a (per pole @ 250 V) A 20 32
Rated current AC-7c A — —
Nominal lamp rating:
230 V incandescent/halogen W 4000 5000
fluorescent tubes with
electronic ballast W 1500 2000
fluorescent tubes with
electromechanical ballast W 1500 2000
CFL W 1000 1500
230 V LED W 1000 1500
LV halogen or LED with
electronic ballast W 1000 1500
LV halogen or LED with
electromechanical ballast W 1500 2000
Breaking capacity DC1: 30/110/220 V A 40/4/1.2 63/4/1.2
Minimum switching load mW (V/mA) 1000 (17/50) 1000 (17/50)
Contact material AgSnO2 AgSnO2
Coil specification
Nominal voltage (UN) V DC/AC (50/60 Hz) 12 - 24 - 110…120 (110 V DC) - 230…240 (220 V DC)
Rated power AC/DC VA (50 Hz)/W 5 5
Operating range DC/AC (50/60 Hz) (0.85…1.1)UN (0.85…1.1)UN
Holding voltage DC/AC (50/60 Hz) 0.85 UN 0.85 UN
Must drop-out voltage DC/AC (50/60 Hz) 0.2 UN 0.2 UN L
Technical data
Mechanical life AC/DC cycles 3 · 106 3 · 106
Electrical life at rated load AC-7a cycles 100 · 103 100 · 103
Operate/release time  ms 20/45 20/45
XI-2016, www.findernet.com

Insulation between coil


and contacts (1.2/50 µs) kV 6 6
Ambient temperature range °C –5…+55 –5…+55
Protection category IP 20 IP 20
Approvals (according to type)

3
22 22 SERIES
SERIES Modular contactors 25 - 40 - 63 A

Ordering information
Exemple: 22 series, modular contactor 25 A, 4 NO contacts, coil 230 V AC/DC, AgSnO2 contacts, Auto-On-Off selector + mechanical indicator + LED.
A B C D

2 2 . 3 4 . 0 . 2 3 0 . 4 3 4 0
Series D: Special versions
Type 0 = Standard
3 = 25 A modular contactor range C: Options
4 = 40 A modular contactor range 1 = Mechanical indicator
6 = 63 A modular contactor range 2 = Mechanical indicator + LED
Number of contacts 4 = Auto-On-Off selector + mechanical
2 = 2 pole indicator + LED
4 = 4 pole B: Contact circuit
Coil version 3 = All NO contacts
0 = AC (50/60 Hz)/DC 4 = All NC contacts (22.32 only)
5 = 1 NO + 1 NC
Coil rated voltage 6 = 2 NO + 2 NC
See coil specifications 7 = 3 NO + 1 NC
A: Contact material
1 = AgNi
4 = AgSnO2
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type Coil version A B C D
22.32 AC/DC 1-4 3-4-5 2-4 0
22.34 AC/DC 1-4 3-6-7 2-4 0
22.44 AC/DC 4 3-6-7 1 0
22.64 AC/DC 4 3-6-7 1 0

Options
Auto-On-Off selector + mechanical indicator + LED (xx40 option)
Type 22.32 / 22.34 Options
1 Selector
The three-position manual selector has the following
functions:
1
• ON position - the contacts are latched in the operated
state (NO contacts - closed and NC contacts - open), the
mechanical indicator is visible in its window, the LED is
not illuminated.
3 • AUTO position - the state of contacts, mechanical
2 indicator and LED follow the coil supply voltage.
• OFF position - even if terminals A1 - A2 are supplied
with rated voltage, the coil is not energized, and so
the contacts remain in the non-operated state, the
mechanical indicator is not visible and the LED is not
illuminated.
2 LED
3 Mechanical indicator

Type 22.44 / 22.64 Options


Mechanical indicator

L
1
XI-2016, www.findernet.com

4
22 SERIES 22
Modular contactors 25 - 40 - 63 A SERIES

Technical data
Insulation 22.32/22.34 22.44/22.64
Rated insulation voltage  V AC 250 440 440
Pollution degree 3* 2 3
Insulation between coil and contact set
Type of insulation Reinforced Reinforced
Overvoltage category III III
Rated impulse voltage kV (1.2/50 µs) 6 4
Dielectric strength V AC 4000 2000
Insulation between adjacent contacts
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50 µs) 4 4
Dielectric strength V AC 2500 2000
Insulation between open contacts NO contact NC contact NO/NC contacts
Contact gap mm 3 1.5 3
Overvoltage category III II III
Rated impulse voltage kV (1.2/50 µs) 4 2.5 4
Dielectric strength V AC/kV (1.2/50 µs) 2500/4 2000/3 2000/3
* Only for versions without Auto-On-Off selector. For versions with Auto-On-Off selector pollution degree 2 applies.
Conducted disturbance immunity Reference standard
Fast transients (burst 5/50 ns, 5 kHz) at coil terminals EN 61000-4-4 Level 4 (4 kV) Level 2 (2 kV)
Voltage pulses (surge 1.2/50 µs) at supply terminals (differential mode) EN 61000-4-5 Level 4 (4 kV) Level 2 (2 kV)
Short circuit protection 22.32 / 22.34 22.44 22.64
Rated conditional short circuit current kA 3 3 3
Back-up fuse A 32 (gL/gG type) 63 80
Terminals Solid and stranded cable
22.32 / 22.34 22.44 / 22.64
2
Max. wire size – contact terminals mm 1 x 6 / 2 x 4 1 x 25 (solid) - 1 x 16 (stranded)
AWG 1 x 10 / 2 x 12 1 x 4 (solid) - 1 x 6 (stranded)
Max. wire size – coil terminals mm 2
1 x 4 / 2 x 2.5 1 x 2.5
AWG 1 x 12 / 2 x 14 1 x 14
Min. wire size – contact and coil terminals mm 2
1 x 0.2 1 x 1 (coil) - 1 x 1.5 (contacts)
AWG 1 x 24 1 x 18 (coil) - 1 x 16 (contacts)
1.2 (coil terminals) -
Screw torque Nm 0.8
3.5 (contact terminals)
Wire strip length  mm 9 10
Other data 22.32 22.34 22.44 22.64
Vibration resistance (10…150)Hz g 4 4 3 3
Shock resistance g 10 10 15 15
Power lost to the environment without contact current W 2 2 5 5
with rated current W 4.8 6.3 17 37
NOTE
22.32/22.34: It is suggested an air gap of 9 mm between adjacent relays for installations and working conditions close to the limit (that is, ambient
temperature > 40 °C, coil operated for a prolonged period of time, all contacts loaded with current > 20 A). L
22.44/22.64: The maximum ambient temperature with 3 adjacent contactors is + 40 °C; when more than 3 contactors are installed, it is necessary an air
gap of 9 mm.
With 2 adjacent contactors the maximum ambient temperature is + 55 °C; when more than 2 contactors are installed, it is necessary an air
gap of 9 mm.
XI-2016, www.findernet.com

5
22 22 SERIES
SERIES Modular contactors 25 - 40 - 63 A

Contact specification
Ratings and utilization categories according to EN 61095: 2009
Type Utilization category
AC-7a AC-7b AC-7c
Rated current Rated electrical Rated current Rated electrical Rated current Rated electrical
(A) life (Cycles) (A) life (Cycles) (A) life (Cycles)
70 · 103 (NO)
22.32….1xx0 (AgNi contacts) 25 10 30 · 103 — —
30 · 103 (NC)
22.32….4xx0 (AgSnO2 contacts) 25 30 · 103 10 30 · 103 10 30 · 103
150 · 103 (NO)
22.34….1xx0 (AgNi contacts) 25 10 30 · 103 — —
100 · 103 (NC)
22.34….4xx0 (AgSnO2 contacts) 25 30 · 103 10 30 · 103 10 30 · 103
22.44….4xx0 40 100 · 103 22 150 · 103 — —
22.64….4xx0 63 100 · 103 30 150 · 103 — —
Utilization category: AC-7a = Slightly inductive loads (cos ϕ = 0.8)
AC-7b = Motor loads; (cos ϕ = 0.45, Imaking = 6x Ibreaking)
AC-7c = Compensated electric discharge lamps (cos ϕ = 0.9, C = 10 mF/A)
H 22 - Maximum DC1 breaking capacity - Type 22.32/22.34 H 22 - Maximum DC1 breaking capacity - Type 22.44/22.64
DC breaking current (A)

DC breaking current (A)

type 22.64

type 22.44

DC voltage (V) DC voltage (V)

• When switching a resistive load (DC1) having voltage and current values under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Coil specifications
AC/DC version data (type 22.32) AC/DC version data (type 22.34)
Nominal Coil Operating range Rated coil Nominal Coil Operating range Rated coil
voltage code consumption voltage code consumption
UN Umin Umax IN at UN (AC) UN Umin Umax IN at UN (AC)
V V V mA V V V mA
12 0.012 9.6 13.2 165 12 0.012 9.6 13.2 165
24 0.024 19.2 26.4 83 24 0.024 19.2 26.4 83
48 0.048 38.4 52.8 42 48 0.048 38.4 52.8 42
60 0.060 48 66 33 60 0.060 48 66 33
120 (110…125) 0.120 88 138 16.5 120 (110…125) 0.120 88 138 16.5
230 184 (AC) 264 (AC) 230 184 (AC) 264 (AC)
(230…240 AC) 0.230 8.7 (230…240 AC) 0.230 8.7
(220 DC)
176 (DC) 242 (DC) (220 DC)
176 (DC) 242 (DC)

AC/DC version data (type 22.44 / 22.64) R 22 - Coil operating range v ambient temperature
Nominal Coil Operating range Rated coil
voltage code consumption
UN Umin Umax IN at UN (AC)
L V V V mA
12 0.012 10.2 13.2 417
24 0.024 20.4 26.4 208
120
0.120 102 138 41
(110…125)
230
XI-2016, www.findernet.com

264 (AC)
(230…240 AC) 0.230 196 21
242 (DC)
(220 DC)

1 - Max. permitted coil voltage.


2 - Min. pick-up voltage with coil at ambient temperature.

6
22 SERIES 22
Modular contactors 25 - 40 - 63 A SERIES

Wiring diagrams
Line and neutral switched Line only switched

Type 22.32 Type 22.34 Type 22.34

Line and neutral switched Line only switched

Type 22.44/22.64 Type 22.44/22.64

L
XI-2016, www.findernet.com

7
22 22 SERIES
SERIES Modular contactors 25 - 40 - 63 A

Outline drawings
Type 22.32 Type 22.32 + 022.33/022.35
Screw terminal Screw terminal

Type 22.34 Type 22.34 + 022.33/022.35


Screw terminal Screw terminal

Type 22.44/22.64 Type 22.44/22.64 + 022.63/022.65


Screw terminal Screw terminal

Type 022.33/022.35 Type 022.63/022.65


Screw terminal Screw terminal

L
XI-2016, www.findernet.com

8
22 SERIES 22
Modular contactors 25 - 40 - 63 A SERIES

Auxiliary modules 022.33 022.35 022.63 022.65

Mechanically linked contacts according


to Annex L of EN 60947-5-1

33

34

Type of contactor Type 22.32 Type 22.44022.63


Type 22.34 Type 22.64
Contact specification
Contact configuration 2 NO 1 NO + 1 NC 2 NO 1 NO + 1 NC
Conventional free air thermal current IthA 6 6
Rated power AC15 (230 V) VA 700 700
Electrical life at rated load cycles 30 · 103 30 · 103
Minimum switching load  mW (V/mA) 1000 (10/10) 1000 (10/10)
Contact material AgNi AgNi
Short circuit protection
Rated conditional short circuit current kA 1 1
Back-up fuse A 6 (gL/gG type) 6 (gL/gG type)
Terminals Solid and stranded cable Solid and stranded cable
Max. wire size mm2 1 x 4 / 2 x 2.5 1 x 2.5
AWG 1 x 12 / 2 x 14 1 x 14
Min. wire size mm2 1 x 0.2 1 x 1
AWG 1 x 24 1 x 18
Screw torque Nm 0.8 0.6
Wire strip length mm 9 9
Power lost to the environment
without contact current W — —
with rated current W 0.5 0.5
Approvals (according to type)
NOTE: It is not possible to assembly the auxiliary module on 22.32.0.xxx.x4x0 (2 NC versions).

22.32 + 022.33/022.35 22.44 + 022.63/022.65


L
XI-2016, www.findernet.com

22.34 + 022.33/022.35 22.64 + 022.63/022.65

9
22 22 SERIES
SERIES Modular contactors 25 - 40 - 63 A

Accessories
Adaptor for panel mounting (for 22.32 type), plastic, 17.5 mm wide 020.01

020.01

Adaptor for panel mounting (for 22.34 type), plastic, 35 mm wide 011.01

011.01

Sheet of marker tags (CEMBRE'S Thermal transfer printers) for all relays
060.48
(48 tags), 6 x 12 mm

060.48

Identification tag, plastic, 1 tag, 17x25.5 mm 019.01

019.01

Separator for rail mounting, plastic, 9 mm wide 022.09

022.09

PEAN
8-way jumper link for type 22.32, 17.5 mm wide 022.18 (blue)
O
Rated values 10 A - 250 V
EUR

T
N
T E
EUR

P A O
PEAN

022.18

PEAN
6-way jumper link for type 22.34, 35 mm wide 022.26 (blue)
O
Rated values 10 A - 250 V
EUR

T
N
T E
EUR

P A

L
O
PEAN

022.26