ABB DCS Function Code 15

The summer (2-input) function performs a weighted sum of two inputs according to the equation: Output = (S1 x S3) + (S2 x S4). It can be used to perform proportional, bias, or difference functions by choosing the proper gains and inputs. It can also scale non-zero based signals by referencing the second input to a constant value. For example, an input range of 200-500 could be scaled to an output of 10-110 by setting S3 to 0.333, S2 to -1, and S4 to 56.667.

Uploaded by

rabi gurung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
277 views2 pages

ABB DCS Function Code 15

The summer (2-input) function performs a weighted sum of two inputs according to the equation: Output = (S1 x S3) + (S2 x S4). It can be used to perform proportional, bias, or difference functions by choosing the proper gains and inputs. It can also scale non-zero based signals by referencing the second input to a constant value. For example, an input range of 200-500 could be scaled to an output of 10-110 by setting S3 to 0.333, S2 to -1, and S4 to 56.667.

Uploaded by

rabi gurung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

15.

Summer (2-Input)

15. Summer (2-Input)


This function performs a weighted sum of two inputs. By choosing the proper gains and inputs this block can perform
proportional, bias or difference functions. It also can be used as a scaler for non-zero based signals by referencing the
second input to a constant block.
The following equation describes the operation of this function:

Output  (<S1> S3)  (<S2>  S4)

Outputs
S1
 (K)
(1 5 )
S2
N
Blk Type Description

N R Output value is the weighted algebraic sum of the two


input signals

Specifications

Spec Tune Default Type Range Description

S1 N 5 I Note 1 Block address of first input

S2 N 5 I Note 1 Block address of second input

S3 Y 1.000 R Full Gain parameter of first input

S4 Y 1.000 R Full Gain parameter of second input


NOTES:
1. Maximum values are: 9,998 for the BRC-100/200/300, IMMFP11/12
31,998 for the HC800, BRC-400/410, HPG800 and HAC

Applications
Besides performing proportional, bias or difference functions, this code also can be used for scaling. By referencing the
second input to a constant block or to a manual set constant block (function code 2), a non-zero based signal can be
scaled.
The example in Figure 15-1 shows how to scale an input with a range of 200 to 500 engineering units to give an output of
ten to 110 engineering units.

The S3 constant is calculated using the equation:

S = Output Span-
--------------------------------
<S1> Span
– 10 -
= 110
-----------------------
500 – 200
= 0.333

Fixed block four connects to S2 to give it a constant value of -1.0. Specification S2 could be set to any fixed value by using
function code 2, but this approach requires more memory than using a fixed block. Since <S2> and S4 are both constants
in this example, they can be considered as a unit. The following equation determines the value for the product of <S2> and
S4:

<S2> S4 = Output min. – (<S1> min. S3 min.)


In this example then:

<S2>  S4 = 10 - [(200)(0.333)] = -56.667

2VAA000844R0001 Vol. 1 15-1


15. Summer (2-Input)

<S2> and S4 could then be set to any allowable value that will give the product of -56.667. In our example, <S2> is set to
-1.000 so S4 is set to 56.667.

INPUT
200-500 EU

-1.000
S1 DESIRED
(15)
FIXED
BLOCK
S2  (K) 220
OUTPUT
10-110 EU
4
S3 = 0.333
S4 = 56.667
T01619A

Figure 15-1 Scaler

15-2 2VAA000844R0001 Vol. 1