Invertek Drives Optidrive E2 Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

Optidrive ODE-2 User Guide Revision 3.

30

User Guide

1
Introduction
IP20 & IP66 (NEMA 4X)
AC Variable Speed Drive
0.37 – 11kW (0.5 – 15HP)
110 – 480V

Installation and Operating Instructions

www.invertekdrives.com
1
Optidrive ODE-2 User Guide Revision 3.30

Easy Start Up Guide


1
Introduction

Supply Voltage
AC Supply Voltage - 110 – 115, 200 – 240, 400 – 480 VAC + / - 10%
(50 / 60 Hz) - 1 or 3 Phase
Check the drive rating information on page 26
L1 L2 L3
Earth L N

Fuses or MCB
Fuses or MCB - Fuse Ratings given on page 26
- Recommended cable sizes shown on page 26
Always follow local and national codes of practice

Mechanical Mounting
- Information can be found on page 10

Keypad operation can be found on page 16

Control Terminals
Based on the factory default (out of box) settings
- Connect a Start / Stop switch between terminals 1 & 2
- Close the switch to Start (Enable) the drive
- Open the switch to Stop (Disable) the drive

- Connect a potentiometer (5kΩ minimum) between


terminals 5, 6 and 7 as shown below to vary the speed
from minimum (0Hz) to maximum (50 / 60 Hz)

Motor Cable Information


- Check the rating information on page 26 for sizing
information
- For EMC compliance, use a shielded type cable

Motor Connections
- Check for Star or Delta connection according to the motor
nameplate and voltage rating (See page 13)
Motor Nameplate Details
- Enter the motor rated voltage in P-07
- Enter the motor rated current in P-08
- Enter the motor rated frequency in P-09
www.invertekdrives.com
2
Optidrive ODE-2 User Guide Revision 3.30

1
Easy Start Up Guide

Introduction
Mechanical Mounting
- Information can be found
on page 10

Control Terminals
Based on the factory default (out of box)
settings
- Connect a Start / Stop switch
between terminals 1 & 2
- Close the switch to Start (Enable)
the drive
- Open the switch to Stop (Disable)
the drive Keypad operation can be found
on page 16
- Connect a potentiometer (5kΩ
minimum) between terminals 5, 6
and 7 as shown below to vary the
speed from minimum (0Hz) to
maximum (50 / 60 Hz)

Fuses or MCB Motor Cable Information


- Fuse Ratings given on page 26 - Check the rating
- Recommended cable sizes shown information on page 26 for
on page 26 sizing information
Always follow local and national codes Fuses - For EMC compliance, use a
of practice or MCB shielded type cable

Earth L N
L1 L2 L3

AC Supply Voltage
(50 / 60 Hz) Motor Connections
- Check for Star or Delta
connection according to the
Supply Voltage motor nameplate and voltage
- 110 – 115, 200 – 240, 400 – 480 rating (See page 13)
VAC + / - 10% Motor Nameplate Details
- 1 or 3 Phase - Enter the motor rated voltage
Check the drive rating information on in P-07
page 26 - Enter the motor rated current
in P-08
- Enter the motor rated
frequency in P-09

www.invertekdrives.com
3
1 Optidrive ODE-2 User Guide Revision 3.30

Easy Start Up Guide


Introduction

Local Speed Potentiometer


The local speed potentiometer Mechanical Mounting
will adjust the output frequency - Information can be found
from minimum (Parameter P-02, on page 10
default setting = 0Hz) to
maximum (Parameter P-01,
default setting = 50 / 60 Hz)

Run Reverse / Off / Run


Forward Switch
With the factory parameter
settings, this switch allows the
Keypad operation can be found
drive to be started in the forward
on page 16
and reverse operating directions.
Alternative switch functions can
be programmed, such as Local /
Remote, Hand / Auto, see page
15

Mains Disconnect / Isolator

Motor Cable Information


- Check the rating
information on page 26 for
Fuses or MCB sizing information
- Fuse Ratings given on page - For EMC compliance, use a
26 shielded type cable
- Recommended cable sizes Fuses
shown on page 26 or MCB
Always follow local and national
codes of practice

Earth L N
L1 L2 L3

AC Supply Voltage
(50 / 60 Hz) Motor Connections
- Check for Star or Delta
connection according to
the motor nameplate and
Supply Voltage voltage rating (See page
- 110 – 115, 200 – 240, 400 – 480 13)
VAC + / - 10% Motor Nameplate Details
- 1 or 3 Phase - Enter the motor rated
Check the drive rating information on voltage in P-07
page 26 - Enter the motor rated
current in P-08
- Enter the motor rated
frequency in P-09
www.invertekdrives.com
4
Optidrive ODE-2 User Guide Revision 3.30
Declaration of Conformity

1
Invertek Drives Ltd hereby states that the Optidrive ODE-2 product range conforms to the relevant safety provisions of the Low Voltage
Directive 2006/95/EC and the EMC Directive 2004/108/EC and has been designed and manufactured in accordance with the following

Introduction
harmonised European standards:

EN 61800-5-1: 2003 Adjustable speed electrical power drive systems. Safety requirements. Electrical, thermal and energy.
nd
EN 61800-3 2 Ed: 2004 Adjustable speed electrical power drive systems. EMC requirements and specific test methods

EN 55011: 2007 Limits and Methods of measurement of radio disturbance characteristics of industrial, scientific and
medical (ISM) radio-frequency equipment (EMC)
EN60529 : 1992 Specifications for degrees of protection provided by enclosures

Electromagnetic Compatibility
All Optidrives are designed with high standards of EMC in mind. All versions suitable for operation on Single Phase 230 volt and Three Phase 400
volt supplies and intended for use within the European Union are fitted with an internal EMC filter. This EMC filter is designed to reduce the
conducted emissions back into the supply via the power cables for compliance with the above harmonised European standards.
It is the responsibility of the installer to ensure that the equipment or system into which the product is incorporated complies with the EMC
legislation of the country of use. Within the European Union, equipment into which this product is incorporated must comply with the EMC
Directive 2004/108/EC. When using an Optidrive with an internal or optional external filter, compliance with the following EMC Categories, as
defined by EN61800-3:2004 can be achieved:

Drive Type / Rating EMC Category


Cat C1 Cat C2 Cat C3
1 Phase, 230 Volt Input No additional filtering required
ODE-2-x2xxx-1xBxx Use shielded motor cable

3 Phase, 400 Volt Input Use External Filter OPT-2— No additional filtering required
ODE-2-x4xxx-3xAxx E3xxxx
Use shielded motor cable
Compliance with EMC standards is dependent on a number of factors including the environment in which the drive is installed,
Note
motor switching frequency, motor, cable lengths and installation methods adopted.
For shielded motor cable lengths greater than 100m and up to 200m, an output dv / dt filter must be used (please refer to the
Invertek Stock Drives Catalogue for further details)
Compliance with EMC directives is achieved with the factory default parameter settings

All rights reserved. No part of this User Guide may be reproduced or transmitted in any form or by any means, electrical or mechanical including
photocopying, recording or by any information storage or retrieval system without permission in writing from the publisher.

Copyright Invertek Drives Ltd © 2014

All Invertek Optidrive units carry a 2 year warranty against manufacturing defects from the date of manufacture. The manufacturer accepts no
liability for any damage caused during or resulting from transport, receipt of delivery, installation or commissioning. The manufacturer also
accepts no liability for damage or consequences resulting from inappropriate, negligent or incorrect installation, incorrect adjustment of the
operating parameters of the drive, incorrect matching of the drive to the motor, incorrect installation, unacceptable dust, moisture, corrosive
substances, excessive vibration or ambient temperatures outside of the design specification.

The local distributor may offer different terms and conditions at their discretion, and in all cases concerning warranty, the local distributor
should be contacted first.

This user guide is the “original instructions” document. All non-English versions are translations of the “original instructions”.

The contents of this User Guide are believed to be correct at the time of printing. In the interest of a commitment to a policy of continuous
improvement, the manufacturer reserves the right to change the specification of the product or its performance or the contents of the User
Guide without notice.

This User Guide is for use with version 1.20 Firmware.


User Guide Revision 3.30

Invertek Drives Ltd adopts a policy of continuous improvement and whilst every effort has been made to provide accurate and up to date
information, the information contained in this User Guide should be used for guidance purposes only and does not form the part of any
contract.

www.invertekdrives.com
5
Optidrive ODE-2 User Guide Revision 3.30
1. Introduction ........................................................................................................................................................................7
1
1.1. Important Safety Information 7
2. General Information and Ratings ........................................................................................................................................8
Introduction

2.1. Identifying the Drive by Model Number 8


2.2. Drive Model Numbers 8
3. Mechanical Installation .......................................................................................................................................................9
3.1. General 9
3.2. Before Installation 9
3.3. UL Compliant Installation 9
3.4. Mechanical Dimensions and Mounting – IP20 Open Units 9
3.5. Guidelines for Enclosure Mounting – IP20 Units 9
3.6. Mechanical Dimensions – IP66 (Nema 4X) Enclosed Units 10
3.7. Guidelines for mounting (IP66 Units) 10
3.8. Gland Plate and Lock Off 11
3.9. Removing the Terminal Cover 11
3.10. Routine Maintenance 11
4. Power Wiring ....................................................................................................................................................................12
4.1. Grounding the Drive 12
4.2. Wiring Precautions 12
4.3. Incoming Power Connection 13
4.4. Drive and Motor Connection 13
4.5. Motor Terminal Box Connections 13
4.6. Motor Thermal overload Protection. 14
4.7. Control Terminal Wiring 14
4.8. Connection Diagram 14
4.9. Using the REV/0/FWD Selector Switch (Switched Version Only) 15
4.10. Control Terminal Connections 15
5. Operation .........................................................................................................................................................................16
5.1. Managing the Keypad 16
5.2. Terminal Control 16
5.3. Keypad Control 16
6. Parameters .......................................................................................................................................................................17
6.1. Standard Parameters 17
6.2. Extended Parameters 18
6.3. Adjusting the Voltage / Frequency (V/f) characteristics 20
6.4. P-00 Read Only Status Parameters 21
7. Analog and Digital Input Configurations ...........................................................................................................................22
7.1. Terminal Mode (P-12 = 0) 22
7.2. Keypad Mode (P-12 = 1 or 2) 23
7.3. Modbus Control Mode (P-12 = 4) 24
7.4. User PI Control Mode 24
7.5. Motor Thermistor Connection 24
8. Modbus RTU Communications ..........................................................................................................................................25
8.1. Introduction 25
8.2. Modbus RTU Specification 25
8.3. RJ45 Connector Configuration 25
8.4. Modbus Telegram Structure 25
8.5. Modbus Register Map 25
9. Technical Data ..................................................................................................................................................................26
9.1. Environmental 26
9.2. Rating Tables 26
9.3. Additional Information for UL Compliance 27
10. Trouble Shooting ..........................................................................................................................................................28
10.1. Fault Code Messages 28

www.invertekdrives.com
6
Optidrive ODE-2 User Guide Revision 3.30

1. Introduction

1
1.1. Important Safety Information

Introduction
Please read the IMPORTANT SAFETY INFORMATION below, and all Warning and Caution information elsewhere.
Danger : Indicates a risk of electric shock, which, if not Danger : Indicates a potentially hazardous situation
avoided, could result in damage to the equipment and other than electrical, which if not avoided, could
possible injury or death. result in damage to property.
This variable speed drive product (Optidrive) is intended for professional incorporation into complete equipment or systems as
part of a fixed installation. If installed incorrectly it may present a safety hazard. The Optidrive uses high voltages and currents,
carries a high level of stored electrical energy, and is used to control mechanical plant that may cause injury. Close attention is
required to system design and electrical installation to avoid hazards in either normal operation or in the event of equipment
malfunction. Only qualified electricians are allowed to install and maintain this product.
System design, installation, commissioning and maintenance must be carried out only by personnel who have the necessary
training and experience. They must carefully read this safety information and the instructions in this Guide and follow all
information regarding transport, storage, installation and use of the Optidrive, including the specified environmental limitations.
Do not perform any flash test or voltage withstand test on the Optidrive. Any electrical measurements required should be carried
out with the Optidrive disconnected.
Electric shock hazard! Disconnect and ISOLATE the Optidrive before attempting any work on it. High voltages are present at the
terminals and within the drive for up to 10 minutes after disconnection of the electrical supply. Always ensure by using a suitable
multimeter that no voltage is present on any drive power terminals prior to commencing any work.
Where supply to the drive is through a plug and socket connector, do not disconnect until 10 minutes have elapsed after turning
off the supply.
Ensure correct earthing connections. The earth cable must be sufficient to carry the maximum supply fault current which
normally will be limited by the fuses or MCB. Suitably rated fuses or MCB should be fitted in the mains supply to the drive,
according to any local legislation or codes.
Ensure correct earthing connections and cable selection as per defined by local legislation or codes. The drive may have a
leakage current of greater than 3.5mA; furthermore the earth cable must be sufficient to carry the maximum supply fault current
which normally will be limited by the fuses or MCB. Suitably rated fuses or MCB should be fitted in the mains supply to the drive,
according to any local legislation or codes.
Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits.
Within the European Union, all machinery in which this product is used must comply with Directive 2006/42/EC, Safety of
Machinery. In particular, the machine manufacturer is responsible for providing a main switch and ensuring the electrical
equipment complies with EN60204-1.
The level of integrity offered by the Optidrive control input functions – for example stop/start, forward/reverse and maximum
speed is not sufficient for use in safety-critical applications without independent channels of protection. All applications where
malfunction could cause injury or loss of life must be subject to a risk assessment and further protection provided where needed.
The driven motor can start at power up if the enable input signal is present.
The STOP function does not remove potentially lethal high voltages. ISOLATE the drive and wait 10 minutes before starting any
work on it. Never carry out any work on the Drive, Motor or Motor cable whilst the input power is still applied.
The Optidrive can be programmed to operate the driven motor at speeds above or below the speed achieved when connecting
the motor directly to the mains supply. Obtain confirmation from the manufacturers of the motor and the driven machine about
suitability for operation over the intended speed range prior to machine start up.
Do not activate the automatic fault reset function on any systems whereby this may cause a potentially dangerous situation.
IP66 drives provide their own pollution degree 2 environments. IP20 drives must be installed in a pollution degree 2
environment, mounted in a cabinet with IP54 or better.
Optidrives are intended for indoor use only.
When mounting the drive, ensure that sufficient cooling is provided. Do not carry out drilling operations with the drive in place,
dust and swarf from drilling may lead to damage.
The entry of conductive or flammable foreign bodies should be prevented. Flammable material should not be placed close to the
drive
Relative humidity must be less than 95% (non-condensing).
Ensure that the supply voltage, frequency and no. of phases (1 or 3 phase) correspond to the rating of the Optidrive as delivered.
Never connect the mains power supply to the Output terminals U, V, W.
Do not install any type of automatic switchgear between the drive and the motor
Wherever control cabling is close to power cabling, maintain a minimum separation of 100 mm and arrange crossings at 90
degrees
Ensure that all terminals are tightened to the appropriate torque setting
Do not attempt to carry out any repair of the Optidrive. In the case of suspected fault or malfunction, contact your local Invertek
Drives Sales Partner for further assistance.

www.invertekdrives.com
7
Optidrive ODE-2 User Guide Revision 3.30

2. General Information and Ratings


2

This chapter contains information about the Optidrive E2 including how to identify the drive
General Information and Ratings

2.1. Identifying the Drive by Model Number


Each drive can be identified by its model number, as shown in the table below. The model number is on the shipping label and the drive
nameplate. The model number includes the drive and any options.

ODE - 2 - 1 2 037 - 1 K B 1 2
Product Family IP Rating 2 = IP20
Generation X = IP66 Non Switched
Y = IP66 Switched
Dynamic Brake 1 = Not Fitted
Transistor 4 = Internal Transistor
Frame Size Filter Type 0 = No Filter
A = Internal 400V EMC Filter
B = Internal 230V EMC Filter
Input Voltage 1 = 110 – 115 Power Type K = kW
2 = 200 – 240 H = HP
4 = 380 - 480
Power Rating No. Of Input Phases
2.2. Drive Model Numbers
110-115V ±10% - 1 Phase Input - 3 Phase 230V Output (Voltage Doubler)
kW Model Number HP Model Number Frame
kW HP Output Current (A)
With Filter Without Filter With Filter Without Filter Size

N/A N/A N/A ODE-2-11005-1H01# 0.5 2.3 1


N/A N/A N/A ODE-2-11010-1H01# 1 4.3 1
N/A N/A N/A ODE-2-21015-1H04# 1.5 5.8 2

200-240V ±10% - 1 Phase Input


kW Model Number HP Model Number Frame
kW HP Output Current (A)
With Filter Without Filter With Filter Without Filter Size

ODE-2-12037-1KB1# ODE-2-12037-1K01# 0.37 ODE-2-12005-1HB1# ODE-2-12005-1H01# 0.5 2.3 1


ODE-2-12075-1KB1# ODE-2-12075-1K01# 0.75 ODE-2-12010-1HB1# ODE-2-12010-1H01# 1 4.3 1
ODE-2-12150-1KB1# ODE-2-12150-1K01# 1.5 ODE-2-12020-1HB1# ODE-2-12020-1H01# 2 7 1
ODE-2-22150-1KB4# ODE-2-22150-1K04# 1.5 ODE-2-22020-1HB4# ODE-2-22020-1H04# 2 7 2
ODE-2-22220-1KB4# ODE-2-22220-1K04# 2.2 ODE-2-22030-1HB4# ODE-2-22030-1H04# 3 10.5 2
2) 2)
N/A ODE-2-32040-1K04# 4.0 N/A ODE-2-32050-1H04# 5 16 3

200-240V ±10% - 3 Phase Input


kW Model Number HP Model Number Frame
kW HP Output Current (A)
With Filter Without Filter With Filter Without Filter Size

N/A ODE-2-12037-3K01# 0.37 N/A ODE-2-12005-3H01# 0.5 2.3 1


N/A ODE-2-12075-3K01# 0.75 N/A ODE-2-12010-3H01# 1 4.3 1
N/A ODE-2-12150-3K01# 1.5 N/A ODE-2-12020-3H01# 2 7 1
ODE-2-22150-3KB4# ODE-2-22150-3K04# 1.5 ODE-2-22020-3HB4# ODE-2-22020-3H04# 2 7 2
ODE-2-22220-3KB4# ODE-2-22220-3K04# 2.2 ODE-2-22030-3HB4# ODE-2-22030-3H04# 3 10.5 2
ODE-2-32040-3KB4# ODE-2-32040-3K04# 4.0 ODE-2-32050-3HB4# ODE-2-32050-3H04# 5 18 3

380-480V ±10% - 3 Phase Input


kW Model Number HP Model Number Frame
kW HP Output Current (A)
With Filter Without Filter With Filter Without Filter Size

ODE-2-14075-3KA1# ODE-2-14075-3K01# 0.75 ODE-2-14010-3HA1# ODE-2-14010-3H01# 1 2.2 1


ODE-2-14150-3KA1# ODE-2-14150-3K01# 1.5 ODE-2-14020-3HA1# ODE-2-14020-3H01# 2 4.1 1
ODE-2-24150-3KA4# ODE-2-24150-3K04# 1.5 ODE-2-24020-3HA4# ODE-2-24020-3H04# 2 4.1 2
ODE-2-24220-3KA4# ODE-2-24220-3K04# 2.2 ODE-2-24030-3HA4# ODE-2-24030-3H04# 3 5.8 2
ODE-2-24400-3KA4# ODE-2-24400-3K04# 4 ODE-2-24050-3HA4# ODE-2-24050-3H04# 5 9.5 2
ODE-2-34055-3KA4# ODE-2-34055-3K04# 5.5 ODE-2-34075-3HA4# ODE-2-34075-3H04# 7.5 14 3
ODE-2-34075-3KA4# ODE-2-34075-3K04# 7.5 ODE-2-34100-3HA4# ODE-2-34100-3H04# 10 18 3
ODE-2-34110-3KA421) ODE-2-34110-3K0421) 11 ODE-2-34150-3HA421) ODE-2-34150-3H0421) 15 24 3
Replace the # on the end of the part number with the relevant IP code designation shown in figure 1
Note 1) 11kW / 15HP drives are available in IP20 enclosures only
2) Model not UL Approved

www.invertekdrives.com
8
Optidrive ODE-2 User Guide Revision 3.30

3. Mechanical Installation

3
3.1. General

Mechanical Installation
 The Optidrive should be mounted in a vertical position only, on a flat, flame resistant, vibration free mounting using the integral
mounting holes or DIN Rail clip (Frame Sizes 1 and 2 only).
 The Optidrive must be installed in a pollution degree 1 or 2 environment only.
 Do not mount flammable material close to the Optidrive
 Ensure that the minimum cooling air gaps, as detailed in section 3.5 and 3.7 are left clear
 Ensure that the ambient temperature range does not exceed the permissible limits for the Optidrive given in section 9.1
 Provide suitable clean, moisture and contaminant free cooling air sufficient to fulfil the cooling requirements of the Optidrive
3.2. Before Installation
 Carefully Unpack the Optidrive and check for any signs of damage. Notify the shipper immediately if any exist.
 Check the drive rating label to ensure it is of the correct type and power requirements for the application.
 To prevent accidental damage always store the Optidrive in its original box until required. Storage should be clean and dry and within
the temperature range –40°C to +60°C
3.3. UL Compliant Installation
Refer to section 9.3 on page 27 for Additional Information for UL Compliance.
3.4. Mechanical Dimensions and Mounting – IP20 Open Units

Drive A B C D E F G H I J Weight
Size mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in Kg lb
1 173 6.81 160 6.30 109 4.29 162 6.38 5 0.20 123 4.84 83 3.27 50 1.97 5.5 0.22 10 0.39 1.0 2.2
2 221 8.70 207 8.15 137 5.39 209 8.23 5.3 0.21 150 5.91 110 4.33 63 2.48 5.5 0.22 10 0.39 1.7 3.8
3 261 10.28 246 9.69 - - 247 9.72 6 0.24 175 6.89 131 5.16 80 3.15 5.5 0.22 10 0.39 3.2 7.1
Mounting Bolts All Frame Sizes 4 x M4 (#8)
Tightening Torques Control Terminals 0.5 Nm (4.5 lb-in)
All Frame Sizes
Power Terminals 1 Nm (8.85 lb-in)

3.5. Guidelines for Enclosure Mounting – IP20 Units


 IP20 drives are suitable for use in pollution degree 1 environments, according to IEC-664-1. For pollution degree 2 or higher
environments, drives should be mounted in a suitable control cabinet with sufficient ingress protection to maintain a pollution
degree 1 environment around the drive.
 Enclosures should be made from a thermally conductive material.
 Ensure the minimum air gap clearances around the drive as shown below are observed when mounting the drive.
 Where ventilated enclosures are used, there should be venting above the drive and below the drive to ensure good air circulation.
Air should be drawn in below the drive and expelled above the drive.
 In any environments where the conditions require it, the enclosure must be designed to protect the Optidrive against ingress of
airborne dust, corrosive gases or liquids, conductive contaminants (such as condensation, carbon dust, and metallic particles) and
sprays or splashing water from all directions.
 High moisture, salt or chemical content environments should use a suitably sealed (non-vented) enclosure.
The enclosure design and layout should ensure that the adequate ventilation paths and clearances are left to allow air to circulate through the
drive heatsink. Invertek Drives recommend the following minimum sizes for drives mounted in non-ventilated metallic enclosures:-

www.invertekdrives.com
9
Optidrive ODE-2 User Guide Revision 3.30
Drive X Y Z Recommended
Size Above & Either
3

Between airflow
Below Side
3
Mechanical Installation

mm in mm in mm in CFM (ft /min)


1 50 1.97 50 1.97 33 1.30 11
2 75 2.95 50 1.97 46 1.81 11
3 100 3.94 50 1.97 52 2.05 26
Note :
Dimension Z assumes that the drives are mounted side-by-side with
no clearance.

Typical drive heat losses are 3% of operating load conditions.

Above are guidelines only and the operating ambient temperature of


the drive MUST be maintained at all times.

3.6. Mechanical Dimensions – IP66 (Nema 4X) Enclosed Units

Drive Size A B D E F G H I J Weight


mm in mm in mm in mm in mm In mm in mm in mm in mm in kg lb
1 232.0 9.13 207.0 8.15 189.0 7.44 25.0 0.98 179.0 7.05 161.0 6.34 148.5 5.85 4.0 0.16 8.0 0.31 3.1 6.8
2 257.0 10.12 220.0 8.67 200.0 7.87 28.5 1.12 187.0 7.36 188.0 7.40 176.0 6.93 4.2 0.17 8.5 0.33 4.1 9.0
3 310.0 12.20 276.5 10.89 251.5 9.90 33.4 1.31 245.0 9.64 211.0 8.30 197.5 7.78 4.2 0.17 8.5 0.33 7.6 16.7
Mounting Bolts All Frame Sizes 4 x M4 (#8)
Tightening Torques Control Terminals 0.5 Nm (4.5 lb-in)
All Frame Sizes
Power Terminals 1 Nm (8.85 lb-in)

3.7. Guidelines for mounting (IP66 Units)


 Before mounting the drive, ensure that the chosen location meets the environmental condition requirements for the drive shown in
section 9.1
 The drive must be mounted vertically, on a suitable flat surface
 The minimum mounting clearances as shown in the table below must be observed
 The mounting site and chosen mountings should be sufficient to support the weight of the drives
 Using the drive as a template, or the dimensions shown above, mark the locations required for drilling
 Suitable cable glands to maintain the ingress protection of the drive are required. Gland holes for power and motor cables are pre-
moulded into the drive enclosure, recommended gland sizes are shown above. Gland holes for control cables may be cut as required.

Drive Size X Above & Below Y Either Side


mm in mm in
2 200 7.87 10 0.39
3 200 7.87 10 0.39
Note :
Typical drive heat losses are approximately 3% of operating load
conditions.

Above are guidelines only and the operating ambient temperature of the
drive MUST be maintained at all times.
Cable Gland Sizes
Frame Power Cable Motor Cable Control Cables
2 M25 (PG21) M25 (PG21) M20 (PG13.5)
3 M25 (PG21) M25 (PG21) M20 (PG13.5)

www.invertekdrives.com
10
Optidrive ODE-2 User Guide Revision 3.30
3.8. Gland Plate and Lock Off

3
The use of a suitable gland system is required to maintain the appropriate IP / Nema rating. The gland plate has pre moulded cable entry
holes for power and motor connections suitable for use with glands as shown in the following table. Where additional holes are required,

Mechanical Installation
these can be drilled to suitable size. Please take care when drilling to avoid leaving any particles within the product.
Cable Gland recommended Hole Sizes & types:
Power & Motor Cables Control & Signal Cables
Moulded Hole Imperial Gland Metric Gland Knockout Size Imperial Gland Metric Gland
Size
Size 1 22mm PG13.5 M20 22mm PG13.5 M20
Size 2 & 3 27mm PG21 M25 22mm PG13.5 M20
Flexible Conduit Hole Sizes:
Drill Size Trade Size Metric
Size 1 28mm ¾ in 21
Size 2 & 3 35mm 1 in 27
 UL rated ingress protection ("Type " ) is only met when cables are installed using a UL recognized bushing or fitting for a flexible-
conduit system which meets the required level of protection ("Type")
 For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC
 Not intended for rigid conduit system
Power Isolator Lock Off
On the switched models the main power isolator switch can be locked in the ‘Off’ position using a 20mm standard shackle padlock (not
supplied).
IP66 / Nema 4X Gland Plate IP66 / Nema 4X Unit Lock Off

3.9. Removing the Terminal Cover


To access the connection terminals, the drive front cover needs to be removed as shown.
IP66 / Nema 4X Units
Removing the 2 screws on the front of the product allows access to the connection terminals, as shown below.

3.10. Routine Maintenance


The drive should be included within the scheduled maintenance program so that the installation maintains a suitable operating environment,
this should include:
 Ambient temperature is at or below that set out in the “Environment” section.
 Heat sink fans freely rotating and dust free.
 The Enclosure in which the drive is installed should be free from dust and condensation; furthermore ventilation fans and air filters
should be checked for correct air flow.

Checks should also be made on all electrical connections, ensuring screw terminals are correctly torqued; and that power cables have no signs
of heat damage.

www.invertekdrives.com
11
Optidrive ODE-2 User Guide Revision 3.30

4. Power Wiring
4

4.1. Grounding the Drive


Power Wiring

This manual is intended as a guide for proper installation. Invertek Drives Ltd cannot assume responsibility for the compliance
or the non-compliance to any code, national, local or otherwise, for the proper installation of this drive or associated
equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
This Optidrive contains high voltage capacitors that take time to discharge after removal of the main supply. Before working
on the drive, ensure isolation of the main supply from line inputs. Wait ten (10) minutes for the capacitors to discharge to safe
voltage levels. Failure to observe this precaution could result in severe bodily injury or loss of life.
Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved
should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in
their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
Grounding Guidelines
The ground terminal of each Optidrive should be individually connected DIRECTLY to the site ground bus bar (through the filter if installed).
Optidrive ground connections should not loop from one drive to another, or to, or from any other equipment. Ground loop impedance must
confirm to local industrial safety regulations. To meet UL regulations, UL approved ring crimp terminals should be used for all ground wiring
connections.
The drive Safety Ground must be connected to system ground. Ground impedance must conform to the requirements of national and local
industrial safety regulations and/or electrical codes. The integrity of all ground connections should be checked periodically.
Protective Earth Conductor
The Cross sectional area of the PE Conductor must be at least equal to that of the incoming supply conductor.
Safety Ground
This is the safety ground for the drive that is required by code. One of these points must be connected to adjacent building steel (girder, joist), a
floor ground rod, or bus bar. Grounding points must comply with national and local industrial safety regulations and/or electrical codes.
Motor Ground
The motor ground must be connected to one of the ground terminals on the drive.
Ground Fault Monitoring
As with all inverters, a leakage current to earth can exist. The Optidrive is designed to produce the minimum possible leakage current whilst
complying with worldwide standards. The level of current is affected by motor cable length and type, the effective switching frequency, the
earth connections used and the type of RFI filter installed. If an ELCB (Earth Leakage Circuit Breaker) is to be used, the following conditions
apply: -
 A Type B Device must be used
 The device must be suitable for protecting equipment with a DC component in the leakage current
 Individual ELCBs should be used for each Optidrive

Drives with an EMC filter have an inherently higher leakage current to Ground (Earth). For applications where tripping occurs the EMC filter can
be disconnected (on IP20 units only) by removing the EMC screw on the side of the product.
Remove the screws as indicated below

The Optidrive product range has input supply voltage surge suppression components fitted to protect the drive from line voltage transients,
typically originating from lightning strikes or switching of high power equipment on the same supply.

When carrying out a HiPot (Flash) test on an installation in which the drive is built, the voltage surge suppression components may cause the
test to fail. To accommodate this type of system HiPot test, the voltage surge suppression components can be disconnected by removing the
VAR screw. After completing the HiPot test, the screw should be replaced and the HiPot test repeated. The test should then fail, indicating that
the voltage surge suppression components are once again in circuit.
Shield Termination (Cable Screen)
The safety ground terminal provides a grounding point for the motor cable shield. The motor cable shield connected to this terminal (drive end)
should also be connected to the motor frame (motor end). Use a shield terminating or EMI clamp to connect the shield to the safety ground
terminal.
4.2. Wiring Precautions
Connect the Optidrive according to sections 4.8.1 and 4.8.2, ensuring that motor terminal box connections are correct. There are two
connections in general: Star and Delta. It is essential to ensure that the motor is connected in accordance with the voltage at which it will be
operated. For more information, refer to section 4.5 Motor Terminal Box Connections.

It is recommended that the power cabling should be 4-core PVC-insulated screened cable, laid in accordance with local industrial regulations
and codes of practice.

www.invertekdrives.com
12
Optidrive ODE-2 User Guide Revision 3.30

4.3. Incoming Power Connection

4
 For 1 phase supply, power should be connected to L1/L, L2/N.
 For 3 phase supplies, power should be connected to L1, L2, and L3. Phase sequence is not important.

Power Wiring
 For compliance with CE and C Tick EMC requirements, a symmetrical shielded cable is recommended.
 A fixed installation is required according to IEC61800-5-1 with a suitable disconnecting device installed between the Optidrive and the
AC Power Source. The disconnecting device must conform to the local safety code / regulations (e.g. within Europe, EN60204-1, Safety
of machinery).
 The cables should be dimensioned according to any local codes or regulations. Guideline dimensions are given in section 9.2.
 Suitable fuses to provide wiring protection of the input power cable should be installed in the incoming supply line, according to the
data in section 9.2. The fuses must comply with any local codes or regulations in place. In general, type gG (IEC 60269) or UL type T
fuses are suitable; however in some cases type aR fuses may be required. The operating time of the fuses must be below 0.5 seconds.
 Where allowed by local regulations, suitably dimensioned type B MCB circuit breakers of equivalent rating may be utilised in place of
fuses, providing that the clearing capacity is sufficient for the installation.
 When the power supply is removed from the drive, a minimum of 30 seconds should be allowed before re-applying the power. A
minimum of 5 minutes should be allowed before removing the terminal covers or connection.
 The maximum permissible short circuit current at the Optidrive Power terminals as defined in IEC60439-1 is 100kA.
 An optional Input Choke is recommended to be installed in the supply line for drives where any of the following conditions occur:-
o The incoming supply impedance is low or the fault level / short circuit current is high
o The supply is prone to dips or brown outs
o An imbalance exists on the supply (3 phase drives)
o The power supply to the drive is via a busbar and brush gear system (typically overhead Cranes).
 In all other installations, an input choke is recommended to ensure protection of the drive against power supply faults. Part numbers
are shown in the table.
Supply Frame Size AC Input Inductor
1 OPT-2-L1016-20
230 Volt
2 OPT-2-L1025-20
1 Phase
3 N/A
2 OPT-2-L3006-20
400 Volt
2 OPT-2-L3010-20
3 Phase
3 OPT-2-L3036-20

4.4. Drive and Motor Connection


 The drive inherently produces fast switching of the output voltage (PWM) to the motor compared to the mains supply, for motors
which have been wound for operation with a variable speed drive then there is no preventative measures required, however if the
quality of insulation is unknown then the motor manufacturer should be consulted and preventative measures may be required.
 The motor should be connected to the Optidrive U, V, and W terminals using a suitable 3 or 4 core cable. Where a 3 core cable is
utilised, with the shield operating as an earth conductor, the shield must have a cross sectional area at least equal to the phase
conductors when they are made from the same material. Where a 4 core cable is utilised, the earth conductor must be of at least
equal cross sectional area and manufactured from the same material as the phase conductors.
 The motor earth must be connected to one of the Optidrive earth terminals.
 For compliance with the European EMC directive, a suitable screened (shielded) cable should be used. Braided or twisted type
screened cable where the screen covers at least 85% of the cable surface area, designed with low impedance to HF signals are
recommended as a minimum. Installation within a suitable steel or copper tube is generally also acceptable.
 The cable screen should be terminated at the motor end using an EMC type gland allowing connection to the motor body through the
largest possible surface area
 Where drives are mounted in a steel control panel enclosure, the cable screen may be terminated directly to the control panel using a
suitable EMC clamp or gland, as close to the drive as possible.
 For IP66 drives, connect the motor cable screen to the internal ground clamp
4.5. Motor Terminal Box Connections
Most general purpose motors are wound for operation on dual voltage supplies. This is indicated on the nameplate of the motor. This
operational voltage is normally selected when installing the motor by selecting either STAR or DELTA connection. STAR always gives the higher
of the two voltage ratings.
Incoming Supply Voltage Motor Nameplate Voltages Connection

230 230 / 400

Delta

400 400 / 690

400 230 / 400 Star

www.invertekdrives.com
13
Optidrive ODE-2 User Guide Revision 3.30
4.6. Motor Thermal overload Protection.
4

4.6.1. Internal Thermal Overload Protection.


The drive has an in-built motor thermal overload function; this is in the form of an “I.t-trP” trip after delivering >100% of the value set in P-08
Power Wiring

for a sustained period of time (e.g. 150% for 60 seconds).


4.6.2. Motor Thermistor Connection
Where a motor thermistor is to be used, it should be connected as follows :-

Control Terminal Strip Additional Information


1 2 3 4  Compatible Thermistor : PTC Type, 2.5kΩ trip level
 Use a setting of P-15 that has Input 3 function as External Trip, e.g. P-15 = 3. Refer to section 7 for
further details.

4.7. Control Terminal Wiring


 All analog signal cables should be suitably shielded. Twisted pair cables are recommended.
 Power and Control Signal cables should be routed separately where possible, and must not be routed parallel to each other.
 Signal levels of different voltages e.g. 24 Volt DC and 110 Volt AC, should not be routed in the same cable.
 Maximum control terminal tightening torque is 0.5Nm.
2
 Control Cable entry conductor size: 0.05 – 2.5mm / 30 – 12 AWG.
4.8. Connection Diagram
4.8.1. IP66 (Nema 4X) Switched Units
Power Connections
A Incoming Power Supply
B External MCB or Fuse
C Optional Input Choke
D Optional Input Filter
E Internal Isolator / Disconnect
F Optional Brake Resistor
G Shielded Motor Cable
I Relay Output
Control Connections
J Internal Forward / Off / Reverse
Switch
K Internal Speed Control Pot

8 Analog Output
0 – 10 Volts
9 0 Volt
10 Relay Output
11 ‘Drive Healthy’ = Closed

4.8.2. IP20 & IP66 (Nema 4X) Non- Switched Units


Power Connections
A Incoming Power Supply
B Isolator / Disconnect
C MCB or Fuse
D Optional Input Choke
E Optional Input Filter
F Optional Brake Resistor
G Shielded Motor Cable
I Relay Output
Control Connections
1 + 24 Volt (100mA) User Output
2 Digital Input 1
Drive Run / Stop
3 Digital Input 2
Forward / Reverse
4 Digital Input 3
Analog / Preset Speed
5 + 10 Volt Output
6 Analog Input 1
7 0 Volt
8 Analog Output 0 – 10 Volts
9 0 Volt
10 Relay Output
11 ‘Drive Healthy’ = Closed

www.invertekdrives.com
14
Optidrive ODE-2 User Guide Revision 3.30
4.9. Using the REV/0/FWD Selector Switch (Switched Version Only)

4
By adjusting the parameter settings the Optidrive can be configured for multiple applications and not just for Forward or Reverse.
This could typically be for Hand/Off/Auto applications (also known and Local/Remote) for HVAC and pumping industries.

Power Wiring
Parameters to Set
Switch Position Notes
P-12 P-15
Factory Default Configuration
Run Reverse STOP Run Forward 0 0 Run Forward or Reverse with speed controlled from the
Local POT
Run forward with speed controlled form the local POT
STOP STOP Run Forward 0 5,7
Run Reverse - disabled
Run Forward with speed controlled from the Local POT
Preset Speed 1 STOP Run Forward 0 1
Preset Speed 1 provides a ‘Jog’ Speed set in P-20
Run Forward or Reverse with speed controlled from the
Run Reverse STOP Run Forward 0 6, 8
Local POT
Run in Hand – Speed controlled from the Local POT
Run in Auto STOP Run in Hand 0 4 Run in Auto 0 Speed controlled using Analog input 2 e.g.
from PLC with 4-20mA signal.
In Speed Control the speed is controlled from the Local
Run in Speed Control STOP Run in PI Control 5 1 POT
In PI Control, Local POT controls PI set point
In Preset Speed Control, P-20 sets the Preset Speed
Run in Preset Speed 0, 2, 4,5,
STOP Run in PI Control 5 In PI Control, POT can control the PI set point
Control 8..12
(P-44=1)
Hand – speed controlled from the Local POT
Run in Hand STOP Run in Auto 3 6
Auto – Speed Reference from Modbus
Hand – Speed reference from Preset Speed 1 (P-20)
Run in Hand STOP Run in Auto 3 3
Auto – Speed Reference from Modbus
NOTE To be able to adjust parameter P-15, extended menu access must be set in P-14 (default value is 101)
4.10. Control Terminal Connections
Default Connections Control Signal Description
Terminal
1 +24V User Output, +24V, 100mA.

2 Digital Input 1 Positive logic


“Logic 1” input voltage range: 8V … 30V DC
3 Digital Input 2 “Logic 0” input voltage range: 0V … 4V DC
Digital Input 3 / Digital: 8 to 30V
4
Analog Input 2 Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
5 +10V User Output +10V, 10mA, 1kΩ minimum
Analog Input 1 / Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
6
Digital Input 4 Digital: 8 to 30V
7 0V User ground connected terminal 9
Analog Output / Analog: 0 to 10V,
8 20mA maximum
Digital Output Digital: 0 to 24V
9 0V User ground connected terminal 7

10 Relay Common

11 Relay NO Contact Contact 250Vac, 6A / 30Vdc, 5A

www.invertekdrives.com
15
Optidrive ODE-2 User Guide Revision 3.30

5. Operation
5

5.1. Managing the Keypad


Operation

The drive is configured and its operation monitored via the keypad and display.
Used to display real-time information, to access and exit
NAVIGATE
parameter edit mode and to store parameter changes
Used to increase speed in real-time mode or to increase
UP
parameter values in parameter edit mode
Used to decrease speed in real-time mode or to decrease
DOWN
parameter values in parameter edit mode
RESET / Used to reset a tripped drive.
STOP When in Keypad mode is used to Stop a running drive.
When in keypad mode, used to Start a stopped drive or to
START reverse the direction of rotation if bi-directional keypad
mode is enabled
Changing Parameters
To change a parameter value press and hold the key for >1s whilst the drive displays . The display changes to , indicating
parameter 01. Press and release the key to display the value of this parameter. Change to the required value using the and keys.
Press and release the key once more to store the change. Press and hold the key for >1s to return to real-time mode. The display shows
 if the drive is stopped or the real-time information (e.g. speed) if the drive is running.
Reset Factory Default Settings
To reset factory default parameters, press , and for >2s. The display shows . Press the button to acknowledge and reset
the drive.
5.2. Terminal Control
When delivered, the Optidrive is in the factory default state, meaning that it is set to operate in terminal control mode and all parameters (P-xx)
have the default values as indicated in section 6 Parameters.
1. Connect the drive and motor according to the connection diagram shown at the beginning of this User Guide
2. Enter motor data from motor nameplate, P-07 = motor rated voltage, P-08 = motor rated current, P-09 = motor rated frequency.
3. With the potentiometer set to zero, switch on the supply to the drive. The display will show .
4. Close the control switch, terminals 1-2. The drive is now ‘enabled’ and the output frequency/speed are controlled by the
potentiometer. The display shows zero speed in Hz (.) with the potentiometer turned to minimum.
5. Turn the potentiometer to maximum. The motor will accelerate to 50Hz (the default value of P-01) under the control of the
accelerating ramp time P-03. The display shows 50Hz (.) at max speed.
6. To display motor current (A), briefly press the (Navigate) key.
7. Press again to return to speed display.
8. To stop the motor, either turn the potentiometer back to zero or disable the drive by opening the control switch (terminals 1-2).
If the enable/disable switch is opened the drive will decelerate to stop at which time the display will show . If the potentiometer is turned
to zero with the enable/disable closed the display will show .(0.0Hz), if left like this for 20 seconds the drive will go into standby mode,
display shows , waiting for a speed reference signal.
5.3. Keypad Control
To allow the Optidrive to be controlled from the keypad in a forward direction only, set P-12 =1:
1. Connect the drive and motor according to the connection diagram shown at the beginning of this User Guide
2. Enable the drive by closing the switch between control terminals 1 & 2. The display will show .
3. Press the key. The display shows ..
4. Press to increase speed.
5. The drive will run forward, increasing speed until is released. The rate of acceleration is controlled by the setting of P-03, check this
before starting.
6. Press to decrease speed. The drive will decrease speed until is released. The rate of deceleration is limited by the setting in P-
04
7. Press the key. The drive will decelerate to rest at the rate set in P-04.
8. The display will finally show  at which point the drive is disabled
9. To preset a target speed prior to enable, press the key whilst the drive is stopped. The display will show the target speed, use the
& keys to adjust as required then press the key to return the display to .
10. Pressing the key will start the drive accelerating to the target speed.

To allow the Optidrive to be controlled from the keypad in a forward and reverse direction, set P-12 =2:
11. Operation is the same as when P-12=1 for start, stop and changing speed.
12. Press the key. The display changes to ..
13. Press to increase speed
14. The drive will run forward, increasing speed until is released. Acceleration is limited by the setting in P-03. The maximum speed is
the speed set in P-01.
15. To reverse the direction of rotation of the motor, press the key again.

www.invertekdrives.com
16
Optidrive ODE-2 User Guide Revision 3.30

6. Parameters

6
6.1. Standard Parameters

Parameters
Par. Description Minimum Maximum Default Units
P-01 Maximum Frequency / Speed Limit P-02 500.0 50.0 (60.0) Hz / Rpm
Maximum output frequency or motor speed limit – Hz or rpm. If P-10 >0, the value entered / displayed is in Rpm
P-02 Minimum Frequency / Speed Limit 0.0 P-01 0.0 Hz / Rpm
Minimum speed limit – Hz or rpm. If P-10 >0, the value entered / displayed is in Rpm
P-03 Acceleration Ramp Time 0.00 600.0 5.0 s
Acceleration ramp time from 0.0 to base frequency (P-09) in seconds.
P-04 Deceleration Ramp Time 0.00 600.0 5.0 s
Deceleration ramp time from base frequency (P-09) to standstill in seconds. When set to 0.00, the value of P-24 is used.
P-05 Stopping Mode 0 2 0 -
0 : Ramp To Stop. When the enable signal is removed, the drive will ramp to stop, with the rate controlled by P-04. If the mains
supply is lost, the drive will try to continue running by reducing the speed of the load, and using the load as a generator.
1 : Coast to Stop. When the enable signal is removed, or if the mains supply is lost, the motor will coast (freewheel) to stop
2 : Ramp To Stop. When the enable signal is removed, the drive will ramp to stop, with the rate controlled by P-04. If the mains
supply is lost the drive will ramp to stop using the P-24 decel ramp with dynamic brake control.
P-06 Energy Optimiser 0 1 0 -
0 : Disabled
1 : Enabled. When enabled, the Energy Optimiser attempts to reduce the overall energy consumed by the drive and motor when
operating at constant speeds and light loads. The output voltage applied to the motor is reduced. The Energy Optimiser is intended
for applications where the drive may operate for some periods of time with constant speed and light motor load, whether constant
or variable torque.
P-07 Motor Rated Voltage 0 250 / 500 230 / 400 V
This parameter should be set to the rated (nameplate) voltage of the motor (Volts)
P-08 Motor Rated Current Drive Rating Dependent A
This parameter should be set to the rated (nameplate) current of the motor
P-09 Motor Rated Frequency 25 500 50 (60) Hz
This parameter should be set to the rated (nameplate) frequency of the motor
P-10 Motor Rated Speed 0 30000 0 Rpm
This parameter can optionally be set to the rated (nameplate) rpm of the motor. When set to the default value of zero, all speed
related parameters are displayed in Hz, and the slip compensation for the motor is disabled. Entering the value from the motor
nameplate enables the slip compensation function, and the Optidrive display will now show motor speed in estimated rpm. All
speed related parameters, such as Minimum and Maximum Speed, Preset Speeds etc. will also be displayed in Rpm.
P-11 Voltage Boost 0.0 20.0 3.0 %
Voltage boost is used to increase the applied motor voltage at low output frequencies, in order to improve low speed and starting
torque. Excessive voltage boost levels may result in increased motor current and temperature, and force ventilation of the motor
may be required. A suitable setting can usually be found by operating the motor under low load or no load conditions at
approximately 5Hz, and adjusting P-11 until the motor current is no more than 80% of the rated full load current.
P-12 Primary Command Source 0 6 0 -
0: Terminal Control. The drive responds directly to signals applied to the control terminals.
1: Uni-directional Keypad Control. The drive can be controlled in the forward direction only using an external or remote Keypad
2: Bi-directional Keypad Control. The drive can be controlled in the forward and reverse directions using an external or remote
Keypad. Pressing the keypad START button toggles between forward and reverse.
3: Modbus Network Control. Control via Modbus RTU (RS485) using the internal Accel / Decel ramps
4 : Modbus Network Control. Control via Modbus RTU (RS485) interface with Accel / Decel ramps updated via Modbus
5 : PI Control. User PI control with external feedback signal
6 : PI Analog Summation Control. PI control with external feedback signal and summation with analog input 1
P-13 Trip Log History N/A N/A N/A N/A
Previous 4 trips stored in order of occurrence, with the most recent first. Press UP or DOWN to step through all four. The most
recent trip is always displayed first. UV trip is only stored once. Further fault event logging functions are available through
parameter group zero.
P-14 Extended Menu Access code 0 9999 0 -
Set to “101” (default) for extended menu access. Change code in P-37 to prevent unauthorised access to the Extended Parameter
Set

www.invertekdrives.com
17
Optidrive ODE-2 User Guide Revision 3.30

6.2. Extended Parameters


6

Par. Description Minimum Maximum Default Units


P-15 Digital Input Function Select 0 12 0 -
Parameters

Defines the function of the digital inputs depending on the control mode setting in P-12. See section 8, Analog and Digital Input
Configurations for more information.
P-16 Analog Input 1 Signal Format See Below U0-10 -
 = 0 to 10 Volt Signal (Uni-polar). The drive will remain at 0.0Hz if the analog reference after scaling and offset are applied is
<0.0%
 = 0 to 10 Volt Signal, bi-directional operation. The drive will operate the motor in the reverse direction of rotation if the
analog reference after scaling and offset are applied is <0.0%
 = 0 to 20mA Signal
 = 4 to 20mA Signal, the Optidrive will trip and show the fault code  if the signal level falls below 3mA
 = 4 to 20mA Signal, the Optidrive will run at Preset Speed 1 (P-20) if the signal level falls below 3mA
 = 20 to 4mA Signal, the Optidrive will trip and show the fault code  if the signal level falls below 3mA
 = 20 to 4mA Signal, the Optidrive will run at Preset Speed 1 (P-20) if the signal level falls below 3mA
P-17 Maximum Effective Switching Frequency 4 32 8 / 16 kHz
Sets maximum effective switching frequency of the drive. If “rEd” is displayed, the switching frequency has been reduced to the level in P00-
14 due to excessive drive heatsink temperature.
P-18 Output Relay Function Select 0 7 1 -
Selects the function assigned to the relay output. The relay has two output terminals, Logic 1 indicates the relay is active, and
therefore terminals 10 and 11 will be linked together.
0 : Drive Enabled (Running). Logic 1 when the motor is enabled
1 : Drive Healthy. Logic 1 when power is applied to the drive and no fault exists
2 : At Target Frequency (Speed). Logic 1 when the output frequency matches the setpoint frequency
3: Drive Tripped. Logic 1 when the drive is in a fault condition
4 : Output Frequency >= Limit. Logic 1 when the output frequency exceeds the adjustable limit set in P-19
5 : Output Current >= Limit. Logic 1 when the motor current exceeds the adjustable limit set in P-19
6 : Output Frequency < Limit. Logic 1 when the output frequency is below the adjustable limit set in P-19
7 : Output Current < Limit. Logic 1 when the motor current is below the adjustable limit set in P-19
P-19 Relay Threshold Level 0.0 200.0 100.0 %
Adjustable threshold level used in conjunction with settings 4 to 7 of P-18
P-20 Preset Frequency / Speed 1 P-02 P-01 0.0 Hz / Rpm
P-21 Preset Frequency / Speed 2 P-02 P-01 0.0 Hz / Rpm
P-22 Preset Frequency / Speed 3 P-02 P-01 0.0 Hz / Rpm
P-23 Preset Frequency / Speed 4 P-02 P-01 0.0 Hz / Rpm
Preset Speeds / Frequencies selected by digital inputs depending on the setting of P-15
If P-10 = 0, the values are entered as Hz. If P-10 > 0, the values are entered as Rpm.
P-24 2nd Decel Ramp Time (Fast Stop) 0.00 25.0 0.00 s
This parameter allows an alternative deceleration ramp down time to be programmed into the Optidrive, which can be selected by
digital inputs (dependent on the setting of P-15) or selected Automatically in the case of a mains power loss if P-05 = 2.
When set to 0.00, the drive will coast to stop.
P-25 Analog Output Function Select 0 9 8 -
Digital Output Mode. Logic 1 = +24V DC
0 : Drive Enabled (Running). Logic 1 when the Optidrive is enabled (Running)
1 : Drive Healthy. Logic 1 When no Fault condition exists on the drive
2 : At Target Frequency (Speed). Logic 1 when the output frequency matches the setpoint frequency
3: Drive Tripped. Logic 1 when the drive is in a fault condition
4 : Output Frequency >= Limit. Logic 1 when the output frequency exceeds the adjustable limit set in P-19
5 : Output Current >= Limit. Logic 1 when the motor current exceeds the adjustable limit set in P-19
6 : Output Frequency < Limit. Logic 1 when the output frequency is below the adjustable limit set in P-19
7 : Output Current < Limit. Logic 1 when the motor current is below the adjustable limit set in P-19
Analog Output Mode
8 : Output Frequency (Motor Speed). 0 to P-01, resolution 0.1Hz
9 : Output (Motor) Current. 0 to 200% of P-08, resolution 0.1A
P-26 Skip frequency hysteresis band 0.0 P-01 0.0 Hz / Rpm
P-27 Skip Frequency 0.0 P-01 0.0 Hz / Rpm
The Skip Frequency function is used to avoid the Optidrive operating at a certain output frequency, for example at a frequency
which causes mechanical resonance in a particular machine. Parameter P-27 defines the centre point of the skip frequency band,
and is used conjunction with P-26. The Optidrive output frequency will ramp through the defined band at the rates set in P-03 and P-
04 respectively, and will not hold any output frequency within the defined band. If the frequency reference applied to the drive is
within the band, the Optidrive output frequency will remain at the upper or lower limit of the band.
P-28 V/F Characteristic Adjustment Voltage 0 250 / 500 0 V
P-29 V/F Characteristic Adjustment Frequency 0.0 P-09 0.0 Hz
This parameter in conjunction with P-28 sets a frequency point at which the voltage set in P-29 is applied to the motor. Care must be
taken to avoid overheating and damaging the motor when using this feature. See section 6.3 for further information.

www.invertekdrives.com
18
Optidrive ODE-2 User Guide Revision 3.30
Par. Description Minimum Maximum Default Units
P-30 Terminal Mode Restart function N/A N/A Auto-0 -

6
Defines the behaviour of the drive relating to the enable digital input and also configures the Automatic Restart function.

Parameters
 : Following Power on or reset, the drive will not start if Digital Input 1 remains closed. The Input must be closed after a
power on or reset to start the drive.
 : Following a Power On or Reset, the drive will automatically start if Digital Input 1 is closed.
 to  : Following a trip, the drive will make up to 5 attempts to restart at 20 second intervals. The drive must be
powered down to reset the counter. The numbers of restart attempts are counted, and if the drive fails to start on the final attempt,
the drive will fault with, and will require the user to manually reset the fault.
P-31 Keypad / Modbus Mode Restart Function 0 3 1 -
This parameter is active only when operating in Keypad Control Mode (P-12 = 1 or 2) or Modbus Mode (P-12 = 3 or 4). When settings
0 or 1 are used, the Keypad Start and Stop keys are active, and control terminals 1 and 2 must be linked together. Settings 2 and 3
allow the drive to be started from the control terminals directly, and the keypad Start and Stop keys are ignored.
Settings 0 and 2 : The drive will always start at the Minimum Frequency / Speed (P-02)
Settings 1 and 3 : The drive will always start at the last operating Frequency / Speed
0 : Minimum Speed, Keypad Start
1 : Previous Speed, Keypad Start
2 : Minimum Speed, Terminal Enable
3 : Previous Speed, Terminal Enable
P-32 DC Injection Time On Stop 0.0 25.0 0.0 s
Defines the time for which a DC current is injected into the motor once the output frequency reaches 0.0Hz. The voltage level is the
same as the boost level set in P-11.
P-33 Spin Start (S2 & S3 Only) / DC Injection Time On Start (S1 Only) 0 1 0 -
Frame Size 2 and 3 Drives only – Spin Start
0 : Disabled
1 : Enabled. When enabled, on start up the drive will attempt to determine if the motor is already rotating, and will begin to control
the motor from its current speed. A short delay may be observed when starting motors which are not turning.
Frame Size 1 Drives Only – DC Injection Time On Starting
Sets a time for which DC current is injected into the motor to ensure it is stopped when the drive is enabled.
P-34 Brake Chopper Enable 0 2 0 -
0 : Disabled
1 : Enabled With Software Protection. Enables the internal brake chopper with software protection for a 200W continuous rated
resistor
2 : Enabled Without Software Protection. Enables the internal brake chopper without software protection. An external thermal
protection device should be fitted.
P-35 Analog Input 1 Scaling 0.0 500.0 100.0 %
Scales the analog input by this factor, e.g. if P-16 is set for a 0 – 10V signal , and the scaling factor is set to 200.0%, a 5 volt input will
result in the drive running at maximum frequency / speed (P-01)
P-36 Modbus RTU Serial Communications Configuration See Below
This parameter has three sub settings used to configure the Modbus RTU Serial Communications. The Sub Parameters are
1st Index : Drive Address : Range  0 - 63
nd
2 Index : Baud Rate : Selects the baud rate between 9.6kbps to 115.2kbps (default) for Modbus RTU communication.
rd
3 Index : Watchdog Timeout : Defines the time for which the drive will operate without receiving a valid command telegram to
Register 1 (Drive Control Word) after the drive has been enabled. Setting 0 disables the Watchdog timer. Setting a value of 30, 100,
1000, or 3000 defines the time limit in milliseconds for operation. A ‘’ suffix selects trip on loss of communication. An ‘’ suffix
means that the drive will coast stop (output immediately disabled) but will not trip.
P-37 Access Code Definition 0 9999 101 -
Defines the access code which must be entered in P-14 to access parameters above P-14
P-38 Parameter Access Lock 0 1 0 -
0 : Unlocked. All parameters can be accessed and changed
1 : Locked. Parameter values can be displayed, but cannot be changed
P-39 Analog Input 1 Offset -500.0 500.0 0.0 %
Sets an offset, as a percentage of the full scale range of the input, which is applied to the analog input signal
P-40 Display Speed Scaling Factor 0.000 6.000 0.000 -
Allows the user to program the Optidrive to display an alternative output unit scaled from the output frequency or speed, e.g. to
display conveyer speed in metres per second. This function is disabled if P-40 = 0.00
P-41 PI Controller Proportional Gain 0.0 30.0 1.0 -
PI Controller Proportional Gain. Higher values provide a greater change in the drive output frequency in response to small changes
in the feedback signal. Too high a value can cause instability
P-42 PI Controller Integral Time 0.0 30.0 1.0 s
PI Controller Integral Time. Larger values provide a more damped response for systems where the overall process responds slowly
P-43 PI Controller Operating Mode 0 1 0 -
0 : Direct Operation. Use this mode if an increase in the motor speed should result in an increase in the feedback signal
1 : Inverse Operation. Use this mode if an increase in the motor speed should result in a decrease in the feedback signal
2 : Direct Operation, Scaled Feedback. As Option 0, but with scaled display of PI Feedback. The feedback value (0 – 100.0%) is
multiplied by the scaling factor set in P-40.
3 : Inverse Operation, Scaled Feedback. As Option 1, but with scaled display of PI Feedback. The feedback value (0 – 100.0%) is
multiplied by the scaling factor set in P-40.

www.invertekdrives.com
19
Optidrive ODE-2 User Guide Revision 3.30
Par. Description Minimum Maximum Default Units
P-44 PI Reference (Setpoint) Source Select 0 1 0 -
6

Selects the source for the PID Reference / Setpoint


Parameters

0 : Digital Preset Setpoint. P-45 is used


1 : Analog Input 1 Setpoint
P-45 PI Digital Setpoint 0.0 100.0 0.0 %
When P-44 = 0, this parameter sets the preset digital reference (setpoint) used for the PI Controller
P-46 PI Feedback Source Select 0 2 0 -
0 : Analog Input 2 (Terminal 4)
1 : Analog Input 1 (Terminal 6)
2 : Motor Current
3 : DC Bus Voltage Scaled 0 – 1000 Volts = 0 – 100%
4 : Analog 1 – Analog 2. The value of Analog Input 2 is subtracted from Analog 1 to give a differential signal. The value is limited to 0.
5 : Largest (Analog 1, Analog 2). The largest of the two analog input values is always used for PI feedback
P-47 Analog Input 2 Signal Format N/A N/A N/A U0-10
 = 0 to 10 Volt Signal
 = 0 to 20mA Signal
 = 4 to 20mA Signal, the Optidrive will trip and show the fault code  if the signal level falls below 3mA
 = 4 to 20mA Signal, the Optidrive will ramp to stop if the signal level falls below 3mA
 = 20 to 4mA Signal, the Optidrive will trip and show the fault code  if the signal level falls below 3mA
 = 20 to 4mA Signal, the Optidrive will ramp to stop if the signal level falls below 3mA
P-48 Standby Mode Timer 0.0 250.0 0.0 s
When standby mode is enabled, the drive will enter standby mode following a period of operating at minimum speed (P-02) for the
time set in P-48. When in Standby Mode, the drive display shows , and the output to the motor is disabled.
Standby mode can be disabled by setting P-48 = 0.0
P-49 PI Control Wake Up Error Level 0.0 100.0 0.0 %
When the drive is operating in PI Control Mode (P-12 = 5 or 6), and Standby Mode is enabled (P-48 > 0.0), P-49 can be used to define
the PI Error Level (E.g. difference between the setpoint and feedback) for which the drive will remain in Standby Mode. This allows
the drive to ignore small feedback errors and remain in Standby mode until the feedback drops sufficiently.
P-50 Thermal Overload Value Retention 0 1 0 -
0 : Disabled.
1 : Enabled. All Optidrives feature electronic thermal overload protection for the connected motor, designed to protect the motor
against damage. An internal overload accumulator monitors the motor output current over time, and will trip the drive if the usage
exceeds the thermal limit. When P-50 is disabled, removing the power supply from the drive and re-applying will reset the value of
the accumulator. When P-50 is enabled, the value is retained during power off.

6.3. Adjusting the Voltage / Frequency (V/f) characteristics


The V/f characteristic is defined by several parameters as follows :-
P-07 : Motor Rated Voltage
P-09 : Motor Rated Frequency
The voltage set in parameter P-07 is applied to the motor at the frequency set Under
normal operating conditions, the voltage is linearly reduced at any point below the
motor rated frequency to maintain a constant motor torque output as shown by the
line ‘A’ on the graph.
Voltage

By using parameters P-28 and P-29, the voltage to be applied at a particular frequency
can be directly set by the user, thereby altering the V/F characteristic.
Reducing the voltage at a particular frequency reduces the current in the motor and
hence the torque and power, hence this function can be used in fan and pump
applications where a variable torque output is desired by setting the parameters as
follows :-
P-28 = P-07 / 4
P-29 = P-09 / 2
This function can also be useful if motor instability is experienced at certain
Frequency frequencies, if this is the case increase or decrease the voltage (P-28) at the speed of
instability (P-29).

For applications requiring energy saving, typically HVAC and pumping, the energy
optimiser (P-06) parameter can be enabled. This automatically reduces the applied
motor voltage on light load.

www.invertekdrives.com
20
Optidrive ODE-2 User Guide Revision 3.30

6.4. P-00 Read Only Status Parameters

6
Description Display range Explanation
 1st Analog input value 0 … 100% 100% = max input voltage

Parameters
 2nd Analog input value 0 … 100% 100% = max input voltage
 Speed reference input -P-01 … P-01 Displayed in Hz if P-10 = 0, otherwise displayed in RPM
 Digital input status Binary value Drive digital input status
 Internal Temperature -10 - 50ᵒC Displays the internal drive temperature
DC Bus Ripple Displays the level of voltage ripple present on the DC Bus, used
 0 – 150V
for phase loss and imbalance monitoring
 Applied motor voltage 0 … 600V AC Value of RMS voltage applied to motor
 DC bus voltage 0 … 1000V dc Internal DC bus voltage
°
 Internal Heatsink temperature -20 … 100 °C Temperature of heatsink in C
 Hours run meter 0 to 99 999 hours Not affected by resetting factory default parameters
Run time since last trip (1) Run-time clock stopped by drive disable (or trip), reset on next
 0 to 99 999 hours enable only if a trip occurred. Reset also on next enable after a
drive power down.
Run time since last trip (2) Run-time clock stopped by drive disable (or trip), reset on next
enable only if a trip occurred (under-volts not considered a trip)
 0 to 99 999 hours
– not reset by power down / power up cycling unless a trip
occurred prior to power down
Run time since last disable Run-time clock stopped on drive disable, value reset on next
 0 to 99 999 hours
enable
Drive Effective Switching Actual drive effective output switching frequency. This value
Frequency maybe lower than the selected frequency in P-17 if the drive is
 4 to 32 kHz too hot. The drive will automatically reduce the switching
frequency to prevent an over temperature trip and maintain
operation.
 DC bus voltage log 0 … 1000V 8 most recent values prior to trip, updated every 250ms
 Thermistor temperature log -20 … 120 °C 8 most recent values prior to trip, updated every 500ms
Motor current 0 to 2x rated 8 most recent values prior to trip, updated every 250ms

current
Software ID, IO & motor ctrl Version number and checksum.
 e.g. “1.00”, “47AE” “1” on LH side indicates I/O processor,
“2“ indicates motor control
Drive serial number 000000 … 999999 Unique drive serial number

00-000 … 99-999 e.g. 540102 / 32 / 005
Drive identifier Drive rating, drive type
 Drive rating
e.g. 0.37, 1 230,3P-out
Parameter group zero access and navigation
When P-14 = P-37, all P-00 parameters are visible. Default value is 101.
When the user scrolls to P-00, pressing will display “XX”, where XX represents the secondary number within P-00. (i.e. 1 to 20). The
User can then scroll to the required P-00 parameter.
Pressing once more will then display the value of that particular group zero parameter.
For those parameters which have multiple values (e.g. software ID), pressing the and keys will display the different values within that
parameter.
Pressing returns to the next level up. If is then pressed again (without pressing or ), the display changes to the next level up
(main parameter level, i.e. P-00).
If or is pressed whilst on the lower level (e.g. P00-05) to change the P-00 index, pressing <NAVIGATE> quickly displays that parameter
value.

www.invertekdrives.com
21
Optidrive ODE-2 User Guide Revision 3.30

7. Analog and Digital Input Configurations


7

7.1. Terminal Mode (P-12 = 0)


Analog and Digital Input Configurations

P-15 Digital input 1 (T2) Digital input 2 (T3) Digital input 3 (T4) Analog input (T6) Comments
Open: Stop (disable) Open : Forward run Open : Analog speed ref
0 Analog input 1 reference
Closed: Run (enable) Closed : Reverse run Closed : Preset speed 1
Open: Stop (disable) Open: Analog speed ref Open: Preset speed 1
1 Analog input 1 reference
Closed: Run (enable) Closed : Preset speed 1/2 Closed : Preset speed 2
Digital Input 2 Digital Input 3 Preset Speed
4 Preset speeds selectable.
Open Open Preset Speed 1
Analog input used as digital
Open: Stop (disable) Open: Preset speeds 1-4
2 Closed Open Preset Speed 2 input Closed status: 8V < Vin
Closed: Run (enable) Closed : Max Speed(P-01)
< 30V
Open Closed Preset Speed 3
Closed Closed Preset Speed 4
External trip input : Connect external motor
Open: Stop (disable) Open : Analog speed ref
3 Open: Trip, Analog input 1 reference thermistor PTC type or
Closed: Run (enable) Closed : Preset speed 1
Closed: Run similar to digital input 3
Open: Stop (disable) Open : Analog input 1 Switches between analog
4 Analog input 2 reference Analog input 1 reference
Closed: Run (enable) Closed : Analog input 2 inputs 1 and 2
Closing digital inputs 1 and 2
Open: Fwd Stop Open: Reverse Stop Open : Analog speed ref
5 Analog input 1 reference together carries out a fast
Closed: Fwd Run Closed: Reverse Run Closed : Preset speed 1
stop (P-24)
External trip input : Connect external motor
Open: Stop (disable) Open : Forward
6 Open: Trip, Analog input 1 reference thermistor PTC type or
Closed: Run (enable) Closed : Reverse
Closed: Run similar to digital input 3
External trip input : Closing digital inputs 1 and 2
Open: Stop (disable) Open: Stop (disable)
7 Open: Trip, Analog input 1 reference together carries out a fast
Closed: Fwd Run (enable) Closed: Rev Run (enable)
Closed: Run stop (P-24)
Digital Input 3 Analog Input 1 Preset Speed
Open Open Preset Speed 1
Open: Stop (disable) Open : Forward
8 Closed Open Preset Speed 2
Closed: Run (enable) Closed : Reverse
Open Closed Preset Speed 3
Closed Closed Preset Speed 4
Digital Input 3 Analog Input 1 Preset Speed
Open: Stop (disable) Open: Stop (disable) Open Open Preset Speed 1 Closing digital inputs 1 and 2
9 Closed: Forward Run Closed: Reverse Run Closed Open Preset Speed 2 together carries out a fast
(enable) (enable) Open Closed Preset Speed 3 stop (P-24)
Closed Closed Preset Speed 4
Normally Open (NO) Normally Closed (NC) Open : Analog speed ref
10 Analog input 1 reference
Momentary close to run Momentary open to stop Closed:Preset speed 1
Closing digital inputs 1 and 3
Normally Open (NO) Normally Closed (NC) Normally Open (NO)
11 Analog input 1 reference together carries out a fast
Momentary close to run Momentary open to stop Momentary close to rev
stop (P-24)
Open: Stop (disable) Open: Fast Stop (disable) Open : Analog speed ref
12 Analog input 1 reference
Closed: Run (enable) Closed: Run (enable) Closed : Preset speed 1
NOTE Negative Preset Speeds will be inverted if Run Reverse selected

Typical Applications
Terminal Mode P-12=0, P-15=0 Terminal Mode P-12=0, P-15 = 1 Terminal Mode P-12=0, P-15=2
+24 Volt +24 Volt +24 Volt

Run (Enable) Run (Enable) Run (Enable)

For / Rev Analog / Preset Preset Speeds 1 – 4


Select
Analog / Preset Preset1 / Preset2

+ 10 Volts + 10 Volts

Reference Reference Preset / Max

0 Volts 0 Volts

Analog speed input with 1 preset speed and Analog speed input with 2 preset speeds 4 preset speeds and max speed select switch.
fwd/rev switch Effectively giving 5 preset speeds

www.invertekdrives.com
22
Optidrive ODE-2 User Guide Revision 3.30
Terminal Mode P-12=0, P-15=3 Terminal Mode P-12=0, P-15=4 Terminal Mode P-12=0, P-15=11

7
+24 Volt +24 Volt +24 Volt

Analog and Digital Input Configurations


Run (Enable) Run (Enable) Run Forward
Local / Remote
Analog / Preset 1 Stop
(Hand / Auto)
Remote (Auto)
External Trip Run Reverse
Reference
+ 10 Volts + 10 Volts + 10 Volts
Local (Hand)
Reference Reference
Reference
0 Volts 0 Volts 0 Volts
Analog speed input with 1 preset speed and Local or remote analog speeds Push button fwd/rev/stop with fast stop
nd
motor thermistor trip (2 analog inputs) using 2 deceleration ramp

7.2. Keypad Mode (P-12 = 1 or 2)


P-15 Digital input 1 (T2) Digital input 2 (T3) Digital input 3 (T4) Analog input (T6) Comments
0, 5, Open: Stop (disable) Closed : remote UP push- Closed : remote DOWN Open : Forward
8..12 Closed: Run (enable) button push-button +24V : Reverse
Open: Stop (disable) Speed reference = PI
1 No effect No effect No effect
Closed: Run (enable) Controller Output
Open: Stop (disable) Closed : remote UP push- Closed : remote DOWN Open : Keypad speed ref
2
Closed: Run (enable) button push-button +24V : Preset speed 1
Connect external motor
Open: Stop (disable) Closed : remote UP push- External trip input : Closed : remote DOWN
3 1) thermistor PTC type or
Closed: Run (enable) button Open: Trip, Closed: Run push-button
similar to digital input 3
Open: Stop (disable) Closed : remote UP push- Open : Keypad speed ref
4 Analog input 1
Closed: Run (enable) button Closed : Analog input 1
Connect external motor
Open: Stop (disable) Open : Forward run External trip input : Open : Keypad speed ref
6 1) thermistor PTC type or
Closed: Run (enable) Closed : Reverse run Open: Trip, Closed: Run +24V : Preset speed 1
similar to digital input 3
Closing digital inputs 1 and 2
Open: Forward Stop Open: Reverse Stop External trip input : Open : Keypad speed ref
7 together carries out a fast
Closed: Forward Run Closed: Reverse Run Open: Trip, Closed: Run +24V : Preset speed 1
stop (P-24)
Example Wiring
Keypad Mode P-12=1 or 2, P-15=0
+24 Volt

Run (Enable)

Increase Speed

Reduce Speed

+ 10 Volts

Forward / Reverse

0 Volts
Remote push button speed control with
fwd/rev

By default if the enable signal is present the drive will not Enable until the START button is pressed. To automatically enable the drive when the
NOTE
enable signal is present set P-31 = 2 or 3. This then disables the use of the START & STOP buttons

www.invertekdrives.com
23
Optidrive ODE-2 User Guide Revision 3.30

7.3. Modbus Control Mode (P-12 = 3 or 4)


7

P-15 Digital input 1 (T2) Digital input 2 (T3) Digital input 3 (T4) Analog input (T6) Comments
Run and stop commands
Analog and Digital Input Configurations

0, 2,
Open: Stop (disable) given via the RS485 link and
4..5, No effect No effect No effect
Closed: Run (enable) Digital input 1 must be closed
8..12
for the drive to run.
Open: Stop (disable) Speed reference = PI
1 No effect No effect No effect
Closed: Run (enable) Controller Output
Connect external motor
Open: Stop (disable) Open : Master speed ref External trip input :
3 1) No effect thermistor PTC type or
Closed: Run (enable) Closed : Preset speed 1 Open: Trip, Closed: Run
similar to digital input 3
Open: Stop (disable) Open : Master speed ref External trip input : Master Speed Ref - start and
6 1) Analog input reference
Closed: Run (enable) Closed : Analog input Open: Trip, Closed: Run stop controlled via RS485.
Keypad Speed Ref - drive
Open: Stop (disable) Open : Master speed ref External trip input : auto runs if digital input 1
7 1) No effect
Closed: Run (enable) Closed : keypad speed ref Open: Trip, Closed: Run closed, depending on P-31
setting
For further information on the MODBUS RTU Register Map information and communication setup; please contact your Invertek Drives Sales
Partner.
7.4. User PI Control Mode (P-12 = 5 or 6)
P-15 Digital input 1 (T2) Digital input 2 (T3) Digital input 3 (T4) Analog input (T6) Comments
Analog Input 1 can provide
0, 2, Open: Stop (disable) Open : PI control
PI feedback analog input Analog input 1 an adjustable PI setpoint, by
9..12 Closed: Run (enable) Closed : Preset speed 1
setting P-44 = 1
Analog Input 1 can provide
Open: Stop (disable) Open : PI control
1 PI feedback analog input Analog input 1 an adjustable PI setpoint, by
Closed: Run (enable) Closed : Analog input 1
setting P-44 = 1
Connect external motor
Open: Stop (disable) Open : PI control External trip input :
3, 7 1) PI feedback analog input thermistor PTC type or
Closed: Run (enable) Closed : Preset speed 1 Open: Trip, Closed: Run
similar to digital input 3
Normally Open (NO) Normally Closed (NC) Normally Open (NO)
4 PI Feedback Analog Input Analog Input 1
Momentary close to run Momentary open to stop Momentary close to run
Normally Open (NO) Normally Closed (NC) Open: PI Control Normally Open (NO)
5 PI Feedback Analog Input
Momentary close to run Momentary open to stop Closed: Preset Speed 1 Momentary close to run
Normally Open (NO) Normally Closed (NC) Open: External Trip Normally Open (NO)
6 PI Feedback Analog Input
Momentary close to run Momentary open to stop Closed: Run Momentary close to run
Analog Input 1 can provide
Open: Stop (disable) Open : Forward run
8 PI feedback analog input Analog input 1 an adjustable PI setpoint, by
Closed: Run (enable) Closed : Reverse run
setting P-44 = 1

Example Wiring
PI Mode P-12=5, P-15=0 PI Mode P-12=5, P-15=1 PI Mode P-12=5, P-15=3
+24 Volt +24 Volt +24 Volt

Run (Enable) Run (Enable) Run (Enable)

PI / Preset Speed 1 PI / Local (Hand) PI / Preset Speed 1

PI Feedback PI Feedback External Trip

+10 Volt

Local (Hand) Ref PI Feedback

0 Volt 0 Volt 0 Volt

Remote closed loop PI feedback control Remote closed loop PI feedback control with Remote closed loop PI feedback control with
with Local Preset speed 1 Local Analog speed input Local Preset speed 1 and motor thermistor
trip

NOTE By default the PI reference is set for a digital reference level set in P-45.
When using an Analog reference set P-44 = 1 (analog) and connect reference signal to analog input 1 (T6).
The default settings for proportional gain (P-41), integral gain (P-42) and feedback mode (P-43) are suitable for most HVAC and pumping
applications.
The analog reference used for PI controller can also be used as the local speed reference when P15=1.

7.5. Motor Thermistor Connection


The motor thermistor should be connected between terminals 1 and 4 as shown. A
1 : + 24 Volt
setting of P-15 where Digital Input 3 is programmed for ‘External Trip’ must be used.
The current flow through the thermistor is automatically controlled to prevent a
4 : External Trip
failure.

www.invertekdrives.com
24
Optidrive ODE-2 User Guide Revision 3.30

8. Modbus RTU Communications

8
8.1. Introduction

Modbus RTU Communications


The Optidrive E2 can be connected to a Modbus RTU network via the RJ45 connector on the front of the drive.
8.2. Modbus RTU Specification
Protocol Modbus RTU
Error check CRC
Baud rate 9600bps, 19200bps, 38400bps, 57600bps, 115200bps (default)
Data format 1 start bit, 8 data bits, 1 stop bits, no parity.
Physical signal RS 485 (2-wire)
User interface RJ45

8.3. RJ45 Connector Configuration


For full MODBUS RTU register map 1 No Connection
2 No Connection
information please refer to your Invertek 3 0 Volts
Drives Sales Partner. 4 -RS485 (PC)
5 +RS485 (PC)
6 +24 Volt
When using MODBUS control the Analog and 7 -RS485 (Modbus RTU)
8 +RS485 (Modbus RTU)
Digital Inputs
can be configured as shown in section 7.3
Warning:
This is not an Ethernet
connection. Do not connect
directly to an Ethernet port.

8.4. Modbus Telegram Structure


The Optidrive ODE-2 supports Master / Slave Modbus RTU communications, using the 03 Read Holding Registers and 06 Write Single Holding
Register commands. Many Master devices treat the first Register address as Register 0, therefore it may be necessary to convert the Register
Numbers detail in section 8.5 by subtracting 1 to obtain the correct Register address. The telegram structure is as follows:-

Command 03 – Read Holding Registers Command 06 – Write Single Holding Register


Master Telegram Length Slave Response Length Master Telegram Length Slave Response Length
Slave Address 1 Byte Slave Address 1 Byte Slave Address 1 Byte Slave Address 1 Byte
Function Code (03) 1 Byte Starting Address 1 Byte Function Code (06) 1 Byte Function Code (06) 1 Byte
1st Register Address 2 Bytes 1st Register Value 2 Bytes Register Address 2 Bytes Register Address 2 Bytes
No. Of Registers 2 Bytes 2nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes
CRC Checksum 2 Bytes Etc... CRC Checksum 2 Bytes CRC Checksum 2 Bytes
CRC Checksum 2 Bytes

8.5. Modbus Register Map


Register Par. Supported Function
Type Range Explanation
Number Commands Low Byte High Byte
1 - R/W 03,06 Drive Control Command 0..3 16 Bit Word.
Bit 0 : Low = Stop, High = Run Enable
Bit 1 : Low = Decel Ramp 1 (P-04), High = Decel
Ramp 2 (P-24)
Bit 2 : Low = No Function, High = Fault Reset
Bit 3 : Low – No Function, High = Coast Stop
Request
2 - R/W 03,06 Modbus Speed reference setpoint 0..5000 Setpoint frequency x10, e.g. 100 = 10.0Hz
4 - R/W 03,06 Acceleration and Deceleration Time 0..60000 Ramp time in seconds x 100, e.g. 250 = 2.5 seconds
6 - R 03 Error code Drive status Low Byte = Drive Error Code, see section 10.1
High Byte = Drive Status as follows :-
0 : Drive Stopped
1: Drive Running
2: Drive Tripped
7 R 03 Output Motor Frequency 0..20000 Output frequency in Hz x10, e.g. 100 = 10.0Hz
8 R 03 Output Motor Current 0..480 Output Motor Current in Amps x10, e.g. 10 = 1.0 Amps
11 - R 03 Digital input status 0..15 Indicates the status of the 4 digital inputs
Lowest Bit = 1 Input 1
20 P00-01 R 03 Analog Input 1 value 0..1000 Analog input % of full scale x10, e.g. 1000 = 100%
21 P00-02 R 03 Analog Input 2 value 0..1000 Analog input % of full scale x10, e.g. 1000 = 100%
22 P00-03 R 03 Speed Reference Value 0..1000 Displays the setpoint frequency x10, e.g. 100 = 10.0Hz
23 P00-08 R 03 DC bus voltage 0..1000 DC Bus Voltage in Volts
24 P00-09 R 03 Drive temperature 0..100 Drive heatsink temperature in ºC
All user configurable parameters are accessible as Holding Registers, and can be Read from or Written to using the appropriate Modbus
command. The Register number for each parameter P-04 to P-047 is defined as 128 + Parameter number, e.g. for parameter P-15, the register
number is 128 + 15 = 143. Internal scaling is used on some parameters, for further details, please contact your Invertek Drives Sales Partner.

www.invertekdrives.com
25
Optidrive ODE-2 User Guide Revision 3.30

9. Technical Data
9

9.1. Environmental
Technical Data

Operational ambient temperature range Open Drives : -10 … 50°C (frost and condensation free)
Enclosed Drives : -10 ... 40°C (frost and condensation free)
Storage ambient temperature range : -40 … 60°C
Maximum altitude : 2000m. Derate above 1000m : 1% / 100m
Maximum humidity : 95%, non-condensing
NOTE For UL compliance: the average ambient temperature over a 24 hour period for 200-240V, 2.2kW and 3HP, IP20 drives is 45°C.

9.2. Rating Tables

110 - 115 Volt (+ / - 10%) 1 Phase Input, 3 Phase 230V Output


Frame kW HP Nominal Fuse Supply Nominal Motor Maximum Recommended
Size Input Or Cable Output Cable Motor Brake
Current MCB (Type B) Size Current Size Cable Resistance
Non UL UL mm AWG / kcmil mm AWG / kcmil Length Ω
1 0.37 0.5 11.0 16 15 2.5 14 2.3 1.5 14 50 N/A
1 0.75 1 19.0 25 25 4 10 4.3 1.5 14 50 N/A
2 1.1 1.5 25.0 32 35 6 8 5.8 1.5 14 100 50

200 - 240 Volt (+ / - 10%) 1 Phase Input, 3 Phase Output


Frame kW HP Nominal Fuse Supply Nominal Motor Maximum Recommended
Size Input Or Cable Output Cable Motor Brake
Current MCB (Type B) Size Current Size Cable Resistance
Non UL UL mm AWG / kcmil mm AWG / kcmil Length Ω
1 0.37 0.5 6.4 10 10 1.5 14 2.3 1.5 14 50 N/A
1 0.75 1 8.5 16 10 1.5 14 4.3 1.5 14 50 N/A
1 1.5 2 13.9 25 20 2.5 12 7 1.5 14 50 N/A
2 1.5 2 15.2 25 20 2.5 12 7 1.5 14 100 100
2 2.2 3 19.5 25 25 4 10 10.5 1.5 14 100 50
3 4 5 30.5 40 40 4 8 16 2.5 12 100 50

200 - 240 Volt (+ / - 10%) 3 Phase Input, 3 Phase Output


Frame kW HP Nominal Fuse Supply Nominal Motor Maximum Recommended
Size Input Or Cable Output Cable Motor Brake
Current MCB (Type B) Size Current Size Cable Resistance
Non UL UL (A) mm AWG / kcmil mm AWG / kcmil Length Ω
1 0.37 0.5 3.0 6 6 1.5 14 2.3 1.5 14 50 N/A
1 0.75 1 4.5 6 6 1.5 14 4.3 1.5 14 50 N/A
1 1.5 2 7.3 10 10 1.5 14 7 1.5 14 50 N/A
2 1.5 2 7.3 10 10 1.5 14 7 1.5 14 100 100
2 2.2 3 11.0 16 15 2.5 12 10.5 1.5 14 100 50
3 4 5 18.8 20 20 4 10 18 2.5 10 100 50

380 - 480 Volt (+ / - 10%) 3 Phase Input, 3 Phase Output


Frame kW HP Nominal Fuse Supply Nominal Motor Maximum Recommended
Size (400V) (460V) Input Or Cable Output Cable Motor Brake
Current MCB (Type B) Size Current Size Cable Resistance
Non UL (A) mm AWG / kcmil mm AWG / kcmil Length Ω
UL
1 0.75 1 2.4 6 6 1.5 14 2.2 1.5 14 25 -
1 1.5 2 5.1 6 10 1.5 14 4.1 1.5 14 25 -
2 1.5 2 5.1 6 10 1.5 14 4.1 1.5 14 50 200
2 2.2 3 7.5 10 10 1.5 14 5.8 1.5 14 50 200
2 4 5 11.2 16 15 2.5 12 9.5 1.5 14 50 100
3 5.5 7.5 19.0 20 20 4 10 14 1.5 12 100 100
3 7.5 10 21.0 25 25 4 10 18 2.5 10 100 50
3 11 15 28.0 32 35 10 8 24 4 10 100 50

Note : For UL compliance, Motor Cable to be 75°C Copper, fuse current ratings in brackets (), UL Class T must be used.

www.invertekdrives.com
26
Optidrive ODE-2 User Guide Revision 3.30
9.3. Additional Information for UL Compliance

9
Optidrive E2 is designed to meet the UL requirements. In order to ensure full compliance, the following must be fully observed.
 For an up to date list of UL compliant products, please refer to UL listing NMMS.E226333

Technical Data
 The drive can be operated within an ambient temperature range as stated in section 9.1
 For IP20 units, installation is required in a pollution degree 1 environment
 For IP66 (Nema 4X) units, installation in a pollution degree 2 environment is permissible
 UL Listed ring terminals / lugs must be used for all bus bar and grounding connections

Input Power Supply Requirements


Supply Voltage 200 – 240 RMS Volts for 230 Volt rated units, + /- 10% variation allowed. 240 Volt RMS Maximum
380 – 480 Volts for 400 Volt rated units, + / - 10% variation allowed, Maximum 500 Volts RMS
Imbalance Maximum 3% voltage variation between phase – phase voltages allowed
All Optidrive E2 units have phase imbalance monitoring. A phase imbalance of > 3% will result in the drive tripping.
For input supplies which have supply imbalance greater than 3% (typically the Indian sub- continent & parts of Asia
Pacific including China) Invertek Drives recommends the installation of input line reactors.
Frequency 50 – 60Hz + / - 5% Variation
Short Circuit Capacity Voltage Rating Min kW (HP) Max kW (HP) Maximum supply short-circuit current
115V 0.37 (0.5) 1.1 (1.5) 5kA rms (AC)
230V 0.37 (0.5) 4 (5) 5kA rms (AC)
400 / 460V 0.75 (1) 11 (15) 5kA rms (AC)
All the drives in the above table are suitable for use on a circuit capable of delivering not more than the above
specified maximum short-circuit Amperes symmetrical with the specified maximum supply voltage.
Motor Cable 75°C Copper must be used
Fusing UL Class T Fuses must be used
Incoming power supply connection must be according to section 4.3
All Optidrive E2 units are intended for indoor installation within controlled environments which meet the condition limits shown in section
9.1
Branch circuit protection must be installed according to the relevant national codes. Fuse ratings and types are shown in section 9.2
Suitable Power and motor cables should be selected according to the data shown in section 9.2
Power cable connections and tightening torques are shown in section 3.1
Optidrive E2 provides motor overload protection in accordance with the National Electrical Code (US).
 Where a motor thermistor is not fitted, or not utilised, Thermal Overload Memory Retention must be enabled by setting P-50 = 1
 Where a motor thermistor is fitted and connected to the drive, connection must be carried out according to the information shown
in section 7.5

www.invertekdrives.com
27
Optidrive ODE-2 User Guide Revision 3.30

10. Trouble Shooting


Trouble Shooting 10

10.1. Fault Code Messages


Display Fault Description Corrective Action
Fault Code Number
 0x00 Drive is healthy and in a stopped condition. The motor is not energised. No enable signal is present to start the drive
Factory Default parameters Press the STOP key, drive is ready to configure for particular application
 0X0A
have been loaded
Instantaneous Over current Fault occurs immediately on drive enable or run command
on the drive output. Check the output wiring connections to the motor and the motor for short circuits phase
Excess load or shock load on to phase and phase to earth.
the motor. Fault occurs during motor starting
Check the motor is free to rotate and there are no mechanical blockages. If the motor has
a brake fitted, check the brake is releasing correctly. Check for the correct star-delta
 0x03 motor wiring. Ensure the motor nameplate current is correctly entered in P-08. Increase
 the acceleration time in P-03. Reduce the motor boost voltage setting in P-11
Fault occurs when motor operating at constant speed
Investigate overload or malfunction.
Fault occurs during motor acceleration or deceleration
The Accel/Decel times are too short requiring too much power. If P-03 or P-04 cannot be
increased, a bigger drive may be required
Motor thermal overload Ensure the correct motor nameplate current value is entered in P-08. Check for correct
protection trip. The drive Star or Delta wiring configuration. Check to see when the decimal points are flashing
has tripped after delivering (which indicates the output current > P-08 value) and either increase acceleration ramp
.  0x04
>100% of value in P-08 for a (P-03) or decrease motor load. Check the total motor cable length is within the drive
period of time to prevent specification. Check the load mechanically to ensure it is free, and that no jams, blockages
damage to the motor. or other mechanical faults exist
Brake channel over current Check the cabling to the brake resistor and the brake resistor for short circuits or damage.
 0x01 (excessive current in the Ensure the resistance of the brake resistor is equal to or greater than the minimum value
brake resistor) for the relevant drive shown in the table in section 9.2
Brake resistor thermal Only occurs if P-34 = 1. The internal software protection for the brake resistor has
overload. The drive has activated to prevent damage to the brake resistor.
tripped to prevent damage If an Invertek standard braking resistor is being used, P-34 MUST be 1
to the brake resistor Increase the deceleration time (P-04) or 2nd deceleration time (P-24). Reduce the load
 0x02 inertia
For Other Brake Resistors
Ensure the resistance of the brake resistor is equal to or greater than the minimum value
for the relevant drive shown in the table in section 9.2. Use an external thermal
protection device for the brake resistor. In this case, P-34 may be set to 2
Hardware Over Current Check the wiring to motor and the motor for phase to phase and phase to earth short
circuits. Disconnect the motor and motor cable and retest. If the drive trips with no motor
 0x05
connected, it must be replaced and the system fully checked and retested before a
replacement unit is installed.
Over voltage on DC bus Check the supply voltage is within the allowed tolerance for the drive. If the fault occurs
. 0x06 on deceleration or stopping, increase the deceleration time in P-04 or install a suitable
brake resistor and activate the dynamic braking function with P-34
Under voltage on DC bus The incoming supply voltage is too low. This trip occurs routinely when power is removed
. 0x07 from the drive. If it occurs during running, check the incoming power supply voltage and
all components in the power feed line to the drive.
Heatsink over temperature The drive is too hot. Check the ambient temperature around the drive is within the drive
specification. Ensure sufficient cooling air is free to circulate around the drive.
 0x08
Increase the panel ventilation if required. Ensure sufficient cooling air can enter the drive,
and that the bottom entry and top exit vents are not blocked or obstructed.
Under temperature Trip occurs when ambient temperature is less than -10°C. Temperature must be raised
 0x09
over -10°C in order to start the drive.
Faulty thermistor on Refer to your IDL Authorised Distributor.
 0x10
heatsink.
External trip E-trip requested on digital input 3. Normally closed contact has opened for some reason.
 0x0B
(on digital Input 3) If motor thermistor is connected check if the motor is too hot.
Comms loss trip Check communication link between drive and external devices. Make sure each drive in
 0x0C
the network has its unique address.
 0x0E Input phase loss trip Drive intended for use with a 3 phase supply has lost one input phase.
 0x0F Spin start failed Spin start function failed to detect the motor speed.
Internal memory fault. Parameters not saved, defaults reloaded.
 0x11
Try again. If problem recurs, refer to your IDL Authorised Distributor.
Analog input current out of Check input current in range defined by P-16.
 0x12
range
 - Internal drive Fault Refer to your IDL Authorised Distributor.

 - Internal drive Fault Refer to your IDL Authorised Distributor.

 82-E2MAN-IN_V3.30
www.invertekdrives.com
28

You might also like