Invertek Drives Optidrive E2 Manual
Invertek Drives Optidrive E2 Manual
Invertek Drives Optidrive E2 Manual
30
User Guide
1
Introduction
IP20 & IP66 (NEMA 4X)
AC Variable Speed Drive
0.37 – 11kW (0.5 – 15HP)
110 – 480V
www.invertekdrives.com
1
Optidrive ODE-2 User Guide Revision 3.30
Supply Voltage
AC Supply Voltage - 110 – 115, 200 – 240, 400 – 480 VAC + / - 10%
(50 / 60 Hz) - 1 or 3 Phase
Check the drive rating information on page 26
L1 L2 L3
Earth L N
Fuses or MCB
Fuses or MCB - Fuse Ratings given on page 26
- Recommended cable sizes shown on page 26
Always follow local and national codes of practice
Mechanical Mounting
- Information can be found on page 10
Control Terminals
Based on the factory default (out of box) settings
- Connect a Start / Stop switch between terminals 1 & 2
- Close the switch to Start (Enable) the drive
- Open the switch to Stop (Disable) the drive
Motor Connections
- Check for Star or Delta connection according to the motor
nameplate and voltage rating (See page 13)
Motor Nameplate Details
- Enter the motor rated voltage in P-07
- Enter the motor rated current in P-08
- Enter the motor rated frequency in P-09
www.invertekdrives.com
2
Optidrive ODE-2 User Guide Revision 3.30
1
Easy Start Up Guide
Introduction
Mechanical Mounting
- Information can be found
on page 10
Control Terminals
Based on the factory default (out of box)
settings
- Connect a Start / Stop switch
between terminals 1 & 2
- Close the switch to Start (Enable)
the drive
- Open the switch to Stop (Disable)
the drive Keypad operation can be found
on page 16
- Connect a potentiometer (5kΩ
minimum) between terminals 5, 6
and 7 as shown below to vary the
speed from minimum (0Hz) to
maximum (50 / 60 Hz)
Earth L N
L1 L2 L3
AC Supply Voltage
(50 / 60 Hz) Motor Connections
- Check for Star or Delta
connection according to the
Supply Voltage motor nameplate and voltage
- 110 – 115, 200 – 240, 400 – 480 rating (See page 13)
VAC + / - 10% Motor Nameplate Details
- 1 or 3 Phase - Enter the motor rated voltage
Check the drive rating information on in P-07
page 26 - Enter the motor rated current
in P-08
- Enter the motor rated
frequency in P-09
www.invertekdrives.com
3
1 Optidrive ODE-2 User Guide Revision 3.30
Earth L N
L1 L2 L3
AC Supply Voltage
(50 / 60 Hz) Motor Connections
- Check for Star or Delta
connection according to
the motor nameplate and
Supply Voltage voltage rating (See page
- 110 – 115, 200 – 240, 400 – 480 13)
VAC + / - 10% Motor Nameplate Details
- 1 or 3 Phase - Enter the motor rated
Check the drive rating information on voltage in P-07
page 26 - Enter the motor rated
current in P-08
- Enter the motor rated
frequency in P-09
www.invertekdrives.com
4
Optidrive ODE-2 User Guide Revision 3.30
Declaration of Conformity
1
Invertek Drives Ltd hereby states that the Optidrive ODE-2 product range conforms to the relevant safety provisions of the Low Voltage
Directive 2006/95/EC and the EMC Directive 2004/108/EC and has been designed and manufactured in accordance with the following
Introduction
harmonised European standards:
EN 61800-5-1: 2003 Adjustable speed electrical power drive systems. Safety requirements. Electrical, thermal and energy.
nd
EN 61800-3 2 Ed: 2004 Adjustable speed electrical power drive systems. EMC requirements and specific test methods
EN 55011: 2007 Limits and Methods of measurement of radio disturbance characteristics of industrial, scientific and
medical (ISM) radio-frequency equipment (EMC)
EN60529 : 1992 Specifications for degrees of protection provided by enclosures
Electromagnetic Compatibility
All Optidrives are designed with high standards of EMC in mind. All versions suitable for operation on Single Phase 230 volt and Three Phase 400
volt supplies and intended for use within the European Union are fitted with an internal EMC filter. This EMC filter is designed to reduce the
conducted emissions back into the supply via the power cables for compliance with the above harmonised European standards.
It is the responsibility of the installer to ensure that the equipment or system into which the product is incorporated complies with the EMC
legislation of the country of use. Within the European Union, equipment into which this product is incorporated must comply with the EMC
Directive 2004/108/EC. When using an Optidrive with an internal or optional external filter, compliance with the following EMC Categories, as
defined by EN61800-3:2004 can be achieved:
3 Phase, 400 Volt Input Use External Filter OPT-2— No additional filtering required
ODE-2-x4xxx-3xAxx E3xxxx
Use shielded motor cable
Compliance with EMC standards is dependent on a number of factors including the environment in which the drive is installed,
Note
motor switching frequency, motor, cable lengths and installation methods adopted.
For shielded motor cable lengths greater than 100m and up to 200m, an output dv / dt filter must be used (please refer to the
Invertek Stock Drives Catalogue for further details)
Compliance with EMC directives is achieved with the factory default parameter settings
All rights reserved. No part of this User Guide may be reproduced or transmitted in any form or by any means, electrical or mechanical including
photocopying, recording or by any information storage or retrieval system without permission in writing from the publisher.
All Invertek Optidrive units carry a 2 year warranty against manufacturing defects from the date of manufacture. The manufacturer accepts no
liability for any damage caused during or resulting from transport, receipt of delivery, installation or commissioning. The manufacturer also
accepts no liability for damage or consequences resulting from inappropriate, negligent or incorrect installation, incorrect adjustment of the
operating parameters of the drive, incorrect matching of the drive to the motor, incorrect installation, unacceptable dust, moisture, corrosive
substances, excessive vibration or ambient temperatures outside of the design specification.
The local distributor may offer different terms and conditions at their discretion, and in all cases concerning warranty, the local distributor
should be contacted first.
This user guide is the “original instructions” document. All non-English versions are translations of the “original instructions”.
The contents of this User Guide are believed to be correct at the time of printing. In the interest of a commitment to a policy of continuous
improvement, the manufacturer reserves the right to change the specification of the product or its performance or the contents of the User
Guide without notice.
Invertek Drives Ltd adopts a policy of continuous improvement and whilst every effort has been made to provide accurate and up to date
information, the information contained in this User Guide should be used for guidance purposes only and does not form the part of any
contract.
www.invertekdrives.com
5
Optidrive ODE-2 User Guide Revision 3.30
1. Introduction ........................................................................................................................................................................7
1
1.1. Important Safety Information 7
2. General Information and Ratings ........................................................................................................................................8
Introduction
www.invertekdrives.com
6
Optidrive ODE-2 User Guide Revision 3.30
1. Introduction
1
1.1. Important Safety Information
Introduction
Please read the IMPORTANT SAFETY INFORMATION below, and all Warning and Caution information elsewhere.
Danger : Indicates a risk of electric shock, which, if not Danger : Indicates a potentially hazardous situation
avoided, could result in damage to the equipment and other than electrical, which if not avoided, could
possible injury or death. result in damage to property.
This variable speed drive product (Optidrive) is intended for professional incorporation into complete equipment or systems as
part of a fixed installation. If installed incorrectly it may present a safety hazard. The Optidrive uses high voltages and currents,
carries a high level of stored electrical energy, and is used to control mechanical plant that may cause injury. Close attention is
required to system design and electrical installation to avoid hazards in either normal operation or in the event of equipment
malfunction. Only qualified electricians are allowed to install and maintain this product.
System design, installation, commissioning and maintenance must be carried out only by personnel who have the necessary
training and experience. They must carefully read this safety information and the instructions in this Guide and follow all
information regarding transport, storage, installation and use of the Optidrive, including the specified environmental limitations.
Do not perform any flash test or voltage withstand test on the Optidrive. Any electrical measurements required should be carried
out with the Optidrive disconnected.
Electric shock hazard! Disconnect and ISOLATE the Optidrive before attempting any work on it. High voltages are present at the
terminals and within the drive for up to 10 minutes after disconnection of the electrical supply. Always ensure by using a suitable
multimeter that no voltage is present on any drive power terminals prior to commencing any work.
Where supply to the drive is through a plug and socket connector, do not disconnect until 10 minutes have elapsed after turning
off the supply.
Ensure correct earthing connections. The earth cable must be sufficient to carry the maximum supply fault current which
normally will be limited by the fuses or MCB. Suitably rated fuses or MCB should be fitted in the mains supply to the drive,
according to any local legislation or codes.
Ensure correct earthing connections and cable selection as per defined by local legislation or codes. The drive may have a
leakage current of greater than 3.5mA; furthermore the earth cable must be sufficient to carry the maximum supply fault current
which normally will be limited by the fuses or MCB. Suitably rated fuses or MCB should be fitted in the mains supply to the drive,
according to any local legislation or codes.
Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits.
Within the European Union, all machinery in which this product is used must comply with Directive 2006/42/EC, Safety of
Machinery. In particular, the machine manufacturer is responsible for providing a main switch and ensuring the electrical
equipment complies with EN60204-1.
The level of integrity offered by the Optidrive control input functions – for example stop/start, forward/reverse and maximum
speed is not sufficient for use in safety-critical applications without independent channels of protection. All applications where
malfunction could cause injury or loss of life must be subject to a risk assessment and further protection provided where needed.
The driven motor can start at power up if the enable input signal is present.
The STOP function does not remove potentially lethal high voltages. ISOLATE the drive and wait 10 minutes before starting any
work on it. Never carry out any work on the Drive, Motor or Motor cable whilst the input power is still applied.
The Optidrive can be programmed to operate the driven motor at speeds above or below the speed achieved when connecting
the motor directly to the mains supply. Obtain confirmation from the manufacturers of the motor and the driven machine about
suitability for operation over the intended speed range prior to machine start up.
Do not activate the automatic fault reset function on any systems whereby this may cause a potentially dangerous situation.
IP66 drives provide their own pollution degree 2 environments. IP20 drives must be installed in a pollution degree 2
environment, mounted in a cabinet with IP54 or better.
Optidrives are intended for indoor use only.
When mounting the drive, ensure that sufficient cooling is provided. Do not carry out drilling operations with the drive in place,
dust and swarf from drilling may lead to damage.
The entry of conductive or flammable foreign bodies should be prevented. Flammable material should not be placed close to the
drive
Relative humidity must be less than 95% (non-condensing).
Ensure that the supply voltage, frequency and no. of phases (1 or 3 phase) correspond to the rating of the Optidrive as delivered.
Never connect the mains power supply to the Output terminals U, V, W.
Do not install any type of automatic switchgear between the drive and the motor
Wherever control cabling is close to power cabling, maintain a minimum separation of 100 mm and arrange crossings at 90
degrees
Ensure that all terminals are tightened to the appropriate torque setting
Do not attempt to carry out any repair of the Optidrive. In the case of suspected fault or malfunction, contact your local Invertek
Drives Sales Partner for further assistance.
www.invertekdrives.com
7
Optidrive ODE-2 User Guide Revision 3.30
This chapter contains information about the Optidrive E2 including how to identify the drive
General Information and Ratings
ODE - 2 - 1 2 037 - 1 K B 1 2
Product Family IP Rating 2 = IP20
Generation X = IP66 Non Switched
Y = IP66 Switched
Dynamic Brake 1 = Not Fitted
Transistor 4 = Internal Transistor
Frame Size Filter Type 0 = No Filter
A = Internal 400V EMC Filter
B = Internal 230V EMC Filter
Input Voltage 1 = 110 – 115 Power Type K = kW
2 = 200 – 240 H = HP
4 = 380 - 480
Power Rating No. Of Input Phases
2.2. Drive Model Numbers
110-115V ±10% - 1 Phase Input - 3 Phase 230V Output (Voltage Doubler)
kW Model Number HP Model Number Frame
kW HP Output Current (A)
With Filter Without Filter With Filter Without Filter Size
www.invertekdrives.com
8
Optidrive ODE-2 User Guide Revision 3.30
3. Mechanical Installation
3
3.1. General
Mechanical Installation
The Optidrive should be mounted in a vertical position only, on a flat, flame resistant, vibration free mounting using the integral
mounting holes or DIN Rail clip (Frame Sizes 1 and 2 only).
The Optidrive must be installed in a pollution degree 1 or 2 environment only.
Do not mount flammable material close to the Optidrive
Ensure that the minimum cooling air gaps, as detailed in section 3.5 and 3.7 are left clear
Ensure that the ambient temperature range does not exceed the permissible limits for the Optidrive given in section 9.1
Provide suitable clean, moisture and contaminant free cooling air sufficient to fulfil the cooling requirements of the Optidrive
3.2. Before Installation
Carefully Unpack the Optidrive and check for any signs of damage. Notify the shipper immediately if any exist.
Check the drive rating label to ensure it is of the correct type and power requirements for the application.
To prevent accidental damage always store the Optidrive in its original box until required. Storage should be clean and dry and within
the temperature range –40°C to +60°C
3.3. UL Compliant Installation
Refer to section 9.3 on page 27 for Additional Information for UL Compliance.
3.4. Mechanical Dimensions and Mounting – IP20 Open Units
Drive A B C D E F G H I J Weight
Size mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in Kg lb
1 173 6.81 160 6.30 109 4.29 162 6.38 5 0.20 123 4.84 83 3.27 50 1.97 5.5 0.22 10 0.39 1.0 2.2
2 221 8.70 207 8.15 137 5.39 209 8.23 5.3 0.21 150 5.91 110 4.33 63 2.48 5.5 0.22 10 0.39 1.7 3.8
3 261 10.28 246 9.69 - - 247 9.72 6 0.24 175 6.89 131 5.16 80 3.15 5.5 0.22 10 0.39 3.2 7.1
Mounting Bolts All Frame Sizes 4 x M4 (#8)
Tightening Torques Control Terminals 0.5 Nm (4.5 lb-in)
All Frame Sizes
Power Terminals 1 Nm (8.85 lb-in)
www.invertekdrives.com
9
Optidrive ODE-2 User Guide Revision 3.30
Drive X Y Z Recommended
Size Above & Either
3
Between airflow
Below Side
3
Mechanical Installation
Above are guidelines only and the operating ambient temperature of the
drive MUST be maintained at all times.
Cable Gland Sizes
Frame Power Cable Motor Cable Control Cables
2 M25 (PG21) M25 (PG21) M20 (PG13.5)
3 M25 (PG21) M25 (PG21) M20 (PG13.5)
www.invertekdrives.com
10
Optidrive ODE-2 User Guide Revision 3.30
3.8. Gland Plate and Lock Off
3
The use of a suitable gland system is required to maintain the appropriate IP / Nema rating. The gland plate has pre moulded cable entry
holes for power and motor connections suitable for use with glands as shown in the following table. Where additional holes are required,
Mechanical Installation
these can be drilled to suitable size. Please take care when drilling to avoid leaving any particles within the product.
Cable Gland recommended Hole Sizes & types:
Power & Motor Cables Control & Signal Cables
Moulded Hole Imperial Gland Metric Gland Knockout Size Imperial Gland Metric Gland
Size
Size 1 22mm PG13.5 M20 22mm PG13.5 M20
Size 2 & 3 27mm PG21 M25 22mm PG13.5 M20
Flexible Conduit Hole Sizes:
Drill Size Trade Size Metric
Size 1 28mm ¾ in 21
Size 2 & 3 35mm 1 in 27
UL rated ingress protection ("Type " ) is only met when cables are installed using a UL recognized bushing or fitting for a flexible-
conduit system which meets the required level of protection ("Type")
For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC
Not intended for rigid conduit system
Power Isolator Lock Off
On the switched models the main power isolator switch can be locked in the ‘Off’ position using a 20mm standard shackle padlock (not
supplied).
IP66 / Nema 4X Gland Plate IP66 / Nema 4X Unit Lock Off
Checks should also be made on all electrical connections, ensuring screw terminals are correctly torqued; and that power cables have no signs
of heat damage.
www.invertekdrives.com
11
Optidrive ODE-2 User Guide Revision 3.30
4. Power Wiring
4
This manual is intended as a guide for proper installation. Invertek Drives Ltd cannot assume responsibility for the compliance
or the non-compliance to any code, national, local or otherwise, for the proper installation of this drive or associated
equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
This Optidrive contains high voltage capacitors that take time to discharge after removal of the main supply. Before working
on the drive, ensure isolation of the main supply from line inputs. Wait ten (10) minutes for the capacitors to discharge to safe
voltage levels. Failure to observe this precaution could result in severe bodily injury or loss of life.
Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved
should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in
their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
Grounding Guidelines
The ground terminal of each Optidrive should be individually connected DIRECTLY to the site ground bus bar (through the filter if installed).
Optidrive ground connections should not loop from one drive to another, or to, or from any other equipment. Ground loop impedance must
confirm to local industrial safety regulations. To meet UL regulations, UL approved ring crimp terminals should be used for all ground wiring
connections.
The drive Safety Ground must be connected to system ground. Ground impedance must conform to the requirements of national and local
industrial safety regulations and/or electrical codes. The integrity of all ground connections should be checked periodically.
Protective Earth Conductor
The Cross sectional area of the PE Conductor must be at least equal to that of the incoming supply conductor.
Safety Ground
This is the safety ground for the drive that is required by code. One of these points must be connected to adjacent building steel (girder, joist), a
floor ground rod, or bus bar. Grounding points must comply with national and local industrial safety regulations and/or electrical codes.
Motor Ground
The motor ground must be connected to one of the ground terminals on the drive.
Ground Fault Monitoring
As with all inverters, a leakage current to earth can exist. The Optidrive is designed to produce the minimum possible leakage current whilst
complying with worldwide standards. The level of current is affected by motor cable length and type, the effective switching frequency, the
earth connections used and the type of RFI filter installed. If an ELCB (Earth Leakage Circuit Breaker) is to be used, the following conditions
apply: -
A Type B Device must be used
The device must be suitable for protecting equipment with a DC component in the leakage current
Individual ELCBs should be used for each Optidrive
Drives with an EMC filter have an inherently higher leakage current to Ground (Earth). For applications where tripping occurs the EMC filter can
be disconnected (on IP20 units only) by removing the EMC screw on the side of the product.
Remove the screws as indicated below
The Optidrive product range has input supply voltage surge suppression components fitted to protect the drive from line voltage transients,
typically originating from lightning strikes or switching of high power equipment on the same supply.
When carrying out a HiPot (Flash) test on an installation in which the drive is built, the voltage surge suppression components may cause the
test to fail. To accommodate this type of system HiPot test, the voltage surge suppression components can be disconnected by removing the
VAR screw. After completing the HiPot test, the screw should be replaced and the HiPot test repeated. The test should then fail, indicating that
the voltage surge suppression components are once again in circuit.
Shield Termination (Cable Screen)
The safety ground terminal provides a grounding point for the motor cable shield. The motor cable shield connected to this terminal (drive end)
should also be connected to the motor frame (motor end). Use a shield terminating or EMI clamp to connect the shield to the safety ground
terminal.
4.2. Wiring Precautions
Connect the Optidrive according to sections 4.8.1 and 4.8.2, ensuring that motor terminal box connections are correct. There are two
connections in general: Star and Delta. It is essential to ensure that the motor is connected in accordance with the voltage at which it will be
operated. For more information, refer to section 4.5 Motor Terminal Box Connections.
It is recommended that the power cabling should be 4-core PVC-insulated screened cable, laid in accordance with local industrial regulations
and codes of practice.
www.invertekdrives.com
12
Optidrive ODE-2 User Guide Revision 3.30
4
For 1 phase supply, power should be connected to L1/L, L2/N.
For 3 phase supplies, power should be connected to L1, L2, and L3. Phase sequence is not important.
Power Wiring
For compliance with CE and C Tick EMC requirements, a symmetrical shielded cable is recommended.
A fixed installation is required according to IEC61800-5-1 with a suitable disconnecting device installed between the Optidrive and the
AC Power Source. The disconnecting device must conform to the local safety code / regulations (e.g. within Europe, EN60204-1, Safety
of machinery).
The cables should be dimensioned according to any local codes or regulations. Guideline dimensions are given in section 9.2.
Suitable fuses to provide wiring protection of the input power cable should be installed in the incoming supply line, according to the
data in section 9.2. The fuses must comply with any local codes or regulations in place. In general, type gG (IEC 60269) or UL type T
fuses are suitable; however in some cases type aR fuses may be required. The operating time of the fuses must be below 0.5 seconds.
Where allowed by local regulations, suitably dimensioned type B MCB circuit breakers of equivalent rating may be utilised in place of
fuses, providing that the clearing capacity is sufficient for the installation.
When the power supply is removed from the drive, a minimum of 30 seconds should be allowed before re-applying the power. A
minimum of 5 minutes should be allowed before removing the terminal covers or connection.
The maximum permissible short circuit current at the Optidrive Power terminals as defined in IEC60439-1 is 100kA.
An optional Input Choke is recommended to be installed in the supply line for drives where any of the following conditions occur:-
o The incoming supply impedance is low or the fault level / short circuit current is high
o The supply is prone to dips or brown outs
o An imbalance exists on the supply (3 phase drives)
o The power supply to the drive is via a busbar and brush gear system (typically overhead Cranes).
In all other installations, an input choke is recommended to ensure protection of the drive against power supply faults. Part numbers
are shown in the table.
Supply Frame Size AC Input Inductor
1 OPT-2-L1016-20
230 Volt
2 OPT-2-L1025-20
1 Phase
3 N/A
2 OPT-2-L3006-20
400 Volt
2 OPT-2-L3010-20
3 Phase
3 OPT-2-L3036-20
Delta
www.invertekdrives.com
13
Optidrive ODE-2 User Guide Revision 3.30
4.6. Motor Thermal overload Protection.
4
8 Analog Output
0 – 10 Volts
9 0 Volt
10 Relay Output
11 ‘Drive Healthy’ = Closed
www.invertekdrives.com
14
Optidrive ODE-2 User Guide Revision 3.30
4.9. Using the REV/0/FWD Selector Switch (Switched Version Only)
4
By adjusting the parameter settings the Optidrive can be configured for multiple applications and not just for Forward or Reverse.
This could typically be for Hand/Off/Auto applications (also known and Local/Remote) for HVAC and pumping industries.
Power Wiring
Parameters to Set
Switch Position Notes
P-12 P-15
Factory Default Configuration
Run Reverse STOP Run Forward 0 0 Run Forward or Reverse with speed controlled from the
Local POT
Run forward with speed controlled form the local POT
STOP STOP Run Forward 0 5,7
Run Reverse - disabled
Run Forward with speed controlled from the Local POT
Preset Speed 1 STOP Run Forward 0 1
Preset Speed 1 provides a ‘Jog’ Speed set in P-20
Run Forward or Reverse with speed controlled from the
Run Reverse STOP Run Forward 0 6, 8
Local POT
Run in Hand – Speed controlled from the Local POT
Run in Auto STOP Run in Hand 0 4 Run in Auto 0 Speed controlled using Analog input 2 e.g.
from PLC with 4-20mA signal.
In Speed Control the speed is controlled from the Local
Run in Speed Control STOP Run in PI Control 5 1 POT
In PI Control, Local POT controls PI set point
In Preset Speed Control, P-20 sets the Preset Speed
Run in Preset Speed 0, 2, 4,5,
STOP Run in PI Control 5 In PI Control, POT can control the PI set point
Control 8..12
(P-44=1)
Hand – speed controlled from the Local POT
Run in Hand STOP Run in Auto 3 6
Auto – Speed Reference from Modbus
Hand – Speed reference from Preset Speed 1 (P-20)
Run in Hand STOP Run in Auto 3 3
Auto – Speed Reference from Modbus
NOTE To be able to adjust parameter P-15, extended menu access must be set in P-14 (default value is 101)
4.10. Control Terminal Connections
Default Connections Control Signal Description
Terminal
1 +24V User Output, +24V, 100mA.
10 Relay Common
www.invertekdrives.com
15
Optidrive ODE-2 User Guide Revision 3.30
5. Operation
5
The drive is configured and its operation monitored via the keypad and display.
Used to display real-time information, to access and exit
NAVIGATE
parameter edit mode and to store parameter changes
Used to increase speed in real-time mode or to increase
UP
parameter values in parameter edit mode
Used to decrease speed in real-time mode or to decrease
DOWN
parameter values in parameter edit mode
RESET / Used to reset a tripped drive.
STOP When in Keypad mode is used to Stop a running drive.
When in keypad mode, used to Start a stopped drive or to
START reverse the direction of rotation if bi-directional keypad
mode is enabled
Changing Parameters
To change a parameter value press and hold the key for >1s whilst the drive displays . The display changes to , indicating
parameter 01. Press and release the key to display the value of this parameter. Change to the required value using the and keys.
Press and release the key once more to store the change. Press and hold the key for >1s to return to real-time mode. The display shows
if the drive is stopped or the real-time information (e.g. speed) if the drive is running.
Reset Factory Default Settings
To reset factory default parameters, press , and for >2s. The display shows . Press the button to acknowledge and reset
the drive.
5.2. Terminal Control
When delivered, the Optidrive is in the factory default state, meaning that it is set to operate in terminal control mode and all parameters (P-xx)
have the default values as indicated in section 6 Parameters.
1. Connect the drive and motor according to the connection diagram shown at the beginning of this User Guide
2. Enter motor data from motor nameplate, P-07 = motor rated voltage, P-08 = motor rated current, P-09 = motor rated frequency.
3. With the potentiometer set to zero, switch on the supply to the drive. The display will show .
4. Close the control switch, terminals 1-2. The drive is now ‘enabled’ and the output frequency/speed are controlled by the
potentiometer. The display shows zero speed in Hz (.) with the potentiometer turned to minimum.
5. Turn the potentiometer to maximum. The motor will accelerate to 50Hz (the default value of P-01) under the control of the
accelerating ramp time P-03. The display shows 50Hz (.) at max speed.
6. To display motor current (A), briefly press the (Navigate) key.
7. Press again to return to speed display.
8. To stop the motor, either turn the potentiometer back to zero or disable the drive by opening the control switch (terminals 1-2).
If the enable/disable switch is opened the drive will decelerate to stop at which time the display will show . If the potentiometer is turned
to zero with the enable/disable closed the display will show .(0.0Hz), if left like this for 20 seconds the drive will go into standby mode,
display shows , waiting for a speed reference signal.
5.3. Keypad Control
To allow the Optidrive to be controlled from the keypad in a forward direction only, set P-12 =1:
1. Connect the drive and motor according to the connection diagram shown at the beginning of this User Guide
2. Enable the drive by closing the switch between control terminals 1 & 2. The display will show .
3. Press the key. The display shows ..
4. Press to increase speed.
5. The drive will run forward, increasing speed until is released. The rate of acceleration is controlled by the setting of P-03, check this
before starting.
6. Press to decrease speed. The drive will decrease speed until is released. The rate of deceleration is limited by the setting in P-
04
7. Press the key. The drive will decelerate to rest at the rate set in P-04.
8. The display will finally show at which point the drive is disabled
9. To preset a target speed prior to enable, press the key whilst the drive is stopped. The display will show the target speed, use the
& keys to adjust as required then press the key to return the display to .
10. Pressing the key will start the drive accelerating to the target speed.
To allow the Optidrive to be controlled from the keypad in a forward and reverse direction, set P-12 =2:
11. Operation is the same as when P-12=1 for start, stop and changing speed.
12. Press the key. The display changes to ..
13. Press to increase speed
14. The drive will run forward, increasing speed until is released. Acceleration is limited by the setting in P-03. The maximum speed is
the speed set in P-01.
15. To reverse the direction of rotation of the motor, press the key again.
www.invertekdrives.com
16
Optidrive ODE-2 User Guide Revision 3.30
6. Parameters
6
6.1. Standard Parameters
Parameters
Par. Description Minimum Maximum Default Units
P-01 Maximum Frequency / Speed Limit P-02 500.0 50.0 (60.0) Hz / Rpm
Maximum output frequency or motor speed limit – Hz or rpm. If P-10 >0, the value entered / displayed is in Rpm
P-02 Minimum Frequency / Speed Limit 0.0 P-01 0.0 Hz / Rpm
Minimum speed limit – Hz or rpm. If P-10 >0, the value entered / displayed is in Rpm
P-03 Acceleration Ramp Time 0.00 600.0 5.0 s
Acceleration ramp time from 0.0 to base frequency (P-09) in seconds.
P-04 Deceleration Ramp Time 0.00 600.0 5.0 s
Deceleration ramp time from base frequency (P-09) to standstill in seconds. When set to 0.00, the value of P-24 is used.
P-05 Stopping Mode 0 2 0 -
0 : Ramp To Stop. When the enable signal is removed, the drive will ramp to stop, with the rate controlled by P-04. If the mains
supply is lost, the drive will try to continue running by reducing the speed of the load, and using the load as a generator.
1 : Coast to Stop. When the enable signal is removed, or if the mains supply is lost, the motor will coast (freewheel) to stop
2 : Ramp To Stop. When the enable signal is removed, the drive will ramp to stop, with the rate controlled by P-04. If the mains
supply is lost the drive will ramp to stop using the P-24 decel ramp with dynamic brake control.
P-06 Energy Optimiser 0 1 0 -
0 : Disabled
1 : Enabled. When enabled, the Energy Optimiser attempts to reduce the overall energy consumed by the drive and motor when
operating at constant speeds and light loads. The output voltage applied to the motor is reduced. The Energy Optimiser is intended
for applications where the drive may operate for some periods of time with constant speed and light motor load, whether constant
or variable torque.
P-07 Motor Rated Voltage 0 250 / 500 230 / 400 V
This parameter should be set to the rated (nameplate) voltage of the motor (Volts)
P-08 Motor Rated Current Drive Rating Dependent A
This parameter should be set to the rated (nameplate) current of the motor
P-09 Motor Rated Frequency 25 500 50 (60) Hz
This parameter should be set to the rated (nameplate) frequency of the motor
P-10 Motor Rated Speed 0 30000 0 Rpm
This parameter can optionally be set to the rated (nameplate) rpm of the motor. When set to the default value of zero, all speed
related parameters are displayed in Hz, and the slip compensation for the motor is disabled. Entering the value from the motor
nameplate enables the slip compensation function, and the Optidrive display will now show motor speed in estimated rpm. All
speed related parameters, such as Minimum and Maximum Speed, Preset Speeds etc. will also be displayed in Rpm.
P-11 Voltage Boost 0.0 20.0 3.0 %
Voltage boost is used to increase the applied motor voltage at low output frequencies, in order to improve low speed and starting
torque. Excessive voltage boost levels may result in increased motor current and temperature, and force ventilation of the motor
may be required. A suitable setting can usually be found by operating the motor under low load or no load conditions at
approximately 5Hz, and adjusting P-11 until the motor current is no more than 80% of the rated full load current.
P-12 Primary Command Source 0 6 0 -
0: Terminal Control. The drive responds directly to signals applied to the control terminals.
1: Uni-directional Keypad Control. The drive can be controlled in the forward direction only using an external or remote Keypad
2: Bi-directional Keypad Control. The drive can be controlled in the forward and reverse directions using an external or remote
Keypad. Pressing the keypad START button toggles between forward and reverse.
3: Modbus Network Control. Control via Modbus RTU (RS485) using the internal Accel / Decel ramps
4 : Modbus Network Control. Control via Modbus RTU (RS485) interface with Accel / Decel ramps updated via Modbus
5 : PI Control. User PI control with external feedback signal
6 : PI Analog Summation Control. PI control with external feedback signal and summation with analog input 1
P-13 Trip Log History N/A N/A N/A N/A
Previous 4 trips stored in order of occurrence, with the most recent first. Press UP or DOWN to step through all four. The most
recent trip is always displayed first. UV trip is only stored once. Further fault event logging functions are available through
parameter group zero.
P-14 Extended Menu Access code 0 9999 0 -
Set to “101” (default) for extended menu access. Change code in P-37 to prevent unauthorised access to the Extended Parameter
Set
www.invertekdrives.com
17
Optidrive ODE-2 User Guide Revision 3.30
Defines the function of the digital inputs depending on the control mode setting in P-12. See section 8, Analog and Digital Input
Configurations for more information.
P-16 Analog Input 1 Signal Format See Below U0-10 -
= 0 to 10 Volt Signal (Uni-polar). The drive will remain at 0.0Hz if the analog reference after scaling and offset are applied is
<0.0%
= 0 to 10 Volt Signal, bi-directional operation. The drive will operate the motor in the reverse direction of rotation if the
analog reference after scaling and offset are applied is <0.0%
= 0 to 20mA Signal
= 4 to 20mA Signal, the Optidrive will trip and show the fault code if the signal level falls below 3mA
= 4 to 20mA Signal, the Optidrive will run at Preset Speed 1 (P-20) if the signal level falls below 3mA
= 20 to 4mA Signal, the Optidrive will trip and show the fault code if the signal level falls below 3mA
= 20 to 4mA Signal, the Optidrive will run at Preset Speed 1 (P-20) if the signal level falls below 3mA
P-17 Maximum Effective Switching Frequency 4 32 8 / 16 kHz
Sets maximum effective switching frequency of the drive. If “rEd” is displayed, the switching frequency has been reduced to the level in P00-
14 due to excessive drive heatsink temperature.
P-18 Output Relay Function Select 0 7 1 -
Selects the function assigned to the relay output. The relay has two output terminals, Logic 1 indicates the relay is active, and
therefore terminals 10 and 11 will be linked together.
0 : Drive Enabled (Running). Logic 1 when the motor is enabled
1 : Drive Healthy. Logic 1 when power is applied to the drive and no fault exists
2 : At Target Frequency (Speed). Logic 1 when the output frequency matches the setpoint frequency
3: Drive Tripped. Logic 1 when the drive is in a fault condition
4 : Output Frequency >= Limit. Logic 1 when the output frequency exceeds the adjustable limit set in P-19
5 : Output Current >= Limit. Logic 1 when the motor current exceeds the adjustable limit set in P-19
6 : Output Frequency < Limit. Logic 1 when the output frequency is below the adjustable limit set in P-19
7 : Output Current < Limit. Logic 1 when the motor current is below the adjustable limit set in P-19
P-19 Relay Threshold Level 0.0 200.0 100.0 %
Adjustable threshold level used in conjunction with settings 4 to 7 of P-18
P-20 Preset Frequency / Speed 1 P-02 P-01 0.0 Hz / Rpm
P-21 Preset Frequency / Speed 2 P-02 P-01 0.0 Hz / Rpm
P-22 Preset Frequency / Speed 3 P-02 P-01 0.0 Hz / Rpm
P-23 Preset Frequency / Speed 4 P-02 P-01 0.0 Hz / Rpm
Preset Speeds / Frequencies selected by digital inputs depending on the setting of P-15
If P-10 = 0, the values are entered as Hz. If P-10 > 0, the values are entered as Rpm.
P-24 2nd Decel Ramp Time (Fast Stop) 0.00 25.0 0.00 s
This parameter allows an alternative deceleration ramp down time to be programmed into the Optidrive, which can be selected by
digital inputs (dependent on the setting of P-15) or selected Automatically in the case of a mains power loss if P-05 = 2.
When set to 0.00, the drive will coast to stop.
P-25 Analog Output Function Select 0 9 8 -
Digital Output Mode. Logic 1 = +24V DC
0 : Drive Enabled (Running). Logic 1 when the Optidrive is enabled (Running)
1 : Drive Healthy. Logic 1 When no Fault condition exists on the drive
2 : At Target Frequency (Speed). Logic 1 when the output frequency matches the setpoint frequency
3: Drive Tripped. Logic 1 when the drive is in a fault condition
4 : Output Frequency >= Limit. Logic 1 when the output frequency exceeds the adjustable limit set in P-19
5 : Output Current >= Limit. Logic 1 when the motor current exceeds the adjustable limit set in P-19
6 : Output Frequency < Limit. Logic 1 when the output frequency is below the adjustable limit set in P-19
7 : Output Current < Limit. Logic 1 when the motor current is below the adjustable limit set in P-19
Analog Output Mode
8 : Output Frequency (Motor Speed). 0 to P-01, resolution 0.1Hz
9 : Output (Motor) Current. 0 to 200% of P-08, resolution 0.1A
P-26 Skip frequency hysteresis band 0.0 P-01 0.0 Hz / Rpm
P-27 Skip Frequency 0.0 P-01 0.0 Hz / Rpm
The Skip Frequency function is used to avoid the Optidrive operating at a certain output frequency, for example at a frequency
which causes mechanical resonance in a particular machine. Parameter P-27 defines the centre point of the skip frequency band,
and is used conjunction with P-26. The Optidrive output frequency will ramp through the defined band at the rates set in P-03 and P-
04 respectively, and will not hold any output frequency within the defined band. If the frequency reference applied to the drive is
within the band, the Optidrive output frequency will remain at the upper or lower limit of the band.
P-28 V/F Characteristic Adjustment Voltage 0 250 / 500 0 V
P-29 V/F Characteristic Adjustment Frequency 0.0 P-09 0.0 Hz
This parameter in conjunction with P-28 sets a frequency point at which the voltage set in P-29 is applied to the motor. Care must be
taken to avoid overheating and damaging the motor when using this feature. See section 6.3 for further information.
www.invertekdrives.com
18
Optidrive ODE-2 User Guide Revision 3.30
Par. Description Minimum Maximum Default Units
P-30 Terminal Mode Restart function N/A N/A Auto-0 -
6
Defines the behaviour of the drive relating to the enable digital input and also configures the Automatic Restart function.
Parameters
: Following Power on or reset, the drive will not start if Digital Input 1 remains closed. The Input must be closed after a
power on or reset to start the drive.
: Following a Power On or Reset, the drive will automatically start if Digital Input 1 is closed.
to : Following a trip, the drive will make up to 5 attempts to restart at 20 second intervals. The drive must be
powered down to reset the counter. The numbers of restart attempts are counted, and if the drive fails to start on the final attempt,
the drive will fault with, and will require the user to manually reset the fault.
P-31 Keypad / Modbus Mode Restart Function 0 3 1 -
This parameter is active only when operating in Keypad Control Mode (P-12 = 1 or 2) or Modbus Mode (P-12 = 3 or 4). When settings
0 or 1 are used, the Keypad Start and Stop keys are active, and control terminals 1 and 2 must be linked together. Settings 2 and 3
allow the drive to be started from the control terminals directly, and the keypad Start and Stop keys are ignored.
Settings 0 and 2 : The drive will always start at the Minimum Frequency / Speed (P-02)
Settings 1 and 3 : The drive will always start at the last operating Frequency / Speed
0 : Minimum Speed, Keypad Start
1 : Previous Speed, Keypad Start
2 : Minimum Speed, Terminal Enable
3 : Previous Speed, Terminal Enable
P-32 DC Injection Time On Stop 0.0 25.0 0.0 s
Defines the time for which a DC current is injected into the motor once the output frequency reaches 0.0Hz. The voltage level is the
same as the boost level set in P-11.
P-33 Spin Start (S2 & S3 Only) / DC Injection Time On Start (S1 Only) 0 1 0 -
Frame Size 2 and 3 Drives only – Spin Start
0 : Disabled
1 : Enabled. When enabled, on start up the drive will attempt to determine if the motor is already rotating, and will begin to control
the motor from its current speed. A short delay may be observed when starting motors which are not turning.
Frame Size 1 Drives Only – DC Injection Time On Starting
Sets a time for which DC current is injected into the motor to ensure it is stopped when the drive is enabled.
P-34 Brake Chopper Enable 0 2 0 -
0 : Disabled
1 : Enabled With Software Protection. Enables the internal brake chopper with software protection for a 200W continuous rated
resistor
2 : Enabled Without Software Protection. Enables the internal brake chopper without software protection. An external thermal
protection device should be fitted.
P-35 Analog Input 1 Scaling 0.0 500.0 100.0 %
Scales the analog input by this factor, e.g. if P-16 is set for a 0 – 10V signal , and the scaling factor is set to 200.0%, a 5 volt input will
result in the drive running at maximum frequency / speed (P-01)
P-36 Modbus RTU Serial Communications Configuration See Below
This parameter has three sub settings used to configure the Modbus RTU Serial Communications. The Sub Parameters are
1st Index : Drive Address : Range 0 - 63
nd
2 Index : Baud Rate : Selects the baud rate between 9.6kbps to 115.2kbps (default) for Modbus RTU communication.
rd
3 Index : Watchdog Timeout : Defines the time for which the drive will operate without receiving a valid command telegram to
Register 1 (Drive Control Word) after the drive has been enabled. Setting 0 disables the Watchdog timer. Setting a value of 30, 100,
1000, or 3000 defines the time limit in milliseconds for operation. A ‘’ suffix selects trip on loss of communication. An ‘’ suffix
means that the drive will coast stop (output immediately disabled) but will not trip.
P-37 Access Code Definition 0 9999 101 -
Defines the access code which must be entered in P-14 to access parameters above P-14
P-38 Parameter Access Lock 0 1 0 -
0 : Unlocked. All parameters can be accessed and changed
1 : Locked. Parameter values can be displayed, but cannot be changed
P-39 Analog Input 1 Offset -500.0 500.0 0.0 %
Sets an offset, as a percentage of the full scale range of the input, which is applied to the analog input signal
P-40 Display Speed Scaling Factor 0.000 6.000 0.000 -
Allows the user to program the Optidrive to display an alternative output unit scaled from the output frequency or speed, e.g. to
display conveyer speed in metres per second. This function is disabled if P-40 = 0.00
P-41 PI Controller Proportional Gain 0.0 30.0 1.0 -
PI Controller Proportional Gain. Higher values provide a greater change in the drive output frequency in response to small changes
in the feedback signal. Too high a value can cause instability
P-42 PI Controller Integral Time 0.0 30.0 1.0 s
PI Controller Integral Time. Larger values provide a more damped response for systems where the overall process responds slowly
P-43 PI Controller Operating Mode 0 1 0 -
0 : Direct Operation. Use this mode if an increase in the motor speed should result in an increase in the feedback signal
1 : Inverse Operation. Use this mode if an increase in the motor speed should result in a decrease in the feedback signal
2 : Direct Operation, Scaled Feedback. As Option 0, but with scaled display of PI Feedback. The feedback value (0 – 100.0%) is
multiplied by the scaling factor set in P-40.
3 : Inverse Operation, Scaled Feedback. As Option 1, but with scaled display of PI Feedback. The feedback value (0 – 100.0%) is
multiplied by the scaling factor set in P-40.
www.invertekdrives.com
19
Optidrive ODE-2 User Guide Revision 3.30
Par. Description Minimum Maximum Default Units
P-44 PI Reference (Setpoint) Source Select 0 1 0 -
6
By using parameters P-28 and P-29, the voltage to be applied at a particular frequency
can be directly set by the user, thereby altering the V/F characteristic.
Reducing the voltage at a particular frequency reduces the current in the motor and
hence the torque and power, hence this function can be used in fan and pump
applications where a variable torque output is desired by setting the parameters as
follows :-
P-28 = P-07 / 4
P-29 = P-09 / 2
This function can also be useful if motor instability is experienced at certain
Frequency frequencies, if this is the case increase or decrease the voltage (P-28) at the speed of
instability (P-29).
For applications requiring energy saving, typically HVAC and pumping, the energy
optimiser (P-06) parameter can be enabled. This automatically reduces the applied
motor voltage on light load.
www.invertekdrives.com
20
Optidrive ODE-2 User Guide Revision 3.30
6
Description Display range Explanation
1st Analog input value 0 … 100% 100% = max input voltage
Parameters
2nd Analog input value 0 … 100% 100% = max input voltage
Speed reference input -P-01 … P-01 Displayed in Hz if P-10 = 0, otherwise displayed in RPM
Digital input status Binary value Drive digital input status
Internal Temperature -10 - 50ᵒC Displays the internal drive temperature
DC Bus Ripple Displays the level of voltage ripple present on the DC Bus, used
0 – 150V
for phase loss and imbalance monitoring
Applied motor voltage 0 … 600V AC Value of RMS voltage applied to motor
DC bus voltage 0 … 1000V dc Internal DC bus voltage
°
Internal Heatsink temperature -20 … 100 °C Temperature of heatsink in C
Hours run meter 0 to 99 999 hours Not affected by resetting factory default parameters
Run time since last trip (1) Run-time clock stopped by drive disable (or trip), reset on next
0 to 99 999 hours enable only if a trip occurred. Reset also on next enable after a
drive power down.
Run time since last trip (2) Run-time clock stopped by drive disable (or trip), reset on next
enable only if a trip occurred (under-volts not considered a trip)
0 to 99 999 hours
– not reset by power down / power up cycling unless a trip
occurred prior to power down
Run time since last disable Run-time clock stopped on drive disable, value reset on next
0 to 99 999 hours
enable
Drive Effective Switching Actual drive effective output switching frequency. This value
Frequency maybe lower than the selected frequency in P-17 if the drive is
4 to 32 kHz too hot. The drive will automatically reduce the switching
frequency to prevent an over temperature trip and maintain
operation.
DC bus voltage log 0 … 1000V 8 most recent values prior to trip, updated every 250ms
Thermistor temperature log -20 … 120 °C 8 most recent values prior to trip, updated every 500ms
Motor current 0 to 2x rated 8 most recent values prior to trip, updated every 250ms
current
Software ID, IO & motor ctrl Version number and checksum.
e.g. “1.00”, “47AE” “1” on LH side indicates I/O processor,
“2“ indicates motor control
Drive serial number 000000 … 999999 Unique drive serial number
00-000 … 99-999 e.g. 540102 / 32 / 005
Drive identifier Drive rating, drive type
Drive rating
e.g. 0.37, 1 230,3P-out
Parameter group zero access and navigation
When P-14 = P-37, all P-00 parameters are visible. Default value is 101.
When the user scrolls to P-00, pressing will display “XX”, where XX represents the secondary number within P-00. (i.e. 1 to 20). The
User can then scroll to the required P-00 parameter.
Pressing once more will then display the value of that particular group zero parameter.
For those parameters which have multiple values (e.g. software ID), pressing the and keys will display the different values within that
parameter.
Pressing returns to the next level up. If is then pressed again (without pressing or ), the display changes to the next level up
(main parameter level, i.e. P-00).
If or is pressed whilst on the lower level (e.g. P00-05) to change the P-00 index, pressing <NAVIGATE> quickly displays that parameter
value.
www.invertekdrives.com
21
Optidrive ODE-2 User Guide Revision 3.30
P-15 Digital input 1 (T2) Digital input 2 (T3) Digital input 3 (T4) Analog input (T6) Comments
Open: Stop (disable) Open : Forward run Open : Analog speed ref
0 Analog input 1 reference
Closed: Run (enable) Closed : Reverse run Closed : Preset speed 1
Open: Stop (disable) Open: Analog speed ref Open: Preset speed 1
1 Analog input 1 reference
Closed: Run (enable) Closed : Preset speed 1/2 Closed : Preset speed 2
Digital Input 2 Digital Input 3 Preset Speed
4 Preset speeds selectable.
Open Open Preset Speed 1
Analog input used as digital
Open: Stop (disable) Open: Preset speeds 1-4
2 Closed Open Preset Speed 2 input Closed status: 8V < Vin
Closed: Run (enable) Closed : Max Speed(P-01)
< 30V
Open Closed Preset Speed 3
Closed Closed Preset Speed 4
External trip input : Connect external motor
Open: Stop (disable) Open : Analog speed ref
3 Open: Trip, Analog input 1 reference thermistor PTC type or
Closed: Run (enable) Closed : Preset speed 1
Closed: Run similar to digital input 3
Open: Stop (disable) Open : Analog input 1 Switches between analog
4 Analog input 2 reference Analog input 1 reference
Closed: Run (enable) Closed : Analog input 2 inputs 1 and 2
Closing digital inputs 1 and 2
Open: Fwd Stop Open: Reverse Stop Open : Analog speed ref
5 Analog input 1 reference together carries out a fast
Closed: Fwd Run Closed: Reverse Run Closed : Preset speed 1
stop (P-24)
External trip input : Connect external motor
Open: Stop (disable) Open : Forward
6 Open: Trip, Analog input 1 reference thermistor PTC type or
Closed: Run (enable) Closed : Reverse
Closed: Run similar to digital input 3
External trip input : Closing digital inputs 1 and 2
Open: Stop (disable) Open: Stop (disable)
7 Open: Trip, Analog input 1 reference together carries out a fast
Closed: Fwd Run (enable) Closed: Rev Run (enable)
Closed: Run stop (P-24)
Digital Input 3 Analog Input 1 Preset Speed
Open Open Preset Speed 1
Open: Stop (disable) Open : Forward
8 Closed Open Preset Speed 2
Closed: Run (enable) Closed : Reverse
Open Closed Preset Speed 3
Closed Closed Preset Speed 4
Digital Input 3 Analog Input 1 Preset Speed
Open: Stop (disable) Open: Stop (disable) Open Open Preset Speed 1 Closing digital inputs 1 and 2
9 Closed: Forward Run Closed: Reverse Run Closed Open Preset Speed 2 together carries out a fast
(enable) (enable) Open Closed Preset Speed 3 stop (P-24)
Closed Closed Preset Speed 4
Normally Open (NO) Normally Closed (NC) Open : Analog speed ref
10 Analog input 1 reference
Momentary close to run Momentary open to stop Closed:Preset speed 1
Closing digital inputs 1 and 3
Normally Open (NO) Normally Closed (NC) Normally Open (NO)
11 Analog input 1 reference together carries out a fast
Momentary close to run Momentary open to stop Momentary close to rev
stop (P-24)
Open: Stop (disable) Open: Fast Stop (disable) Open : Analog speed ref
12 Analog input 1 reference
Closed: Run (enable) Closed: Run (enable) Closed : Preset speed 1
NOTE Negative Preset Speeds will be inverted if Run Reverse selected
Typical Applications
Terminal Mode P-12=0, P-15=0 Terminal Mode P-12=0, P-15 = 1 Terminal Mode P-12=0, P-15=2
+24 Volt +24 Volt +24 Volt
+ 10 Volts + 10 Volts
0 Volts 0 Volts
Analog speed input with 1 preset speed and Analog speed input with 2 preset speeds 4 preset speeds and max speed select switch.
fwd/rev switch Effectively giving 5 preset speeds
www.invertekdrives.com
22
Optidrive ODE-2 User Guide Revision 3.30
Terminal Mode P-12=0, P-15=3 Terminal Mode P-12=0, P-15=4 Terminal Mode P-12=0, P-15=11
7
+24 Volt +24 Volt +24 Volt
Run (Enable)
Increase Speed
Reduce Speed
+ 10 Volts
Forward / Reverse
0 Volts
Remote push button speed control with
fwd/rev
By default if the enable signal is present the drive will not Enable until the START button is pressed. To automatically enable the drive when the
NOTE
enable signal is present set P-31 = 2 or 3. This then disables the use of the START & STOP buttons
www.invertekdrives.com
23
Optidrive ODE-2 User Guide Revision 3.30
P-15 Digital input 1 (T2) Digital input 2 (T3) Digital input 3 (T4) Analog input (T6) Comments
Run and stop commands
Analog and Digital Input Configurations
0, 2,
Open: Stop (disable) given via the RS485 link and
4..5, No effect No effect No effect
Closed: Run (enable) Digital input 1 must be closed
8..12
for the drive to run.
Open: Stop (disable) Speed reference = PI
1 No effect No effect No effect
Closed: Run (enable) Controller Output
Connect external motor
Open: Stop (disable) Open : Master speed ref External trip input :
3 1) No effect thermistor PTC type or
Closed: Run (enable) Closed : Preset speed 1 Open: Trip, Closed: Run
similar to digital input 3
Open: Stop (disable) Open : Master speed ref External trip input : Master Speed Ref - start and
6 1) Analog input reference
Closed: Run (enable) Closed : Analog input Open: Trip, Closed: Run stop controlled via RS485.
Keypad Speed Ref - drive
Open: Stop (disable) Open : Master speed ref External trip input : auto runs if digital input 1
7 1) No effect
Closed: Run (enable) Closed : keypad speed ref Open: Trip, Closed: Run closed, depending on P-31
setting
For further information on the MODBUS RTU Register Map information and communication setup; please contact your Invertek Drives Sales
Partner.
7.4. User PI Control Mode (P-12 = 5 or 6)
P-15 Digital input 1 (T2) Digital input 2 (T3) Digital input 3 (T4) Analog input (T6) Comments
Analog Input 1 can provide
0, 2, Open: Stop (disable) Open : PI control
PI feedback analog input Analog input 1 an adjustable PI setpoint, by
9..12 Closed: Run (enable) Closed : Preset speed 1
setting P-44 = 1
Analog Input 1 can provide
Open: Stop (disable) Open : PI control
1 PI feedback analog input Analog input 1 an adjustable PI setpoint, by
Closed: Run (enable) Closed : Analog input 1
setting P-44 = 1
Connect external motor
Open: Stop (disable) Open : PI control External trip input :
3, 7 1) PI feedback analog input thermistor PTC type or
Closed: Run (enable) Closed : Preset speed 1 Open: Trip, Closed: Run
similar to digital input 3
Normally Open (NO) Normally Closed (NC) Normally Open (NO)
4 PI Feedback Analog Input Analog Input 1
Momentary close to run Momentary open to stop Momentary close to run
Normally Open (NO) Normally Closed (NC) Open: PI Control Normally Open (NO)
5 PI Feedback Analog Input
Momentary close to run Momentary open to stop Closed: Preset Speed 1 Momentary close to run
Normally Open (NO) Normally Closed (NC) Open: External Trip Normally Open (NO)
6 PI Feedback Analog Input
Momentary close to run Momentary open to stop Closed: Run Momentary close to run
Analog Input 1 can provide
Open: Stop (disable) Open : Forward run
8 PI feedback analog input Analog input 1 an adjustable PI setpoint, by
Closed: Run (enable) Closed : Reverse run
setting P-44 = 1
Example Wiring
PI Mode P-12=5, P-15=0 PI Mode P-12=5, P-15=1 PI Mode P-12=5, P-15=3
+24 Volt +24 Volt +24 Volt
+10 Volt
Remote closed loop PI feedback control Remote closed loop PI feedback control with Remote closed loop PI feedback control with
with Local Preset speed 1 Local Analog speed input Local Preset speed 1 and motor thermistor
trip
NOTE By default the PI reference is set for a digital reference level set in P-45.
When using an Analog reference set P-44 = 1 (analog) and connect reference signal to analog input 1 (T6).
The default settings for proportional gain (P-41), integral gain (P-42) and feedback mode (P-43) are suitable for most HVAC and pumping
applications.
The analog reference used for PI controller can also be used as the local speed reference when P15=1.
www.invertekdrives.com
24
Optidrive ODE-2 User Guide Revision 3.30
8
8.1. Introduction
www.invertekdrives.com
25
Optidrive ODE-2 User Guide Revision 3.30
9. Technical Data
9
9.1. Environmental
Technical Data
Operational ambient temperature range Open Drives : -10 … 50°C (frost and condensation free)
Enclosed Drives : -10 ... 40°C (frost and condensation free)
Storage ambient temperature range : -40 … 60°C
Maximum altitude : 2000m. Derate above 1000m : 1% / 100m
Maximum humidity : 95%, non-condensing
NOTE For UL compliance: the average ambient temperature over a 24 hour period for 200-240V, 2.2kW and 3HP, IP20 drives is 45°C.
Note : For UL compliance, Motor Cable to be 75°C Copper, fuse current ratings in brackets (), UL Class T must be used.
www.invertekdrives.com
26
Optidrive ODE-2 User Guide Revision 3.30
9.3. Additional Information for UL Compliance
9
Optidrive E2 is designed to meet the UL requirements. In order to ensure full compliance, the following must be fully observed.
For an up to date list of UL compliant products, please refer to UL listing NMMS.E226333
Technical Data
The drive can be operated within an ambient temperature range as stated in section 9.1
For IP20 units, installation is required in a pollution degree 1 environment
For IP66 (Nema 4X) units, installation in a pollution degree 2 environment is permissible
UL Listed ring terminals / lugs must be used for all bus bar and grounding connections
www.invertekdrives.com
27
Optidrive ODE-2 User Guide Revision 3.30
82-E2MAN-IN_V3.30
www.invertekdrives.com
28