External & Internal Design Conditions: Project: 22 Tower Street, Bedford Row & Jockeys Field & 49-51 FARRINGDON

This document provides design conditions and assumptions for cooling and ventilation load calculations for an office building project located at 22 Tower Street, Bedford Row & Jockeys Field & 49-51 Farringdon in London, UK. It includes external summer and winter design temperatures, internal summer and winter design temperatures, U-values for walls, glazing, partitions and roofs/floors. It also lists assumptions for internal heat gains from people, lighting, equipment and infiltration rates. Maximum summer design conditions occur in July, winter in January and monsoon in June.

Uploaded by

rahul anand
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
116 views2 pages

External & Internal Design Conditions: Project: 22 Tower Street, Bedford Row & Jockeys Field & 49-51 FARRINGDON

This document provides design conditions and assumptions for cooling and ventilation load calculations for an office building project located at 22 Tower Street, Bedford Row & Jockeys Field & 49-51 Farringdon in London, UK. It includes external summer and winter design temperatures, internal summer and winter design temperatures, U-values for walls, glazing, partitions and roofs/floors. It also lists assumptions for internal heat gains from people, lighting, equipment and infiltration rates. Maximum summer design conditions occur in July, winter in January and monsoon in June.

Uploaded by

rahul anand
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

PROJECT:

22 TOWER STREET , BEDFORD ROW & JOCKEYS FIELD


& 49-51 FARRINGDON
OFFICE BUILDING SPACE
COOLING & VENTILATION LOAD CALCULATIONS

EXTERNAL & INTERNAL DESIGN CONDITIONS

EXTERNAL DESIGN CONDITIONS Reference

1 CITY LONDON
2 LOCATION UNITED KINGDOM
3 LATITUDE 51.48°N
4 LONGITUDE 0.45°W
5 SUMMER DB 28 0C From 2005 ASHRAE Handbook - Fundamentals
6 SUMMER MCWB 18.60C (SI)Design conditions for LONDON/HEATHROW,
8 MONSOON WB 25.90C United Kingdom
7 MONSOON MCDB 19.70C
9 WINTER DB - 3.40C
10 SUMMER DAILY RANGE 9.20C
11 ALTITUDE 24 MTRS
INTERNAL DESIGN CONDITIONS
BSRIA ,TABLE 25: Internal Environment Design
1 SUMMER 24±2 °C Criteria for Different Types of Building.
Page No-66
2 WINTER 20±2 °C
PROJECT: UK PROJECT

NAME OF THE BUILDINGS : 22 TOWER STREET , BEDFORD ROW & JOCKEYS FILED & 49-51 FARRINGDON

BUILDING TYPE: OFFICE BUILDING

ASSUMPTION REGISTER
Element Description Input Data REFERENCE INTEC REMARKS CLIENT REMARKS

Solid brick walls-No cavity or 1.6 (W/m2.K) As per Client's Input Received Dated 28-08-2018
insulation/Door - Existing Building

Solid brick walls for New Extension 0.25 (W/m2.K) As per Client's Input Received Dated 28-08-2018
conservatory -U value

Existing glazing/Windows -U value 1.6 (W/m2.K) As per Client's Input Received Dated 28-08-2018

Glazing/Windows for New Extension 1.2 (W/m2.K) As per Client's Input Received Dated 28-08-2018
conservatory -U value
U Values

Shading co-efficient of glazing/glass 0.9 As per Client's Input Received Dated 28-08-2018

Solar Heat Gain co-efficient of SHGC = SC X 0.87 = 0.78 As per Client's Input Received Dated 28-08-2018
glazing/glass

From CIBSE guide A,Pg 183


Partition walls 1.6 (W/m2.K) Table 3.50 Thermal properties of typical internal
partitions.

Exposed Roofs (W/m2.K) Please suggest for the U value

Floors (W/m2.K) Please suggest for the U value

People (Watts) Sensible Heat - 90 (W) From CIBSE guide A,Pg 6-2
Latent Heat - 50 (W) Table 6.1 Heat emissions from an adult male body

Lighting (W/sqm) 12 From BSRIA ,Pg 53


Table 17 Internal Heat gains in offices

Small Power (W/sqm) 25 From BSRIA ,Pg 53


Table 17 Internal Heat gains in offices
Internal Heat Gains

Computers (Sensible Heat- 75(W)


Office Equipments Monitor (Sensible Heat- 80 (W) From ASHRAE Pocket Handbook,Pg 169-170
Printers (Sensible Heat-275(W) Working,125 (W) Idle Heat gain from Typical Computer & office Equipment
Microwave (Sensible Heat- 400 (W)
Coffee Machine (Sensible Heat- 1050(W),Latent Heat- 450(W), 150w per
meeting room for tv screen on the wall.

12-16 L/s/person From BSRIA ,Pg 66- 67


(Note - Shall consider 12 L/s/person) Table 25 Internal & external design criteria
Outdoor Air Fresh Air
10 L/s/person As per Client's Input Received Dated 28-08-2018 On
Excel calculation Sheet

0.8 ACH As per Client's Input Received Dated 28-08-2018

Infiltration Leaky Building


1 ACH From CIBSE guide A,Pg 4-10
Table 4.10 Empirical values for air infiltration rate.

Maximum design conditions for Summer - July From 2005 ASHRAE Handbook - Fundamentals
Solar Heat Gains based on Orientation Of the Building and Winter Occours In- January (SI)Design conditions for LONDON/HEATHROW, United
Month WALLS Monsoon Occours In- June
Kingdom
ROOFS/FLOORS &
GLASS

Weather Data Sheet Please Refer To the PDF Attached in the mail & confirm

Orientation Based on Google Maps and Autocad

RFI REGISTER
1 Please provide the Sections for elevations In AutoCad For Calculations.

2 Number of electrical Equipments used in Office ,Kitchen Space ,coffee machines, microwave, Laser printers, Fax machines