Prosper Complete
Prosper Complete
Prosper Complete
PROSPER
USER GUIDE
The information in this document is subject to change as major improvements and/or
amendments to the program are generated. When necessary, Petroleum Experts will
issue the proper documentation.
The software described in this manual is furnished under a licence agreement. The
software may be used or copied only in accordance with the terms of the agreement. It
is against the law to copy the software on any medium except as specifically allowed in
the license agreement. No part of this documentation may be reproduced or
transmitted in any form or by any means, electronic or mechanical, including
photocopying, recording, or information storage and retrieval systems for any purpose
other than the purchaser's personal use, unless express written consent has been
given by Petroleum Experts Limited.
1 Introduction ......................................................................................................................................................... 1
1.1 Using PROSPER................................................................................................................................................ 1
1.2 PROSPER and Systems Analysis...................................................................................................................... 3
1.2.1 A Note About PROSPER........................................................................................................................... 5
1.3 Examples .......................................................................................................................................................... 7
1.3.1 Example 1 – Naturally Flowing Oil Well................................................................................................... 7
1.3.2 Example 2 – Gas Lift Design ................................................................................................................... 7
1.3.3 Example 3 – Well and Flowline Modelling ............................................................................................... 7
1.3.4 Example 4 – Temperature Prediction ...................................................................................................... 8
1.3.5 Example 5 – ESP Lifted Well................................................................................................................... 8
1.3.6 Example 6 – HSP Lifted Well................................................................................................................... 8
1.3.7 Example 7 – Retrograde Condensate Well ............................................................................................. 9
1.3.8 Example 8 – Gravel Packed well ............................................................................................................. 9
1.3.9 Example 9 – Horizontal Well – Friction dP .............................................................................................. 9
1.3.10 Example 10 – Multi-Layer dP Pressure Loss........................................................................................... 9
1.3.11 Example 11 – Multi-lateral well ................................................................................................................ 9
1.3.12 Example 12 – Modelling of a smart well completion using multilateral option in PROSPER .................. 10
1.3.13 Example 13 – Gas injector with downhole chokes using multilateral model.......................................... 10
1.3.14 Example 14 – Multilateral model including PCP .................................................................................... 10
2 File Management ................................................................................................................................................. 1
2.1 PROSPER Files ................................................................................................................................................. 1
2.1.1 PVT Data (*.PVT) .................................................................................................................................... 1
2.1.2 Input Data (*.SIN) .................................................................................................................................... 1
2.1.3 Analysis Data (*.ANL) ............................................................................................................................. 2
2.1.4 Output Data (*.OUT) ............................................................................................................................... 2
2.1.5 Creating a New File ................................................................................................................................. 3
2.1.6 Opening an Existing File.......................................................................................................................... 3
2.1.7 Saving a File ............................................................................................................................................ 3
2.1.8 Copying a File.......................................................................................................................................... 4
2.2 Preferences ...................................................................................................................................................... 4
2.2.1 Screen ..................................................................................................................................................... 4
2.2.2 File ........................................................................................................................................................... 6
2.2.3 Plot........................................................................................................................................................... 7
2.2.4 User Applications..................................................................................................................................... 9
2.2.5 Limits ..................................................................................................................................................... 10
2.2.6 Units....................................................................................................................................................... 11
2.3 Software Key Maintenance............................................................................................................................. 11
2.4 Evaluate OpenServer Statement .................................................................................................................... 11
2.5 User Correlations............................................................................................................................................ 12
2.6 Printing............................................................................................................................................................ 13
2.6.1 Preparing to Print................................................................................................................................... 13
2.6.2 Selecting and configuring a Printer........................................................................................................ 13
2.6.3 Printing Export Data............................................................................................................................... 13
2.6.4 Selecting an Exported Data to Print....................................................................................................... 15
2.6.5 Word Processing in PROSPER............................................................................................................... 15
2.6.6 Clipboard Command.............................................................................................................................. 15
2.7 Command Buttons .......................................................................................................................................... 16
3 Quick Start Guide ................................................................................................................................................ 1
3.1 Example – Naturally Flowing Oil Well ............................................................................................................... 1
3.1.1 Model Set Up .................................................................................................................................................... 1
3.1.1.1 Options ......................................................................................................................................................... 2
3.1.1.2 PVT Data...................................................................................................................................................... 3
3.1.1.3 Equipment Data............................................................................................................................................ 8
3.1.1.4 IPR Data..................................................................................................................................................... 12
3.1.2 Matching of the model to a test.............................................................................................................. 15
3.1.2.1 VLP Matching ........................................................................................................................................ 15
3.1.2.2 IPR Matching ......................................................................................................................................... 21
3.1.3 Performing a System Analysis............................................................................................................... 25
3.1.4 Calculating Gradient Traverses ............................................................................................................. 30
3.1.5 Generating VLP Curves for Simulators.................................................................................................. 32
4 Data Input - General ............................................................................................................................................ 1
4.1 PROSPER Main Menu ..................................................................................................................................... 1
PETROLEUM EXPERTS LTD
TABLE OF CONTENTS 2-7
PROSPER MANUAL
3-7 TABLE OF CONTENTS
PROSPER MANUAL
7-7 TABLE OF CONTENTS
2. Its PVT section which can generate fluid properties using standard
correlations and allows them to be modified to better fit measured lab data.
PROSPER allows detailed PVT data in the form of tables to be imported for
use in the calculations. A third option is to use the Equation of State method.
This option also allows the User to enter the equation of state model
parameters and uses the standard Peng-Robinson EOS model to generate
properties given a multi-stage separator scheme. With this option the Users
can also import all PVT data in the form of tables, which could have been
generated using their own proprietary EOS models.
3. The tool can be used to model reservoir inflow performance (IPR) for single,
multilayer, or multilateral wells with complex and highly deviated
completions, optimising all aspects of a completion design including
perforation details and gravel packing.
6. It can be used to design, optimise and troubleshoot gas lifted, coiled tubing,
ESP, PCP, HSP (hydraulic pump), Jet pump equipped wells (NEW!!!).
2 - 10 Chapter 1 - Introduction
7. Its choke calculator can be used to predict flow rates given the choke size,
or the choke size for a specified production rate and of course, the pressure
drop across a known choke at a specified rate.
9. The tool can utilise externally programmed dynamic link libraries (DLL) for
multiphase flow correlations, Equation of State (EOS) PVT calculations,
choke calculations and Inflow (IPR) models.
10. The tool can be used in a matching or predictive mode. Matching of real
data is available in the PVT, IPR, Gradient matching and VLP matching
sections.
• In matching mode, real data can be entered and matched using non-
linear regression methods to create custom correlations that fit the
input data.
• In predictive mode, the correlations created can be used to make
estimates of future well performance.
11. PROSPER can be used to model complex (topographically) and extensive (in
length) surface pipelines. Complex steady state slug analysis can also be
performed by taking into account slug build up and decay due to pipeline
topography, giving an indication of expected slug length and frequency.
12. The software also accepts Black Oil PVT tables directly from Petroleum
Experts’ PVTP thermodynamics analysis program. EOS fluid
characterisation parameters can also be directly imported.
13. A flexible units system has been implemented. Data may be input using one
set of units and output using a second set of units. Validation limits and
display resolution can be independently set for each variable type.
14. It has the utility for flagging of potential hydrate formation, if the User
chooses this in the options. The additional input required for this calculation
is the hydration formation tables as a part of PVT.
Fluid Type:
• Oil and Water (Black oil or Equation of State PVT)
• Dry and Wet Gas (Black oil or Equation of State PVT)
• Retrograde Condensate (Black Oil or Equation of State PVT)
• Emulsion viscosity can be optionally applied for any combination of
inflow, tubing and ESP’s or HSP’s.
• Separation mode: Single or Two Stage separation or Multistage (for
Compositional model)
• Modelling of non-Newtonian fluids for oil wells
• Modelling of Condensed Water Vapour for gas wells
PETROLEUM EXPERTS LTD
Chapter 1 - Introduction 3-10
Prediction Type:
• Pressure Only
• Pressure and Temperature Offshore
• Pressure and Temperature on Land
Temperature Model:
• Enthalpy Balance
• Rough Approximation
• Improved Approximation
Completion:
• Cased Hole
• Open Hole
• Gravel Pack
Reservoir:
• Single Well
• Multi-lateral Well in a Multi-layered Reservoir
• Gas Coning (Rate dependent GOR calculator)
Well potential and producing pressure losses are both dependent on fluid (PVT)
properties. The accuracy of systems analysis calculations is therefore dependent
on the accuracy of the fluid properties model (i.e. PVT). The pressure drop in a
pipeline or wellbore is the summation of 3 components:
PROSPER MANUAL
4 - 10 Chapter 1 - Introduction
• Gravity head
• Friction loss
• Acceleration
The gravity component is due to the density of the fluid mixture at each point in the
system and is a complex function of the relative velocity of the phases present.
PROSPER makes a flash computation at each calculation step to determine the
proportion of oil, water and gas present. The no-slip density is then calculated
using the proportions of each phase and the predicted density at each pressure and
temperature step.
Industry standard 2-phase correlations are then applied to determine the increase
in apparent fluid density due to the higher vertical velocity of gas compared to oil
and water (slippage). The gravity head loss is proportional to the fluid density
corrected for slip. The slip correction to be applied depends on the flow regime,
fluid velocity etc. The need for an accurate PVT description for predicting the
gravity head loss is clear.
Friction losses are controlled by fluid viscosity and geometric factors (pipe diameter
and roughness). In the majority of oilfield applications, (i.e. large elevation
difference between inlet and outlet with liquids present) the gravitational component
normally accounts for around 90% of the overall head loss. Therefore, the total
pressure drop function is not particularly sensitive to the value of the friction loss
coefficient.
Historically, systems analysis software has lumped all flowing pressure loss terms
together and allowed the User to match real data by adjusting the roughness
coefficient of the friction loss term. This will certainly achieve a match for a
particular rate, but cannot be expected to achieve a match over a significant range
of rates due to the different dependencies of the gravity and friction loss terms on
liquid velocity.
PROSPERs approach is to first construct a robust PVT model for the reservoir fluid.
Entering laboratory PVT data and adjusting the correlation model until it fits the
measured data improve the accuracy of forward prediction.
Constructing an accurate PVT model confines the uncertainty in the gravity loss
term to the slip correction only.
In the VLP matching phase, PROSPER divides the total pressure loss into friction
and gravity components and uses a non-linear regression technique to separately
optimise the value of each component. Not only does the matching process result
in a more accurate model, it will quickly highlight inconsistencies in either the PVT
or equipment description.
Provided sufficiently accurate field data is available, robust PVT, IPR and VLP
models can be prepared by performance matching. Each model component is
PETROLEUM EXPERTS LTD
Chapter 1 - Introduction 5-10
The Pressure and Temperature calculation option will generate both temperature
and pressure profiles. Three temperature models are provided. The Rough
Approximation model utilises a User-input overall heat transfer coefficient. It
determines the steady state temperature profile from the mass flow rates of oil,
water and gas before commencing the pressure loss calculations. This method
runs quickly, but unless calibrated using measured temperature data, it is not
accurate.
The Enthalpy Balance model calculates the heat transfer coefficients at each
calculation step by considering heat flow and enthalpy changes. The Joule
Thompson effect, convection and radiation are modelled. These calculations
require considerably more input data than for pressure only calculations and must
commence from a known temperature and pressure (the sand face for producers or
wellhead for injectors). Computation times are longer than for the Rough
Approximation option, but this method is predictive and gives accurate results
over a wide range of conditions. The Enthalpy Balance model is completely
transient and can be used to study temperature changes over time.
Temperature prediction is useful for generating temperature profiles in:
The production riser is properly accounted for by PROSPER. The User-input riser
geometry determines the heat loss coefficients calculated by the program between
the seabed and wellhead.
The Improved Approximation is a full Enthalpy Balance model, with the difference
that the heat exchange coefficient is not calculated but defined by the User along
the completion. Like the Enthalpy Balance model, the Joule Thompson effect is
accounted for.
PROSPER is also able to predict condensate liquid drop out using either black oil or
compositional models.
PROSPER MANUAL
6 - 10 Chapter 1 - Introduction
PROSPER uses a "Smart Menu" system. Only data relevant to a particular problem
need to be entered.
The flow chart shown over leaf gives an outline of the calculation steps required to
carry out a simple systems analysis using PROSPER.
1.3 Examples
To help illustrate the power of PROSPER, examples are provided with the program.
We suggest running through them to become familiar with the program and its
various options. These examples are in ~\samples\PROSPER directory. The location
of this directory depends on where the program has been installed.
A very useful Quick Start Guide (NEW!!!) will provide the User with an example
showing how to build, match and use a well model.
PROSPER MANUAL
8 - 10 Chapter 1 - Introduction
• Use existing PVT and VLP data as the basis of a new analysis
• Calculate pump intake and outlet pressures
• Design an HSP system
• Evaluate pump operating point sensitivities
PROSPER MANUAL
10 - 10 Chapter 1 - Introduction
The File menu provides additional options such as defining the default data
directory, as well as the facility to establish access links to other programs running
under Windows.
PROSPER will (optionally) open the last file accessed when it starts. PROSPER also
displays a file status screen that shows the application options selected in summary
format: input PVT and IPR data, the equipment type summary and the analysis
output.
To protect the work, good practise is to save the data on a regular basis. This
simple procedure could potentially prevent hours of input and analysis being lost.
PROSPER files are ranked by their order of input, which essentially reflects the way
data should be entered into the program, that is from the LEFT to the RIGHT of the
PROSPER menu. It is possible to note that the order of files also corresponds to
options on the menu bar as moving through the program.
The file hierarchy does not prevent the User from creating and combining any
number of input and output data files. Until the User becomes familiar with the
program, we recommend to work with *.OUT files. This can avoid confusion as the
program will automatically open and save the required data files to run a complete
analysis cycle.
More experienced users can take advantage of the flexible file structure to combine
the data files from different wells. This "sharing" of data is useful in areas where
wells have similar fluid properties or reservoir IPR's. If disk space is a concern, the
data contained in a .ANL file together with its complementary .PVT and .SIN files
can be used to re-create a given set of calculation outputs, therefore avoiding the
need to always save large .OUT files on disk.
For example, if one wants to run an analysis with the PVT data of Well 1, the input
data (*.SIN) data of Well 2 and the analysis data of Well 3, the following steps can
be followed to achieve that:
• Open Well 3.ANL
• Open Well 2.SIN
• Recall Well 1.PVT under the PVT menu.
• Under the Options menu, select the processing options.
• Modify the data files if necessary.
• Next, select the Save As command and save the data under a new file
name.
The Save command stores all the changes made in the active file. By default, the
Save command saves a file under its original name and to the drive and directory
last selected. A prompt will be displayed to select one of the following file types:
PROSPER MANUAL
4 - 18 CHAPTER 2 - FILE MANAGEMENT
2.2 Preferences
The Preferences screen is used to customise the program to r particular
requirements. Click Preferences from the File menu to customise PROSPER. Click
on the appropriate tab at the top of the data entry section in order to change the
option require. The various tabs are described below:
2.2.1 Screen
Figure 2-1
Preferences: Screen Tab
This tab is used to customise the appearance of the PROSPER front screen and all
data entry (dialog) screens.
Dialog Font
This changes the font type and size used to display all data entry screens. This
may be useful to make all dialogs smaller in case of a low-resolution screen or
larger to improve readability in case of a high-resolution screen. Use the Reset
button to reset the dialog screen font to its default value.
Status Screen
Selecting On the screen status information will be continuously displayed and
updated during the program usage. Selecting Off the screen status information
screen will not be displayed (apart from whenever a new file is opened).
Font Height
If the font height is modified then an attempt is made to scale the font so that all
information displayed in each panel on the status screen will be visible. This will
vary depending on the relative size of the program window to the total screen. If
the font height is not modified then some information may not be displayed as the
size of the program window is varied.
Screen Font
Use this option to change the font type and size used to display information on the
status (front) screen of the program.
Label Colour
Change the colour used to display labels on the status screen
Text Colour
Change the colour used to display text on the status screen
Background
Change the colour used for the background of the status screen
Box Colour
Change the colour used for the background of each panel on the status screen
Box Shadow
Change the colour used for the 3D shadow effect on the status screen panels
Box Highlight
Change the colour used for the 3D-highlight effect on the status screen panels
For all of the above “Colour” options the Choose button to the right will bring up a
dialog screen to select an appropriate colour.
PROSPER MANUAL
6 - 18 CHAPTER 2 - FILE MANAGEMENT
2.2.2 File
Figure 2-2
Preferences:
File Tab
Location of PROSPER.INI
The PROSPER.INI file is used to store all the customised information for r version of
PROSPER. The normal location is in the WINDOWS directory. If Prosper is based
on a network installation, then this option can to use to ensure that each user of the
program can maintain their own customised settings locally.
Use this option to specify the default location of output files from the reporting
subsystem.
Confirm Calculations
Switches (on or off) the message that appears at the end of any calculation
function.
2.2.3 Plot
Figure 2-3
Preferences
Plot Tab
Use this tab to set defaults for all aspects of the plot.
X Grid Blocks
Number of GAPs between grid lines on X-axis. (Range 1-20)
Y Grid Blocks
PROSPER MANUAL
8 - 18 CHAPTER 2 - FILE MANAGEMENT
Plot Labels
Shows or hides the plot labels.
Plot Scales
Shows or hides the plot scales
Plot Legend
Shows or hides the plot legend. If the legend is hidden, the body of the plot will
expand to fill the whole window.
Scaling Method
Endpoint or rounded. Endpoint means the scales are taken from the exact
extremities of the data being plotted. Rounded means that ranges are chosen to
surround the data but with whole numbers ensured for the end points and the
gridline intervals.
Mouse Readout
Switches the mouse cursor position readout no or off.
Line Thickness
To select the thickness of plotted lines
Vertical Font
Selects the default font for all vertical text (Y-axis)
Horizontal Font
Selects the default font for all horizontal text
Default Colours
Sets the default colour scheme for the plot
Figure 2-4
Preferences
User Applications Tab
This tab allows to add up to four of the User’s favourite or most-often used
Windows applications to the PROSPER menu. Although PROSPER has a very flexible
reporting system the User may wish to use a spreadsheet (such as EXCEL), a
word processor (such as WORD) and a presentation package (such as Power
Point) to build presentation quality reports using PROSPER output in a slick and
efficient manner.
Any output (plots and reports) produced by PROSPER is automatically copied to the
Clipboard. From there it can easily be pasted into one of the above-mentioned
applications using one simple keystroke. Using the power and flexibility of the
chosen application, high quality reports and presentations can be easily prepared.
All plots can be saved in Windows Metafile format. These can be easily read by
a word processing package or presentation graphics package and give the
maximum flexibility for user customisation.
All reports can be saved in TSV (Tab Separated Variable) format using the Export
facility that means they will automatically be tabulated when read into the favourite
spreadsheet.
Enter a description and a command line for each application to be added to the
PROSPER menu.
Use the Browse buttons to browse for the application requires. Use the Clear
buttons to initialise the appropriate application information.
PROSPER MANUAL
10 - 18 CHAPTER 2 - FILE MANAGEMENT
2.2.5 Limits
Figure 2-5
Preferences
Limits Tab
This tab allows the User to specify limiting values and tolerances for the following
parameters:
2.2.6 Units
Figure 2-6
Preferences
Units Tab
This tab allows specifying the default Units Systems to use for new files.
If setting the option "Always Use Default Units" to "Yes", then the units displayed for
any file read in will always be set to the default choice, regardless of the settings in
the file.
PROSPER MANUAL
12 - 18 CHAPTER 2 - FILE MANAGEMENT
Figure 2-7
Evaluate Open
server command
Type or Paste the OS string in the String field, then select one of basic OS
commands (DoGet, DoSet, DoCommand), if required enter the Value (valid only if
using DoSet) and click Evaluate to perform the function.
In the Returned value it is possible to read the results of the operation.
Before a DLL can be accessed, it must first be installed into PROSPER. This is
done by clicking File ⏐ User Correlations. Select either Flow Correlation, Equation
of State Model, Choke Correlation or Inflow Performance Model. PROSPER will
display a list of the currently installed DLLs of the selected type. To add a
correlation, click Add and select the appropriate file from the file dialogue. Click OK
and it will be hooked into PROSPER.
MODEL EXTENSION
Flow Correlation .COR
Equation of State PVTP .EOS
Model
Choke Correlation .CHK
Inflow Performance Model .RSM
Information about particular correlations can be obtained by clicking the Info button.
A screen similar to the following will be displayed.
Figure 2-8
Flow Correlation
Information
2.6 Printing
To print export data, select the Output menu and the Export option. Select the
sections to report on the dialogue box. The program will lead the User through a
series of input screens to set up the required report sections. From the main
dialogue box, select a destination for r data.
PROSPER MANUAL
14 - 18 CHAPTER 2 - FILE MANAGEMENT
Figure 2-9
Output Results Reports
The appearance of printed reports is controlled by the export data set-up options
that have been set.
Click Setup to display the following screen:
Figure 2-10
Export Data Printer
Options
Select a suitable font and set the margins etc. that will be used for printed export
data. Only non-proportional fonts are allowed in reports to maintain vertical
alignment of the columns.
PROSPER default font is recognised by most print set-ups. To avoid
 potential printing problems, always set up the system to use a font
that is supported on the system prior to printing PROSPER export data
for the first time.
Click OK to return to the output screen. Clicking Print initiates generation of the
export data and sends it to the selected destination.
PROSPER MANUAL
16 - 18 CHAPTER 2 - FILE MANAGEMENT
All This command button is used in the Equipment and Gas Lifted (safety
equipment) option screens. It will select all input parameters and data
points for automated editing.
Calculate Performs the various calculations on the input parameters for the
correlations selected.
Continue Continues to the next input screen. Any changes to the fields will be
saved and retained in memory for later calculations. A warning
message will be displayed when fields requiring input data are left
blank.
Copy To copy existing data points, select the line entries to duplicate and
click on Copy. Next, select the destination line(s) and click on Copy
again. Subsequent line entries will be not be overwritten by this
operation.
Correlations Displays the results of any matching performed under the VLP/IPR
Match option.
Delete This command button is used in the Equipment and Gas Lifted (safety
equipment) option screens. It allows deleting individual or several data
points.
To delete, select the line entries to erase and click on Delete. If one
wishes to delete all existing line entries, click All and then Delete. The
program will clear the input screen.
Edit This command button is used in the main Equipment screen. One or
more items can be modified at a time. When used with 'All', all items
will be selected for editing.
Export Brings up the Data Export interface. This will be specific to the data on
the active window.
Help Provides on screen help for PROSPER. For general information, press
the 'ALT' and 'H' keys together in the Main menu, or the Index button
under any help screen. Specific help screens are also available for
each window.
Import Calls up the general import interface that allows to grab data from any
text file. This button will usually be found where tabular data is to be
input.
Insert This allows to add one or several data points providing there are
sufficient entry fields. Select the line number where to add a new entry
and click on Insert. The program will move existing line entries down to
accommodate the inserted line(s).
Match Displays a variable screen where match data can be entered in order to
adjust existing correlations to fit real data.
Move Allows to re-arrange data points. Select the line(s) to transfer and click
on Move. Next, select the destination line(s) and click on Move again.
Subsequent line entries will be moved down to accommodate the
transferred line(s).
Plot Plots any calculated results and displays them on screen. Hard copies
of the screen display can be printed by selecting the Hardcopy
command button on the Plot screen.
Recall Allows to recall and existing PVTP file. The User will be prompted for
the directory and name of the file.
Report Calls up the reporting interface with a report that is specific to the active
window. This is generally found on windows that display the results of
calculations. It is then possible to choose to print this report. The report
is generated from a system report template.
Reset Resets the Match parameters in order to reinstate the original textbook
correlations.
Save Saves a current PVTP file. If this is a new data file, the User will be
prompted for a file name.
Summary Displays a summary screen of the input equipment parameters or
system units.
The following command buttons are used in the Plot Menu and Plot screens.
Clipboard Sends black and white or colour copies of the screen plot to the
Windows Clipboard where it may be retrieved by a word processing
program for inclusion in reports.
Colours Allows to define the screen display colours of r plot labels, scales, grids,
etc.
PROSPER MANUAL
18 - 18 CHAPTER 2 - FILE MANAGEMENT
Hardcopy Generates black and white or colour print copies of the screen plot. It is
automatically sent to the device selected in \.
Labels Allows to label r plot. All plot labels are stored in memory and saved
when Output files are generated.
Scales Allows to re-define the minimum and maximum values for the X and Y
plot axes.
Figure 3.1:
Prosper main screen
The first 4 sections are input data screens, whilst the last contains all the calculation
and design features.
Each of these sections is directly accessible from the PROSPER main screen by
double clicking on them, or from the menu toolbar, where their access is ordered
from left to right, top to bottom. This order reflects the recommended workflow to
follow to set up the model.
In the following we will use the menu toolbar
3.1.1.1 Options
To begin setting up the system options, select Options⏐Options or double-click on
the ‘SUMMARY DATA’ area and make the following selections:
This completes the main system setup and reinitialises the program. If the status
screen is being displayed, the main system areas (‘SUMMARY DATA’, ‘PVT DATA’,
‘IPR DATA’, ‘EQUIPMENT DATA’ and ‘CALCULATION SUMMARY’) can be now easily
accessed.
In the following table there are the parameters characterising the Black Oil model for
this example:
 The solution GOR is the gas dissolved in the oil at the original bubble
point pressure. If the well also produces free gas, it should not be
included here.
PROSPER MANUAL
4 - 33 CHAPTER 4 – QUICK START GUIDE
In order to enter the Black Oil model, access the PVT section by selecting PVT⎪Input
Data from the menu toolbar
Figure 3.2:
PVT input screen
In the PVT main section click Match Data and enter the laboratory measured PVT
flash data. Up to 5 tables can be entered at different temperatures.
Enter the following match data:
In this very simple example we are entering only data referring to the bubble point,
but bear in mind that in each table data up to 10 values of pressure can be entered.
Figure 3.3:
PVT Match Data
Once entered the above data, click Done to return to the main PVT Data input
screen.
3. Match the PVT Black Oil correlations to the PVT match data entered and
choose the best correlation
The following step is to tune the black oil correlations in order to match the lab data
entered. In this way we make sure that the PVT model we are going to use
reproduces measured data.
To match the correlations to the laboratory measured data, from the main PVT input
data screen select Regression:
Figure 3.4:
Regression screen
PROSPER MANUAL
6 - 33 CHAPTER 4 – QUICK START GUIDE
Figure 3.5:
Correlation Parameters
screen
This table reports the list of match parameters for all the PVT properties for each
correlation.
Please note that additional match parameters (Parameter 3 and 4) have been
introduced to allow the FVF to be independently tuned below (P1 and P2) and above
(P3 and P4) the bubble point.
The less correction a correlation requires to fit the measured data, the better it is.
In particular, the closer to 1 is Parameter 1, the better the correlation.
Note that the displayed standard deviation shows how well the matching process
converges: the higher the Standard Deviation, the worse the matching.
Inspecting the above reported table, Standing has for this example the best overall fit
for Pb, GOR and FVF whilst Beggs et al fits best for the oil viscosity. Therefore,
Standing will be selected to correlate Pb, GOR and FVF and Beggs et al for the oil
viscosity.
Make sure that Standing and Beggs et al have been selected in the Correlations input
box in the main PVT panel:
Figure 3.6:
Correlation Parameters
screen
The matched data can be plotted by clicking Plot from the regression menu as in the
example below:
Figure 3.7:
Matched PVT Plot
All further calculations will be performed using the matched PVT data unless the
match parameters are subsequently reset from the Correlations menu
PROSPER MANUAL
8 - 33 CHAPTER 4 – QUICK START GUIDE
Casing 6”
11000 ft
MD
11400 ft
MD
The equipment to specify in PROSPER is the one that the fluid “sees” from the
bottomhole up to the wellhead. The bottomhole corresponds at the top of the
perforations and is the point at which the Vertical Lift Performance curves (VLP) and
the Inflow Performance Relationships (IPR) are referred.
1 2
PETROLEUM EXPERTS LTD
CHAPTER 3 – QUICK START GUIDE 9 - 33
Figure 3.8:
Equipment data
screen
It is possible to enter the data screen by screen, or, more comfortably, go through
the entry screens automatically starting with the well deviation survey. To do so,
select first All, then Edit.
The first screen displayed is the Deviation Survey:
Figure 3.9:
Deviation Survey
Once the deviation is entered, click on Done to go to the Surface Equipment screen:
PROSPER MANUAL
10 - 33 CHAPTER 4 – QUICK START GUIDE
Figure 3.10:
Surface Equipment
This screen allows the User to describe the equipment of a surface pipeline. For this
example, leave blank and click on Cancel to go on to the Downhole Equipment
screen:
Figure 3.11:
Downhole Equipment
To select the equipment (Tubing, Casing, SSSV, etc.) click in the Type filed and
select from the drop-down menu.
As already pointed out previously, only the equipment in which the fluid flows must
be entered. Note that the Xmas tree elevation has been taken to be the same as the
deviation survey reference.
Descriptive information about the downhole equipment can be written in the label
fields as reminder.
Click Done to advance to the Geothermal Gradient screen and enter the following:
Measured Fluid
Depth Temperature
(feet) (deg F)
0 45
11400 210
Figure 3.12:
Geothermal Gradient
screen
Then Done to go to the next screen, which reports the Average Heat Capacities:
Figure 3.13:
Average Heat Capacities
PROSPER MANUAL
12 - 33 CHAPTER 4 – QUICK START GUIDE
Figure 3.14:
Equipment data
screen
Figure 3.15:
Equipment data screen
Figure 3.16:
IPR input screen
In this screen the IPR model can be selected and some fundamental reservoir
parameters are entered.
Select the Darcy IPR method and enter the following in the IPR Select Model screen:
Figure 3.17:
IPR input screen
The following section to access is the Input Data screen. The Input Data screen
contains all the parameters characterising the selected Inflow model and the
Geometrical Skin entry.
PROSPER MANUAL
14 - 33 CHAPTER 4 – QUICK START GUIDE
Click on the Input Data button in the top right hand corner of the window, then enter
the following reservoir data:
Reservoir Permeability 50 md
Reservoir Thickness 200 feet
Drainage Area 500 acres
Dietz Shape Factor 31.6 (for a circular drainage area)
Wellbore Radius 0.354 feet
Figure 3.18:
IPR input screen
Figure 3.19:
Mechanical/Geometric Skin
entry screen
Figure 3.20:
Darcy IPR Plot
PROSPER MANUAL
16 - 33 CHAPTER 4 – QUICK START GUIDE
Figure 3.21:
VLP/IPR (Quality Check)
screen
This screen contains a table that can host up to 1000 well tests.
Enter here the well test data, which for this example are:
Figure 3.22:
VLP/IPR (Quality Check)
screen
2. Compare the multiphase flow correlations (QC) and select the best
correlation
Before running the comparison of the correlations, it is possible to tune the
temperature prediction model (in this case Rough Approximation) to match the
temperature measurement of the test. To do that, select the test by clicking on its
row number:
Figure 3.23:
VLP/IPR (Quality Check)
screen – test selection
And then click on Estimate U value. The program will calculate the value of the
overall heat exchange coefficient that matches the well test temperature
measurement:
Figure 3.24:
Estimate U Value
results
Click Ok, then Done to go to the main panel. Then go to the Geothermal Gradient
screen in the Equipment Data area and enter the just determined U value:
Figure 3.25:
Geothermal Gradient
PROSPER MANUAL
18 - 33 CHAPTER 4 – QUICK START GUIDE
Figure 3.26:
Tubing Correlation
Comparison
Then Calculate and Calculate again. The program will determine the pressure
gradient traverses for the selected correlations. Plot to visualise the gradients and
the well test:
Figure 3.27:
Gradient traverses plot
From the analysis of this plot two main considerations can be done:
- The well test measurement lies within the boundaries set by the two
correlations Fancher-Brown and Duns and Ros Modified. This means that the
test is ok
- Zooming the plot (draw a box around the desired area) it is possible to notice
that PE2 is the closest correlation
Result: the best correlation to use to match this test is Petroleum Experts 2.
To carry out a VLP match, in the VLP/IPR Matching screen select Match VLP as
shown below:
Figure 3.28:
VLP/IPR (Quality Check)
screen
PROSPER MANUAL
20 - 33 CHAPTER 4 – QUICK START GUIDE
In the displayed Match screen select the correlations to match (in this case PE2)
from the list and click on match:
Figure 3.29:
Correlation matching
The program will regress in order to determine a set of match parameters that fit the
test. Click on Statistics to access the results of the regression:
Figure 3.30:
Statistics
Note on the match parameters: if the data is consistent, these two parameters
should be close to unity within ±10% of tolerance. If the difference is bigger, then the
test data used for the matching and the model should be reviewed.
Once matched a correlation, the two match parameters will be appended to the
correlation name to indicate that the correlation selected has been matched:
Figure 3.31:
Estimate U Value results
 When more than one test data points are available for flow
correlation calibration, it is recommended to use the following
procedure:
• Use minimum number of test points (possibly one) to
calibrate the correlation.
• Check how well the calibrated model predicts the other test
points (those not used in calibration).
• This ensures reliability of the model in predictive mode.
Figure 3.32:
VLP/IPR (Quality Check)
screen
PROSPER MANUAL
22 - 33 CHAPTER 4 – QUICK START GUIDE
In the following screen select the just matched correlation and calculate the VLP:
Figure 3.33:
VLP/IPR (Quality Check)
screen
PROSPER will compute the VLP curves for the match data (WHP, flow rate, water cut
etc.) using the matched VLP correlation.
Then click IPR to access the IPR calculation screen and click on Calculate.
The VLP and IPR lines intersect quite close to the measured data points:
Figure 3.34:
VLP/IPR Plot
We will now adjust the IPR to better match the test points.
• The available parameters for matching depend on the IPR model in use. For
the Darcy-IPR model, permeability, skin or reservoir pressure could be used.
• For this example, we will assume that the well P.I. has not changed - but we
do not have a recent reservoir pressure.
• We will match the IPR by adjusting the reservoir pressure.
In the plot menu toolbar select Finish to go back to the IPR screen and enter a
reservoir pressure of 4982 psig and water cut of 15%:
Figure 3.35:
VLP/IPR Plot
Click | Calculate to see a new plot. The error in bottomhole pressure is now very
low:
Figure 3.36:
VLP/IPR Plot
PROSPER MANUAL
24 - 33 CHAPTER 4 – QUICK START GUIDE
The PROSPER well model is now matched from reservoir to sand face and surface to
sand face using entered low rate well test.
The model is now ready for calculations or validation against further tests.
The following example shows the validation of the model against a high
Before the model can be used for predictive runs, we will check how well it
reproduces the high rate test, without any matching.
• Click on VLP/IPR.
• Click on Calculate, with PE2 selected as correlation to compute the VLP
curves for both the test cases.
• Click on IPR to go to the IPR input screens. Do not alter any parameter here.
• Hit Calculate, to generate the IPR and VLP intersection plot with the test data
points.
Figure 3.37:
VLP/IPR Plot
The plot displayed represents the matched VLPs and the IPR.
 Note that the model is able to reproduce the high rate test also with
accuracy, even though this data has not been used for calibration.
It can now be used with confidence for predicting future production performance.
Click Main⎪Main to return to the PROSPER main screen.
First node
Water Cut GOR
pressure
[%] [scf/STB]
[psig]
250 15 820
PROSPER MANUAL
26 - 33 CHAPTER 4 – QUICK START GUIDE
Figure 3.38:
System Calculation screen
Other entries:
• Select Dukler Flannigan for the surface flow line correlation. In this case no
surface pipe is part of the model, so this entry has no effect
• Select Petroleum Experts 2 for the multiphase flow correlation (note the match
parameters have been appended to the correlation name)
• Select Bottom Node as ‘Solution Node’. This selects the bottomhole as
solution node
• Select Automatic Linear for the rate method. This divides the internal [0, AOF]
in 20 values linearly spaced
Click on Continue⎪Continue (for the moment we skip the Select Variables screen)
and then Calculate.
One the calculation is finished the results with the calculated IPR and VLP and the
solution are displayed:
Figure 3.39:
System Calculation
On the right hand side the solution rate and flowing pressures and temperatures are
reported. To plot the VLP/IPR, select Plot:
Figure 3.40:
System Plot
2. Running sensitivities
It is possible to determine the behaviour of the well with changing conditions. To
achieve that, sensitivities can be performed on a number of parameters like WC,
GOR, Reservoir Pressure, and so on.
For this example we will run sensitivities on Water Cut, Skin and Tubing/Pipe
diameter.
Ranges of these parameters:
Parameter Range
Water cut 0, 40, 80 %
Skin 0,2,4
Tubing /Pipe Diameter 3.958, 4.892
PROSPER MANUAL
28 - 33 CHAPTER 4 – QUICK START GUIDE
To run sensitivities, go back to the Select Variables screen, select the variable in
each combo-box and enter the above reported ranges:
Figure 3.41:
Select Variables screen
Then Continue.
The program now asks between which nodes should the tubing size sensitivity be
run:
Figure 3.42:
Elect diameter
range
Select the Xmas tree as First Node and the bottom of the production tubing
(@11,000 ft) as Last Node with the combo boxes.
Click on Continue then Calculate to begin the system analysis calculation.
Once the calculations have finished, click Plot to take a look at the VLP and IPR
curves plotted for the range of sensitivity variables as follows:
Figure 3.43:
VLP/IPR System Plot
It is possible to generate plots that show how the solution changes with changing
sensitivity parameters by using the Sensitivity plotting feature.
For example supposing that we want a plot of Liquid rate produced against Water
Cut parametric in the skin for a given value of the diameter, select Sensitivity from
the Calculation screen and in the plot manu toolbar select Variables and then choose
as requested:
Figure 3.44:
Variables selection in the
Sensitivity Plot
PROSPER MANUAL
30 - 33 CHAPTER 4 – QUICK START GUIDE
Figure 3.45:
Sensitivity Plot
These results show that for the 3.958" ID tubing a liquid production gain of around
1100-1200 STB/day is possible by removing the skin for various water cuts.
This can be done in two ways: by clicking Sensitivity PvD on the System Calculation
screen or from the main menu by selecting Calculation ⏐ Gradient (Traverse).
Figure 3.46:
Sensitivity Plot
Figure 3.47:
Gradient calculation
This calculation will determine the pressure gradient along the wellbore for the
conditions corresponding to the solution point.
Selecting Plot the traverse is plotted:
Figure 3.48:
Gradient Plot
Click on Main then File | Save As and save the file as Oilwell.out.
PROSPER MANUAL
32 - 33 CHAPTER 4 – QUICK START GUIDE
Figure 3.49:
VLP (3 variables)
In the first screen enter any value for Top Node Pressure, Water Cut and GOR: as
sensitivities will be run to generate the curves for a range of sensitivity parameters,
the values in the first screen will be overwritten by the sensitivity values entered.
Parameter Range
First Node Pressure 200, 600, 1000, 3000 psig
Water Cut 0, 40, 80 %
Gas Oil ratio 400, 820, 2000 scf/STB
Figure 3.50:
VLP (3 variables) Select
Variables screen
Figure 3.51:
VLP (3 variables) Select
Variables screen
To export the curves to GAP or MBAL (.TPD format), select Petroleum Experts
GAP/MBAL, then click on Continue, enter a file name and click on Save to save the
lift curves as a .tpd file.
PROSPER MANUAL
4 Data Input - General
This section describes the PROSPER main menu and the input data required before
an analysis can be performed. Data should be entered by working through the
PROSPER menus following the logic order from left to right and top to bottom. The
following menus are described in this section:
• Main menu
• Options menu
To start PROSPER, select the appropriate icon and press ↵ or double-click the
program icon. A screen similar to the following will appear:
Figure 4.1
Main Menu
The menu options across the top of the screen are the PROSPER main menu
options. Each is described below.
2 - 13 Chapter 4 - Data Input - General
4.1.1 File
The File menu is a management menu with commands that enables to open, save
or create new data files. It is possible to use this menu to define the default data
directory, printer set-ups options and hook in external DLLs. A facility for accessing
other Windows programs via PROSPER is also provided.
4.1.2Options
The Options menu is the starting point of PROSPER and the key to the program.
Use this menu to define the application and principal well features such as -
prediction method, artificial lift type and fluid type. The options selected are unique
to the current file and apply until changed by the user, or another file is recalled.
These options also determine the subsequent screens, menus and commands that
are displayed.
4.1.3PVT
Use the PVT menu to define well fluid properties and select fluid property
correlations. PVT correlations can be modified to match laboratory-measured data
using a non-linear regression technique. Alternatively, detailed PVT data may be
entered in tables.
4.1.4System
The System menu is used to define the well's downhole and surface equipment as
well as the reservoir inflow performance. When applicable, gas lift and ESP or HSP
equipment data for artificially lifted wells are entered from this menu.
4.1.5Matching
The Matching menu allows comparison of field data with calculated pressure drops
in well tubing and surface piping. All available correlations can be compared to
allow selection of the model that best suits the field conditions.
4.1.6Calculation
The Calculation menu provides with the relevant calculation options. Calculations
to determine pressure and temperature profiles, perform sensitivity analyses, make
gradient comparisons and generate lift curve tables are available in this menu.
4.1.7Design
ESP, HSP, PCP, Jet Pumps, Multiphase Pumps sizing as well as gas lift mandrel
placement and valve setting pressure calculations, coiled tubing and diluents
injection are available from the Design menu. Access to the databases that hold
gas lift valves, ESP, HSP, PCP, Jet pumps (NEW!!!) equipment characteristics is
via the Design menu also.
4.1.8Output
The Output menu is used to generate reports, to export data and to plot data.
Report templates are provided and user templates can also be defined. The data
used can be input data, analysis data, results or plots. Reports can be saved in
various file formats (RTF, TXT and native) and can be displayed or sent to a printer.
Export data can be viewed on screen, sent to the Windows clipboard, sent to a
printer or saved in a file. Plots can be printed directly, saved to a report file or a
Windows metafile. Selected plots can also be sent to the clipboard where they can
be retrieved by other Windows-based programs.
4.1.9Wizard NEW!!!
This menu accesses the wizard area of PROSPER. This allows to Create/Edit and
Run wizards that allow the User to build and run models step-by-step guided
fashion.
4.1.10 Units
This menu is used to define the input and output units of measurement. A flexible
system of units is provided allowing to customise the internal units system.
4.1.11 Help
Provides on-line help for PROSPER. The User can get help on specific tasks, fields
or commands. Help is also given on the keyboard and miscellaneous Windows
commands.
To access the Options menu, point to the menu name and click the mouse or press
ALT+O.
PROSPER MANUAL
4 - 13 Chapter 4 - Data Input - General
Figure 4.2
System
Options
Summary
The entry screen is divided in two main sections - System options and User
information.
Under the System options section, define the well characteristics such as fluid type,
well completion, lift method, etc. These selections determine information that will
be required to enter later. The lower section of the screen comprises the header
information and comments that identify the well and will appear on the report and
screen plot titles.
Option Selection
To select an option, click on the arrow to the right of the required field. The list of
available choices will be displayed.
4.2.1Fluid Description
4.2.1.1 Fluid
• Oil and Water (Black Oil Model or Compositional)
• Dry and Wet Gas (Black Oil Model or Compositional)
Dry and Wet Gas is handled under the assumption that condensation
occurs at the separator. The liquid is put back into the gas as an
equivalent gas quantity. The pressure drop is therefore calculated on the
basis of a single-phase gas, unless water is present.
• Retrograde Condensate (Black Oil Model or Compositional)
This fluid type accounts for the condensate drop out in the tubing.
4.2.1.2 Method
• Black Oil
This option uses industry standard Black Oil models. Five correlations
are available for oil producers. For gas condensate systems an internally
developed model is used. These correlations can be adjusted to match
measured data using non-linear regression.
• Equation of State
Reservoir fluid is modelled by pseudo components having user-specified
properties. The two equation of state models Peng-Robinson and
Soave-Redlich-Kwong are available in PROSPER to predict PVT
properties.
User EOS DLLs can also be linked into PROSPER.
PROSPER MANUAL
6 - 13 Chapter 4 - Data Input - General
4.2.1.4 Separator
• Single Stage
This available for black oil option for following fluids:
• Oil and water
• Dry and Wet Gas
• Retrograde Condensate
• Two Stage
This option is available for Black oil model in case of Oil and Water fluid
type only.
Separator and tank properties are entered and recombined by PROSPER.
4.2.1.5 Emulsions
• No or Emulsion + Pump viscosity correction
Select Emulsion + Pump viscosity correction to allow input of Emulsion
viscosity in the PVT section. This option must be selected to turn on ESP
or HSP viscosity corrections.
4.2.1.6 Hydrates
• Disable Warning or Enable Warning
Select Enable Warning to allow flagging of hydrates formation in
calculation screens. To use this feature, go to the PVT section and enter
or import the hydrates formation table.
This option is available for Dry and Wet Gas and Retrograde Condensate
fluid types with PVT Black Oil model. If ‘Calculate Condensed Water
Vapour’ is selected, the condensation of water vapour will be taken into
account when performing pressure drop calculation.
4.2.2Well
4.2.3Artificial Lift
4.2.3.1 Method
The following 8 lift method options are available when Oil is selected as a fluid type.
• None
No artificial Lift selected.
• Gas Lift
Three different approaches are provided. Annular gas lift is handled by
PROSPER. If the Flow Type is Annular Flow and a Gas Lift method is
selected, then PROSPER automatically switches to model gas injection
down the tubing, and production up the annulus.
PROSPER MANUAL
8 - 13 Chapter 4 - Data Input - General
4.2.3.2 Type
If Gas Lift is the chosen method, then the following types are available.
• No Friction Loss In Annulus
It is the classic approach for the annulus gas gradient. The pressure
drop due to friction in the annulus is ignored and the gas gradient is
determined by the top casing pressure and the temperature profile.
• Friction Loss In Annulus
The pressure drop due to friction in the annulus is taken into account, but
the top casing pressure is assumed constant. If this option is selected
the tubing equipment screens will automatically change and require
tubing OD and casing ID data to be entered.
• Safety Equipment
Surface delivery lines, chokes, the gas lift injection string and safety
valves in the annulus are taken into account. Top casing pressures will
change with injection rate.
If Hydraulic Drive Downhole Pump is the chosen method, then the following
types are available.
If Progressive Cavity Pump is the chosen method, then the following types are
available.
If Coiled Tubing Gas Lift is the chosen method, then the following types are
available.
• No Friction Loss in Coiled Tubing
Friction losses along the coiled tubing are neglected.
• Friction Loss in Coiled Tubing
Friction losses along the coiled tubing are accounted for.
If Diluent Injection is the chosen method, then the following types are available:
• Tubing Injection-Annular Production
The power fluid is injected in the tubing and the production flows through
the annulus
• Annular Injection-Tubing Production
The power fluid is injected in the annulus and the production flows
through the tubing
If Jet Pump is the chosen method, then the following types are available:
• Tubing Injection-Annular Production
The power fluid is injected in the tubing and the production flows through
the annulus
• Annular Injection-Tubing Production
The power fluid is injected in the annulus and the production flows
through the tubing
If Multiphase Pump is the chosen method, then the following types are available:
• Framo Pumps
PROSPER MANUAL
10 - 13 Chapter 4 - Data Input - General
4.2.4Calculation Type
4.2.4.1 Predict
The program is capable of predicting either pressure only or pressure and
temperature changes simultaneously.
• Pressure Only
If this option is selected, the flowing temperature profile must be entered.
This calculation option is fast and provides accurate pressure profiles.
• Pressure and Temperature (On Land and Offshore)
This option will calculate both pressure and temperature profiles using
the method specified in Temperature Model.
4.2.4.2 Model
Three models for temperature calculations are available:
• Rough Approximation
Calculates the heat loss from the well to the surroundings using an
overall heat transfer coefficient, the temperature difference between the
fluids and the surrounding formation and the average heat capacity of
the well fluids. The geothermal gradient entry screen is used to input
formation temperatures (e.g. from logging runs) at measured depth
points. A minimum of the surface and first node temperatures are
required. Temperatures entered should be the extrapolated static
temperatures, and should not be confused with the entry of measured
flowing temperatures required for the Predicting pressure only case.
• Enthalpy Balance
This rigorous thermodynamic model considers heat transfer by
conduction, radiation, and forced and free convection. Heat transfer
coefficients are calculated using values held in a user-definable
database. The temperature prediction calculations are transient,
allowing sensitivities against flowing time to be run. This temperature
model requires considerably more input data and computation time for
either Predicting Pressure Only or the Rough Approximation
temperature model.
pressure loss is the required result (for e.g. process calculations and
material selection).
• Improved Approximation
As the Enthalpy Balance model, this is also a full enthalpy balance
pressure and temperature prediction model, with the difference that
the term of the enthalpy balance concerning the heat exchange with
the outside (which includes free and forced convection, conduction
and radiation) is simplified by a heat loss term characterised by an
overall heat exchange coefficient.
For this reason data related to the completion hardware and thermal
properties are not necessary.
Like any enthalpy balance model, Joule-Thomson Effect is also
accounted for.
These characteristics make this model particularly useful when an
accurate calculation of temperature is sought for and only a few data
on the completion are available.
The geothermal gradient entry screen is used to input formation
temperatures (e.g. from logging runs) at measured depth points. A
temperature gradient in the sea can be entered for offshore
applications. A minimum of the surface and first node temperatures
are required. Temperatures entered should be the extrapolated static
temperatures, and should not be confused with the entry of measured
flowing temperatures required for the Predicting pressure only case.
PROSPER MANUAL
12 - 13 Chapter 4 - Data Input - General
4.2.4.3 Calculation
• Full System
Calculations for pipelines, tubing and reservoir
• Pipeline Only
Calculations for pipelines only
4.2.4.4 Output
• Show calculating Data
• Hide calculating Data
Select Hide to speed up calculations by not updating calculation screen
displays. This will automatically be set to Hide when run from GAP
4.2.5Well Completion
4.2.5.1 Type
• Cased Hole or Open Hole
This selection determines the appropriate IPR Completion models to use.
4.2.6Reservoir
4.2.6.1 Type
• Single Branch or Multilateral Well
In the single branch option the IPR screen comes with various standard
inflow models from which the user selects one.
For the multi-lateral selection, the IPR screen requires detailed drawing
of the downhole completion.
PROSPER MANUAL
5 PVT Data Input
5.2 Introduction
To predict pressure and temperature changes from the reservoir, along the well
bore and flow line tubular, it is necessary to accurately predict fluid properties as a
function of pressure and temperature. The User must enter data that fully
describes the fluid properties or enables the program to calculate them. There are
four possible approaches:
- Correlations: Where only basic PVT data is available, the program uses
traditional black oil correlations, such as Glaso, Beal, Petrosky etc. A unique black
oil model is available for condensates and details of this can be found later in this
guide as well as the PROSPER manual.
- Matching: Where both basic fluid data and some PVT laboratory measurements
are available, the program can modify the black oil correlations to best-fit the
measured data using a non-linear regression technique.
- Tables: Where detailed PVT laboratory data is provided, MBAL uses this data
instead of the calculated properties. This data is entered in table format (PVT
tables), and can be supplied either manually or imported from an outside source.
So called black oil tables can be generated from an EOS model and then be
imported and used in MBAL.
Use of Tables: Tables are usually generated using one fluid composition
which implies a single GOR for the fluid. This will therefore not provide the
right fluid description when we have injection of hydrocarbons in the
reservoir or when the reservoir pressure drops below the bubble/dew point.
Use of EOS: The basic equations of state are not predictive unless matched
to measured lab data. Care has to be taken in order to make sure that the
EOS has been matched and is applicable for the range of Pressures and
Temperatures to be investigated.
The program also allows fluid properties to be calculated and plotted for specified
pressure and temperature ranges. The PVT menu has three options - Report, Input
and Export. Select Report to inspect previously entered data, Export to save data
to a text file, or Input to set up a new problem or edit an existing one.
Recommended Steps
• Enter data as requested on PVT input data screen and select correlations
that are known to best fit the region or oil type.
Figure 5-1
PVT Input Screen
Enter the required data in the fields provided. Movement from one box to another
can be done using the TAB key. Next, select a Pb, Rs and Bo correlation and a
viscosity correlation to use then click OK.
 Enter the oil solution GOR. This should not include free gas production.
For gas production in wells producing injection or gas cap gas the solution
GOR should still be entered. The balance of “free” gas production is
accounted for elsewhere.
Mole Percent CO2, N2 and H2S refers to the separator gas stream composition.
5.3.2 Emulsions
If Options | Emulsions is selected PROSPER allows selection of the emulsion
occurrence in the system from the PVT input dialogue. This tells PROSPER where
the viscosity corrections will take place during calculation
The Flowline Emulsion Data button opens the Emulsion Data entry screen.
Water cut can be entered at this point that will then be used to calculate the
emulsion viscosity in the PVT calculation section.
PROSPER MANUAL
4 - 34 Chapter 5 - PVT Data Input
5.3.3 Tables
In PROSPER the PVT data can also be entered as tables by clicking Tables from
the main PVT input screen. Up to fifty separate tables may be entered, each at a
different temperature. The program will use the data from the tables in all further
calculations provided the Use Tables option has been selected on the input data
screen. This option should be used only when extensive table data is available for
a range of temperatures.
Figure 5-2
PVT Tables
Rather than entering the values by hand, PROSPER can read in tables of Black Oil
PVT properties. To do this, click the Import button from the Tables screen, and
PROSPER will prompt for the name of an ASCII file containing the PVT data.
Petroleum Experts’ PVT Package can be used to calculate and export Black Oil PVT
tables. An example of the PVT Table import file format is given in Appendix E.
Alternatively, data can be passed directly from Excel on a table-only basis using the
Clip button. The Clip button will paste the copied data from Excel into the selected
PVT table.
PROSPER interpolates the entered table data and if the entered data is
 incomplete i.e., one table containing only a single row of values will result
in interpolation errors.
Figure 5-3
PVT Match Data Screen
Since gas evolution in the tubing is a constant composition process, Flash data,
not differential liberation data should be used for matching. For each match data
table, enter the temperature and bubble point, then enter pressure versus gas oil
ratio, oil FVF and oil viscosity. Where data is incomplete or not available, leave the
field blank. Use the GOR and FVF at bubble point plus the viscosity if available.
Enter only the minimum number of points to ensure a good match.
Better results for sparse laboratory PVT data sets are usually obtained using
correlations matched to the available lab data rather than using a PVT table lookup.
PROSPER MANUAL
6 - 34 Chapter 5 - PVT Data Input
5.3.5 Regression
This option is used to perform the non-linear regression, which adjusts the
correlations to best-fit laboratory measured PVT data. The non-linear regression
matching technique can be used on up to five PVT match tables, each with a
different temperature. The following PVT properties can be used as match
variables:
Pb Bubble point pressure.
GOR Gas oil ratio versus pressure.
FVF Oil formation volume factor versus pressure.
Oil viscosity Oil viscosity versus pressure.
It is not necessary to match on all properties for all applications. In cases where
the PVT data is incomplete or of poor quality, better results can often be obtained
by matching on the best characterised parameters only. However, because bubble
point can be difficult to accurately predict from correlations, it is recommended that,
where possible, it is used as a match parameter. The minimum data required to
perform a regression match is the bubble point and GOR.
 The form of the correlations for FVF is different above and below the bubble
point. If the FVF at bubble point is not available, the regression may not achieve
good results. When matching the oil FVF, always enter data at the bubble point.
Do not enter many match points only use the minimum number to define the
shape of the correlation curves. In most cases, only data at the bubble point is
required.
Figure 5-4
PVT Regression Screen
5.3.6 Match
From the Regression screen, individual correlations can be matched to selected
measured PVT data by:
5.3.6.2 Parameters
Having performed the matching process, the match parameters are displayed by
clicking the Parameters button. The non-linear regression technique applies a
multiplier - Parameter 1, and a shift - Parameter 2 to the correlations. The standard
deviation is also displayed, which represents the overall closeness of fit. The lower
the standard deviation, the better the fit. The best overall model is the one that has
Parameter 1 closest to unity.
Figure 5-5
PVT Match
Parameters
PROSPER MANUAL
8 - 34 Chapter 5 - PVT Data Input
In all circumstances, always enter match data at the bubble point to ensure that no
discontinuities occur.
5.3.7 Calculations
In order to make a plot or listing of fluid property data, PROSPER must first calculate
the values over a specified range of temperatures and pressures. Using the
calculated data point’s plots of fluid properties versus temperature or pressure can
be generated. The following is an example of the PVT ⏐ Calculations screen. If the
correlations have been matched, then the fluid properties will be calculated using
the modified correlations.
Figure 5-6
PVT Calculation
Setup
The PVT section can be used as a convenient calculator by entering User selected
data points, then entering specific temperatures and pressures to calculate fluid
properties.
PROSPER MANUAL
10 - 34 Chapter 5 - PVT Data Input
Figure 5-8
PVT calculation Layout
Figure 5-9
PVT Results
Plot
Carefully examine the PVT plots for consistency with the match data. If necessary,
select a different correlation and repeat the PVT calculations until satisfactory
results have been obtained.
There is also the possibility of transferring the displayed calculation to the Tables by
pressing on the Tables button.
 For multi-well projects, set up matched PVT models for each producing
area first. This will save time and reduce the potential for error by recalling
the relevant PVT data into each well file.
PROSPER MANUAL
12 - 34 Chapter 5 - PVT Data Input
5.3.10 Correlations
This option displays the match parameters and standard deviations for each
matched correlation. See section 5.2.4.4 for a more detailed explanation of this
5.3.11 Composition
In the PVT Input Data screen, click the Composition button, and PROSPER will use
the PVT properties (Oil Gravity, GOR) to estimate the composition of the reservoir
fluid. The estimated composition is used internally by PROSPER to calculate
thermodynamic properties needed in the choke and enthalpy balance temperature
models. The following is an example of an estimated Black Oil composition:
Figure 5-10
Estimated Composition
Click BI Coefficients and PROSPER will display the Binary Interaction coefficients to
be used in an EOS description of the fluid. An example BI Coefficients display is
shown below:
Figure 5-11
BI Coefficients for
Estimated
Composition
Figure 5-12
PVT input data
PROSPER MANUAL
14 - 34 Chapter 5 - PVT Data Input
Figure 5-13
Viscosity Modelling
(Information Required)
5.3.13 Emulsions
PROSPER can model the effect of Oil/Water emulsions on mixture viscosity for
Black Oil PVT systems. The behaviour of emulsions in producing well equipment is
not well understood. Emulsion PVT in PROSPER provides a means to assess
possible effects of increased emulsion viscosity by curve fitting experimentally
determined data. It must be emphasised that the method is empirical and does not
represent any rigorous model of emulsion behaviour.
In the laboratory, stable emulsions can be prepared from many crude oil / water
systems. Emulsion samples discovered in surface separation equipment do not
necessarily imply that emulsions are present in the well. Field experience shows
that the effect of emulsions is usually less than predicted by laboratory tests.
Emulsion PVT should be used with caution and only when it is certain that
emulsions are present and it is necessary to evaluate their effect on calculated
pressures.
To enable emulsion PVT in PROSPER, the Emulsion option must first be selected
on the Options screen. Emulsion viscosity will replace the mixture viscosity for
selected elements of the production system. Experimental or empirical emulsion
viscosity data can be entered and curve-fitted using non-linear regression. The
fitted curve is used to optionally replace the oil/water mixture viscosity in IPR, VLP
and pump calculations. When selected, emulsion viscosity for the User-entered
value of water cut will be substituted for the fluid mixture viscosity.
Drop down the Emulsion box and select from the following:
• No viscosity corrections
Turns off emulsion viscosity corrections
• Everywhere
Emulsion viscosity for IPR, VLP and pump if present
• Pump only
Emulsion viscosity for pump only
Figure 5-14
Emulsion Match Data
Entry
The pressure and temperature that correspond to the experimental conditions are
entered in Experimental Parameters. This enables PROSPER to correct the
emulsion viscosity for temperature and pressure.
Figure 5-15
Emulsion
Viscosity Plot
When Emulsions Everywhere have been selected, the calculated Oil Viscosity in
the PVT section will be replaced by the emulsion viscosity for the value of Water
Cut entered.
If Water is selected, then the only other data required is the salinity of the power
fluid. The program will then estimate fluid properties using the normal water PVT
model.
If Other Fluid is selected, then tables of fluid properties need to be entered that
PROSPER will use for interpolation. The program will never extrapolate so please
ensure that the table data covers the expected ranges of pressures and
temperatures. Click the Properties button and the following screen will be
displayed.
Figure 5-16
Power Fluid Properties
Data Entry
PROSPER MANUAL
18 - 34 Chapter 5 - PVT Data Input
Tables of data for up to 10 temperatures may be entered. Please ensure that the
tables span the expected range of conditions that will be encountered.
The Generate feature allows to automatically calculate the tables using the
 PVT model in the main screen.
If a PVT model is available for the power fluid, the suggestion is the
following:
1. Enter in the PVT main screen the fluid black oil properties
3. Enter in the main screen the black oil parameters for the produced
fluid
Click the | Hydrates button and the following entry screen will be displayed.
Figure 5-17
Hydrates Formation
Table Data Entry
PROSPER MANUAL
20 - 34 Chapter 5 - PVT Data Input
Figure 5-18
Dry and Wet Gas PVT
The bottom-right part of the screen will only appear when the option Calculate
Condensate Water Vapour is selected in the Options | Water Viscosity section.
If this option is selected, the effects of condensation of water vapour on the
pressure drop calculation in the tubing / pipeline will be taken into account.
This model applies to most gas wells. The condensate production is included in the
gas stream as an increase in density - the flow remains single-phase gas plus free
water if present. The separator temperature is assumed to be the same as the top
node temperature. If there is significant hydrocarbon liquid drop out in the tubing, a
retrograde condensate model should be used.
 The Gray VLP correlation has an internal PVT routine that models the
effect of liquid dropout in the tubing. This overrides the Dry and Wet gas
PVT.
The black oil condensate model must not be matched as previously done for oils.
This is because the black oil model for condensate in PROSPER uses a
mathematical model and matching could throw the model out of bounds.
Figure 5-19
Black Oil Condensate
PVT
Note:
If tank GOR and tank gas gravity is unknown, they can be left at 0. The
unmeasured tank gas rate should be estimated using a suitable correlation and
added to the separator gas. For such cases, the total produced GOR should be
entered under separator GOR. Condensate gravity is at standard conditions.
 If the separator pressure is above dew point, then there can be no liquid
production. When the dew point is unknown, set it to the reservoir
pressure. PROSPER handles conflicting input data by dropping the
separator pressure to atmospheric, and increasing the separator gas
gravity as required accounting for the liquid production indicated by the
Separator GOR. The mass balance is respected at all times.
PROSPER MANUAL
22 - 34 Chapter 5 - PVT Data Input
PROSPER uses produced CGR data for matching. To convert lab data in terms of
vaporised CGR to produced CGR, simply subtract the lab vaporised CGR data
values from the vaporised CGR at dew point. The following plot illustrates the
process:
70
60
50
40 Dew Point Pressure
30
20
10
0
0 500 1000 1500 2000 2500 3000
Pressure (psia)
The black oil condensate model must not be matched as previously done
 for oils. This is because the black oil model for condensate in PROSPER
uses a mathematical model and matching could throw the model out of
bounds.
5.5.2 Calculations
Fluid property data can be calculated for a specified range of temperatures and
pressures. If the correlations have been matched, then the matched correlations
will be used for the calculations. Plots of fluid properties versus temperature or
pressure can be generated.
The equations used in PROSPER are derived from Van der Waals Equation and in
common with it represent the total pressure as a summation of an attractive and a
repulsive element:
where ‘b’ represents the hard-sphere volume of the molecules and ‘a’ the
intermolecular attraction.
The two cubic Equations of State which are available in PROSPER are:
1) Peng-Robinson (PR)EoS:
and,
2) Soave-Redlich-Kwong(SRK)EoS:
PROSPER MANUAL
24 - 34 Chapter 5 - PVT Data Input
where
and
and
The PVT calculation method is identical for all reservoir fluid types i.e., oil and
water, condensate or gas.
The choice of fluid type affects the choice of IPR and VLP models as well as the
range of available sensitivity variables.
Figure 5-21
EOS fluid selection
PROSPER MANUAL
26 - 34 Chapter 5 - PVT Data Input
Figure 5-22
EOS set-up options
Optimisation Mode
Over the past few years, our PVT experts have been working on ways to speed up
the calculation of properties from an EOS model. Speed is one of the main issues
with fully compositional models and the options in this field will define the speed of
calculations.
The objective of this option is to speed up the calculations without penalising the
accuracy the results. The Medium mode is the fastest (up to 80 times)
Volume Shift
Option to enable/disable the use of Volume Shift in the EoS.
conservation of mass.
Figure 5-23
Importing K-Values
PROSPER MANUAL
28 - 34 Chapter 5 - PVT Data Input
Figure 5-24
PVTP separator
calculation
Once the calculations are complete, under the Analysis tab the Export K-Values
button can be used:
Figure 5-25
Exporting K-Values
Figure 5-26
Exporting K-Values from
PVTP
Now the program will allow the User to export a *.pks file that can be imported in
PROSPER containing all the information with regards to separator stages and K
values.
Figure 5-27
Importing K-Values in
PROSPER
PROSPER MANUAL
30 - 34 Chapter 5 - PVT Data Input
 These options should reflect the EOS available for the fluid (from
PVTP for example) and the process (path) the fluid follows to standard
conditions (which will affect the volumes and quality of the resulting
fluid)
Figure 5-28
Equation of
State PVT
The EOS fluid model is activated via the Options Summary screen where the
various EOS options can be selected. The Options can also be changed from the
EoS main screen by selecting Change.
Use of regressed critical volume data will improve the quality of calculated liquid
viscosities. Where critical volume data is unavailable, PROSPER uses a correlation
to estimate the values. The Parachor is used for surface tension calculation. Binary
interaction components are entered on a screen similar to that shown below by
clicking on the BI coeffs button from the EOS input screen.
Figure 5-29
Binary Interaction
Coefficients Input
After entering the interaction coefficients, click OK to return to the input screen.
Then click Generate to display a screen requesting the range of pressures and
temperatures and the number of pressure and temperature steps to calculate.
PROSPER MANUAL
32 - 34 Chapter 5 - PVT Data Input
Figure 5-30
EOS Calculation Screen
Figure 5-31
Pressure and
temperature ranges
Figure 5-32
EOS
calculation
results
Figure 5-33
GOR vs. pressure
plot
Click the Properties button and the program will determine the equivalent black oil
properties by flashing the fluid to atmospheric (i.e. standard) conditions using the
separator scheme entered in the main screen.
Figure 5-34
Equivalent
Black Oil
Properties
 Production rates entered in PROSPER when using EOS PVT assume the
produced fluid is flashed directly to atmosphere. E.g. for oil, enter the
production rate that results in the correct wellhead mass flow rate when the
oil gravity is the same as shown by the Properties calculation.
PROSPER MANUAL
34 - 34 Chapter 5 - PVT Data Input
Figure 5-35
EOS Phase
Envelope
The EOS input screen allows pseudo component data to be imported directly from
data files such as those generated by Petroleum Experts' PVT package or other
programs. Simply click Import and select the appropriate file from the dialogue box.
Once fluid properties have been generated, they can be saved in a .PVT file by
clicking the Save button and entering a file name when prompted.
 Before importing PVT data, first ensure that PROSPER is using the correct
units for pressure and temperature.
 The Gray VLP correlation’s internal PVT will over-ride the EOS PVT.
The data required for temperature prediction depends on the temperature model
used. For the Rough Approximation and Improved Approximation, there is little
additional data required. For the rigorous Enthalpy Balance temperature model, it
is necessary to completely define the well environment, including all casing strings,
cement tops, formation lithology etc.
 For subsea systems, any depth reference (e.g. sea level, drill floor, ground
level) can be used. If ground level is used, then a tied back well would
have a negative wellhead elevation. To minimise the potential for errors in
correcting the depths, it is recommended to use the same reference as
used for the deviation survey data.
Figure 6-1
Equipment Input
To start data entry for a new application, click All ⏐ Edit. PROSPER will then
display all the relevant input screens in sequence. If data has already been
entered, clicking the Summary command button will display a summary of the
current equipment. To go back and edit one particular equipment item, click on the
button beside the appropriate item. Data can be entered for the surface equipment
and then include or exclude it temporarily from any calculation by setting the
Disable Surface Equipment choice box at the bottom of the screen to Yes.
The editing buttons Cut, Copy, Paste, Insert and Delete operate on data records
that have been selected by clicking on their row number button(s). All records can
be simultaneously selected by clicking the All button. Use the Import button to
import data from a wide variety of sources.
When more than 18 points are available, the Filter allows a determined number of
points (up to 18) that best-fit the entered points (see figure below).
There is a Measured Depth to True Vertical Depth (and the reverse is true)
 at the bottom.
If the user wishes to find the TVD at a given MD, just enter the MD value in
the relevant space and select Calculate. If the user wishes to find the MD
at a given TVD, just enter the TVD value in the relevant space and select
Calculate.
Figure 6-2
Deviation Survey Input
In the Raw Data table (Figure 6.3) enter the data from the survey. It is possible to
copy the table by selecting the first row (click on the number 1) and Paste from the
Clipboard.
These are the additional buttons:
Once depths have been entered, plot the well profile by selecting Plot. A plot
similar to the one below will be displayed:
PROSPER MANUAL
4 - 30 Chapter 6 - Equipment Data Input
Figure 6-3
Raw data table
Figure 6-4
Well Deviation Plot
The reference depth used by PROSPER for all calculations is zero in the
 Deviation Survey table. The Deviation Survey table is interpolated to
determine the difference in TVD between any two well nodes. MD and
TVD data must be at least as deep as the bottomhole tubing depth;
PROSPER will not calculate beyond the last depth in the table.
 Deviation survey data entry is required also for vertical wells - enter 0,0
for the surface reference and an MD the same as the TVD of the intake
node. The deviation survey has to start with 0 measured depth and 0
TVD. Due to this reason, the reference depth (where TVD = 0) has to be
at or above the wellhead.
For Horizontal wells the deviation survey may be entered only up to the
 heel of the well, as the well from the heel all the way up to the toe is a part
of the inflow description.
Figure 6-5
Surface Equipment
Input
TVD, Length Format
Fittings have been added to the surface equipment section of PROSPER to account
for the various pressure losses associated with pipe fittings throughout a given
system (Figure 6-6).
PROSPER MANUAL
6 - 30 Chapter 6 - Equipment Data Input
Figure 6-6
Surface Equipment
Input
TVD, Length Format
PROSPER defines surface equipment as the pipe work between the production
manifold and the upstream side of the wellhead choke. The production manifold is
regarded by PROSPER as presenting a constant backpressure, regardless of flow
rate. If systems analysis is to be performed relative to the wellhead, (i.e. gathering
system pressure losses are neglected) then no surface equipment input is required.
The surface equipment model can be described using the following 2 elements:
• Pipe
• Choke
The manifold is set as the first equipment type automatically by PROSPER. Surface
equipment geometry can be entered either as pairs of X, Y co-ordinates relative to
the manifold or the Xmas Tree, Reverse X, Y (Y co-ordinates deeper than the
reference depth are negative) or TVD of the upstream end and the length of the
pipe segment.
The difference in TVD between the ends of a pipe segment is used to calculate
gravity head losses. The internal diameter (ID), roughness and pipe length entered
determine the friction pressure loss. The flowing temperatures for each upstream
node must also be entered when calculation option Pressure only is selected.
The Rate Multiplier column enables simulation of the pressure drop due to several
identical wells being connected to a production manifold via a common surface flow
line. The fluid velocity in the flowline is multiplied by the value entered increasing
the frictional pressure losses. For most applications it should be left at its default
value of 1.
The editing buttons Cut, Copy, Paste, Insert and Delete operate on data records
that have been selected by clicking on their row number button(s). All records can
be simultaneously selected by clicking the All button. Use the Import button to
import data from a wide variety of sources. Up to 200 pipe segments can be
entered, enabling the user to model very long pipelines.
Figure 6-7
Surface Equipment Input
X,Y Co-ordinates Format
PROSPERS multi-phase choke pressure loss correlation accounts for both critical
and sub-critical flow. We would recommend the use of the ELF Choke correlation
that it similar to the Petroleum Experts’ method and is more robust in extreme
conditions.
Ensure that the length of each pipe segment is equal to or greater than the
 difference in TVD between its ends.
The downhole and surface equipment entries must describe a continuous
system. The TVD and temperature of the upstream end of the last
pipeline segment should be equal to the Xmas tree TVD and temperature.
In X,Y co-ordinates, the Y co-ordinate of the last pipe segment must be
the same elevation as the wellhead TVD. (i.e. same magnitude, but
opposite sign)
To check that the surface equipment description is accurate, click Plot to display a
plot of the pipe elevation as follows:
PROSPER MANUAL
8 - 30 Chapter 6 - Equipment Data Input
Figure 6-8
Surface Equipment Input
Pipe Elevation Plot
Figure 6-9
Downhole
Equipment Input
The tubing string can be modelled using the following element types:
• Tubing
• SSSV
• Restriction
• Casing
PROSPER automatically inserts the Xmas tree as the first downhole equipment
item. To describe the tubing string, work from the shallowest depth downwards,
entering the bottom depth of changes in tubing diameter, ID and roughness factor.
Casing is treated the same as tubing for pressure drop calculations. Downhole
equipment details should be entered down to the producing interval being analysed.
The deepest depth entries for the tubing, deviation survey and temperature should
be consistent.
 Below the uppermost producing perforation, the flow profile (as measured
by a production logging tool) depends on layer productivity etc. The
uppermost producing perforation is the deepest point in the well passing
100% of the production. Below this point, the calculated frictional pressure
gradient may be over-estimated in high rate wells having small I.D.
completions.
To select tubing string elements to build up the tubing string description, click on
the list box arrows to the right of the item fields and select the equipment from the
drop-down list. The editing buttons Cut, Copy, Paste, Insert and Delete operate
on data records that have been selected by clicking on their row number button(s).
All records can be simultaneously selected by clicking the All button. Use the Import
button to import data from a wide variety of sources. Up to 18 tubing string
elements can be input. For complex completions, simplify the data entry by
entering only the major elements that dominate the overall tubing pressure drop.
The Rate Multiplier column enables simulation of the pressure drop due to
intermittent sections of dual completion. The fluid velocity in the tubing is multiplied
by the value entered - thereby increasing the frictional pressure losses. For
standard single tubing completions it should be left at its default value of 1.
PROSPER MANUAL
10 - 30 Chapter 6 - Equipment Data Input
Figure 6-10
Temperature Survey
The editing buttons Cut, Copy, Paste, Insert and Delete operate on data records
that have been selected by clicking on their row number button(s). All records can
be simultaneously selected by clicking the All button. Use the Import button to
import data from a wide variety of sources.
 PROSPER interpolates temperatures from the survey data for depths within
the table limits, and uses linear extrapolation elsewhere. To eliminate
potential errors, ensure that a temperature is entered for the deepest node
depth. It is recommended that the maximum temperature survey depth,
deviation survey depth and intake node depths are all consistent.
6.1.5 Summary
Before leaving the System ⏐ Equipment screen, the accuracy of the equipment
description should be checked by making an equipment summary. Click Summary
to display the summary screen.
Figure 6-11
System Summary
Selecting the appropriate button from the Summary screen can draw a sketch of
the surface and downhole equipment. Select Draw Downhole to display a sketch
similar to the following:
Figure 6-12
Downhole Drawing
PROSPER MANUAL
12 - 30 Chapter 6 - Equipment Data Input
Figure 6-13
Enthalpy Balance
Equipment Input
Figure 6-14
Surface Environment Input
(Off Shore)
The screen below shows an offshore well with a 30" OD riser run to a seabed depth
of 400 ft. The well also has a 7" OD liner run to 14000 ft with the liner top set at
11000 ft.
PROSPER MANUAL
14 - 30 Chapter 6 - Equipment Data Input
Figure 6-15
Drilling and
Completion Input
The completion fluid Liquid and Gas properties can have a significant effect on the
heat loss through the annulus. If pressure is maintained on the annulus, the mud
weight used should be modified to reflect the actual annulus pressure at the packer
depth. If the well is being gas lifted, the program assumes that the annulus is full of
gas down to the injection point.
The editing buttons Cut, Copy, Paste, Insert and Delete operate on data records
that have been selected by clicking on their row number button(s). All records can
be simultaneously selected by clicking the All button. Use the Import button to
import data from a wide variety of sources.
For complex completions fluids, select the appropriate Customised Options from
the main Drilling and Completions section. Completion fluid property data will be
entered via look-up table data. Figure 6-14 shows the data required when selecting
the Completion Fluid Gas Type | Customised option from the drilling and
completions section.
Figure 6-16
Customised
Completion Fluid
Lookup Table – data
entry
6.2.4 Lithology
The program contains a database of thermal properties for various rock types
including Sandstone, Shale, Limestone, Dolomite, Halite and others. The thermal
properties database can be edited and added to as required. If detailed lithology
data is available it should be entered in the screen as shown below. If no data is
available, use shale from surface to total depth.
PROSPER MANUAL
16 - 30 Chapter 6 - Equipment Data Input
Figure 6-17
Litho logy Input
The reservoir temperature and pressure should be entered for the production
reference depth. The formation temperature gradient is interpolated between the
reservoir and surface environment temperatures.
The editing buttons Cut, Copy, Paste, Insert and Delete operate on data records
that have been selected by clicking on their row number button(s). All records can
be simultaneously selected by clicking the All button. Use the Import button to
import data from a wide variety of sources.
 Thermal properties for buried pipelines are taken from the shallowest
formation type entered in the Lithology screen.
Figure 6-18
Surface Equipment
Input
To calculate heat losses, additional data such as outside diameter, material type
and insulation (if used) are required to be input. The surface equipment model can
utilise the following equipment types:
• Line pipe
• Coated pipeline
• Flexible tubes
• User selected
• Choke
To allow for pipe bends, etc., enter an equivalent length/diameter. The choke
calculation handles both sub-critical and critical flow. The program will calculate the
temperature drop across the choke. Descriptive labels for each element can be
entered in the Label field if desired. Labels appear on reports and calculation
screens. Surface equipment geometry can be optionally entered as TVD of the
upstream end of the pipe segment and length or as X, Y (from the manifold or the
Xmas Tree) co-ordinate pairs. Refer to Section 6.1.2 above for more details.
The Rate Multiplier column enables simulation of the pressure drop due to several
wells being connected to a production manifold via a common surface flow line.
The fluid velocity in the flowline is multiplied by the value entered - thereby
increasing the frictional pressure losses. For most applications it should be left at
its default value of 1. As an example, the pressure drop in a flowline connected to
3 identical wells could be modelled using a pipeline rate multiplier of 3. 2 parallel
flowlines having identical dimensions can be modelled by entering the actual
dimensions for one pipe and a pipeline rate multiplier of 0.5. It is also possible to
vary the rate multiplier along the pipeline to simulate varying sections of dual
pipelines for example.
The editing buttons Cut, Copy, Paste, Insert and Delete operate on data records
that have been selected by clicking on their row number button(s). All records can
be simultaneously selected by clicking the All button. Use the Import button to
PROSPER MANUAL
18 - 30 Chapter 6 - Equipment Data Input
import data from a wide variety of sources. Up to 200 pipe segments can be
entered, enabling the user to model very long pipelines.
Pipe insulation (e.g. concrete, foam or bitumen) can be modelled. To define the
pipe insulation click the Enter button to display the following screen:
Figure 6-19
Pipe Insulation Input
Select the required insulation type from the drop-down list, then enter the thickness.
Enter the insulation beginning with the innermost layer. PROSPER uses the thermal
properties in its database to calculate the thermal conductivity of the composite
insulation. Click OK to return to the surface equipment screen. Different
insulations can be entered for each section of the flowline as required. The
calculated composite thermal conductivity is referenced to the pipe inside diameter.
Pipes can be laid on the surface (burial depth = 0) or buried. The diagram below
shows the burial depth geometry.
Figure 6-20
Pipe Burial Depth
The burial depth is the distance between the soil surface and the bottom of the pipe
(including insulation, if present). The pipe is partially buried if the burial depth <
O.D. of the insulated pipe.
 Ensure that the flowline pipe geometry is consistent with the pipe burial
depth. If necessary, insert another node and change the burial depth for
e.g. the riser.
 The soil conductivity around buried surface pipes is taken from the
Thermal Properties database for the shallowest rock type entered in the
Litho logy screen. In previous PROSPER releases, the soil conductivity
was fixed at 3.5 W/m/K.
The thermal properties database for downhole equipment elements can be edited
or added to if required. Pressure and temperature changes across subsurface
safety valves and restrictions (nipples) are correctly modelled. The following is an
example of a downhole equipment data input screen:
PROSPER MANUAL
20 - 30 Chapter 6 - Equipment Data Input
Figure 6-21
Downhole
Equipment Input
For the Enthalpy Balance temperature model the casing dimensions and material
type are entered under Drilling and Completion, so the downhole equipment
description is required only for the tubing string.
To select tubing string elements to build up the tubing string description, click on
the list box arrows to the right of the item fields and make the appropriate selection
from the drop-down list. The editing buttons Cut, Copy, Paste, Insert and Delete
operate on data records that have been selected by clicking on their row number
button(s). All records can be simultaneously selected by clicking the All button. Use
the Import button to import data from a wide variety of sources. Up to 18 tubing
string elements can be input. For complex completions, simplify the data entry by
entering only the major elements that dominate the overall tubing pressure drop.
The Rate Multiplier column enables simulation of the pressure drop due to
intermittent sections of dual completions. The fluid velocity in the tubing is
multiplied by the value entered - thereby increasing the frictional pressure losses.
For standard single tubing completions it should be left at its default value of 1.
6.2.7 Databases
This optional feature is used to access the thermal properties databases for editing
or addition of user-defined materials. Select Databases and click Edit and the
following selection screen will be displayed:
Figure 6-22
Temperature Databases
Selection
PROSPER MANUAL
22 - 30 Chapter 6 - Equipment Data Input
Figure 6-23
Insulation Properties Entry
 Check that the units are correct prior to entering the thermal properties.
Edited values remain in memory and become part of a particular well model file
when the file is saved. To permanently save edited values or new user-defined
entries for use in other projects click the Save button to keep them in the database.
The Reset button is used to return all entries to their default values.
Figure 6-24
System Equipment Input
To start data entry for a new application, click All ⏐ Edit. PROSPER will then
display all the relevant input screens in sequence. If data has already been
entered, clicking the Summary command button will display a schematic summary
of the current equipment.
To go back and edit one particular equipment item, click on the button beside the
appropriate item. Data can be entered for the surface equipment and then include
or exclude it temporarily from any calculation by using the Disable Surface
Equipment choice box at the bottom of the screen.
PROSPER MANUAL
24 - 30 Chapter 6 - Equipment Data Input
Figure 6-25
Surface
Equipment Input
The heat transfer coefficient should not be confused with the pipe thermal
conductivity. The overall heat transfer coefficient accounts for the heat flow
through the production tubing, annulus and insulation (if present) to the
surroundings. Heat transfer by forced and free convection, conduction and
radiation must all be accounted for in the value of the overall heat transfer
coefficient. In PROSPER, the overall heat transfer coefficient is referenced to the
pipe inside diameter. Please refer to Section 6.1.2 for more details.
Figure 6-26
Geothermal Gradient
Input
As for surface equipment, enter an overall heat transfer coefficient that describes
the resistance to heat flow by all mechanisms (convection, radiation and
conduction) from the well to its surroundings. The Enthalpy Balance temperature
model is a convenient way to determine average heat transfer coefficients. The
heat transfer area is referenced to the pipe inside diameter.
PROSPER MANUAL
26 - 30 Chapter 6 - Equipment Data Input
Figure 6-27
Average Heat Capacities
Enter values that correspond to average conditions in the well. Note that for oil,
and especially gas that Cp values are strong functions of both temperature and
pressure.
 The default values will often give reasonable results in moderate GOR oil
wells. However, actual Cp values for oil and gas vary widely. Do not rely
on the defaults - obtain good estimates of Cp, or use the Enthalpy
Balance method where accurate temperature prediction is required.
Figure 6-28
System Equipment Input
(Improved Approximation
Method)
To start data entry for a new application, click All ⏐ Edit. PROSPER will then display
all the relevant input screens in sequence. If data has already been entered,
clicking the Summary command button will display a summary of the current
equipment. To go back and edit one particular equipment item, click on the button
beside the appropriate item.
Data can be entered for the surface equipment and then include or exclude it
temporarily from any calculation by using the Disable Surface Equipment choice
box at the bottom of the Equipment Data screen.
Figure 6-29
Surface
Equipment Input
The heat transfer coefficient can be specified for each pipe segment and should not
be confused with the pipe thermal conductivity.
The heat transfer coefficient accounts for the heat flow through the production
tubing, annulus and insulation (if present) to the surroundings. Heat transfer by
forced and free convection, conduction and radiation must all be accounted for in
the value of the overall heat transfer coefficient. In PROSPER, the overall heat
transfer coefficient is referenced to the pipe inside diameter.
Figure 6-30
Geothermal Gradient
Input
As for surface equipment, enter an overall heat transfer coefficient that describes
the resistance to heat flow by all mechanisms (convection, radiation and
conduction) from the well to its surroundings. This value can vary throughout the
formation. The Enthalpy Balance temperature model is a convenient way to
determine average heat transfer coefficients. The heat transfer area is referenced
to the pipe inside diameter.
Figure 6-31
Sea Temperature Gradient
Enter the data to describe to temperature gradient in the sea. Up to 20 points may
be entered. Use the Import button to retrieve the data from a wide variety of
sources
1. Section Buttons. At the top right of the dialog screen are two buttons, labelled
Select Model and Input Data. These allow switching between screens that
control model selection and detailed data input. The former also contains data
pertaining to all models (such as reservoir pressure and temperature), and the
latter manages the data input specific to the chosen model. The selection
buttons have the same function in the multilateral data entry screens.
2. Action Buttons. To the left of the section buttons is a set of buttons that perform
various actions such as Calculate. Only the left-most group appears in the
multilateral data entry screens.
3. Model Selection Screen. The child screen is the area below the action and
section buttons and contains either the model selection or the data input
screens. The same occurs in the multilateral interface, although the actual
model selection and data input screens are different.
Figure 7-1
Main Data Entry
Screen
Section Buttons
As well as switching between the model selection and data input screens the
section buttons also indicate the validation status of the screens. The selection of
one screen or the other is shown by the indentation of the button for that screen
and the validity of the data is flagged by the colour. Green means that all the
required data are entered and within the numerical range for the units chosen;
where appropriate, extra consistency checks have also been carried out. Red
implies that either there is insufficient data entered or it is out of range/inconsistent.
In addition, if no models at all are selected the Select Model and Input Data
buttons are marked invalid. Also, if not enough models are selected the Select
Model button is marked invalid (e.g. a reservoir but no skin model).
Cancel
This exits the screen and restores the data to its state at the start of the main edit
session.
Validate
Checks the data on the current child screen for validity. If the data are not valid, the
validation dialog will appear with diagnostic messages.
Reset
This replaces the data of the current child screen with the data that was current
when the screen was entered.
Help
This displays information relevant to the current child screen.
Calculate
Saves and validates all the data pertaining to the chosen models (e.g. Darcy
reservoir model and Enter Skin By Hand) then runs the correct calculation routine if
the data are valid. On successful completion of the calculation the results are
automatically plotted.
Plot
Will produce a plot screen appropriate to the current reservoir model (for example,
a Darcy plot) and plot the data from the last Calculate command.
Report
Enters the PROSPER Reporting System. The report produced will depend on the
current model choices. A fuller description of the reporting is found in Chapter 12.
Export
Can export current data (input and results) to the printer, a file, the clipboard or the
screen. It thus forms another method of reporting and is described more fully in
Chapter 13.
Transfer Data
PROSPER MANUAL
4 - 75 Chapter 7 - IPR Data Input
Saves and validates all the current data before opening a standard ‘File Save As’
dialog that provides an opportunity to save the data to file in MBAL input format
(.MIP).
If PROSPER has been opened from a session in GAP then the data are
 posted to GAP instead. The transfer button does not prompt for creation
of a .MIP file.
Save Results
This option is only enabled when PROSPER is run from GAP. On a successful
validation options to either over-write the current file or to save the PROSPER file
using ‘File Save As’ options are provided.
GAP
This option is only enabled when PROSPER is run from GAP. It shuts down the IPR
screen and minimises PROSPER, thus bringing GAP to the forefront.
Note that the ‘Save and Validate’ sequence carried out by several of the
 action button commands does not actually save to file but transfers data
from the context of the IPR data screen to the PROSPER data structure
in memory. Hence, files should regularly be saved to avoid losing work
due to power failures or crashes.
This part of the IPR input screen controls the choice of almost all the tabbed dialogs
that will be seen in the subsequent data input screen.
There are four major selections done in this screen. These are:
• Reservoir input
o The User also specifies the pressure, temperature, producing GOR and
water cut at this screen.
• Relative permeability.
o This option can be set to Yes or No in case of oils. If set to Yes, the User
has the option of defining a set of relative permeability curves, which will
be used to change productivity of the system with changing water cut.
The gravel pack selection and the type of completion (cased or open hole)
 are chosen from the main Options screen (in the PROSPER main menu)
but some reservoir models have internal gravel pack data entries instead.
In case gas coning option has been selected in main options, for oils the
 coning button is displayed to allow the activation of a dialog screen in
which parameters for the calculation of rate-dependent GOR's can be
entered
If the fluid is a gas or a condensate the format of the screen is very similar; only the
reservoir and other model input selections vary for example, in gas systems, we
have CGR and WGR instead of GOR and WC.
The choice of reservoir models governs which subsidiary models (principally skin)
is enabled. Thus, horizontal well models do not require a deviation skin data entry
and some of the more complex reservoir models (e.g. multi-layer with dP friction
loss) contain their own skin and gravel pack models.
Only one dialog is displayed at any one time, corresponding to the tab
 selected as shown in Figure 7-2.
Figure 7-2
Data Input Screen
PROSPER MANUAL
6 - 75 Chapter 7 - IPR Data Input
• Reservoir Model
• Mech/Geom Skin
• Dev/PP Skin
• Gravel Pack
• Relative Perm
 The tabs are coloured according to the validity of the data on the
corresponding dialogs.
• If the tab is green, then the data are valid for the current system
set-up.
• If the tab is grey, then this tab is not applicable to the current
reservoir model (or model selection) and so is inaccessible.
 The various screens as shown in the Figure 7-2, accessible by the bottom
tabs comprise the dialog screens, where the input parameters for the
selection are entered. In the area below the Section and Action buttons. In
the case of the model selection screen it is mainly occupied with ways of
choosing models, namely three list boxes, a drop-down list box and a
push button.
For example Figure 7.2 shows a Darcy reservoir model dialog encapsulated in the
data input screen contained in the main entry screen.
• The Reservoir Model tab is marked invalid (due to the unlikely reservoir thickness of
–1 feet).
• The Dev/PP Skin tab and relative permeability tabs are marked disabled. In this
case it is because the ‘Enter Skin By Hand’ option is selected which is assumed to
contain the deviation and partial penetration information. In the latter case relative
permeability is simply not selected (see Figure 7.1, showing the model selection
screen).
 On each of the IPR Input screens there is a validate button. Pressing this
button invokes a checking routine which flags for the any invalid entries.
• Entering a value against a blank field as seen in all the entries of the Figure
7-2.
• Pressing a push button, which takes us further into another screen, where
actual data required is entered as indicated against Dietz calculator on
Figure 7-2.
Petroleum Experts Ltd
Chapter 7 - IPR Data Input 7 - 75
 Some models require data entered for multiple layers (e.g. multi-layer and
multi-layer with dP friction loss) and/or multiple completion zones (e.g.
horizontal well with dP friction loss and Wong-Clifford deviation/partial
penetration skin model).
In dialogs with grid entry it is also possible to select, copy, cut and paste
blocks of the table, using mouse drag operations and the buttons provided
on the screen. As the data in a table are typically interdependent some
consistency validation checks are carried out in addition to the range
validation.
From the Multi-rate models the average reservoir pressure can be back
calculated.
If test data is available it can be entered and plotted against the calculated
inflow.
Well skin can be either directly entered or calculated using the Locke,
Macleod or Karakas and Tariq methods for a mechanical/geometrical
skin, and the Cinco/Martin-Bronz or Wong-Clifford methods for a
deviation/partial penetration skin.
These models can be combined with gravel pack and relative permeability
models if the option is enabled (the former in the Options screen from the
PROSPER main menu and the latter from the IPR main data entry screen).
PROSPER MANUAL
8 - 75 Chapter 7 - IPR Data Input
Once a specific model is chosen and data entered for it, after which an IPR can be
calculated using the Calculate button. The following sections list various inflow
models that are available for oil wells.
The User input productivity index (PI) is used to calculate the IPR. P.I. Entry
replaces the Straight-line IPR in older releases of PROSPER.
Q = J ( Pr − Pb )
7.2.2 Vogel
The program uses the straight-line inflow relationship above the bubble point and
the Vogel empirical solution below the bubble point. A single flowing bottom hole
pressure and surface test rate is used to calculate the IPR, below the bubble point.
From this IPR the rate and bubble point pressure are used to evaluate the PI for the
straight-line part of the inflow above the bubble point.
When calculating IPR sensitivities for reservoir pressure, PROSPER retains the
correct well productivity. Otherwise, changing the reservoir pressure changes the
Vogel well productivity.
2
Q Pwf ⎛ Pwf ⎞
= 1 − 0.2 − 0.8⎜⎜ ⎟⎟
Qmax Pr ⎝ Pr ⎠
7.2.3 Composite
This is an extension of the Vogel inflow solution (Petrobras method) that accounts
for water cut.
Vogel essentially decreases the inflow below bubble point because of gas
formation. However, if the water cut is higher the inflow potential will increase and
approach a straight-line IPR due to single-phase flow. The composite model
captures this by using the following formulation.
Q
J=
⎧ P ⎛ ⎛ Pwf ⎞
2
⎞⎫⎪
⎪
Fo ⎨ Pr − Pb + b ⎜1 − 0.2
Pwf
− 0.8⎜⎜ ⎟⎟ ⎟ + F {P − P }
1 .8 ⎜ Pr ⎝ Pr ⎠ ⎟⎬ w r wf
⎪⎩ ⎝ ⎠⎪⎭
A test flow rate, flowing bottomhole pressure and water cut are required to be
entered.
PROSPER MANUAL
10 - 75 Chapter 7 - IPR Data Input
7.2.4 Darcy
The program uses the Darcy inflow equation above the bubble point and the Vogel
solution below the bubble point. Required input is:
• Reservoir permeability (total permeability at the prevailing water cut and GOR)
• Reservoir thickness (thickness of producing reservoir rock)
• Drainage area
• Well bore radius
• Dietz shape factor (to account for the shape of the drainage area)
7.2.5 Fetkovich
The Fetkovich equation for oil is a modified form of the Darcy equation, which
allows for two phase flow below the bubble point. The Fetkovich equation can be
expressed as:
Q = J ( Pr − Pb ) + J ' ( Pr − Pwf )
2 2
Enter the same inputs as for the Darcy example plus the relative permeability for
oil. Skin can be entered either by hand or calculated using Locke's, Macleod's or
the Karakas and Tariq method.
The fit values of C and n are posted on the IPR plot. If the reservoir pressure is not
available, the program will calculate it. For producing wells, enter a reservoir
pressure lower than the measured flowing bottomhole pressures. The program will
dismiss the reservoir pressure that has been entered and calculate it. For injection
wells, input a reservoir pressure higher than the test pressures entered. The
program will then calculate the reservoir pressure.
7.2.7 Jones
The Jones equation for oil is a modified form of the Darcy equation, which allows
for both Darcy and non-Darcy pressure drops. The Jones equation can be
expressed in the form:
( Pr − Pwf ) = aQ 2 + bQ
Where "a" and "b" are calculated from reservoir properties or can be determined
from a multi-rate test. The same data as for the Darcy model plus the perforated
Petroleum Experts Ltd
Chapter 7 - IPR Data Input 11 - 75
interval is required. Skin can be directly entered or calculated using the available
methods.
i.e. ( Pr − Pwf ) = aQ 2 + bQ
7.2.9 Transient
This IPR method takes into account the change of deliverability with time. This
method can be particularly important for tight reservoirs. Both the Darcy and Jones
equations assume that the well has reached pseudo-steady state flow conditions.
In tight reservoirs, the transient equation can be used to determine the inflow
performance as a function of flowing time. Once the flowing time is long enough for
pseudo-steady state flow to develop within the drainage radius, the Darcy inflow
model is then used. Enter the same data as the Darcy example plus:
162.6 qo µ o Bo ⎛ ⎛ ko t ⎞ ⎞
Pr − Pwf = ⎜ Log ⎜ 2 ⎟ − 3.23 + 0.87 S ⎟
ko h ⎝ ⎝ φµ o Ct rw ⎠ ⎠
Time is the flowing time since the last reservoir pressure equalisation up to the time
of the analysis. If the flowing time exceeds TpSSS , the deliverability is evaluated
using TpSSS , which is equivalent to using the pseudo-steady state Darcy model.
 Gravel packs can be combined with the hydraulically fractured well IPR to
model Frac-Packed wells
• Drainage area
• Well bore radius
• Dietz shape factor (Depends on the shape of the drainage area)
• Time (Inflow is transient in early time)
• Fracture height
• Fracture half length
• Dimensionless fracture conductivity
Figure 7-3
Horizontal Well Geometry
30 h = 50'
0.01 zw = 25'
rw = 0.25'
kh = 50 md
25 0.1 vis = 1 cp
1.0
P.I. (BOPD/psi)
20
Simulator - Lines
PROSPER - Symbols
15
4000'
10
4000'
0
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
L1/2/Lx
PROSPER MANUAL
14 - 75 Chapter 7 - IPR Data Input
Figure 7-5
Multi-Layer IPR Input
Each layer can have different reservoir pressures, inflow models and fluid
properties. The oil gravity, GOR and water cut may be entered for each layer. The
produced fluid properties in the well bore are determined from the summation of the
individual layer contributions. The summation accounts for cross flow between
layers having different pressures. Each layer can be gravel packed if desired. Both
Injectors and Producers can be modelled. For cases where the zones are
separated by significant depth or friction pressure losses are significant, the Multi-
layer - dP Loss network IPR model should be used.
 If PVT matching has been used in the PVT section, it is assumed that it
was performed on the commingled layer fluids. The fit parameters
generated will be applied to all PVT calculations for all layers in
determining the combined inflow performance.
To use the Multi-Layer IPR, enter the reservoir temperature then click Input Data to
enter the tab-controlled screen, and then click on the Reservoir Model tab button.
For each layer, select the inflow model from: Darcy, Multi-rate Jones, or PI Entry
methods then enter the layer PVT properties, average pressures, thickness and
skins. For each layer, click the Layer Data button and enter the information
required by the inflow model.
Figure 7-6
External Entry
IPR
External IPR tables can also be imported from ASCII files. The file format is given
in Appendix E of the PROSPER User Guide.
PROSPER MANUAL
16 - 75 Chapter 7 - IPR Data Input
Figure 7-7
Horizontal well - dP
Friction
The reservoir parameters entered in the upper section of the screen determine the
overall well productivity using the selected model. The zone parameters are used
by the network algorithm to re-scale the overall productivity on a zone-by-zone
basis. A description of the input parameters follows:
Reservoir Parameters
• Horizontal Well Model (Model used for overall well productivity)
• Reservoir permeability (Total permeability at prevailing water cut)
• Reservoir thickness (Thickness of producing reservoir rock h)
• Well bore radius (Radius of open hole rw)
• Horizontal anisotropy (Ratio of Ky/Kx where Kx is permeability in the
direction of the horizontal well and Ky is the
permeability perpendicular to the horizontal well)
• Vertical anisotropy (Ratio of Kz/Ky where Kz is the vertical
permeability)
• Length of well (Horizontal section L)
• Length of drainage area (Reservoir dimension parallel to well Lx)
• Width of drainage area (Reservoir dimension perpendicular to well Ly)
• Distance from length edge to centre of well (Xw)
• Distance from width edge to centre of well (Yw)
• Distance from bottom of reservoir to centre of well (Zw)
Zone Parameters
Data for up to 20 zones can be entered. The required inputs are as follows:
These parameters describe the local permeability and the flow path along the well
bore. Click the Zone Data button to enter details such as skin and perforation
parameters. If the Skin Method is Enter by Hand, the skin and open hole radius are
required. If Karakas & Tariq is selected, then enter the perforation details as in
Section 7.4.1 and PROSPER will estimate the zone skin. If the zone is to be gravel
packed, this data is entered under Zone Data.
 To allow comparison of the IPR with and without friction losses, setting the
zone roughness to zero turns off the friction pressure drop calculation
entirely rather than calculating friction for a smooth pipe
Figure 7-8
Horizontal well -
Coning Calculations
Enter a production rate and porosity then select the required coning calculation
method. Click Calculate to find the critical rate and time to breakthrough for the
rate entered. The pressure along the well bore for the specified rate is calculated
and displayed by clicking Plot.
PROSPER MANUAL
18 - 75 Chapter 7 - IPR Data Input
Figure 7-9
Horizontal well - dP
Friction Loss Plot
Figure 7-10
Horizontal well -
Rate
per Unit Length
 The Horizontal Well - friction dP IPR models the pressure at the heel of the
well as a function of pressure. The intake node is therefore the heel of the
well. The heel should be the last node entered in System ⏐ Equipment
and Deviation Survey tables - it is not necessary to enter details of the
horizontal producing section except in the IPR.
Figure 7-11
Multi-Layer Well-
friction Dp
This screen allows for the entry of up to 49 layers. To enter PVT, IPR data
(permeability, test rates etc. depending on the IPR model selected) and layer skin,
click the appropriate button to display the input screen. The depth entered for TOP
is the depth for which the IPR is to be evaluated. This is normally the same as the
deepest depth entered in System ⏐ Equipment, but it can be set to surface or other
value.
The IPR at surface can be calculated by entering the surface elevation for TOP
depth and a blank zone from surface to the shallowest producing zone. Use blank
zones with appropriate reduced I.D. to simulate the effect of sliding sleeves and
PROSPER MANUAL
20 - 75 Chapter 7 - IPR Data Input
flow controls in a multi-zone completion. Click Calculate and the IPR for each layer
and the summation will be calculated and displayed on a plot as follows:
Figure 7-12
Multi-Layer Well-
friction dP
To list the layer production in detail, click Results and scroll through the layer
results one by one. An example results screen is shown below:
Figure 7-13
Multi-Layer Well- friction dP
Results
Scroll from the selection menu to view the results for each of the layers.
Gravel pack and well skin etc. can be seen by scrolling to the right of the results
table. Negative layer production rates indicate cross-flow into the layer.
 The multilayer option is now available for dry gas and gas condensate
model
7.2.17 SkinAide
The Elf inflow and skin calculation method is incorporated in PROSPER. API
perforation characteristics can be used to estimate perforation damage given
casing and formation properties. A detailed description of SkinAide is given in
Section 7.7.
Once the effective wellbore radius is determined the model calculates the well
productivity the same way the horizontal well with no-flow-boundaries is calculated.
This is for use with wells that are stimulated with one or more transverse vertical
fractures. It is assumed that the fractures are circular, the well goes through their
centre and they are evenly spaced. If there is one fracture it is in the middle of the
well. The data to be entered are the same as those for a horizontal well, along with
the fracture half-length and its dimensionless conductivity.
PROSPER MANUAL
22 - 75 Chapter 7 - IPR Data Input
7.2.20.1 Overview
The algorithm follows the framework outlined in: SPE 30777, Thermally Induced
Fractures: A Field-Proven Analytical Model. SPE Reservoir Evaluation & Engineering,
February 1998. J-L. Detienne, Max Creusot, Nicolas Kessler, Bernard Sahuquet
and J-L. Bergerot. Information was also assembled from SPE 7964 (radial
reservoir temperature profile) and SPE 11332 (coefficient for thermo-elastic stress
equation). Note that the temperature profile derivation uses the same basis as the
work of de Lauwerier referred to in SPE 30777.
The IPR calculated by this model consists, therefore, of two different zones with a
break-point where the fracturing occurs. See the following figure.
Figure 7-14
Thermally Induced
Fracture IPR
The model is not valid for uncontrolled hydraulic fracturing where the fracture length
may be several hundred feet. The fracture should not extend beyond the so-called
cooled injection zone, the extent of which is calculated using the temperature profile
referred to above.
PVT parameter
Injected Fluid Temperature
Thermo-mechanical Parameters
Initial Reservoir Stress
Sweep Efficiency
Injected Fluid Specific Heat Capacity
Overall Reservoir Conductivity
Overall Reservoir Specific Heat Capacity
Overall Reservoir Density
PROSPER MANUAL
24 - 75 Chapter 7 - IPR Data Input
Top and Bottom Surroundings Conductivity
Top and Bottom Surroundings Specific Heat Capacity
Top and Bottom Surroundings Density
Reservoir Thermal Expansion (thermo-elastic correlating coefficient, relates
temperature perturbation to stress perturbation)
Biot's Constant (poro-elastic correlating coefficient, relates pressure perturbation to
stress perturbation)
Poisson's Ratio
Reservoir Young's Modulus
The test water cut and the test reservoir pressure are used to determine the phase
saturations and viscosity at the original PI. With the use of relative permeability
curves, the liquid mobility at the test (reference point) can be calculated from:
K rw K ro
M test = +
µw µo
The water saturation can always be estimated based on the relative permeability
curve and the water cut entered. At a particular reservoir pressure and water cut,
the mobility (M) can be calculated.
M
PI = PI test ×
M test
The possible reduction in liquid mobility due to any increase in the gas saturation is
not accounted for in this option. Hence, If use relative permeability is selected,
there is a further option to consider Vogel correction for GOR using the Standing
Method (Reference: K. E. Brown & H. Dale Beggs “ The technology of artificial lift
methods” – Volume 1). The Vogel correction takes into account the effect of
increasing gas saturation on the well PI. It requires the entry of a test GOR value.
The GOR entered is taken as the total produced GOR. Based on the PVT, then this
used to calculate a free gas saturation Sg.
The Sw is calculated on basis of test water cut and test reservoir pressure. So is
calculated from
So = 1 − Sw − S g
Once the phase saturation and viscosities are known the PI is estimated from total
liquid mobility ratios as indicated above.
When relative permeability is set to ‘No’ the oil and water mobility values are
calculated on basis of the assumption that the free gas down hole is zero. The oil
saturation is calculated as:
So = 1 − Sw
Based on these phase saturations, the PI correction is made.
Figure 7-15
Relative Permeability Data
Input
 For Inflow Models like Darcy with a relative permeability correction, enter a
water cut during test equal to 0, if the permeability entered in the reservoir
input data is true single phase permeability of the rock.
Enter the residual saturation, endpoint relative permeability and Corey exponent for
both oil and water. A Corey exponent of 1.0 defines straight-line relative
permeability curves. Values greater than 1 give a concave upwards curve i.e.
delayed water breakthrough. Corey exponents less than 1 define a concave
downwards relative permeability curve i.e. early water breakthrough.
Matching measured and calculated IPR pressures establishes the well productivity
for the prevailing water cut. Click on Plot to bring up the following plot in the
standard plot window.
PROSPER MANUAL
26 - 75 Chapter 7 - IPR Data Input
Figure 7-16
Relative
Permeability
Curves Display
To enter lab relative permeability, click Test Data to display the following screen:
Figure 7-17
Relative Permeability
Test Data Input
Enter the test data and click OK to display the plot again. If necessary, adjust the
values of Corey exponents for oil and water until PROSPER's calculated relative
permeability curves fit the measured data points.
Having entered and verified the relative permeability data, click Finish to quit the
plot. Next, enter the necessary data for the particular IPR method selected and
click on Calculate to calculate and display a plot of the system IPR. The program
automatically calculates the well Absolute Open Flow Potential (AOF).
Figure 7-18
Example IPR
Plot
To compare measured test pressures and calculated IPR pressures, click Test data
and enter rates and sandface pressures as on the following screen:
Figure 7-19
IPR - Test Data Entry
When relative permeability is being used, water cuts for both the test data and that
used to calculate the IPR curve are required. The water cut during test value will be
carried over from the relative permeability input screen. The water cut for calculation
value can be subsequently changed to evaluate the effect on the calculated IPR.
PROSPER MANUAL
28 - 75 Chapter 7 - IPR Data Input
The following data are required to calculate the total GOR from a rate:
• Reservoir permeability
• Perforation height (vertical distance from perforation top to bottom)
• Vertical anisotropy
• Vertical distance from perforation top to gas-oil contact
• Three correlating parameters: F1, F3 and an exponent
If the gas coning is enabled then a Coning button appears on the model selection
dialog screen. Clicking on this brings up a dialog that allows the correlating
parameters to be tuned. There is an automatic matching facility, which calculates
F3 from the other data and a (rate, GOR) coordinate. Also, the GOR can be
calculated from different rates whilst in this screen in order to verify the parameters.
As for oil, Gas inflow models are divided between design and production
applications. Calculated IPR models can be used to estimate productivity for
different completion options. Other models are available for estimating productivity
from measured flowing pressures.
The average reservoir pressure and reservoir temperature must be entered for all
inflow performance models, however both the Multi-rate C and n and Multi-rate
Jones models can be used to calculate the reservoir pressure from production test
data.
7.3.1 Jones
Petroleum Experts Ltd
Chapter 7 - IPR Data Input 29 - 75
The Jones equation for gas is a modified form of the Darcy equation, which allows
for both laminar and non-Darcy flow pressure drops. The Jones equation can be
expressed in the form:
( Pr2 − Pwf2 ) = aQ2 + bQ
Where "a" and "b" are calculated from reservoir properties or can be determined
from a multi-rate test. Required data entry is:
The Jones IPR model is discouraged to use with high reservoir pressures
 as the assumption of the model is to keep 1 / µ Z constant at pressures
>2400psig.
7.3.2 Forcheimer
The Forcheimer equation expresses the inflow performance in terms of a laminar
and a non-Darcy pressure drop coefficient expressed as:
( Pr2 − Pwf2 ) = aQ2 + bQ
For "a" enter the laminar pressure drop as drawdown/unit production and for “b” the
non-Darcy in drawdown2/(unit production)2.
The Forcheimer equation appears identical to the Jones equation and here the “a”
7.3.4 C and n
This is the common form of the back pressure equation:
Q = C ( Pr2 − Pwf2 ) n
PROSPER MANUAL
30 - 75 Chapter 7 - IPR Data Input
C and n can be determined from a plot of: Q versus (Pr2-Pwf2) on log-log paper. n
is the inverse of the slope and varies between 1 for Darcy flow to 0.5 for completely
non-Darcy flow. This option allows direct entry of C and n.
 It is advised to enter more than one test point. Using a single data point
can generate a non-representative IPR profile.
The program will automatically calculate the reservoir pressure if it is not available.
For producing wells, input a reservoir pressure lower than the measured pressures.
The program will dismiss the reservoir pressure entered and calculate one. For
injection wells, input a reservoir pressure higher than one of the pressures entered.
The program will calculate the reservoir pressure.
Note for injection wells. If flow test data for a producer has been fitted, the
 well will have the correct IPR if it is then converted to an injector.
Figure 7-20
Petroleum Experts IPR
The non-Darcy coefficient can be entered from a well test where available or
calculated using a correlation.
The following diagram illustrates how PROSPER treats total and effective
permeability in the Petroleum Experts IPR model:
PROSPER MANUAL
32 - 75 Chapter 7 - IPR Data Input
Relative Permeability
0.8
0.7
0.6
0.5 Krg when total permeability is entered
0.4
0.3
0.2
0.1 Slc
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Liquid Saturation
The mass flow rate of each phase is directly proportional to its mobility (k/µ), Kr’s
can be determined using PVT and the surface production rates. This technique is
used to determine the reduction in productivity as a function of the produced liquid
ratios. The derivation of the technique and details of the equations used are given
in Appendix C.
The gas gravity, CGR and WGR must be entered for each layer. The produced
fluid in the well bore is equivalent to the summation of the individual layer
contributions. Refer to Multi-layer Inflow for Oil for more details in Section 7.2.13.
saturation are required to be input in addition to the parameters described in the Oil
IPR section 7.2.15.
In the modified isochronal test, the shut-in periods are of equal duration, as are the
flowing periods. The final shut-in pressure before the beginning of the new flow is
used as an approximation of the average reservoir pressure. The same procedure
is typically repeated four times. A stabilized point (pseudosteady state) is usually
obtained at the end of the test.
Modified isochronal tests are commonly used in gas wells, because they require
less time and money to produce results comparable to the isochronal test. This
IPR model is based on standard Back Pressure Model
(
Qg = C Pres − Pwf
2
)
2 n
when n = 1 C=
0 ⋅ 703kh
(
µ g TZ log e 0⋅606
rw
re
)
The flow at any selected rate should be continued long enough for the reservoir to
approach steady-state (stabilized) conditions. The time to reach stabilized
conditions is called the readjustment time. For wells with wide well spacing (large
drainage radius values), low permeabilities, or high gas compressibility’s (low
reservoir pressures), large readjustment times can be expected. In cases where the
readjustment time exceeds the duration of each test, the test data can be corrected
to isochronal conditions and then to stabilized conditions as described below.
When a well is tested from an initial steady state shut-in condition, the increase in
drainage radius with time is not dependent upon the rate. Therefore, separate flow
tests conducted for the same length of time will reach the same drainage radius.
PROSPER MANUAL
34 - 75 Chapter 7 - IPR Data Input
When a well is not shut-in between tests until steady state is reached, successive
tests will indicate values of (P2res – P2wf) which are too large because of the
increasing drainage radius. For the general case, a table of correction factors to be
applied to (P2res – P2wf) to obtain an isochronal performance curve from
conventional performance data can be calculated as follows:
Flow Correlation Factors
where
Point 1: None
Ptj = dimensionless pressure change
Q2 Pt1
Point 2 :
Q1 Pt1 + (Q2 − Q1 ) Pt 2 t d = dimensionless time
The back pressure equation coefficients ‘C’ and 'n' are obtained by non-linear
regression using the isochronally corrected data. 'n', the reciprocal of the slope of
this line, is constrained to a value between 0.5 and 1.
Although 'n' is constant, the coefficient 'C' is not the same at stabilized flow
conditions as it is at isochronal conditions. It is calculated using the same technique
as before, regressing on ‘C’ and keeping ‘n’ constant, after adjusting the isochronal
(P2res - P2wf) values to stabilized conditions using a variation of the following
equation.
1
⎡ ⎛ re ⎞ ⎤
n
⎢ 2 log10 ⎜⎜ 0 ⋅ 60 ⎟⎟ ⎥
( Pres − Pwf ) stab
2 2
=⎢ ⎝ rw ⎠ ⎥
⎢ log10 (0 ⋅ 25t d )iso ⎥
(P
res
2
− Pwf
2
)
iso
⎢ ⎥
⎢⎣ ⎥⎦
0 ⋅1πre φ (1 − S wc ) µ g
2
t stab =
4 ⋅ 39e −6 Pres K rg
• Entered by Hand
• Calculated Using Models.
 It is assumed that this value will contain deviation and partial penetration
information.
• Locke
• McLeod
• Karakas and Tariq
The required input parameters are often difficult to accurately define, therefore the
absolute value of the calculated skin often cannot be precisely predicted. The
power of these techniques is their ability to assess the relative importance of
completion options on the overall value of well skin.
The Elf SkinAide inflow method can also be used to estimate skin pressure drops
for cased- and open-hole completions with and without gravel packs.
PROSPER can also be used to estimate the value of the skin pressure drop across
the completion and the proportion of the total pressure drop attributable to the
various completion elements.
Karakas and Tariq have been found to give good results in many field applications.
The following input data are required:
PROSPER MANUAL
36 - 75 Chapter 7 - IPR Data Input
An example of the input data for the Karakas and Tariq method is shown below:
Figure 7-22
Karakas and
Tariq Skin Input
Figure 7-23
Perforation Geometry
Terms
Enter the requested data and, having entered some reservoir model data, press
Calculate to display an IPR plot. The plot shows the pressure drop resulting from
the total skin as well a breakdown of the individual factors contributing to the total
skin as per the following example. The individual factors to be plotted can be
chosen from the Variables menu option of the plot window.
Figure 7-24
IPR Plot
Figure 7-25
API RP43 calculation
Figure 7-26
API RP43 calculation data
 Note on Skin:
Locke's technique is valid for shots per foot of 1,2,4,6,8,10,12,and 16.
• Cinco/Martin-Bronz
• Wong-Clifford
The second can compute a skin for multiple completions and requires the following
data entered:
1. Reservoir parameters:
• Formation vertical thickness
• Well-bore radius
• Drainage area
• Dietz shape factor
• Formation vertical permeability ratio
• Local vertical permeability ratio
• Horizontal distance from well to reservoir edge
• Depth of top of reservoir
PROSPER MANUAL
40 - 75 Chapter 7 - IPR Data Input
Figure 7-27
Gravel Pack
IPR Input
NEW!!! On the right side of the screen a table shows typical permeability data for different
types of gravels.
The pressure drop across a gravel pack is computed using a summation of a Darcy and a
non-Darcy component. For a cased oil well, the pressure drop due to the gravel pack
(dPgravel) is calculated:
dPgravel = AQ2 + BQ
Where:
A = The non-Darcy term,
Q = The total liquid rate and
B = The Darcy term
Intermediate calculations are required prior to computing the dPgravel value and consider
the following variables:
Kg = Gravel Pack Permeability
β = 1.47E7/Kg^0.55
PerfDi = Perforation Diameter
SPF = Shots per ft
PRFINT = Perforation Interval
AOTF = Area Open To Flow = π(PerfDi/12)2SPF*PRFINT
µo = Oil Viscosity in cp
Bo = oil FVF
ρo = Oil Density
L = Gravel pack length
Figure 7-28
Gravel Pack Geometry
Sketch
Skin can be calculated using one of the methods described in Section 7.3 or
directly entered. Note that partial completion skin is included in the total well skin,
and is not affected by adjusting the gravel pack completion parameters. The total
well skin as measured by a well test prior to gravel packing should be entered.
Click Calculate when finished entering data and an IPR plot similar to that below will
be presented (the plotting of the individual dP components can be chosen from the
Variables menu in the plot window):
PROSPER MANUAL
42 - 75 Chapter 7 - IPR Data Input
Figure 7-29
Gravel Pack
IPR Plot
The contribution of the gravel pack to the total skin pressure drop can be readily
seen on the IPR plot. The value of skin posted on the IPR plot does not include the
gravel pack skin. Click Results on the IPR plot screen to display the breakdown of
dP's resulting from each completion element. Sensitivities can be calculated on
factors such as gravel pack thickness, shots per foot etc. to evaluate the
effectiveness of gravel pack designs. Gravel packed completions are also available
in the Multi-layer IPR model.
The PROSPER gravel pack model allows for non-Darcy (i.e. dP proportional to rate
squared) effects within the gravel pack and the resulting rate dependent skin. Lift
curves for gravel packed wells generated using PROSPER can be calculated from
the sandface, through the completion, and back to the production manifold. This
more correctly models the IPR as compared to simply imposing an additional skin
to allow for the gravel pack pressure loss as is done in many reservoir simulators.
Gravel packs can be combined with the Hydraulically Fractured Well IPR to
 model ‘Frac-Pack’ completions.
Adequate results for injection well IPR can be obtained by reducing the reservoir
temperature on the IPR input screen to near the estimated sandface injection
temperature. The Enthalpy Balance temperature model can be used to estimate
injected fluid temperatures. PROSPER uses the reservoir pressure and temperature
to estimate fluid PVT properties in IPR calculations.
Most of the IPR pressure drop occurs near to the well. With this in mind, use an
effective permeability appropriate to the given conditions. For empirical inflow
models such as Vogel and Multi-Rate methods, the effect of cold injection fluid
viscosity is accounted for in the pressure points. Changing the reservoir
temperature will have no effect in these cases.
7.7 SkinAide
The SkinAide inflow method has been developed by Elf Aquamarine and
acknowledgement is given for its inclusion in PROSPER. The following description is
based on information provided by Elf.
PROSPER MANUAL
44 - 75 Chapter 7 - IPR Data Input
surrounding the well completion in so far as one can imagine an equipotential
cylindrical surface with, say, a 2 m radius, separating the two regions.
Figure 7-30
SkinAide Equipotential
Surfaces
Figure 7-31
SkinAide Perforation
Interference
The pressure drop due to interference between perforations and the damaged zone
is calculated using the Karakas and Tariq correlation.
Figure 7-32
SkinAide Crushed Zone
PROSPER MANUAL
46 - 75 Chapter 7 - IPR Data Input
Figure 7-33
SkinAide Perforation
within the Formation
Figure 7-34
SkinAide Perforation
Tunnel in Casing and
Cement
Figure 7-35
SkinAide Perforation
Casing / Screen Annulus
An approximate analytical solution has been found for flow in this region.
Figure 7-36
SkinAide Hemispherical
Flow
Figure 7-37
SkinAide Model
Options
Select the required options for the Flow and Skin models plus Perforation Data.
The options are listed below:
PROSPER MANUAL
Chapter 7 - IPR Data Input 49 - 75
 Pe, the static reservoir pressure is the average pressure in the well
drainage area, not the pressure at the external boundary. Pe is used
in the Productivity Index equation:
PI = Q / ( Pe − Pwf )
PROSPER MANUAL
50 - 75 Chapter 7 - IPR Data Input
Having selected the required options, SkinAide requires data entry in the following
categories:
The data required can vary according to the options selected. Click each data entry
button in turn and enter the data as follows:
7.7.2.4 Geometry
• Reservoir Thickness - Enter the thickness normal to the bedding plane in dipping
reservoirs. When thin shales are distributed throughout a heterogeneous
reservoir, use the net sand thickness.
Figure 7-38
SkinAide Reservoir
Thickness
Figure 7-39
SkinAide
Completion Geometry
• Distance to Top of Completion - This parameter affects partial completion skin and
is measured along the wellbore. If gross sand thickness is used for reservoir
thickness, enter the actual distance to the top perforation (dimension h1 in the
above sketch). When using net sand, restrict the distance to net sand intervals.
• Drainage Area - Area drained by the subject well
• Dietz Shape Factor - Allows for drainage area shape and well placement.
Figure 7-40
SkinAide Drilled
Hole Diameter
• Hole Diameter - Open hole drilled diameter. Use bit size or calliper measured
size where applicable. Perforation length, damage depth are measured beyond
the hole diameter.
• Deviation - Average angle between the well axis and vertical.
Figure 7-41
SkinAide Deviation
Angle
PROSPER MANUAL
52 - 75 Chapter 7 - IPR Data Input
7.7.2.5 Petrophysics
• Horizontal Permeability - Reservoir permeability measured parallel to the cap rock
(along the bedding plane).
Figure 7-42
SkinAide
Horizontal Permeability
Figure 7-43
SkinAide Non-Darcy
Flow Pressure Loss
Mechanism
In anisotropic reservoirs, formation damage is deeper in the low permeability direction than
the high permeability. An elliptic damaged zone forms in such cases. SkinAide assumes a
circular damaged zone irrespective of reservoir anisotropy.
Figure 7-44
SkinAide Damaged
Zone Geometry
• Damaged Zone Thickness - Since damaged zone skin is controlled by the ratio of
perforation tunnel length to damaged zone depth, enter a damage zone depth
that respects this relationship.
• Damaged Zone Permeability - Determines the ratio of damaged zone to reservoir
permeability. Estimating the true value is not straightforward, however, the
undamaged reservoir permeability could be used as a starting point.
• Damaged Zone Porosity - Porosity to be used in the high velocity flow coefficient
correlation.
• External Casing Diameter - Enter nominal casing diameter opposite the completed
interval.
• Casing Weight - Enter nominal casing weight per unit length opposite the
completed interval.
PROSPER MANUAL
54 - 75 Chapter 7 - IPR Data Input
Figure 7-45
SkinAide
Perforation Geometry
Most of the high velocity flow pressure loss occurs in the crushed zone and is
added to the loss in the reservoir. Note that if a zero crushed zone thickness is
entered, no high flow velocity pressure drops are calculated.
Figure 7-46
SkinAide Perforation +
Damage Geometry
7.7.2.9 Perforations
The perforation data input depends on the option selected. If In-Situ Geometry is
selected, the actual perforation sizes are required. Alternatively, API test data can
be entered for a particular gun, and SkinAide will estimate the perforation geometry
considering completion and reservoir variables such as compressive strength and
casing size.
Figure 7-47
SkinAide
Perforation Efficiency
• Shot Density - Nominal shots per foot for the selected perforating gun.
• Gun Phasing - Angle between two adjacent perforating charges. Affects
interference between perforation tunnels.
Figure 7-48
SkinAide Angle
Between Vertical
Plane
and Perforations
• Angle Between Vertical Plane and Perforations - For anisotropic reservoirs, the
angle between the perforation tunnels and the direction of maximum
permeability influences productivity. When 0° or 180° guns are selected,
perforations are all aligned with the low side of the hole. For other gun
phasings, SkinAide assumes an angle of 45°.
PROSPER MANUAL
56 - 75 Chapter 7 - IPR Data Input
Figure 7-49
SkinAide Perforation
Tunnel Geometry
Figure 7-50
SkinAide Gun
Diameter
and Stand-off
• Gun diameter - Gun diameter is used to correct API perforation test results for
stand-off.
• Reservoir Uniaxial Compressive Strength - Compressive strength is used to
calculate in-situ perforation dimensions. Typical values of reservoir uniaxial
compressive strength are given in the following table:
• Rock Density - Enter apparent In-Situ rock density as measured by a density log,
not the density of the minerals (e.g. Quartz) that comprise the formation grains.
• Casing Elastic Limit - Used for correction of API data to In-situ perforation
dimensions. The elastic limit in thousands of psi corresponds to the pipe steel
quality. e.g. N80 casing has an elastic limit stress of 80,000 psi.
• Reservoir Stress - Used for correction of API data to In-situ perforation
dimensions. Stress is assumed to be Isotropic. Generally the minimum
effective stress (frac gradient) is suitable.
Figure 7-51
SkinAide Gravel
Pack Geometry
• Screen Outside Diameter - The space between the screen O.D. and the drilled
hole diameter is occupied by gravel.
• Annulus Gravel Permeability - Permeability of gravel in the space between the
screen and the open hole. Gravel size is specified in terms of mesh size. e.g.
20/40 mesh gravel will pass a sieve with 1/20 inch holes, but not pass a 1/40
inch sieve. Average laboratory measured permeability values for various gravel
sizes are given in the following table:
PROSPER MANUAL
58 - 75 Chapter 7 - IPR Data Input
The inflow and skin pressure drop are computed by clicking the Calculate button
once all the relevant input data have been entered and Plot to display the results.
To evaluate the contribution of individual completion components in the inflow
performance, click Variables and select the parameters to display as in the
following screen example:
Figure 7-52
SkinAide IPR Variable
Selection
Select the required variables by clicking their check boxes. Click Done to display
the results:
Figure 7-53
SkinAide IPR dP
Skin Plot
Skin Components
The conceptual models used to calculate the total skin factor include :
- a contribution due to the position of the producing interval with respect to reservoir
geometry, called geometric skin Sgeometric
- contributions due to pressure losses close to the actual wellbore, beginning with
the pressure loss due to the damaged zone and ending with pressure loss in the
casing/screen annulus for gravel packed wells. This contribution to the total skin is
called the completion skin Scompletion.
The total skin is the sum of the two components
Stotal =Sgeometric + Scompletion
The contribution Scompletion to the total skin is particularly convenient when using
reservoir engineering equations. However Scompletion does not necessarily reflect the
quality of the completion itself. Indeed, imagine two wells with identical completions,
producing reservoirs with identical properties, the thickness of one reservoir is
double that of the other:
Figure 7-54
SkinAide Completion
Skin
Scompletion = a k h DPcompletion / ( Q m B )
Since DPcompletion is identical but reservoir thickness h differs by a factor 2, applying
the above relation leads to values of Scompletion, which differ, by a factor 2.
PROSPER MANUAL
60 - 75 Chapter 7 - IPR Data Input
Mechanical skins are defined so as to reflect the quality of well completion. In the
formula for mechanical skins, the vertical reservoir thickness h is replaced by the
length of the producing interval (measured along the wellbore) hp :
Smechanical = a k hp DPskin / ( Q m B )
where, for oil wells,
SI US French
a depends on units 2π 7.07 10-3 0.0536
k permeability m2 mD mD
hp length of the completed interval m ft m
DPskin DPreal well - DPidealized well Pa psi bar
Q flowrate (standard conditions) m3/s bpd m3/d
m viscosity (reservoir conditions) Pa.s cP cP
B fluid formation volume factor v/v v/v v/v
Total and mechanical skins are related by the simple formula :
Smechanical / hp = Scompletion / h
7.8.1.1 Motivation
Multilateral wells are different than single wells because they have a variable
structure. Both the number of branches and the way that they are connected is
variable. Hence, a flexible network data structure is appropriate for modelling these
wells. Furthermore, to provide a consistency with other Petroleum Experts products the
interface has the same look and feel as the one in GAP.
The User interface consists of a framework window that contains several child
windows, as well as the menu and toolbar from which commands are issued. The
child windows include the network windows that contain the system network
drawing, the navigator window that can assist in the viewing of large networks and
up to three visualisation windows, which can show the multilateral network drawn to
scale from three orthogonal points of view.
System Navigator
Four main components of the interface are identified, as indicated on the diagram
above, which are described in more detail in the following sections:
3. Menu bar and toolbar. The menu bar is used for issuing commands to
PROSPER and the interface; it contains an abridged set of commands compared
to a normal application framework window because it is a subsidiary window of
the main programme. The toolbar contains menu accelerators, icons for
selecting and manipulating network nodes and links, and icons for zooming or
un-zooming on the network window.
4. Visualisation screen – up to three windows showing front, side and top views of
the multilateral network.
The system window is used to draw, edit, and view the system. The network nodes
are represented by coloured icons. The different actions that can be performed on
this window are obtained by clicking the right hand mouse button within the area of
the system window, which brings up a menu. Alternatively, the same set of actions
can be performed using the toolbar or the menu, which are described below.
Only the four left most items in the toolbar (tie-point, junction, completion and
tank/reservoir) are nodes: links, the fifth item, are added differently by dragging
between two nodes. Depending on a set of connection rules, the connection will be
made or not and the correct type of link will be chosen. For example, reservoirs
can only be attached to completions and the type of link is logical; in other cases
the link is a piece of tubing. These rules are reviewed in the description of toolbar
items. The network is hierarchical and arrows drawn on the links indicate the
direction of the connections (which is normally the same direction as increasing
vertical depth). Each icon is given a characteristic colour, depending on the
network item it represents. The colours and items are: red (tie-point), green
(junction), yellow (completion), blue (reservoir) and pink (tubing).
Zoom/Un-zoom
To zoom or un-zoom, first select the appropriate icon from the toolbar or from the
right hand mouse menu, as described above. To zoom in on an area, hold the left
hand mouse button while sweeping the mouse cursor over the area of interest.
Alternatively, click once at a point in the system, and the programme will zoom or
un-zoom on that point using a fixed scaling factor (which may be adjusted using the
Preferences dialog in the Preferences menu).
To revert to a full system view at any time, double-click the left hand mouse button
at any point in the window (except on an icon). The view will re-scale to show the
whole of the system.
Mask/Unmask
To mask or unmask, first select the appropriate icon from the toolbar or from the
right hand mouse menu, as described above. To mask a node, click on it with
mask selected; to unmask it click on it with unmask selected. Masking removes a
node from the calculation without removing it and its associated data from the
network (which deleting does). Masking is useful for simulating the effect of
removing or adding in completions. Note that masking a branch will have the effect
of masking those below it in the hierarchy.
Moving Items
Select the move option from the toolbar or from the right hand mouse menu. To
move a single item, place the mouse cursor above it and hold down the left mouse
button while dragging the mouse cursor to the desired new location. To move a
group, select an area as with the zoom option and then hold down the left mouse
button with the mouse cursor in the window before dragging the whole group to a
new location. Items stay selected after a group move but can be de-selected using
the select option.
Deletion of Items
Select the delete icon from the toolbar or from the right hand mouse menu. Groups
of items may be deleted by group-selecting them as above, but with the delete
option chosen. NB: deletion of a node deletes the data associated with it so this option
should be used with caution. To delete a pure (non data-carrying) link re-do it.
Selection of Items
To select an item or items, first choose the select icon (black arrow) from the
toolbar or from the right hand mouse menu, the selected item will change colour.
Group selections can be achieved by first selecting the select icon then drag the left
hand mouse button over the area of interest. The select option is a toggle, so it can
select or de-select items. Group selections can be used to turn off the selection
actioned by a group move.
Editing of Items
If a network item carries data it has an icon associated with it and can be edited by
double clicking on it provided that none of zoom/un-zoom, move, delete or select is
chosen. Editing of network item data is covered in the section on Data Entry.
Panning
To move the view around the system, move the cursor close to the edge of the
view in the direction the system will be moved. The cursor will change to an arrow.
Clicking the left hand mouse button will move the system view by a fixed amount
depending on the current scaling factor. To pan quickly, hold the mouse button
down and, after a short time, the pan action will 'auto-repeat'.
Maximise: Click this button to maximise the window to fill the multilateral
main window.
Close: Click this button to remove the window from the workspace.
The tracking rectangle has two functions. If the focus is currently on a network
window, this rectangle surrounds the area of the network that that views is
displaying. Alternatively, the rectangle may be used to create new views of the
network if the navigator window is currently in focus. When the mouse is moved
over the rectangle, the cursor changes to allow resizing of the rectangle. In this
way, the navigator window facilitates creating views in areas of interest. Double-
clicking the left hand mouse button in the area will create a new system view
displaying the selected area, although resized to preserve a sensible aspect ratio.
Navigator On Top: By default, the navigator is always on top of all system views.
This can be changed by selecting this item from the menu.
Hide Window: The navigator can be hidden using this option and, once removed,
will not appear in subsequent sessions until reopened from the Window menu. The
navigator can also be hidden by clicking on the cross button at the top right hand
corner of the window or by using the Window menu option.
The functions of the various buttons are described below. A quick description can
be gained for a given button by holding the mouse cursor over the button for a
moment. A small yellow box with a short description will appear.
Connections between nodes are created by choosing the ‘Link’ button and holding
down the mouse left hand button whilst dragging between the nodes. There is a
connection hierarchy, which is represented by the branching of a parent branch into
one or more child branches, in the same way that the multilateral well branches out
physically. Indicate the direction of the hierarchy for junction-completion or
completion-completion connections by the order in which they are joined up.
Tie-point. This is the node for which the IPR is solved and is located at
the top of the system (in vertical depth and hierarchically). Hence, the
tie-point can only be a start point.
Junction. The main purpose of the junction is to be a branching node. It
can only have one link into it (from a tie-point, completion or other
junction) but any number coming out.
Completion. This contains both tubing and completion information. It is
attached below a tie-point, junction or another completion. It can only
have one link into it and branches out to either a junction or another
completion. It can also be logically attached (no direction implied) to any
number of reservoirs (but at least one).
Tank/reservoir. This represents a reservoir source and is logically
attached to any number of completions (but at least one).
Link. Connecting to a junction, the link becomes a tubing node and
contains data. Going into a completion, the tubing information is in the
completion and the link is ‘blank’ only indicating the hierarchical
relationship between the nodes it connects with an arrow. Finally, when
connecting a completion and a reservoir, the link is logical and not
hierarchical. Note that re-doing a link between two nodes will delete it.
PROSPER MANUAL
66 - 75 Chapter 7 - IPR Data Input
Tools
These are equivalent to items to the right of, and indeed inside, the drop-down list
box in the tool bar and have been explained above.
Analyse
This menu contains options to plot and report the IPR results in a similar way to
those in the Single Well IPR. The multi-lateral is treated as one reservoir model
option, such as the multi-layer with dP friction loss. There is also a Calculate
option, which brings up the dialog in the following figure.
Figure 7-56
Multi-lateral
Calculation Dialog
The Calculate screen gives the option of calculating one IPR point or a curve. In
the former case pressure can be calculated from a rate or rate from a pressure. In
the latter case, pressure is calculated for a range of rates up to the AOF, as with
other IPR calculations. From this screen it is possible to specify the number of IPR
points (maximum 20) and the minimum pressure to calculate to. These are to help
speed up calculations if appropriate. Results of the points for curve calculation will
be reported at the bottom section of the screen. Also, having a bearing on
calculation speed is the switch between infinite and finite conductivity modes of
calculation. In the latter case the pressure drop in the tubing is taken into account.
Before carrying out the calculation, the network structure is validated and any
errors are reported in the white list box in the middle section of the screen. If the
structure is not valid the calculation is not carried out. The Details button is used to
display pressure and rate-related parameters with respect to the measured and
vertical tubing depths of each branch.
During a calculation, diagnostic information is reported to the list box. Also, a
Cancel button is placed above the Calculate button to allow stopping the
calculation. The buttons to the left of the list box perform the functions in the
Analyse menu, except Help, which brings up this section. The push button Done
exits the screen.
Visualise
These items are dealt with in the section on visualisation screens.
Preferences
PROSPER MANUAL
68 - 75 Chapter 7 - IPR Data Input
The preferences dialog is gained from the Preferences item of the frame window
menu. It allows customisation of a set of User-interface variables for subsequent
PROSPER sessions. The following options are available:
• Enable Flyover Status Information. If this is checked then a status box appear
as the mouse is moved over the network item icons.
• Auto-repeat delay when panning. When panning, the left-hand mouse button
may be held down to ‘auto-repeat’ the action. The value given in this field
represents the time (in ms) before the auto-repeat action starts from when the
mouse button is clicked.
• Fraction of screen to pan per click. This represents the ‘resolution’ of panning.
• Zoom/un-zoom factor. A single click in a system window while the zoom or un-
zoom icons are active results in a fixed scaling to be applied to the view, while
the centre of the view is changed to the position in which the mouse was
clicked. The value entered in this field is the fixed scaling factor, and as such
should be greater than one.
Output
Printer Setup - to set up the printer if not already done.
Print - prints the current child window as a hard-copy, metafile or to the clipboard,
whether a network window or a visualisation screen.
Window Menu
• New Window. This creates a new system view. The new view is zoomed out to
include all the components.
• Close All. Shuts down all system windows in the application.
• Cascade. This reorganises the system windows into a ‘cascade’.
• Tile. Tiles the system windows.
• Toggle toolbar display. This will remove the toolbar if it is currently displayed,
and vice-versa. If the toolbar is not displayed, toolbar commands can be
accessed via the right hand mouse button on the system view window.
• Toggle navigator display. Displays or hides the navigator window.
Below this is a list of currently active system windows. The current focus window
may be changed by clicking on one.
Help
Brings up this information on the network interface.
Other Items
Apart from the preferences it is possible to change other aspects of the User
interface: namely font and icon sizes.
Petroleum Experts Ltd
Chapter 7 - IPR Data Input 69 - 75
Network Fonts
Fonts used in the network drawing may be changed. To do this, select the Fonts
option from the menu obtained following a right hand mouse button click in the
system window. This will bring up a font selection dialog. Select the required font
and style and press OK. The new font will be applied to all network drawings and
also to labels in the visualisation windows.
Icon Sizes
The sizes of the icons used to represent the network nodes can be changed. Select
the Icon Sizes option from the menu obtained following a right hand mouse button
click in the system window. The following dialog will appear:
Figure 7-57
The dialog consists of a slider with a data entry field, which contains the current
icon size (this defaults to 50 out of an arbitrary 0 – 100 range for a new file).
Change the icon size by adjusting the slider or entering a new size in the entry field.
Check the ‘Automatic Update’ box to update the system window with the new size
as the slider is moved.
When the new icon size is entered, click on This View or All Views. In the latter
case the change will be applied to all network windows. In the former case, only the
currently active network view will be changed. The new icon size will not be saved;
i.e. all changes will be lost when the current file is exited.
The geometry used is left-handed Cartesian. It is assumed that the positive x axis
is along the direction of zero azimuth, positive y is at 90 degrees and positive z is in
the direction of increasing depth. The front view shows the (x, z) plane, where y is
increasing going into the screen and consequently positive z corresponds to
moving down the screen and positive x corresponds to moving to the right. The
side view shows the (y, z) plane, where x increases coming out of the screen, z
PROSPER MANUAL
70 - 75 Chapter 7 - IPR Data Input
increases going down the screen and y increases going to the right. The top view
shows the (y, x) plane where z is increasing going into the screen, x increases
going down the screen and y increases going to the right.
The screens are brought up using the Visualise menu. One of the three views
(front, side and top) or all of them can be activated using the appropriate menu
command. If all the views are shown then they are tiled with any active network
windows. The title bar of each view window shows the extent of the network for the
plane in question. The co-ordinates are shown with respect to the start of a
(hypothetical) straight tubing, which enters the tie-point in the direction of zero
azimuth and has measured and vertical depths equivalent to those of the tie-points.
In a similar way to the network window one can pan across a visualisation window
by moving the mouse cursor close to one of the window edges and clicking on the
left button when the panning cursor appears. The fraction of the screen traversed
and the auto-repeat delay are controlled by the same options as in the network
window (chosen from the Preferences dialog).
7.8.2.1 Overview
The data associated with any network item is accessed by double-clicking on its
icon when none of the network manipulation options (zoom/un-zoom, delete, move
and select) have been chosen. This brings up a screen with editable data fields in
it.
Apart from the tie-point and junction data screens, the main data entry screen for
each node is similar to that of the single well main data entry screen (see Section
7.1). However, the reservoir data input child screen does not have any tab buttons
in it. The main data screens differ from the single well case in the action buttons:
only the left-most group - Done, Cancel, Reset, Validate and Help - are available.
Their function is the same as in the single well case. Hence, the differences
between the single well IPR data entry and the similar multilateral ones lie in the
model selection and data input child screens.
Given the hierarchical nature of the network, editing a parent branch causes the
starting points (e.g. depths) of child branches to be initialised. Those data fields
that are initialised from outside a particular network item are set read-only (coloured
cyan) when the screen to edit that net item is brought up. Hence, in order to edit a
net item and fill it with valid data it is normally necessary to have edited the parent
branch first. However, it is not a requirement to edit the network in hierarchical
order as any child net item can be filled with invalid data and saved before editing
its parent.
Another difference from the single well IPR is that in each screen, on the right hand
side, there is a list box containing a drawing of the network where the data carrying
nodes are sorted hierarchically, by type or alphabetically according to a right-hand
mouse button menu selection. By clicking on the line corresponding to a node the
given screen is closed and the screen belonging to the node clicked on is opened.
PROSPER MANUAL
72 - 75 Chapter 7 - IPR Data Input
completion (completion zone start and end measured and true depths) as well as a
field for entering a local (mechanical/geometric) skin value. There is a drop-down
list box in the fifth column, which allows the skin to be calculated using the Karakas
& Tariq method. The selection of ‘Karakas and Tariq’ enables the push button in
the last column, which brings up an appropriate data entry screen when clicked
upon with the mouse left button. On entering valid data and exiting that screen with
Done the skin value is calculated and entered in the skin data column.
Consistency Validation
Beyond the consistency enforced by the validation of individual network items as
they are edited and the automatic entry of some child branch data from parents,
there are other checks carried out on a complete structure whose nodes are
individually valid:
• There must be no more than one tie-point in a network; other loose items are
ignored.
• The top node must be a tie-point.
• All branches must end in a completion; completions must be attached to at least
one reservoir.
• Reservoirs should not overlap in depth (in the current model they are assumed
to be layers).
7.8.3.1 Introduction
The purpose of this exercise is to enter some geometrical data for the simple
multilateral in the following ‘back of an envelope’ sketch (Figure 7.58) and then
visualise it using the Visualise menu. It is assumed that the fluid selected is ‘Oil
and Water’ and the units system is oilfield units. We will also show the procedure
for running a calculation, to which purpose some default PVT and geometric data
should be entered in the reservoir screens. The multilateral has two branches, with
one branch having an azimuth of 170° with respect to the other. The zig-zag lines
indicate completions and the areas between the horizontal straight-lines are
layers/reservoirs. Note that one tubing branch contains two completions and goes
through two reservoirs. This will be modelled as one completion node and logically
attached to two reservoirs. The point at (12000, 10000) feet will serve as a tie-
point.
(12000, 10000)
10000 feet (12100, 10020)
(12200, 10020)
Kh = 100 mD
(12400, 10100)
10100 feet
10200 feet
(13000, 10210) (13000, 10220)
Kh = 50 mD
(14000, 10220)
(14000, 10280)
10300 feet
1. Using the Tools | Add Item option in the frame window menu.
3. Selecting the required option from the drop-down list box in the toolbar.
Once the appropriate node addition option has been selected, click somewhere in
the blank network window to create an icon. Allow the programme to attach a
default label to the node by not entering one. Do this for all the required nodes
listed above.
PROSPER MANUAL
74 - 75 Chapter 7 - IPR Data Input
Tie-point (TP1)
Enter 12000 feet and 10000 feet for measured and vertical depth respectively and
then click on Done.
Tubing (T1)
Make sure that ‘Flow Type’ is ‘Tubing Flow’ on the model selection screen and a
suitable value (0.354 ft) is entered for well-bore radius. Then leave the model
selection screen with its other defaults and enter the data input screen using the
button Input Data in the top right hand corner. In the ‘Deviation’ tabbed dialog enter
the three numbers:
12100 10020 0
in the white boxes in row 2. Now enter the ‘Equipment’ tabbed dialog by clicking
on that tab. In row 1 choose ‘Tubing’ from the drop-down list box and then enter
the four numbers:
Junction (J1)
The co-ordinates (12100, 10020) should already be entered in the junction net item.
C1 Deviation
13000 10210 170 (row 2)
14000 10280 170 (row 3)
C1 Equipment
14000 0.7 0.0006 1 (row 1)
C1 Completion Info.
13000 14000 10210 10280 1 (row 1)
C2 Deviation
12400 10100 0 (row 2)
13000 10220 0 (row 3)
14000 10220 0 (row 4)
C2 Equipment
14000 0.7 0.0006 1 (row 1)
C2 Completion Info.
12200 12400 10020 10100 1 (row 1)
13000 14000 10220 10220 1 (row 2)
The other fields in the model selection and data input screens (for both reservoirs)
should be entered with some reasonable numbers. For example: pressure (5000),
temperature (200), salinity (150000), water cut (15), GOR (800), gas gravity (0.9),
oil gravity (30), vertical permeability (10) and drainage area (500).
PROSPER MANUAL
8 Artificial Lift Data Input
This section describes how to enter the description of artificial lift equipment in a
well for calculating a systems analysis. The Design section describes how to
select suitable gas lift, ESP, HSP, PCP and jet pump equipment for new or existing
wells.
The required input depends on the choice of casing pressure calculation method.
These are the options available that can be selected in the general options:
• Safety Equipment
Friction pressure losses are calculated in the surface piping,
tubing/casing annulus and an annular safety valve where fitted.
To analyse an existing installation, the gas lift details that need to be entered will
depend upon the particular gas lift method that has been selected.
Firstly select the gas lift system type on the Options menu, and then enter the well
data by selecting Gaslift data on the System menu. Enter the required lift gas
composition data and select one of three gas lift methods available. The methods
currently available are:
2 - 16 Chapter 8 - Artificial Lift Data Input
 The program assumes that the casing pressure is sufficient to inject lift
gas at the specified depth to achieve the GLR injection target.
Figure 8-1
Gas Lift Data Input
Fixed Depth of Injection
Figure 8-2
Gas Lift Data Input
Optimum Depth of
Injection
For the Gas lifted (safety equipment) option, the compressor discharge pressure is
requested instead of the casing pressure.
Figure 8-3
Gas Lift Data Input
Valve Depth Specified
If a gas lift design has already been done, or the mandrel depths have been
entered for a Gaslift QuickLook Calculation, the valve details can be copied
across using the Transfer button.
PROSPER MANUAL
4 - 16 Chapter 8 - Artificial Lift Data Input
Figure 8-4
Gas Lift (Safety
Equipment) Input
The safety equipment data can be entered by accessing the Safety Equipment
button in this screen.
The details of the surface injection system are used to calculate the casing head
pressure as a function of gas injection rate and compressor output pressure.
Frictional losses in the annulus are taken into account when calculating the casing
pressure at each gas lift valve depth. The safety valve pressure loss is clearly seen
on the following gradient plot:
Figure 8-5
Gas Lift (Safety
Equipment)
Pressure Traverse
Figure 8-6
Gas Lift (pipe line) Input
And in the Gas Lift Data enter the properties of the gas and the GLR injected:
Figure 8-7
Gas Lift (pipe line) Input
PROSPER MANUAL
6 - 16 Chapter 8 - Artificial Lift Data Input
Figure 8-8
ESP Input Data
The Pump wear factor is used to account for deviation from the manufacturer's
published performance curves due to wear etc.
 For example, entering 0.05 causes the program to scale the pump head
curves down by 5% (i.e. head is 95% of the database value).
When a downhole gas separator is run, the GOR of the oil above the separator will
be lower than the produced oil GOR. Depending on the completion, the separated
gas is produced up the annulus or a separate tubing string. Both casing I.D. and
tubing O.D. are required to be input on the System ⏐ Equipment ⏐ Downhole
Equipment.
Figure 8-9
ESP Pumps
Database
Motors are grouped by series. Select the series clicking on the name of the pump,
and then choose Amend to enter the pump record.
In the Power Options it is possible to find all the motor configurations available. An
example ESP motor database screen is shown below:
Figure 8-10
ESP Motors
Database
PROSPER MANUAL
8 - 16 Chapter 8 - Artificial Lift Data Input
Figure 8-11
ESP Cables
Database
Further details on this database can be found in the chapter dedicated to the ESP
design section.
 Disclaimer
Every effort is made to ensure that the sample pump and motor
coefficients supplied with PROSPER are current. However, it is the User’s
responsibility to ensure they are both accurate and up-to-date. For critical
design work, always contact the equipment supplier for the latest
performance data.
Figure 8-12
HSP Input Data
The Pump wear factor is defined as in the ESP pumps, as seen in the previous
section.
Turbine speed is assumed to be the same as the Pump speed. The % Power Fluid
of Reservoir Fluid defines what fraction of the total produced liquids the power fluid
represents.
 A figure of 100% means that the amount of power fluid used to drive the
turbine is the same as the amount of produced reservoir fluids.
PROSPER MANUAL
10 - 16 Chapter 8 - Artificial Lift Data Input
Figure 8-13
HSP Pumps
Database
Figure 8-14
HSP Turbines
Database
Note that for the turbine different configurations are available (as seen previously in
the ESP motor database); to access then select the turbine and choose Amend.
Further details of database maintenance methods are given in HSP Design section.
 Disclaimer
Every effort is made to ensure that the sample pump and turbine
coefficients supplied with PROSPER are current. However, it is the User’s
responsibility to ensure they are both accurate and up-to-date. For critical
design work, always contact the equipment supplier for the latest
performance data.
Figure 8.15
In order to select the correspondent pump and rods, the pump database must be
set up first. The section devoted to the PCP design will describe how to enter the
correspondent pump and rods database.
PROSPER MANUAL
12 - 16 Chapter 8 - Artificial Lift Data Input
Figure 8.16
Coiled Tubing
Data
Two lift methods are available: Specified Injection Depth and Optimum Injection
Depth. Please refer to the Gas Lift section above for further details.
When Diluent injection is selected as Artificial Lift Method, Diluent Injection is active
in the System menu.
The only input data required are injection rate and depth:
Figure 8.17
Diluent Injection
Data
Figure 8.18
In this section the User has to select the Pump and enter specify its position and
maximum size along with injection rate and pressure.
The loss coefficients are also required. These coefficients are a measure of the
energy loss due to the friction in the above quoted sections of the pump.
The coefficients are provided by the Jet Pump manufacturers.
PROSPER MANUAL
14 - 16 Chapter 8 - Artificial Lift Data Input
Figure 8-19
Jet Pumps Database
To access the database record for each pump, select it and choose Amend.
Further details of database maintenance methods are given in Jet Pump Design
section.
 Disclaimer
Every effort is made to ensure that the sample pump and turbine
coefficients supplied with PROSPER are current. However, it is the User’s
responsibility to ensure they are both accurate and up-to-date. For critical
design work, always contact the equipment supplier for the latest
performance data.
Figure 8.20
Framo Data
The Pump Wear Factor is defined in the same way as in the ESP pumps. Please
refer to that section for details.
Other input data are the power available, the pump configuration (single pump or
pumps in parallel) and the pump model.
Figure 8-21
FRAMO Pumps
Database
PROSPER MANUAL
16 - 16 Chapter 8 - Artificial Lift Data Input
To access the database record for each pump, select it and choose Amend.
Further details of database maintenance methods are given in Jet Pump Design
section.
 Disclaimer
Every effort is made to ensure that the sample pump and turbine
coefficients supplied with PROSPER are current. However, it is the User’s
responsibility to ensure they are both accurate and up-to-date. For critical
design work, always contact the equipment supplier for the latest
performance data.
Gradient Matching
Existing correlations can be modified using non-linear regression to best fit a
gradient survey. Comparison of the fit parameters will identify which correlation
required the least adjustment to match the measured data.
 This should be used only if for a given rate more than one measurement is
available along the production string.
Pipeline Matching
The program uses actual wellhead and manifold pressures together with
temperature data points to match surface pressure drop correlations. Separate
screens allow the match parameters to be viewed and the best match selected.
Correlation Comparison
This is the primary step in quality control of measured well test data.
This option allows pressure gradient plots to be generated with different
correlations to be compared with measured gradient survey data. The comparison
enables the User to:
- Understand if the measurements “make sense”, that is to say, violate or not
the principles of physics
- Select the flow correlation that best fits the experimental measurement
Correlation Comparison is a fundamental step in the quality check of the model.
2 - 26 Chapter 9 - Matching Menu
QuickLook
This feature is active only if an artificial lift method (Gas Lift, ESP or HSP) is
selected.
It allows calculation of the pressure gradient in an artificially lifted well for a quick
check of lift performance.
For gas lifted wells, valve opening and closing pressures are calculated to permit
troubleshooting gas lift installations.
For ESP and HSP wells, the performance of the ESP and HSP can be checked.
Correlation Parameters
The tubing and pipeline match parameters can be inspected reset or entered by
hand using this menu option. This capability is useful for troubleshooting, or to
input match parameters determined previously.
Correlation Thresholds
This option allows the User to specify a threshold angle for both tubing and pipeline
correlations at which the program will automatically change to another (specified)
correlation. This option will enable vertical risers in sub sea completions to be
modelled more accurately.
For oil wells, Hagedorn Brown performs well for slug flow at moderate to high
production rates but well loading is poorly predicted. Hagedorn Brown should not
be used for condensates and whenever mist flow is the main flow regime.
Hagedorn Brown under predicts VLP at low rates and should not be used for
predicting minimum stable rates.
Duns and Ros Modified usually performs well in mist flow cases and should be
used in high GOR oil and condensate wells. It tends to over-predict VLP in oil
wells. Despite this, the minimum stable rate indicated by the minimum of the VLP
curve is often a good estimate.
Duns and Ros Original is the original published method, without the
enhancements applied in the primary Duns and Ros correlation. The primary Duns
and Ros correlation in PROSPER has been enhanced and optimised for use with
condensates.
Petroleum Experts 2 includes the features of the PE correlation plus original work on
predicting low-rate VLPs and well stability.
Petroleum Experts 3 includes the features of the PE2 correlation plus original work for
viscous, volatile and foamy oils.
Petroleum Experts 4 is an advanced mechanistic model for any angled wells (including
downhill flow) suitable for any fluid (including Retrograde Condensate).
Orkiszewski correlation often gives a good match to measured data. However, its
formulation includes a discontinuity in its calculation method. The discontinuity can
cause instability during the pressure matching process; therefore we do not
encourage its use.
Gray correlation gives good results in gas wells for condensate ratios up to around
50 bbl/MMscf and high produced water ratios. Gray contains its own internal PVT
model which over-rides PROSPERs normal PVT calculations.
 For very high liquid dropout wells, use a Retrograde Condensate PVT and
the Duns and Ros correlation.
 There is no universal rule for selecting the best flow correlation for a given
application. It is recommended that the Correlation Comparison always be
carried out. By inspecting the predicted flow regimes and pressure
results, the User can select the correlation that best models the physical
situation.
Further details can be found in the PROSPER Help menu, under Help⎪Flow
Correlations. References about multiphase flow are reported in Appendix B.
PROSPER MANUAL
4 - 26 Chapter 9 - Matching Menu
 The Gas Oil Ratio is the solution GOR. If the reservoir is under-saturated,
there is no free gas production at the sand face and the GOR free should
be set to zero.
The Gas Oil Ratio can also be entered as Total GOR (Solution + Free
GOR). In this case the GOR Free can be entered as nil. The program will
determine how much gas is in solution and how much in the free phase
according to the PVT.
Figure 9-1
VLP/IPR
Match Input
 The User can now use the ‘Correlation Comparison’ button to transfer the
selected well test data to the correlation comparison section. The
procedure is:
• Click on the button to the left of the well test data that we wish to
The Match Point Comment field is provided to allow the optional entry of notes to
identify the match data set. Examples would be test date, source of pressure data,
comments on test quality etc.
This input screen has a number of features to simplify data manipulation. The
selection buttons on the left hand side are used to select data points for further
editing. Hold down the Ctrl key and click the required buttons to select multiple
points. Copy copies the selected points into memory and onto the Windows
clipboard. Click the selection button of the desired destination and click Paste to
copy the data to the new location. Insert shifts the data down to make room for new
entries. The Delete button deletes the selected records. Data from this table can
be copied to or from the Windows clipboard. Therefore, test data can be read in
from a Windows based spreadsheet by first copying it to the clipboard, and then
pasting it directly into the table.
Bad or inconsistent data points occasionally prevent the program obtaining a good
match. The Disable button causes a selected data record to be ignored in the
matching process. Disabled records are dimmed in the VLP matching screen.
Disabled points can be re-included in the matching process by first selecting the
point and clicking on Enable. By sequentially disabling suspect data points,
potentially inaccurate test points can be identified and eliminated from the match.
To compute the VLP match, click Match VLP to display the VLP matching screen.
Select the correlations to match or just click All to match all correlations. An
example screen is shown below:
PROSPER MANUAL
6 - 26 Chapter 9 - Matching Menu
Figure 9-2
VLP Matching Screen
Click the Statistics button to examine the match parameters as shown on the
example screen below:
Figure 9-3
VLP Match Statistics
PROSPER uses a non-linear regression to tune the VLP correlations to best match
the measured data. It does this by calculating a pressure traverse using a
correlation and determining the error between measured and calculated pressures.
The gravity and friction terms of the pressure loss equations are then adjusted and
the process repeated until the measured and calculated results agree within 1 psi,
or 50 iterations have been completed.
Parameter 1 is the multiplier for the gravity term in the pressure drop
 correlation
Parameter 2 is the multiplier for the friction term.
If all the data are consistent, these two parameters should be within a ±10%
tolerance from the unity.
If PROSPER has to adjust Parameter 1 by more than +-10%, then there is
probably an inconsistency between the fluid density predicted by the PVT
model and the field data (rates/pressures).
If PROSPER has to adjust Parameter 2 by more than +-10%, then probably
the value of the roughness entered in the equipment is incorrect.
In cases the PVT has been correctly matched, the greatest source of uncertainty in
the VLP calculation for oil wells is usually the hold-up correlation. PROSPER will
attempt to make a gravity component (Parameter 1) match by adjusting the hold-up
correlation. If a match is not obtained with a Parameter 1 more than 5% away from
1.0, the density is adjusted. For single phase applications, no hold-up correction is
possible, so any significant deviation from 1.0 for Parameter 1 indicates a PVT
problem.
Once the matching process is complete, the match parameters will be shown
alongside each of the correlations that have been matched. Use the standard
deviations and the magnitude of corrections made to both parameters to aid the
selection of matched correlation.
Use the Correlation Comparison option of the Matching menu to compare the
optimised (matched) correlations with measured test data. To ensure that the
process has been successful, check that the matched VLP traverses plot close to
the measured pressure data points.
PROSPER MANUAL
8 - 26 Chapter 9 - Matching Menu
Figure 9-4
Adjust IPR
Select the desired correlation and then click Calculate, and PROSPER will calculate
the VLP for a range of rates and pressure at the sand face for each of the active
test points that have been entered on the VLP Matching screen. Once this
calculation is completed, click IPR and the IPR input screens will be presented. For
the first pass, accept the unmatched IPR data and display plot. The VLP and test
data will all be plotted on the same diagram as follows:
Figure 9-5
VLP/IPR Plot
The errors between calculated and measured data are shown on the side of the
plot. If the test points are not consistent with the IPR model, the skin, reservoir
pressure etc. can be adjusted until a match is obtained. Inconsistent test data
points will be easily identified on this plot. Clicking Main returns to the Adjust IPR
screen. Matching both the VLP and IPR to actual test data ensures that the
PROSPER well model is capable of accurately reproducing the currently known
producing conditions.
Figure 9-6
Gradient (traverse)
Matching Input
The first node pressure is entered in the Input Parameters section - do not include it
in the Match Data table. The Transfer button copies the measured gradient data to
Correlation comparison. The same guidelines for GOR apply as for VLP/IPR
Matching. Enter the required data and click Calculate. The following will be
displayed:
Figure 9-7
Gradient (traverse)
Matching Calculation
PROSPER MANUAL
10 - 26 Chapter 9 - Matching Menu
Select the correlations to be matched by clicking on them, and then click Match to
start the matching routine. Parameter 1 is the correction factor applied to the
gravity component of pressure drop whilst Parameter 2 is the factor applied to the
frictional element of pressure drop. The match algorithm continues until the
standard error is less than 1 psi, or 30 iterations have been performed. The
adjusted correlation and measured pressures can be visually compared by clicking
Plot. A graph similar to the following is displayed:
Figure 9-8
Gradient (traverse)
Matching Plot
The match points appear as blue squares in the figure reported above.
The calculated pressure gradient can be inspected by clicking View. Click the
Statistics button to display the match parameters. Use the statistics and knowledge
of well conditions and correlation performance to guide the choice of VLP
correlation. Once a correlation has been matched, the match parameters are
appended to the correlation name for all subsequent operations. Should it be
necessary to adjust or clear the match parameters, click the Reset button for a
particular correlation, or use the Reset All button to reset all correlations to their un-
matched state.
Figure 9-9
Surface Pipe
Matching Input
 The User can now use the ‘Correlation Comparison’ button to transfer the
selected pipeline test data to the pipeline correlation comparison section.
The procedure is:
• Click on the button to the left of the pipeline test data that we wish
to perform correlation comparison on.
• Click on the ‘Correlation Comparison’ button
• PROSPER will bring us to the pipeline correlation comparison
screen and at the same time, populate the correlation comparison
screen with the selected pipeline test data.
Enter measured manifold and tubing head pressures for a range of rates and click
Match to enter the calculation screen. Select the correlations to match in the same
manner as for Gradient matching. All editing and calculation controls operate as
described under Gradient matching. Once the matching is complete, click OK to
return to the main menu.
Click Matching ⏐ Correlation comparison to display the following data entry screen:
PROSPER MANUAL
12 - 26 Chapter 9 - Matching Menu
Figure 9-10
Correlation Comparison
Input
 Note that in Correlation comparison, the first node is the wellhead only if
there is no surface equipment or it has been disabled.
Enter the surface flowing conditions at which to compare the correlated gradients.
Select a surface equipment correlation then click on the required downhole
correlations to select a number of them from the list.
Ensure that the rate type is correct for the specific application.
 The value of GOR should reflect the current solution GOR and at no time
should exceed the initial solution GOR.
The GOR Free variable is used to model the effect of free gas production
from a gas cap or injection gas breakthrough. Leave GOR Free set to
zero if there is no free gas production.
The sum of GOR and GOR Free should equal the producing GOR.
Pressure data from a gradient survey can be entered versus depth in the measured
data boxes. The Transfer button copies the measured depths and pressures to the
Gradient match section.
For gas lifted wells, both the injection depth and gas lift injection rate are
 required to be input.
Note that the producing GOR should not include the lift gas injection.
When the input data is complete, click on Calculate to display the calculations
screen, then press the Calculate button to compute the pressure gradient in tabular
form as shown below:
Figure 9-11
Correlation
Comparison
Calculations
For all the correlation selected for calculations, use the scroll thumb below the
results box to access the results of calculations.
A visual comparison of all selected correlations and the test data is easily made by
clicking on the Plot button. The plot can be output or saved using the standard
features of PROSPER and Windows. An example comparison plot is shown below:
PROSPER MANUAL
14 - 26 Chapter 9 - Matching Menu
Figure 9-12
Correlation
Comparison
Plot
This plot is a useful quality check on the PVT and field production data. The
Fancher Brown correlation does not allow for gas/liquid slippage, therefore it should
always predict a pressure that is less than the measured value. Measured data
falling to the left of Fancher Brown on the gradient comparison plot indicates a
problem with fluid density (i.e. PVT) or the field data (pressure or rate). The use of
the gradient comparison plot is recommended to help identify flow regimes and
assess input data quality.
9.6.1 Input
The gas lift QuickLook is accessed from the Matching menu. Clicking QuickLook
from the Matching menu displays the following screen:
Figure 9-13
Gas lift QuickLook Input
The surface measurements section contains two columns for data input.
If unloading valve details have been entered, their opening and closing pressures
will be shown on the plot also.
Tubing head pressure Enter expected flowing pressure for the well.
Tubing head temperature Used only for comparison purposes.
Liquid rate Enter current flow rate.
Water cut Enter current value.
Total gas rate Enter total gas production through the separator - including the lift gas
contained in the produced well stream.
Gas injection rate Enter current injection rate.
Casing head pressure Enter current surface gas injection pressure.
Orifice diameter Enter diameter of orifice where gas is entering the string. This diameter is
used to estimate the pressure drop between casing and tubing at the
injection depth. For wells having multiple injecting orifices at the same
depth, enter an equivalent area.
Injection depth Enter expected depth of injection.
Vertical flow correlation Select the most appropriate correlation for the application. Use a matched
correlation where available.
Dome Pressure Correction When set to Yes, the improved high-pressure dome pressure temperature
above 1200 psi method is used.
PROSPER MANUAL
16 - 26 Chapter 9 - Matching Menu
Figure 9-14
QuickLook Downhole
Measurements
The purpose of this section is to check that all the data is consistent. The static
gradient can also be displayed on the plot by entering two static pressure
measurement points. Downhole measurement entry is optional.
For PROSPER to determine which gas lift valves should be open and closed for the
current producing conditions, the valve depths and characteristics must first be
entered. Click Valves from the QuickLook screen to display the following:
Figure 9-15
QuickLook
Valve Data
The valve type (casing or tubing sensitive), setting depth, port size, R-value and
dome pressure at 60 °F are required to calculate whether valves are open or
closed. Opening pressure etc. fields will be blank until a QuickLook calculation has
been performed. Entering the valve data for the QuickLook is optional.
Select between the up pass and down pass using the buttons located beside the
Case box as in the following example:
PROSPER MANUAL
18 - 26 Chapter 9 - Matching Menu
Figure 9-16
QuickLook Diagnostic
Calculations
In the Results box, the program displays the theoretical dP across the injecting
valve together with the casing pressure theoretically required to balance the flowing
tubing pressure at the injection depth plus the dP across the orifice.
Click Plot to display the two computed gradients plus the valve opening and closing
pressures on the same graph:
Figure 9-17
QuickLook
Diagnostic
Plot
This plot enables the User to see at a glance which valves should be open or
closed, and how changes in operating pressures would impact on the valves. The
results box displays the following computed values:
Historically, ESP wells have been difficult to diagnose (particularly with limited down
hole pressure data) because of uncertainties below (IPR), across (pump head) and
above (tubing hydraulics) the pump. Using the ESP QuickLook, conditions in each
of these areas can be analysed separately.
9.7.1 Input
The ESP QuickLook is accessed from the Matching menu. Clicking QuickLook from
the Matching menu displays the following screen:
PROSPER MANUAL
20 - 26 Chapter 9 - Matching Menu
Figure 9-18
ESP Quicklook
Input
Select the required pump, motor and cable from the buttons at the top of the
screen.
 Note that PROSPER always calculates from the bottom up for ESP
systems since, in order to find the tubing GOR above the pump, conditions
at the pump intake where gas separation takes place must be known. The
calculation of the downward pressure traverse from the entered tubing
head pressure is therefore iterative.
Select between the up pass and down pass using the buttons located beside the
Case box as in the following example:
Figure 9-19
Calculation
Output Screen
Click Plot to display the pressure traverses and the calculated pump intake and
discharge pressures, down hole average rate across the pump (RB/day), free gas
fraction at the pump intake and electrical parameters:
PROSPER MANUAL
22 - 26 Chapter 9 - Matching Menu
Figure 9-20
ESP Output
Plot
If the well bore, inflow and ESP assumptions are all correct, the two pressure
traverses will overlay and the measured and calculated intake and discharge
pressures and surface voltages should coincide.
 The pump discharge pressure is the “tie” point for the system. First match
the pump discharge pressure (if available) from the top down traverse.
The pump discharge pressure depends only on the weight and frictional
resistance to the flow rate through the tubing to surface.
Next match the pump intake pressure from the top down traverse. If the
calculated and measured pressure differential (head) across the pump is
different, then the assumptions of pump wear, fluid density (water cut) and
pump frequency should be examined.
The top down traverse will now give the resulting bottom hole flowing
pressure. This should be compared with the bottom up calculation and will
indicate any discrepancy with the inflow performance module
assumptions.
9.8.1 Input
The HSP QuickLook is accessed from the Matching menu. Clicking QuickLook from
the Matching menu displays the following screen:
Figure 9-21
HSP Quicklook
Input
Select the required pump and turbine from the buttons at the top of the screen.
PROSPER MANUAL
24 - 26 Chapter 9 - Matching Menu
Select between the up pass and down pass using the buttons located beside the
Case box as in the following example:
Figure 9-22
Calculation
Output Screen
Click Plot to display the pressure traverses and the calculated pump intake and
discharge pressures, down hole average rate across the pump (RB/day) and pump
and turbine parameters:
Figure 9-23
HSP Output
Plot
If the well bore, inflow and pump and turbine assumptions are all correct, the two
pressure traverses will overlay and the measured and calculated intake and
discharge pressures and surface voltages should coincide.
 The pump discharge pressure is the “tie” point for the system. First match
the pump discharge pressure (if available) from the top down traverse.
The pump discharge pressure depends only on the weight and frictional
resistance to the flow rate through the tubing to surface.
Next match the pump intake pressure from the top down traverse. If the
calculated and measured pressure differential (head) across the pump is
different, then the assumptions of pump wear, fluid density (water cut) and
pump speed should be examined.
The top down traverse will now give the resulting bottom hole flowing
pressure. This should be compared with the bottom up calculation and will
indicate any discrepancy with the inflow performance module
assumptions.
PROSPER MANUAL
26 - 26 Chapter 9 - Matching Menu
Figure 9-24
Correlation Threshold Input
Screen
Inflow (IPR)
This option calculates the IPR, that is to say, the relationship between tubing intake
rate and the bottomhole flowing pressure (BHFP). The Inflow calculation allows to
quickly run sensitivities without the need to calculate the system solution rate. This
is especially convenient for e.g. frac program design, gravel pack design,
perforation programming.
System (Ipr+Vlp)
This option will calculate both the tubing outflow (VLP) and tubing inflow (IPR)
curves and determine the system operating rate and bottom hole flowing pressure.
It also allows to perform sensitivity analyses with a wide range of variables.
Sensitivity plots can easily be generated.
Two options are available: 3 variables (for naturally flowing wells) and 4 variables
(for artificially lifted wells NEW!!!).
Gradient (Traverse)
This option enables you to generate gradient plots. If the correlations have been
matched, the gradients will be generated using the tuned correlations.
Choke Performance
This is a convenient choke calculator for flow rates, pressure drop or choke
settings.
To select this calculation type, choose Calculation ⏐ Inflow (IPR) from the main
menu toolbar.
Figure 10-1
Inflow (IPR) calculation
A few data on the fluid quality are required, along with the selection of the rate
range for which to run the calculation.
• User selected
Petroleum Experts
Chapter 10 - Calculation Menu 10-3
Figure 10-2
User selected rates
Generation
Enter values for the first and last rates in the table plus the number of entries
required. Depending on the selection of Linear or Geometric spacing, PROSPER
will calculate the required rate table.
Use the Try button for the preview of the entered range and Done to confirm.
 User selected rates can be useful when using the AOF is inappropriate for
the range of sensitivity variables to be considered.
Figure 10-3
IPR Sensitivity
Variables
The range of Inflow variables available depend on the particular IPR model entered
in System ⏐ Inflow performance.
For each of the selected variables enter the values by hand, or click Generate to
have PROSPER calculate a range of values as follows. The Generate feature is
exactly the same as the one for the Rate Method entry.
Leaving the sensitivity variable screen empty will run the calculation with the
default parameters entered in the main IPR section.
Once set up the Inflow sensitivity variables, click OK ⏐ Calculate to calculate the
IPR pressures. Click Plot to display a screen similar to the following:
Figure 10-4
IPR Calculation Results
 On this plot by pressing on the VARIABLES option on the menu bar, you
can get a display of all the variables that have been calculated during IPR
calculations, like skin, dP skin etc. These can be plotted as well.
Petroleum Experts
Chapter 10 - Calculation Menu 10-5
To enter the System Calculation area select Calculation⎪System (Ipr+Vlp) from the
menu toolbar.
Figure 10-5
System Calculation Setup
The first input screen requires the Top Node Pressure and the data concerning the
fluid quality (e.g. WC and GOR) and allows to select correlations for surface and
downhole equipment as well as select a rate method.
The Top Node represents the downstream end of the system, hence it is:
 - The manifold if surface equipment is included in the system
- The wellhead if no surface equipment is included in the system
The Solution Node represents the point at which the nodal analysis is
 performed. Three options are available:
- Bottom Node. It is the bottomhole, that is, the deepest point in the
downhole equipment
- Top Node. See definition in the previous note
- Well Head. It is the Xmas Tree, that is, the upper point of the
downhole equipment.
According to the last two definitions, if no surface equipment is included,
As far as the Rate Method is concerned, refer to the previous section (10.1.1) for
details.
 The Solution Rate reported is given by the VLP and IPR curves
intersection. These curves are interpolated between the selected
calculation rates and so the result may change according to the rate
values used.
 An IPR is required for both Automatic rate methods. For wells having very
high AOFs (e.g. horizontal wells) the well rate is determined mainly by the
tubing size. Manual rate selection may give better results in such cases.
Normally VLP/IPR intersections that occur when the tubing pressures are declining
(on the LHS) are considered to represent unstable flow and are usually ignored.
When Gas Coning occurs, however the GOR is changing constantly for different
rates and it is possible to have two solutions and for the LHS intersection to
represent stable flow. This option allows to consider or not the left-hand
intersection.
Figure 10-6
Left hand intersection
Petroleum Experts
Chapter 10 - Calculation Menu 10-7
Only the sensitivity variables relevant to the chosen system will be available. For
example, if a well is gas lifted you will be given the option of gas injection rate as a
variable. This option will not be available if the well is naturally flowing.
Figure 10-7
Diameter selection
Figure 10-8
Diameter Variable Range
Normally tubing diameter should not be varied in the casing below the tubing shoe.
This option is also useful for determining e.g. the effect of increasing tubing size
above a safety valve while keeping the diameter of the rest of the tubing string
diameter constant.
Figure 10-9
Sensitivity Combinations
Input
 If no liquid rates are entered, the program uses the current list of rates
(either internally calculated or User input) and calculates the solution for
the combination of sensitivity variables for each of up to 10 cases.
Petroleum Experts
Chapter 10 - Calculation Menu 10-9
Once sensitivity values have been entered in either the Combinations or Variables
screen, click Continue to display the calculation screen. Sensitivity values
temporarily overwrite variable values that have been entered on other screens. For
example: Pressure at first node, water cut.
Figure 10-10
Calculation System
On the right hand side there are the results of the system calculation: solution
rates, FBHP, WHP, WHT, etc.
On the left hand side, instead, there are the calculated parameters related to VLP
and IPR. Scroll to the right to read the results.
In the Variables area it is possible to scroll the different cases or the values of the
sensitivity variables for which the calculation were performed.
Details of Solutions
To examine the solution in more detail, click the Solution Details button. Individual
solution points can be viewed by clicking on the arrow buttons located beside each
sensitivity variable. Outflow or Inflow solutions can be viewed as shown in the
following sample screen:
Figure 10-11
Calculation
System Solution
Details
In the case of wells with ESP, HSP, PCP or Jet Pump, the solution details contain
all the results related to the pump.
Plotting Results
The results can be plotted by clicking Plot. The System plot will appear as follows:
Figure 10-12
System Solution Plot
The system plot summarises all the calculations. Each VLP and IPR curve is
identified by up to 3 numbers posted beside them. The variable names and the
corresponding number labels are shown in the panel to the right of the plot. In the
above example, Curve 1,0,0 is for 4500 psig reservoir pressure, 0 % water cut and
4 STB/day/psi productivity index.
Petroleum Experts
Chapter 10 - Calculation Menu 10-11
To plot the solution rates and pressures versus the selected variables, click
Sensitivity and a sensitivity plot will be displayed. To select sensitivity variables to
plot, click Variables and make your selection on the following screen, for example:
Figure 10-13
System Sensitivity
Variables
The Sensitivity screen allows you to choose X- and Y-axis variables. Click OK to
view the Sensitivity plot. The program automatically plots the sensitivity values of
the X-axis variable. If variable Combinations have been used, the sensitivity cases
will be automatically plotted.
Figure 10-14
System Sensitivity Plot
The pressure gradient for any particular solution rate can be calculated by clicking
Sens PvD (Sensitivity Pressure vs. Depth).
Figure 10-15
Sens PvD Setup
Select the desired case by scrolling on the variables, and then Continue and
Calculate to generate the gradient. The results are displayed on the following
screen example:
Figure 10-16
Sens PvD Results
Petroleum Experts
Chapter 10 - Calculation Menu 10-13
Figure 10-17
Sens PvD Plot
Figure 10-18
Plot Variables Selection
By clicking the Extended button, a greater range of plot variables can be accessed.
Virtually any combination of computed results can be plotted against each other.
Figure 10-19
Extended Plot Variables
Return to the standard choice of plot variables by clicking the Original button.
The plots are held in memory until overwritten by a new set of calculations. Plots
can also be displayed or output by selecting Plot from the main menu. The Units
menu can be used to change the display units if required.
Special Note for ESP, HSP, PCP and Jet Pump Applications
When calculating a System solution for a pump equipped well, in the Solution Point
screen lists details of the pump solution such as pump intake pressure etc. (See
example pump solution in the screen below)
Figure 10-20
ESP Solution Point
Clicking Pump Plot on the pump solution screen displays the sensitivity solutions
plotted over the pump characteristic curves (this is available only for ESP and
Petroleum Experts
Chapter 10 - Calculation Menu 10-15
HSP). As shown by the example screen below, the effects of the sensitivity
variables on the pump operating point can be readily evaluated.
Figure 10-21
ESP Solution Plot
This plot is a powerful tool for evaluating how an ESP design can accommodate
future changes of well conditions.
 All pump (both ESP & HSP) designs should be validated by calculating
sensitivities and ensuring that efficient operation at the design rate can be
achieved over the entire range of expected well and pump efficiency
conditions.
For pump (both ESP & HSP) equipped wells, the Sens. PvD gradient calculation
shows the pressure increase across the pump. An example gradient plot is shown
below:
Figure 10-22
ESP Sens. PvD Plot
These curves can be compared with published pressure traverse curves or actual
well data. Pressure traverses can also computed for combinations of sensitivity
variables. The effect of changing tubing sizes, SSSV I.D. etc. can be evaluated
visually by plotting the gradient results.
Figure 10-23
Gradient Traverse Input
Enter the required data, mostly the same as the one requested by System
calculation, plus the first and the last node for the calculation, which will determine
the section of completion for which to run the gradient calculation.
Then select Continue to access the Sensitivity Variables (or Combinations) screen.
Refer to previous sections for the description of this area.
Selecting Continue again will access the calculation screen. In this screen the User
can select the flow correlations for the downhole and the slug method:
Petroleum Experts
Chapter 10 - Calculation Menu 10-17
Figure 10-24
Gradient Traverse
Calculation
Click Calculate to compute flowing gradients for all the sensitivity cases. Once the
calculations have been completed, the results tables can be inspected by clicking
the respective variable arrows until the desired variable combination is visible.
 Important
The Gradient calculation results report very useful parameters
concerning details on the ∆P calculation, PVT data, mass flow
rates and in the case of pipeline gradients, characteristic
parameters of slugs, etc.
A plot of the gradient results similar to that below can be displayed by then clicking
the Plot button:
Figure 10-25
Gradient Traverse
Plot
Gradients can be plotted for the well and flow line separately or combined on the
one plot. Details on the plotting features are available in Section 10.1.1.
PROSPER User Guide
18 - 46 Chapter 10 - Calculation Menu
The Turner Equation is used to study the continuous removal of liquid from gas
wells.
This equation is used to determine the minimum velocity of the producing fluid
necessary to drag away the droplets of liquid. The original formulation of the
equation is the following:
Figure 10-26
Classical Turner Equation
Original Turner
1
σ 4 (ρ l − ρ g )
Equation 1 4
Vt = 20.4 1
ρg 2
Figure 10-27
Gradient traverse
Petroleum Experts
Chapter 10 - Calculation Menu 10-19
Results of the calculation of the Turner velocity are reported in the Gradient
calculation results table, as reported in the figure above.
When gradient traverse calculations are performed the program will estimate the
correspondent value of erosional velocity.
Erosion can be caused by the repeated impact of solid particles on tubing and
pipelines. To avoid this we attempt to estimate the velocity at which erosion will
occur.
Normal practise is to use equation of API 14 E. This can be unreliable especially for
clean production where the limiting value of C (125) can be too restrictive. In
practice, values of 1000 for C have been recorded in pipes where no erosion has
been detected.
C
Figure 10-28
Ve =
Classical
equation of
ρm
Erosional
Velocity Ve - Fluid Erosion Velocity (ft/sec)
A Conoco paper (An Alternative to API14E Erosional Velocity Limits for Sand
Laden Fluids) challenges API14E on the basis that it can be very conservative for
clean service and is not applicable for conditions where corrosion or sand are
present. It proposes a simple alternative approach that has been verified by a
comparison with several multi-phase flow loop tests that cover a broad range of
liquid-gas ratios and sand concentrations. Values of S for different components are
proposed in the paper
D ρm
Ve = S
Figure 10-29
New erosional
velocity W
calculations
S - S Factor (depends on pipe geometry)
D - Pipe Diameter (mm)
ρ m - Mixture Density (Kg/m 3)
The constants C and S for the two formulations can be customised by selecting
System⎪Solids and tab button Erosional Velocity or the Options button in any
calculation screen.
PROSPER calculates the erosional velocity for solid-free fluid using the API-14E
method and the entered “C” value. If the sand production rate has been specified,
PROSPER will calculate the erosional velocity using both the API-14E and Conoco
methods and will then compare the results and will use the computed lower-value
of erosional velocity. To review the computed erosional velocity values using the
Conoco method set the value of “C” sufficiently high until the values do not change
for changing values of “C”.
After gradient calculations are performed, scroll right on the results screen to view
the erosional velocity values.
Figure 10-30
Gradient traverse
Erosional
Velocity and
C Factor
Petroleum Experts
Chapter 10 - Calculation Menu 10-21
The calculated Maximum Grain Diameter is reported in the results table at each
calculation step.
10.1.3.4 Pigging
This calculation can be used to describe the pigging characteristics of the flow in
pipelines.
Assuming 100% removal efficiency of a sphere and that all the liquid removed by
the sphere is in the form of a continuous slug, the pigged slug volume can be
estimated by integrating the difference between the liquid hold-up and the no-slip
hold-up in the pipeline. Also the time to produce the slug can be calculated from
5 ⋅ 614 ∗ VL
Tpr =
⎛ VSL ⎞
A⎜⎜1 - ⎟⎟VSG
⎝ V SL + VSG ⎠
These are the additional results reported in the Gradient Traverse results table:
• Pigged Slug Length
• Pigged Slug Volume
• Time to Produce Pigged Slug Length
• Time for Pigged Slug to reach Outlet
10.1.3.5 Options
The parameters affecting the calculation of the maximum grain size, erosional
velocity, liquid loading (Turner velocity) and pigging, can be accessed in any
Calculation screen by means of Options button.
This screen can also be accessed from the main menu toolbar by selecting
System⎪Solids.
Figure 10-31
VLP Calculation Setup
When User Selected rates are used, you can enter rates in terms of Liquid, Oil or
Gas. The results will be given in terms of the specified rate type, but depending on
the type of well, PROSPER will first convert the rates to equivalent oil or gas to
Petroleum Experts
Chapter 10 - Calculation Menu 10-23
calculate the VLP pressure. This feature can be used when preparing lift curves for
high GOR oil wells. Remember when using gas rates, that increasing the water cut
will also increase the liquid production rate. Extreme VLP pressures can easily
result.
Click Continue to access the Select Variables screen and set up the required
sensitivity variables.
To generate lift curves for simulator (like Eclipse) for an oil well, the VLP is
generally calculated for the following sensitivity variables:
• Variable 1: Pressure at first node
• Variable 2: Water cut
• Variable 3: Gas Oil Ratio
An example calculation variables screen for generating lift curves is shown below:
Figure 10-32
VLP Sensitivity Variables
Select the variables required by your external application and enter a list of values
for each. Click Continue to access the calculation screen, then select Calculate to
generate the lift curves. An example lift curve calculation screen is shown below:
Figure 10-33
VLP Calculation
Results
Petroleum Experts
Chapter 10 - Calculation Menu 10-25
Figure 10-34
VLP Export Options
(3 Variables)
PROSPER appends the export file with a suffix corresponding to the selected file
format as shown in the table above. Depending on the export format selected, the
PROSPER User Guide
26 - 46 Chapter 10 - Calculation Menu
User will be prompted for a file name and additional data such as table number,
flow table I.D. etc. Refer to the simulator documentation for further details.
An example of a 4 variable VLP calculation for a gas lifted well is shown on the
following screen:
Petroleum Experts
Chapter 10 - Calculation Menu 10-27
Figure 10-35
4 Variable VLP Calculation
Setup
The standard option prompts you to enter the bottom hole pressure. PROSPER
calculates from the deepest node to the pump. The pump head for the given
frequency, water cut etc. are calculated to find the pump discharge pressure.
PROSPER then determines the PVT of the oil above the pump after accounting for
possible gas separation and calculates the pressure traverse above the pump to
find the top node arrival pressure for each required production rate point.
Simulators require tables of rates and BHPs ordered by THP. The Lift curves for
simulators option allows input of Top Node pressure, water cut, operating frequency
etc. PROSPER iterates to find the pressure at the deepest node (VLP) for the given
the top node pressure. In both cases, the VLP is the bottom hole pressure for the
specified producing conditions.
 VLP lift curves for simulators or Petroleum Experts’ applications (GAP and
MBAL) can be batch generated for groups of wells by PROSPER
from GAP. Refer to the GAP documentation for details.
Petroleum Experts
Chapter 10 - Calculation Menu 10-29
Figure 10-36
Choke Performance
Calculator
Calculation Options
Select your required calculation option from the following:
• Predict Mass Flow Rate
PROSPER determines the flow rate for specified choke opening and inlet
and outlet pressures
• Predict Pressure Drop
PROSPER calculates the pressure drop across a specified choke opening
for a given flow rate and inlet pressure
• Predict Choke Valve Setting
PROSPER finds the choke size for a specified rate and inlet an outlet
pressures.
Choke Method
Select a choke calculation method from the following options:
• Petroleum Experts
This is an in-house developed choke model based on Perkin’s work (SPE
206333).
• HYDRO
There are 3 distinct methods for modelling specific choke equipment.
Until performance testing is completed and documentation issued, these
choke methods should not be used.
• ELF
A model based on Perkin’s (SPE 206333) approach along with discharge
coefficients determined by the author (Stephane Rastoin of ELF
Aquitaine at TUALP). This is also the recommended method used to
calculate pressure drops down hole for SSSVs and restrictions. It should
be used for the majority of applications.
Click Calculate, and PROSPER will calculate the liquid and mass flow rates Similar
screens are used to enter data for the dP and Choke Setting prediction options.
For critical flow conditions, it may take some time for the calculation to converge.
PROSPER can be run from within GAP in a batch mode for generating performance
curves for groups of wells or independently of GAP by selecting this option.
PROSPER will automatically calculate solutions for gas lifted or naturally flowing
wells. If the solutions are then saved in a .OUT file, GAP can pick up the data
required to calculate performance curves at a later time. For more information,
refer to the GAP documentation.
Petroleum Experts
Chapter 10 - Calculation Menu 10-31
Input data required are gas, water and oil rate information as well as wellhead
temperature and pressure.
This information can be in one of several formats (e.g. Liquid rate, WC and GOR,
etc.) and the correct format for your data can be selected at the top of the
appropriate columns. If the data type in a particular column is changed while there
is data already in that particular column, then the data will be converted to the new
type.
In the case of gas lifted wells the gas lift gas rate is required and in the case of ESP
lifted wells the pump frequency must be entered.
Figure 10-37
The table is quite large allowing to start off with up to 16000 rows of data which is
automatically expandable up to 32000 rows. The data can be scrolled with the
scrollbar at the right hand side of the screen.
Appropriate vertical lift and surface pipe correlations can be selected at the bottom
of the screen.
Selecting the import button allows you to bring in data from an outside source.
Table data can be saved to file using the export button and plots using either time
or the log of time can also be viewed and exported using the plot feature. Within the
plot screen data can be enabled or disabled point by point or in a block manner by
using the right-click mouse button.
Figure 10-38
Data can be ordered with relation to time by using the sort button. This will also
remove any blank rows between data in the table.
10.2.1.1 References
Petroleum Experts
Chapter 10 - Calculation Menu 10-33
Both pressure and temperature losses across chokes and restrictions are
accounted for. A theoretical outline of the Enthalpy Balance model is given in
Appendix C.
• pipelines
• sub sea wells
• high pressure/temperature exploration wells
• predicting temperature/pressure profiles to help predict wax/hydrate
deposits.
• accounting for Joule-Thompson effects
PROSPER 's Enthalpy Balance temperature model is one of the most accurate
temperature prediction methods available.
To reflect the range of calculations possible when using the Enthalpy Balance
temperature model, the following options are available in the Calculation menu:
Correlation Comparison
Compares the pressure traverses calculated with different multiphase flow
correlations.
Match Parameters
Allows entry of match parameters for surface flow lines and well tubing.
Petroleum Experts
Chapter 10 - Calculation Menu 10-35
• Production Rate
• Sand-face pressure.
The calculation is an iterative one and the inlet conditions are changed till
an acceptable top node condition is achieved.
The IPR input in the System menu is used to determine the flowing bottomhole
conditions. An example Constrained System input screen is shown below:
Figure 10-39
Constrained System Input
Enter the Constrained (Top) Node Pressure, Water Cut and Time Since Production
Started. Select suitable Surface Equipment and Vertical Lift correlations.
As for all the calculation types, clicking on Continue displays the Select Variables
screen.
Once entered the sensitivity parameters ranges, select Continue to access the
Calculation Output screen:
Figure 10-40
Constrained
System
Calculation
Click Calculate to start the calculations. The results can be inspected by clicking
the Solution button as shown below.
Figure 10-41
Constrained
System Solution
Screen
To display sensitivity plots select Sensitivity, whilst to calculate the flowing gradient
for any particular solution click on Sensitivity PvD.
Petroleum Experts
Chapter 10 - Calculation Menu 10-37
The IPR input in the System menu can be used to determine the flowing bottom
hole conditions or the User may enter a selection of rates. An example input screen
is shown below:
Figure 10-42
Constrained VLP Input
Select suitable VLP and surface equipment correlations, enter the water cut, the
time since production started and a range of production rates. Click Continue to
enter the Select Variables screen and then to display the calculation screen.
Figure 10-43
Constrained
VLP Calculation
Screen
Figure 10-44
Constrained
VLP Plot
The IPR input in the System menu is used to determine the flowing bottom hole
pressure. An example Unconstrained System input screen is shown below:
Petroleum Experts
Chapter 10 - Calculation Menu 10-39
Figure 10-45
Unconstrained System
Input
Select the flow correlations and the rate method and then click on Continue to enter
the sensitivity variables and then again Continue to display the calculation screen.
Click Calculate to start the calculations.
Figure 10-46
Unconstrained
System
Calculation
Screen
When calculation finishes, the results can be plotted by clicking the Plot button:
Figure 10-47
Unconstrained
System Plot
As the rates and pressures are directly entered, the IPR does not enter into the
calculation. An example Unconstrained VLP input screen is shown below:
Petroleum Experts
Chapter 10 - Calculation Menu 10-41
Figure 10-48
Unconstrained VLP Input
Select correlations for surface equipment and VLP, the calculation nodes and a
table of rates. Note that calculating temperature from top to bottom has no
meaning for the Enthalpy Balance model. Click Continue to enter your sensitivity
variables and Continue again to display the calculation screen. The pressure at
first node can be varied as a sensitivity variable.
Figure 10-49
Unconstrained
VLP Calculation
Screen
The results of wellhead pressure vs. rate can be plotted by clicking the Plot button:
Figure 10-50
Unconstrained
VLP Plot
As the surface pressures and temperatures are calculated by PROSPER, the lift
curves cannot be readily ordered by top node pressure as required for simulators.
A data Export facility has therefore not been included for this option.
The rate is directly input, and the IPR is not used in the calculations. The solution
must commence from a known upstream temperature. First node pressure and
temperature plus the sensitivity variables are input as for an Unconstrained VLP
calculation. An example of Unconstrained Gradient (traverse) input screen is
shown below:
Petroleum Experts
Chapter 10 - Calculation Menu 10-43
Figure 10-51
Unconstrained Gradient
Input
Click Continue to access the sensitivity variables input screen, then again Continue
to display the gradient calculation screen. Click Calculate to calculate pressure and
temperature traverses for all combinations of sensitivity variables. An example
gradient calculation screen is shown below:
Figure 10-52
Unconstrained
Gradient Results
The calculated heat transfer coefficients, average annulus temperature and casing
inside temperatures can be inspected by scrolling to the right in the results screen.
Click Plot to display a plot of temperature and pressure versus depth similar to that
shown below:
Figure 10-53
Unconstrained Gradient Plot
If time since production started has been selected as a sensitivity variable, this plot
can be used to determine how long a well will take to reach a specified well head
temperature. The effect of insulation on high heat loss sections such as risers can
also be readily investigated. Click Variables ⏐ Extended to access a wide range of
computed results. The plot of heat transfer coefficient Vs depth as shown below
can be useful in understanding heat flow in a well:
Figure 10-54
Heat Transfer Coefficient Plot
Note the high values of heat transfer coefficient in the casing and riser. Note that in
this example, the heat flow from the casing is small since the temperature
difference between the fluid and formation is minimal.
Petroleum Experts
Chapter 10 - Calculation Menu 10-45
Figure 10-55
Heat Transfer Coefficient Plot
Click on Continue and Calculate to perform the comparison, the Plot to view the
gradients:
Figure 10-56
Heat Transfer Coefficient Plot
from the output file of a relevant Pressure Only case. The match parameters can
be applied to an Enthalpy Balance case by carrying out the following steps:
• Open the *.OUT file for a Pressure Only case that contains the required
matched correlations.
• Open the *.SIN file for your pressure and temperature prediction application
• Perform the pressure and temperature analysis
• Save a .OUT file for the pressure and temperature prediction application.
This file will now contain the matched correlations.
Petroleum Experts
11 Design Menu
This chapter is
The Design Menu enables the User to perform various artificial lift designs.
From this menu the User can access the design modules for the following artificial lift
technologies:
• Gas Lift
• Electrical Submersible Pump
• Hydraulic Pump
• Progressive Cavity Pump
• Coiled Tubing GasLift
• Jet Pump
The design menu is active only if an artificial lift method has been selected
 in the main Options screen.
The design option will correspond to the artificial lift method selection in
the main Option screen.
Artificial lift design is not enabled when the Enthalpy Balance temperature
model is in use.
From the Design menu the Database containing all the information about gas lift
valves, ESP pumps, motors, cables, etc. is accessible. A dedicated section is
reported at the end of the chapter.
Designs can also be performed for existing wells having mandrels installed at fixed
depths.
Design performance can be evaluated using the Gas Lift QuickLook (as seen in
Chapter 9) or calculating system sensitivities.
Menu Options
If gas lift was selected as a lift method in the Options menu the following additional
options will be available in the Design⎪Gaslift menu:
• New Well
2 -59 Chapter 11 - Design Menu
• Existing Mandrels
• Gas Lift Adjustments
The gas lift design section of the program can be used to determine the optimum gas
lift equipment for a given well. PROSPER calculates the maximum production rate
possible, the corresponding optimum gas lift rate, the valve spacing and size to
unload the well and the test rack setting pressure for each valve for surface
calibration.
Designs can also be prepared for wells having mandrels already set at fixed depths.
Before the User can proceed ahead with artificial lift design, PVT, downhole
equipment and IPR information must be input.
Figure 11-1
Gas Lift Design (new well)
In this screen it is possible to enter the input data for the gas lift design task.
The input data screen is divided into several areas. The Input parameters panel is
used to enter the design operating conditions. The other panels allow the User to
enter the design options for a given application.
• Entered By User
Use this option when designing for a given production rate and gas lift gas
injection rate or when modelling the performance of an existing installation. If
Check Conformance with IPR is selected, the program will modify the rate and
the gas injection rate, if necessary, to honour the IPR.
If a maximum production calculation has been previously done, the lift gas and
design production rates can be User Entered. The design rate can be entered
either in terms of liquid or oil production only. The design lift gas injection is
entered as the Maximum gas available.
• Calculated from Maximum production
PROSPER will find the maximum possible oil production rate by determining both
the optimum gas injection rate and depth. This is achieved by calculating the oil
production for a given GLR injected and increasing the GLR until the optimum is
found.
• Calculated from Maximum revenue
Using User-entered economic parameters for oil and sales gas revenue,
produced water processing and lift gas cost, the program will find the gas lift
design that maximises total revenue (oil and gas revenue less water and
injection gas processing costs). The same search procedure as for Maximum
production is carried out using the cost function in place of the oil production
rate.
Input Parameters
Having set up the calculation options, enter values for the following variables on the
Input Parameters panel:
PROSPER MANUAL
4 -59 Chapter 11 - Design Menu
Water cut
• Design producing water cut.
Minimum Spacing
• Sets the minimum spacing between valves. Use 200 - 400 ft normally.
Minimum transfer dP
• Only active when Ignoring IPR for Unloading has been selected. If
set to zero, unloading valve trims will be sized to inject sufficient gas to
lower the unloading tubing pressure to the transfer pressure at the
valve depth.
• Increasing the value of Minimum transfer dP will lower the unloading
GLR injected and reduce trim sizes.
Referring to the sketch (Figure 11.2) below, the transfer pressure is:
(Pmin) = Ppd - (Ppd - Pid) * % minimum transfer dP /100
Increasing the injection GLR shifts the tubing gradient during unloading closer
to the objective gradient line (i.e. to the left). The unloading valve trim is sized
for the GLR corresponding to the required transfer pressure. Values of 5 to
25% are commonly used.
Figure 11-2
Minimum Transfer dP
 Unloading valve trim sizing depends on whether or not the IPR is used
to determine well flow rates while unloading. Existing Users should
review this section carefully.
Valve Type
• Casing sensitive valves
o Enter the minimum casing pressure drop to close valves.
• Tubing sensitive valves
o Enter the percentage difference in Pcasing - Pwh to close valves.
• Proportional response valves
PROSPER MANUAL
6 -59 Chapter 11 - Design Menu
This design method ensures maximum injection depth and hence maximises
production rates.
Injection Point
Before the gas lift design is performed, the User can decide if the operating valve is
a gas lift valve or an orifice.
• Yes
The API method is used below 1200 psi, and an improved algorithm is used above
1200 psi. This is the default and recommended option.
 For speed in comparing designs, this option can be set to No. However,
the User must be aware that the design rate may not be able to be met by
the well.
Orifice Sizing On
Two options are available:
• Calculated dP at Orifice
• Min dP Across Orifice
PROSPER MANUAL
8 -59 Chapter 11 - Design Menu
On the right-hand side of the input Gas Lift Design input screen there is a navigator
window that allows selecting the type of valves to use in the design from an internal
database.
Figure 11-3
Gas Lift Design (New Well)
Calculation
Displaying the Well Performance Curves / Finding Design Rate (New Well)
The first step is to find the design production rate.
• Click Get Rate. PROSPER will calculate the Gas Lift Performance
Curve and determine the optimum Gas Lift injection rate and maximum
oil production rate.
When the calculations have finished, the results can be displayed in the form of a
well performance curve by clicking Plot. A graph similar to the following will appear:
Figure 11-4
Well
Performance
Curve
The target design rate and GLR injected can be read off the performance curve plot.
The design rate is:
• The maximum oil production shown in the Performance curve plot, provided
that the available gas injection and liquid production rate limits have not been
exceeded.
• In case the maximum gas available is exceeded by the highest oil rate on the
plot, the oil rate corresponding to maximum available gas is taken as design
rate.
• PROSPER will design for the maximum oil production rate entered in the main
input screen, if it exceeds the rate calculated from the performance curve.
PROSPER MANUAL
10 -59 Chapter 11 - Design Menu
• The program will then determine the depth of the operating valve and the
spacing for the unloading valves. Depending on the design settings, this will
usually take more than one pass.
• On the first pass, the injection and unloading valve depths are determined
assuming no casing pressure drop to close valves.
• Having determined the number of valves to use, the operating valve depth is
revised to reflect the new operating casing pressure.
• The spacing procedure is repeated using the revised operating casing
pressure until the number of unloading valves and their setting depths no
longer change.
 When Check Rate Conformance with IPR is set to Yes, PROSPER re-
calculates the solution rate and reduces the design rate if necessary.
The final design production and Gas Lift injection rates are displayed on
the design gradient plot.
Figure 11-5
Gradient with
Valve Depths
The plot shows the tubing and casing pressure gradients for the design rate plus the
position of the operating and unloading valves. The unloading fluid gradients are
plotted also. The design data box lists the Actual production and injection rates
together with the operating surface casing pressure.
Figure 11-6
Valve Design
Results
Click on Calculate to calculate the Dome Pressure and the TestRack Opening
Pressure (valve setting pressure at 60°C).
 The valve depths, tubing pressure, unloading gas injection rate and trim
sizes are shown in the left screen panel.
 Valve types are identified as Valve for unloading valves or Orifice for the
last mandrel if the injection point is selected as orifice. No opening or
dome pressure calculations are made for the orifice.
The design parameters such as valve depth, opening and closing pressures, orifice
size etc. are displayed in the table. Use the scroll thumb below the table to scroll
right to see items e.g. R-value, not visible in the display window.
PROSPER MANUAL
12 -59 Chapter 11 - Design Menu
To perform the fixed mandrel depth design, click Design ⏐ Gas lift design | Existing
mandrels. The following input screen will be displayed:
Figure 11-7
Fixed Mandrel Depth
Design
This screen is similar to the Gas lift design (New well) screen, except that the
variables relating to spacing the valves have been removed.
Please refer to the previous section for the description of the entry fields.
Â
For this design type options for the choice of the first valve can be selected:
PROSPER estimates the standing liquid level from the reservoir pressure and
static pressure gradient. Any mandrels that are above this depth will be set with
“Dummy valves”.
 This approach can save valves for low pressure reservoirs. The User
must be certain that work over fluids can leak off to balance the
reservoir pressure
 Enter the depth of all mandrels in the well, including those fitted with
dummy valves.
PROSPER will select the best depths for the operating and unloading valves
from this list.
When more mandrels are available than needed for the current design,
PROSPER will automatically set dummies at the intermediate depths.
The valve type initially entered is unimportant.
PROSPER will overwrite the valve type when it performs the design.
This table is effectively a list of the potential valve depths and can be used to
prepare designs for new wells where equipment limitations determine the available
mandrel depths.
PROSPER MANUAL
14 -59 Chapter 11 - Design Menu
Figure 11-8
Fixed Mandrel Depth
Details
If entries are made in the Casing Pressure drop or Max. Gas Injected fields
 on the mandrel depth screen shown in the figure above, these values will
overwrite the values entered on the main design screen.
Leave these fields blank to design using the same values of pressure drop
or gas injection for each unloading valve.
If a calculated rate design method has been selected, a screen similar to the
following will be displayed:
Figure 11-9
Fixed Mandrel Depth
Design
PROSPER MANUAL
16 -59 Chapter 11 - Design Menu
• This procedure ensures that the available mandrel depths are honoured at
every calculation step.
Once the calculations have stopped, click Plot to make a plot of the production rate
Vs gas injected. It is similar to that of a new well design.
Figure 11-10
Gas Lift Design
Plot
Figure 11-11
Gas Lift Valve
Calculations
Click Calculate to determine the Dome and the TestRack Opening pressure will be
updated for the new valve series.
• To access parameters such as the transfer pressure and port size, click on
the scroll arrow at the bottom of the Input parameters panel.
 To perform sensitivity calculations for the current design, the valve depths
must be transferred to Equipment ⏐ Gas Lift before making calculations.
Based on flowing tubing pressures PROSPER determines the injection
point during production.
PROSPER MANUAL
18 -59 Chapter 11 - Design Menu
step establishes the flowing tubing pressure gradient to be used for valve
spacing.
• The shallowest unloading valve is placed at the depth that balances the tubing
load fluid pressure with the casing pressure (less a 50 psi safety margin) at
that depth.
• Further unloading valves are placed by traversing down between the load fluid
pressure gradient and gas lifted tubing pressure gradient (calculated for the
design gas lifted production rate) lines.
• Valves are placed ever deeper until the inter-valve spacing equals the pre-set
minimum, or the maximum injection depth has been reached.
• Once the first pass design is complete, PROSPER re-calculates the flowing
gradient tubing using the current operating valve depth. For casing sensitive
valves, the valve depths are re-calculated to allow for the casing pressure
drop to close valves. The process is repeated until the valve depths no longer
change.
When Check Rate Conformance with IPR is set to Yes, the solution rate is checked
to ensure that it can be achieved. PROSPER reduces the design rate if necessary and
repeats the spacing exercise.
Figure 11-12
Valve Spacing - Tubing
Sensitive Valves
PROSPER MANUAL
20 -59 Chapter 11 - Design Menu
Figure 11-13
Gas Lift Adjustments
Once the input data entry is complete, the User has to make sure that the
correspondent valves are transferred. Select Valves and then Transfer to transfer the
valve info from Gas Lift Design or from QuickLook:
Figure 11-14
Transferring valves from
quick look
Figure 11-15
Valves from QuickLook
Once the gaslift equipment details are entered the flowing gradient or static gradient
can be estimated:
PROSPER MANUAL
22 -59 Chapter 11 - Design Menu
Flowing
Calculations are made for flowing conditions at the User-entered target production
rate. PROSPER calculates well performance curves for gas injection at each mandrel
depth. Production rates and pressures at surface and mandrel depth are
determined. Annulus volume and bottoms up times are also calculated. The flowing
gradient for the operating condition can be plotted with opening and closing
pressures for each unloading valve displayed.
Figure 11-16
Flowing calculations
Figure 11-17
Flowing calculations
Static
Calculations are made for shut-in conditions. The static tubing gradient is
determined using the liquid density calculated for the producing water cut. When the
reservoir pressure cannot support a full liquid column, a gas gradient is used back to
surface.
Figure 11-18
Flowing calculations
ESP data entered in the System ⏐ Electrical Submersible Pumps input menu is not
utilised by the ESP design section. The design results will overwrite this section.
In the main ESP Design screen the design parameters can be entered:
PROSPER MANUAL
24 -59 Chapter 11 - Design Menu
Figure 11-19
ESP Design Screen Input
The following description assumes that input of the well details and PVT data have
already been correctly completed and that where applicable, pressure drop
correlations have been matched to field data.
Figure 11-20
ESP Pump Duty
Calculation
Clicking on Calculate the program calculates the pump duty necessary to achieve
the design production rate. PROSPER will display the pump duty solution, as shown
in the figure above.
• PROSPER uses the IPR from System ⏐ Inflow Performance to calculate the
flowing pressure at the sand face and the specified VLP correlation to find the
pump intake pressure for the design production rate.
• The program then works down from the specified top node pressure to arrive
at the required pump discharge pressure.
• The difference between the intake and discharge pressures represents the
required pump head.
• PROSPER compresses the liquid and gas as the pressure increases across
the pump, so the volumetric rate will be less at the discharge than at the pump
inlet.
• The mass flow rate and the required head are used to determine the pump
fluid power requirement.
Emulsions
 If Emulsions have been selected on the Options screen, viscosity
corrections are applied to pump capacity and head. Otherwise, no ESP
viscosity corrections will be applied. If an Emulsion PVT model has been
built in the PVT section, then the emulsion viscosity can be optionally used
in the ESP calculations and elsewhere. As mentioned in the PVT section,
emulsion behaviour in oilfield systems analysis is poorly understood. The
PROSPER MANUAL
26 -59 Chapter 11 - Design Menu
 To check that the separator efficiency chosen in the input is acceptable for
the design case, the Dunbar Criteria may be used as showed below.
Click Sensitivity to display the intake pressure and intake GLR plotted over a range
of gas separator efficiency curves. Check that the design operating point lies above
the empirical limit represented by the Dunbar Factor line.
Figure 11-21
ESP GLR Sensitivity
To do so, select Design: the program will display a pump design screen similar to
that shown below:
Figure 11-22
ESP Design Selection
In the Select drop-down boxes, PROSPER lists the equipment in its database that is
capable of meeting the design requirements.
Select Pump
PROSPER presents pumps that can meet the following criteria:
Select Motor
Once a pump has been selected, the pump efficiency is known; the motor power
requirement can now be calculated.
Proceed to the motor drop-down box and select a motor from those listed.
Select Cable
Once the motor power and voltage option have been determined, a suitable cable
must be selected.
PROSPER MANUAL
28 -59 Chapter 11 - Design Menu
Figure 11-23
ESP Design
Plot
 Normally, the first pass design will have an operating point fairly close to
the selected pump's optimum efficiency. However, as well conditions
change with time, this may not be the best design for the life of the
installation
The ESP system design process is completed by iterating between the Calculation
and Design sections until the final design is optimised over the projected pump run
life.
In the main HSP Design screen the design parameters can be entered:
Figure 11-24
HSP Design Screen Input
PROSPER MANUAL
30 -59 Chapter 11 - Design Menu
The design of an HSP installation using PROSPER is divided into two phases. One is
where the head and power requirement calculations are made and the second part is
where on basis of the calculations, the equipment is selected.
The following description assumes that input of the well details and PVT data have
already been correctly completed and that where applicable, pressure drop
correlations have been matched to field data.
Figure 11-25
HSP Pump Duty
Calculation
Clicking on Calculate the program calculates the pump duty necessary to achieve
the design production rate. PROSPER will display the pump duty solution, as shown
in the figure above.
• PROSPER uses the IPR from System ⏐ Inflow Performance to calculate the
flowing pressure at the sand face and the specified VLP correlation to find the
pump intake pressure for the design production rate.
• The program then works down from the specified top node pressure to arrive
at the required pump discharge pressure.
• The difference between the intake and discharge pressures represents the
required pump head.
• PROSPER compresses the liquid and gas as the pressure increases across
the pump, so the volumetric rate will be less at the discharge than at the pump
inlet.
• The mass flow rate and the required head are used to determine the pump
fluid power requirement.
For certain configurations the produced and power fluids can be commingled above
the pump. Hence, the PVT properties of the well fluids can be different below and
Emulsions
 If Emulsions have been selected on the Options screen, viscosity
corrections are applied to pump capacity and head. Otherwise, no HSP
viscosity corrections will be applied. If an Emulsion PVT model has been
built in the PVT section, then the emulsion viscosity can be optionally used
in the HSP calculations and elsewhere. As mentioned in the PVT section,
emulsion behaviour in oilfield systems analysis is poorly understood. The
emulsion PVT model provides the means to apply empirical corrections
and should be used with caution.
above the pump.
To do so, select Design: the program will display a pump design screen similar to
that shown below:
Figure 11-26
HSP Design Selection
In the Select drop-down boxes, PROSPER lists the equipment in its database that is
capable of meeting the design requirements.
PROSPER MANUAL
32 -59 Chapter 11 - Design Menu
Select Pump
PROSPER presents pumps that can meet the following criteria:
Select Turbine
Once a pump has been selected, the pump efficiency is known, so the turbine power
requirement can now be calculated.
Proceed to the turbine drop down box and select a turbine from those listed.
Figure 11-27
HSP Performance
curve
• Normally, the first pass design will have an operating point fairly close to the
selected pump's optimum efficiency. However, as well conditions change with
time, this may not be the best design for the life of the installation.
• Different combinations of pump and turbine can be quickly experimented with
in the HSP design section until an optimum design is obtained.
• A report can be generated which gives details of the pump selection and
design conditions.
Important Note
 The robustness of the first pass design must then be checked over the
range of expected well operating conditions by running sensitivities in the
System Calculation menu.
The HSP system design process is completed by iterating between the Calculation
and Design sections, until the final design is optimised over the projected pump run
life.
PROSPER MANUAL
34 -59 Chapter 11 - Design Menu
In the main PCP Design screen the design parameters can be entered:
Figure 11-28
PCP Design Screen Input
This is the case of PCP with Sucker Rod. If the PCP is driven by a Downhole Motor,
the data to input are similar to the ones seen in the ESP.
All the parameters are self-explanatory on the basis of the previous sections.
The design of an HSP installation using PROSPER is divided into two phases. One is
where the head and power requirement calculations are made and the second part is
where on basis of the calculations, the equipment is selected.
The following description assumes that inputs of the well details and PVT data have
already been correctly completed and that where applicable, pressure drop
correlations have been matched to field data.
Figure 11-29
PCP Pump Duty
Calculation
Clicking on Calculate the program calculates the pump duty necessary to achieve
the design production rate. PROSPER will display the pump duty solution, as shown
in the figure above.
• PROSPER uses the IPR from System ⏐ Inflow Performance to calculate the
flowing pressure at the sand face and the specified VLP correlation to find the
pump intake pressure for the design production rate.
• The program then works down from the specified top node pressure to arrive
at the required pump discharge pressure.
• The difference between the intake and discharge pressures represents the
required pump head.
• PROSPER compresses the liquid and gas as the pressure increases across
the pump, so the volumetric rate will be less at the discharge than at the pump
inlet.
Emulsions
 If Emulsions have been selected on the Options screen, viscosity
corrections are applied to pump capacity and head. Otherwise, no HSP
viscosity corrections will be applied. If an Emulsion PVT model has been
built in the PVT section, then the emulsion viscosity can be optionally used
in the HSP calculations and elsewhere. As mentioned in the PVT section,
emulsion behaviour in oilfield systems analysis is poorly understood. The
emulsion PVT model provides the means to apply empirical corrections
and should be used with caution.
PROSPER MANUAL
36 -59 Chapter 11 - Design Menu
To do so, select Design: the program will display a pump design screen similar to
that shown below:
Figure 11-30
PCP Design Selection
In the Select drop-down boxes, PROSPER lists the equipment in its database that is
capable of meeting the design requirements.
In the case of motor driven PCP, motor and cable will have to be selected.
As seen for ESP and HSP installations, the PCP design should be checked by
performing sensitivities in System Calculation, in order to verify the design against
the expected change of conditions along the life of the well.
Before performing the design, data concerning the gas lift gas and the coiled tubing
equipment should be entered in the Coiled Tubing Data screen, accessible from the
System menu:
Figure 11-31
Coiled Tubing
Data
Figure 11-32
Coiled Tubing
Design
The input data and the options to enter in this screen are exactly the same as for the
normal Gas Lift Design (design for a User Entered Rate, or for Maximum Production,
etc).
Please refer to section 11.1 for a detailed explanation.
To perform the Design, select Continue. This will access a screen similar to the Gas
Lift Design:
PROSPER MANUAL
38 -59 Chapter 11 - Design Menu
Figure 11-33
Coiled Tubing
Design
In the case of the figure above, select Get Rate to calculate the Gas Lift Performance
Curve and then Design to perform the design.
The program will determine the maximum injection depth, the rate produced and the
gas to inject.
Figure 11-34
Coiled Tubing
Design Plot
Jet Pump data entered in System⎪Jet Pumps is not utilised by the design section
and will be overwritten by the design.
In the main Jet Pump Design screen the design parameters can be entered:
Figure 11-35
HSP Design Screen Input
The design of a Jet Pump installation using PROSPER is divided into two phases.
One is where the head and power requirement calculations are made and the
second part is where on basis of the calculations, the equipment is selected.
The following description assumes that inputs of the well details and PVT data have
already been correctly completed and that where applicable, pressure drop
correlations have been matched to field data.
PROSPER MANUAL
40 -59 Chapter 11 - Design Menu
Figure 11-36
Jet Pump Duty Calculation
Clicking on Calculate the program calculates the pump duty necessary to achieve
the design production rate. PROSPER will display the pump duty solution, as shown
in the figure above.
• PROSPER uses the IPR from System ⏐ Inflow Performance to calculate the
flowing pressure at the sand face and the specified VLP correlation to find the
pump intake pressure for the design production rate.
• The program then works down from the specified top node pressure to arrive
at the required pump discharge pressure.
• The difference between the intake and discharge pressures represents the
required pump head.
• PROSPER compresses the liquid and gas as the pressure increases across
the pump, so the volumetric rate will be less at the discharge than at the pump
inlet.
• According to the Surface Fluid (the Power Fluid) Injection Rate and Injection
Pressure, the program will determine R (ratio between the areas of the nozzle
and of the throat), the diameter of the throat and the diameter of the nozzle
Emulsions
 If Emulsions have been selected on the Options screen, viscosity
corrections are applied to pump capacity and head. Otherwise, no HSP
viscosity corrections will be applied. If an Emulsion PVT model has been
built in the PVT section, then the emulsion viscosity can be optionally used
in the HSP calculations and elsewhere. As mentioned in the PVT section,
emulsion behaviour in oilfield systems analysis is poorly understood. The
emulsion PVT model provides the means to apply empirical corrections
and should be used with caution.
To do so, select Design: the program will display a pump design screen similar to
that shown below:
Figure 11-37
Jet Pump Design
Selection
Select a pump from the database whose Actual performance (in green in the figure
above) is close to the Desired performance.
PROSPER MANUAL
42 -59 Chapter 11 - Design Menu
As seen for ESP, HSP and PCP installations, the Jet Pump design should be
checked by performing sensitivities in System Calculation, in order to verify the
design against the expected change of conditions along the life of the well.
Figure 11-38
Artificial Lift Database -
Options
Figure 11-39
Gas Lift Valve Database
PROSPER MANUAL
44 -59 Chapter 11 - Design Menu
Figure 11-40
Gas Lift Valve Database -
Add Record
 The sample gas lift valve database is provided to allow the User to
run the examples. Before designing for field installation, the User
must first ensure that the database contains current and accurate
valve characteristics.
Figure 11-41
ESP Pumps
Database
The performance curves are provided in the form of coefficients for a polynomial
equation fitted to actual performance data.
Selecting a pump and then Plot, the performance curve of the pump is plotted:
Figure 11-42
ESP Pump
Head
Click Variables to select between Head, Horsepower and Efficiency for plotting.
Figure 11-43
ESP Pumps
Database
PROSPER MANUAL
46 -59 Chapter 11 - Design Menu
Next step is to enter the performance data for head and power as per manufacturer’s
performance curves and fit them to a polynomial. To do so, select Head Coefficients
and HP Coefficients and enter the data:
Figure 11-44
ESP Pumps
Database –
Enter Head
Then Fit to regress and calculate the polynomial coefficients, then Done to go back
to the previous panel. The coefficients have been transferred:
Figure 11-45
ESP Pumps
Database
Figure 11-46
ESP Motors
Database
PROSPER MANUAL
48 -59 Chapter 11 - Design Menu
Figure 11-47
Motor Efficiency
Plot
Figure 11-48
ESP Motors
Database
Enter the data and fit the polynomials by selecting the buttons NamePlate AMPS,
Speed, Efficiency and Power Factor. Use Fit to determine the polynomial
coefficients.
On the right hand side of the screen above (Power Options) enter the different
Power, Voltage and Current the motor is compatible with.
Figure 11-49
ESP Motors
Database
Figure 11-50
ESP Motors
Database
PROSPER MANUAL
50 -59 Chapter 11 - Design Menu
Figure 11-51
HSP Pumps
Database
The performance curves are provided in the form of coefficients for a polynomial
equation fitted to actual performance data.
Figure 11-52
HSP Pump
Performance
Curve
Figure 11-53
HSP Pumps
Database
PROSPER MANUAL
52 -59 Chapter 11 - Design Menu
Figure 11-54
HSP Turbine
Database
The Turbine performance is entered by selecting Add in the Turbine Settings area.
The steps to enter the performance data and fit them to a polynomial are the same
as seen in the ESP section. Refer to that section for details.
Figure 11-55
PCP Pumps
Database
PROSPER MANUAL
54 -59 Chapter 11 - Design Menu
Figure 11-56
HSP Pump
Performance
Curve
Figure 11-57
PCP Pumps
Database
Figure 11-58
PCP Sucker
Rods Database
Figure 11-59
PCP Sucker
Rods
Database
As far as motor and cables are concerned, please refer to the ESP section (11.7.2)
for details.
PROSPER MANUAL
56 -59 Chapter 11 - Design Menu
Figure 11-60
Jet Pumps
Database
Figure 11-61
Jet Pumps
Database
PROSPER MANUAL
58 -59 Chapter 11 - Design Menu
Figure 11-62
FRAMO Pumps
Database
Figure 11-63
FRAMO Pump
Performance
Curve
Figure 11-64
FRAMO Pumps
Database
PROSPER MANUAL
12 Output
The Output menu is used to report, export and plot input data entered into PROSPER
and the results generated by the various calculation options in the program:
• Report
This option generates reports about input data and results
• Export
This option transfers input data and results to different locations (printer,
spreadsheets, screen, etc.)
• Plot
This option generates plots for input data and results
These functions are available also in any of the input/output screens of the program.
2 - 21 Chapter 12 - Output
12.1 Report
The Report option is used to prepare reports and plots from a current analysis. This
section describes how to use the reporting system with the templates provided with
the system and how to customise these templates.
Figure 12-1
Preferences Screen for
Report Directories Setup
In the File tab screen initialise the data relevant to the reporting system. Enter the
“Location Of Report Output Files”. This is the default directory where reports printed
to file are to be placed. Also enter the “Location Of User-Created Reports”. This is
the path to a directory where User-defined report templates are to be stored.
12.1.2 Reports
The reporting interface gives the User complete control over how the reports are
formatted and what information is utilised to make up the report. This is facilitated by
the use of report templates, which can be edited to suit the specific requirements. It
is possible to choose to use the default report templates provided with the system or
to choose to create slightly different versions of these reports. The selected
templates can then be used to generate the actual reports, which can be sent to a
variety of places (printer, file or screen). The report templates are displayed in a
hierarchy and all templates which have been selected (by double-clicking on it) show
an X in the check-box beside the template name.
To access the Reports area, select Output⎪Reports form the menu toolbar.
There are two modes for the editing of report templates: System and User. System
mode does not allow the User to change any template whereas User mode allows
creating new User-defined templates from scratch or based on an already existing
system report template and also allows editing an existing User-defined report
template. Selecting User mode also makes the User Reports section of the template
hierarchy visible. The User Reports hierarchy contains all report templates which
have been tagged as being a derivation of a system report template as well as any
free standing User-defined templates.
Figure 12 -2
PROSPER Reports Main
Window
The reporting main window consists of four main parts: The command segment at
the top of the dialogue containing the buttons, the report selection hierarchy, the
output device selection group and the template type selection group. The output
device group is only used when printing from selected report templates.
OK Print the selected reports to the selected output device and terminate the dialogue
Cancel Terminate the dialogue
Help Bring up the on-line help window
Setup Select a printer
User Switches between System and User edit mode, This shows or hides the User
PROSPER MANUAL
4 - 21 Chapter 12 - Output
Reports section of the report hierarchy and enables or disables the Create and Edit
buttons. If in User mode this button shows the text ‘System’ and vice-versa.
View View a previously saved native format file on-screen. This brings up a file selection
box for choosing the appropriate report and passes this file name to the Report
Executor
Print Print the selected reports to the selected output device
Create Create a new user report (only visible in User edit mode)
Edit Edit an existing user report template or create a new template from a system
template (only visible in User edit mode)
Group Allows the grouping of report templates references and the storing of the group
information in a file for later recall. This allows batch printing of reports for any
analysis
The native (.FR) file format can only be read by the reporting system whereas the
RTF format can be read by many Windows word processing applications. When
printing to file the User will be presented with the following dialogue:
Figure 12 -3
File naming
window
The default directory will be set to the default output directory but this can be altered
using the Select Directory button. This can then be applied to all output files by using
Change All. If it is necessary to change the output directory of one of the files, this
can be achieved by using the Browse button (button that shown on the right side of
the filename box) associated with each report. The filenames can themselves be
edited in the text box, which contains them.
For any given report in the system hierarchy the User can choose to view or print a
report using either the system report template provided or a User-defined report
template based on that system report template (or at least that position in the
Figure 12-4
User-Defined Report
Template Selection
Dialogue
Double clicking on any of the report templates (or selecting and pressing Ok) will
cause it to become the User-defined report template for that hierarchy position for
the current reports session. The default choice is the topmost user defined report
template. It is possible to stop a User-defined report template from being associated
with that hierarchy position by selecting it and then pressing Delete. This does not
actually delete the report template (it can still be seen within the User Reports
section of the hierarchy).
If a report grouping is selected, then a similar dialogue appears and the User can
select the appropriate group file. After selecting a file all the reports referenced in the
group will appear ‘checked’ in the hierarchy and then it is possible to press print for
all of these reports to be sent to the selected output device.
PROSPER MANUAL
6 - 21 Chapter 12 - Output
Figure 12-5
Template
Editor Window
Data fields from PROSPER are added using the F2 key, selecting the data items
required and then pressing Ok when finished. The selected data items will then
appear as fields, one by one, as the left mouse button is clicked. The fields can be
roughly positioned in this way. The User is not limited to one pass at adding data
items to the report template. More items can be added at any time in the same
manner.
Once a field has been added to the report template the User can edit some of the
properties of the text which will be shown in the field and assign a group number to
the field by double clicking the left mouse button on it and the font properties can be
changed by double clicking the right mouse button on it. Other properties, such as
whether the field has a box around it, etc., can be changed through the menu
options, a full description of which are given below.
Figure 12-6
Selection of data items
The template editor commands can be selected by using the menu, toolbar or
keyboard shortcuts. Help can be obtained on any menu item by highlighting the
menu item and then pressing the F1 key or by consulting the index of help topics
under the help menu.
File Menu
This menu contains commands for saving the current report template file and
specifying the report template parameters.
Save:
Use this selection to save the current report template to the current file name. If a file
is not yet specified, the form editor will prompt for a file name. If a file extension is
not provided, the editor automatically appends an .FP extension to the report file. If a
file with the same name already exists on the disk, the form editor will save the
previous file with a backup extension (.RE).
Save As:
This selection is similar to Save File. In addition, it allows saving the report template
to a new file name.
PROSPER MANUAL
8 - 21 Chapter 12 - Output
Report Parameters:
This option allows setting certain report parameters. Firstly, it allows specifying the
name of the report. The margin for the printed page can be set. It is possible to
instruct the report executor to print trial records for adjusting forms such as labels
and invoices and set the default date format for input. The date format that specified
here will be enforced for parameter input during the report execution session, and
any date constant used in expressions.
Report Filter:
This option allows entering a filter criterion for the report. Each data record will be
tested with the expression provided here. A record is selected only if this expression
evaluates to a TRUE value. For example, if the expression was sales->amount>100,
then only the records with the sales amount more than 100 will be selected.
Printer Setup:
This option allows selecting a printer from a list of installed printers and invoking a
printer specific dialogue box for the selected printer. Select the parameters from a
set of printer specific options. These options include page size, page orientation,
resolution, etc. The printer options selected here determine the width and height of
the report.
Exit:
Use this function to exit from the form editor session. If the current file is modified, a
prompt will ask to save the modifications.
Edit Menu:
This menu contains commands to edit the report objects. One or more report objects
must be selected before using this option.
Cut:
Use this option to copy the current item or all the items in the current selection to the
clipboard. The copied items are deleted from the form.
Copy:
Use this option to copy the current item or all the items in the current selection to the
clipboard.
Paste:
Use this option to paste the items from the clipboard to the current form.
Position Text:
Use this option to position the text within the item boundaries. The text can be
justified on the left, right, top, or bottom edges or it can be centred horizontally or
vertically. This option is valid for the label and field type items only.
Item Outlines:
Use this option to specify the item boundaries (left, right, top, and bottom) to draw for
one or more selected items. The colour and width of the boundary lines can be
specified too.
Item Background:
Use this option to set the background colour or pattern for one or more selected
items.
Centre Horizontally:
This option is used to centre horizontally one or more selected items. When more
than one item is selected, the form editor first centres the selection rectangle and
then moves the selected items such that the position of the selected items relative to
the selection rectangle does not change.
Delete Item:
Use this option to delete one or more currently selected items. If the current section
is being deleted, the program asks for confirmation before the deletion. All items
within the section are also deleted.
Fonts:
Use this function to change the font and colour for the text for one or more selected
objects. This option is valid for the field and label type objects only.
When selecting this option, the form editor shows the font and colour selection
dialogue box. The current font and colours are pre-selected in the dialogue box. Use
this dialogue box to specify the selections.
Snap to Grid:
This option allows turning on or off the invisible grid on the form. When the grid is
turned on and an item is moved, it automatically aligns to the closest grid location.
This option also allows setting the grid width.
Report Size:
The following options shrink or elongate the report in the horizontal or vertical
direction by the amount equal to the width or the height of the selection rectangle.
Expand Horizontally
Use this option to create horizontal space by moving items horizontally. For example,
consider three items, A, B, and C placed horizontally. If a new item between the
items A and B is to be inserted, it is possible to use this function to create the desired
space between these two items and place the new item in the newly created space.
To move the items B and C toward right, create a selection rectangle after the item A
and select this option. The width of the selection rectangle specifies the movement of
the items B and C toward right (noted that the selection rectangle does not need to
include all items to be moved). All items toward the right of the selection rectangle
and with the vertical placement between the vertical spaces spanned by the
selection rectangle are moved.
Expand Vertically
Use this option to create additional vertical space by moving the items downward.
For example, consider three items, A, B, and C placed vertically. If a new item
between items A and B is to be inserted, it is possible to use this function to create
the desired space between these two items and place the new item in the newly
created space. To move items B and C downward, create a selection rectangle
PROSPER MANUAL
10 - 21 Chapter 12 - Output
below the item A and select this option. The height of the selection rectangle
specifies the downward movement of items B and C (noted that the selection
rectangle does not need to include all items to be moved). All items below the
selection rectangle are moved.
This option also expands (vertically) the current section by the height of the selection
rectangle.
Compress Horizontally
Use this option to delete extra horizontal space by moving items horizontally. For
example, consider three items, A, B, and C placed horizontally. The User can use
this function to bring items B and C closer to the item A. To move items B and C
toward left, create a selection rectangle after the item A and select this option. The
width of the selection rectangle specifies the movement of items B and C toward left
(noted that the selection rectangle does not need to include all items to be moved).
All items toward the right of the selection rectangle and with the vertical placement
between the vertical spaces spanned by the selection rectangle are moved.
Compress Vertically
Use this option to delete vertical space by moving the items upward. For example,
consider three items, A, B, and C placed vertically. It is possible to use this function
to bring items B and C closer to the item A. To move items B and C upward, create a
selection rectangle below the item A and select this option. The height of the
selection rectangle specifies the upward movement of items B and C (noted that the
selection rectangle does not need to include all items to be moved). All items below
the selection rectangle are moved.
This option also shrinks (vertically) the current section by the height of the selection
rectangle.
Field Menu:
This menu contains options to insert, modify, delete and maintain fields.
Calculation Field: This option is used to paste a calculation field to the report
template. This option will prompt for the name of the field, and the field expression.
The field expression can contain any number of valid operators, functions, system
fields, dialogue fields, and data fields. The field type is determined by the result of
the execution of the field.
After entering the field expression, the form editor displays a positioning rectangle.
Use the mouse to position the field rectangle and click any mouse button. The
current field attributes can be changed using the Edit Current Field Option.
System Field: This option is used to paste a system field to the report template. This
option will display a list of system fields (date, time, page, etc.) to choose from.
When selecting a field, the form editor displays a positioning rectangle. Use the
mouse to position the field rectangle and click any mouse button. The current field
attributes can be changed using the Edit Current Field Option.
Dialogue Field: This option is used to paste a dialogue field to the report template.
A dialogue field must have been created using the Edit Dialogue Field Table before
using this option. The dialogue fields are used to prompt the User for data during the
report execution session.
The option will display a list of dialogue fields to choose from. When selecting a field,
the form editor displays a positioning rectangle. Use the mouse to position the field
rectangle and click any mouse button. The current field attributes can be changed
using the Edit Current Field Option.
Edit Current Field: This option is used to edit the field attributes for the current field.
This option is available only when a 'field' type object is selected.
Edit Field Expression: This option is used to edit the field expression for the current
calculation field. This option is available only when a 'calculation field' type object is
selected (see Insert Calculation Field). The option shows the existing calculation
expression and allows making any modifications.
Modify: This option is used to modify the User prompt, width and prompt order of a
dialogue field. The prompt order determines the order at which the dialogue fields
are presented to the User for data input.
Delete: This option is used to delete a dialogue field from the dialogue field table.
The User cannot delete a dialogue field that is being currently used in the report.
Section Menu:
This menu contains commands to insert, edit and delete report sections.
New: This option is used to create a new section. A section is identified by the
section banner and the separation line at the bottom of a section. There are three
basic types of sections. A header section displays the data that remain constant or
changes only when a sort field changes. The detail section displays the transaction
record fields. A footer section is used to display totals and summary information.
ReportEase allows up to 9 header and footer sections. A higher numbered header
section is allowed only when all the lower numbered headers are already selected.
Similarly, a footer section is allowed only when the corresponding header section is
already selected.
PROSPER MANUAL
12 - 21 Chapter 12 - Output
Edit Current: This option is used to modify the properties of the currently selected
section. For the 'detail' section, the User can specify the number of records to print
across the page. This option can be used to print multiple address labels across the
page.
Sort Field: This option is used to specify a sort field for a header section. A sort field
is used to sort the data records.
Break Field: This option is used to specify a break field for a header section. The
break field is used to determine a sort break. Typically, the break field would be the
same as the sort field. However the break field can be specified differently from the
sort field. A calculation expression can also be specified for a break field.
Filter: This option is used to enter a filter criterion to print a section. Normally, every
section included in the report template is printed in its appropriate sequence.
However, if the User wishes to print a section depending upon a condition, he can
enter this condition expression using this option. The expression must evaluate to a
logical value (TRUE or FALSE). During the report execution, the section will be
printed only if the expression evaluates to a TRUE value.
Line: This menu contains commands to create and edit a line object:
Create a Line: Use this option to draw a line. When selecting this option, the form
editor displays a positioning rectangle. Use the mouse to position the rectangle and
click any mouse key. The line will be drawn within the position rectangle. The line
size can be changed using the sizing tabs.
Edit Current Line: Use this option to edit the angle, colour, and thickness of a 'line' type
object.
Label: This menu contains commands to create and edit a label object:
Create a Label: Use this option to create a new label. When selecting this option,
the form editor displays a positioning rectangle. Use the mouse to position the
rectangle and click any mouse key. The 'label' object will be created within the
positioning rectangle. By default, the form editor inserts the text 'label' in the label
item. The label text can be edited in the editing window.
Edit Current Label: A label text can be edited by simply selecting the desired label
item and clicking on the edit window.
As the User inserts or deletes the text, the length of the label text changes. Normally,
the form editor will automatically adjust the item box boundaries to completely
enclose the new text. However, this automatic size adjustment ceases if the User
manually resizes the item boundary by pulling on the sizing tab. This feature can be
used to enclose the text in an item box larger than the default size.
When selecting this option, the form editor creates a positioning rectangle equal to
the dimensions of the picture. Use the mouse to position the picture rectangle and
click any mouse key. The picture will be placed within the position rectangle. The
picture size can be changed using the sizing tabs.
Arrange:
This menu contains commands to align size and space a set of selected objects:
Alignment At:
Even Spacing:
Horizontally:
Use this option to place the selected items horizontally at an equal distance from
each other. The inter-item distance is equal to the distance between the first two
leftmost items.
Vertically:
PROSPER MANUAL
14 - 21 Chapter 12 - Output
Use this option to place the selected items vertically at an equal distance from each
other. The inter-item distance is equal to the distance between the first two topmost
items.
Even Sizing:
Width:
Use this option to change the width of the selected items to the width of the topmost
item.
Height:
Use this option to change the height of the selected items to the width of the leftmost
item.
Figure 12-7
File Selector
Figure 12-8
Report
Executor
PROSPER MANUAL
16 - 21 Chapter 12 - Output
12.2 Export
An export can be made either directly from the individual sections of the program, or
from the Output | Export menu option. This section describes how to customise
exports.
Figure 12-9
Report Setup Dialogue
After entering the choices, Click Done to return to the main export dialogue box. The
User must then select a destination for the export data. Clicking Print initiates
generation of the data and sends it to the selected destination. Setup accesses a
screen for selecting fonts, margins etc. as in the Plot menu (Section 12.1). The font
selections made for export data are independent of the plotting fonts.
• Clipboard - Clicking Print after selecting this option copies the exported data
onto the Windows clipboard. From the Clipboard, the User can view, edit and
paste the data directly into another Windows application. e.g. a word
processing program.
• Screen - Clicking Print after selecting this option allows viewing the
exported data on the screen. Scroll through the data using the scrolling
thumbs or arrows. When finished viewing, click OK to return to the main
menu.
Once a .PRN file has been saved, further copies of the exported data can be made
using a word processor from outside PROSPER. To ensure that printed exports are
correctly formatted, only non-Proportional fonts can be selected for export data. The
fonts on the export setup screen are independent of those selected on the plot setup
screen.
Click the Layout button on the calculation results screen and select the variables to
display from the layout screen:
Figure 12-10
Calculation Layout
Show All and Hide All buttons are used to make changes to the entire list of
variables. Individual variables can be selected or de-selected by clicking them
PROSPER MANUAL
18 - 21 Chapter 12 - Output
directly. When clicking OK, only the selected variables will be displayed on the
calculation screen.
In addition to the calculation results screens, Layout also controls the variables
displayed in Output ⎮ Export (to file, clipboard, and printer).
12.3 Plot
A plot can be made either directly from individual parts of the program, or from the
Output | Plot menu option. This section describes how to customise plots for both the
screen and hard copy. From the Plot Output main Window select the plot to view by
highlighting it in the list of available plots and then press the Plot button or simply
double-clicking on the appropriate plot
Figure 12-11
Plot Output Setup
Zooming
Plots can be zoomed simply by placing the mouse pointer (which changes to a pair
of cross hairs over the active plot area) at the corner of the region to enlarge, and
then dragging until the area of interest is enclosed by the zoom box. Release the
mouse button and the outlined area will be zoomed to fill the entire plot area.
Scales
PROSPER normally picks appropriate scales to display the data. Use Scales to enter
custom upper and lower limits for both X- and Y- scales. To display round numbers
on the intermediate grid lines, ensure that the span of the upper and lower plot limits
fits evenly with the number of plot blocks set in the Options menu.
Replot
Re-plots the graph using the original scales. Use this option to un-zoom a plot.
Output
Selects the output options menu. Plots can be output to the Windows clipboard, a
Windows metafile or a hard copy device in colour, grey scale or monochrome
formats. Plots can then be pasted directly from the clipboard into other Windows
applications such as a word processor. Windows metafiles can be saved and read
by a variety of applications. If hard copy is selected, the following hard copy options
screen will appear:
Figure 12-12
Hard Copy Options
Select the desired plot options and click Print to output the plot. Depending on the
actual hard copy device connected, the User may need to experiment with font styles
and sizes. Note that some fonts cannot be rotated, and are unsuitable as a Vertical
font. If Y-axis labels are being plotted horizontally, try a different font selection.
Return to the plot menu by clicking OK.
Colours
PROSPER MANUAL
20 - 21 Chapter 12 - Output
This option enables to customise the colour of any item on the plot. Note that laser
printers and monochrome monitors will often produce better results if colour plotting
is disabled. A sample colour customising screen is shown below:
Figure 12-13
Change Colours
Options
The Options button enables to customise the overall appearance of the plot screen
and select font type and size etc. A sample options screen is shown below:
Figure 12-14
Plot Options
Some plots include a results box on the screen. If the default position of the box
interferes with the plot, it can be moved by holding down the Shift key and using the
mouse to drag it to another location. The fonts selected on the Plot options screen
apply only to plots. The export data fonts are set up on a separate screen.
Variables
Use this button to select variables for plotting. The variables available change
according to the type of calculations that have been completed and the particular plot
type that has been selected. Where applicable, extended plot variables can be
selected.
Test Data
Clicking Test data displays a screen in which the User can enter up to 10 measured
data pairs. Once the test data has been entered, it can be displayed together with
the calculated data when the plot is re-drawn. If the current .OUT file is subsequently
saved, the test data will also be saved and will appear on subsequent plots.
Help
Accesses the on-line Help system. See Section 14 for more details of the Help
system.
PROSPER MANUAL
13 Units
This chapter describes the system of units. The built in flexibility of the units
system enables the User to select any variable and define the unit of measurement
to be used. This feature allows to modify the units system so that it corresponds to
data reports supplied by a service company or customise the units system to suit
the User’s own personal preferences.
PROSPER always works internally in Field units. To facilitate data entry and output
display in any units system, PROSPER accepts data in the specified Input units and
converts it to Oilfield units for calculation. The results (in Field units) are converted
back to the specified Output unit set if necessary. By making selections from the
different categories, it is possible to work in the preferred units and save the results
in the units required by company policy.
Figure 13-1
PROSPER Units System
The changes made to the units system are retained in the program memory and
apply to all files opened during the current processing session. The program allows
to create a custom units system.
Figure 13-2
Units Summary
The Units Summary screen is contains the list of parameters and their unit’s
options:
Unit’s selection
Select the units for the input and output of the variables
Validation
Used to set up the error checking limits for each selected input variable.
Click on the Details buttons to the right of each variable name in order to view the
details of each particular variable.
Figure 13-3
Units Summary
3-5
• Canadian S.I.
• German S.I.
• French S.I.
• Latin S.I.
Customised unit systems can be created and saved under new names. Different
units can be selected for both input and output.
Figure 13-4
Units system
To save changes, click Save. A prompt will be displayed to enter a name for the
new Units System. This new system can now be recalled and applied to any file.
Custom unit sets can be erased by clicking the Delete button, then selecting the
unwanted units system. The ability to have separate input and output unit systems
allows the User to work with familiar units and to create reports or export data in
any required unit system. PROSPER calculates them internally in Oilfield Units. To
validate unit conversion factors, click the button located to the right of the particular
variable and the multiplier and shift used for unit conversion will be displayed.
Clicking Report ⏐ Print will create a summary report of conversion factors in use.
If some particular units have been modified during the course of a PROSPER
session, the changes will be written into the .SIN file when the input data are saved.
Irrespective of the current units system settings, recalling a previously saved .SIN
file will cause PROSPER to revert to the units saved in the recalled .SIN file. To
permanently impose a new set of units on the recalled file, open a custom units file
(or use one of the internal unit sets) and then save the .SIN file. The new unit’s
settings will be used whenever the .SIN file is loaded.
Find the required variable by scrolling through the list, and then enter required
changes in the low and high validation limit boxes. Enter the custom validation
limits in the units currently in use. To permanently attach the new validation limits
to a custom units system, click Save before leaving the validation screen by clicking
OK.
5-5
Figure 13-5
Units Detailed
Input and Output units can be selected from this screen. Validation limits can be
entered for the selected units. The Options panel enables to set the number of
decimal places to display for each unit type.
In order to run wizard examples follow first of all select Wizard from the main menu
toolbar:
Figure 14-1
Wizard main window
Then select the desired Wizard and click on Run to run it.
All that the User has to do is to follow the instructions that time to time are
displayed and complete the input screens with the required data.
To modify an existing wizard select Edit. This will access the wizard script window:
2-3 Chapter 14 - Wizard
Figure 14-2
Script window
To create a new wizard select instead New. This will display an empty script
window.
The script consists of a series of VB commands using OpenServer strings to set the
values of the input parameters, perform calculations, and retrieve results.
Please refer to the OpenServer User Guides for further details about the basic
OpenServer functions.
On the top part of the script window there is the Commands list window, which
provides immediate access to all the OpenServer variables. This window allows
selecting the desired variable and getting a copy of it, which can be pasted in the
script window below.
DoCmd(“PROSPER.MENU.<tag>”)
If <tag> is for example Options, the command will display the main PROSPER
options.
DoCmd(“PROSPER.PLOT.<number>”)
If <number> is 1, for example, the command will display the IPR plot.
The example scripts can also be used by experienced Users as templates to build
their own scripts.
Recommendation
Petroleum Experts recommends to set up the models according to the worked
examples shown in the Appendix A. This will allow the User to have a better
understanding of the physics that is behind the software and the importance of the
matching process.
To use the PROSPER on-line help system, the help file must be located in the same
directory as the program. If the User is new to Windows, information on using the
Help system can be made available when selecting the Help option in the
PROSPER main menu and choosing 'Using Help'. This will display a help screen
from which the information required can be selected from a list of topics.
The Help facility has function buttons located at the top of the windows, which can
be used to navigate within the help system. If a particular feature is not currently
available, the button associated with that function is dimmed. Information on
specific help topics may lead to other related topics. Some words in the Help
windows are marked with a solid underline and appear in colour (green) if the User
uses a colour screen.
These words are called jump terms and can be used to move around Help more
quickly. When clicking a jump term, Help will move directly to the topic associated
with the underlined word(s).
Figure 15-1
Help About PROSPER
If the User need to contact Petroleum Experts about a problem with the program, please
have the version number and creation date shown on this screen available should it
be required.
The design assumes that the reservoir pressure will drop to 4000 psig and that the
water cut will rise to 80%.
This example will guide you through opening the existing OILWELL.OUT file,
changing the calculation options and reservoir conditions, performing the design and
finally saving the file under a new name.
Figure A1.1
Setting gas lift options
Variable Value
Gas lift gas gravity 0.8
H2S 0
CO2 0
N2 0
GLR Injected 0
For performing a gas lift design, the gas lift method and GLR injected can be ignored
at this stage.
• Click Done and leave the gas injection depth set to zero (Figure A.2)
Figure A1.2
Gas lift input
PROSPER MANUAL
4 - 172 Appendix A - Worked Examples
Figure A1.3
Gas lift design input
Figure A1.4
Gas lift design - calculated
rate
Figure A1.5
Gas lift Well Performance
Curve
The program has found that around 1460 STB/d of oil could be produced with 5.0
MMscf/d of lift gas injected at the optimum depth of injection. Click on Finish to exit
the plot.
Figure A1.6
Gas lift design gradient
plot
Note down the ‘Actual Gas Injection rate’, ‘Actual Injection pressure’ and ‘Actual
Liquid rate’ from the graph. Having determined the number of valves and their
depths, the next task is to calculate the valve test rack setting pressures as follows:
• Click Results to display valve depths and pressures
PROSPER MANUAL
6 - 172 Appendix A - Worked Examples
• Click Calculate to display the opening and closing pressures together with
the test rack setting pressures.
Figure A1.7
Gas lift design valve
details
The number of valves required to pass the design lift gas rate is shown at the left of
the screen. Click on the scroll arrows to see the selected port sizes, gas injection
rates, etc. Click Report to generate a hard-copy of the gas lift design then click
Main to return to the main screen.
• Click Transfer ⏐ From Gaslift Design ⏐ OK. The design valve depths will
appear as per Figure A1.8
Figure A1.8
System Gas lift data valve
depths
PROSPER now has the valve depths and surface injection pressure, but since GLR
Injected is still set to zero, no gas is being injected in the calculations. The rate of lift
gas injection will be set using a sensitivity variable.
Figure A1.9
System calculation
PROSPER MANUAL
8 - 172 Appendix A - Worked Examples
(Enter the ‘Actual Injection rate that you have noted down
earlier)
For variable 2
− Select Water Cut
Enter 80%, 90%
For variable 3
− Select Reservoir Pressure
Enter 4000, 3500.
Figure A1.10
Sensitivity variables
Click through the solutions and check the solution for 90% water cut and 3500 psi
reservoir pressure. This design is still capable of injection at the deepest (orifice
valve) and the production rate is around 400 BOPD. The sensitivity calculations
show that the design is suitable for the expected future producing conditions.
To set up this problem, open GASLIFT.OUT and make the following changes:
Options Menu
Predict Pressure and Temperature on land
Temperature Model Rough Approximation
Click System | Equipment (tubing etc) | Surface Equipment, input the following
data:
NOTE: Change the Pipe Length units to miles by right clicking on the pipe length
units
PROSPER MANUAL
10 - 172 Appendix A - Worked Examples
Figure A2.1:
Surface equipment Input
Click Done | Summary | Draw Surface and check the equipment data has been
correctly entered (Figure A2.2).
Figure A2.2
Surface equipment
schematic
Gaslift Data
Return to the main menu and click System ⏐ Gaslift Data. Select Fixed Depth of
Injection as the gas lift method, click Continue and enter an injection depth of 7535
ft. The injection gas gravity (S.G) should remain at 0.8.
Use the Generate feature to enter the calculation rates (Figure A2.3). Click
Generate and enter 100 and 15,000 STB/day for the minimum and maximum rates.
Enter 20 for number of rates and use Geometric spacing to propagate the table.
Click Done and PROSPER will fill in the rates table.
Figure A2.3
User selected rate values
For variable 1
− Select Gaslift gas injection rate
Enter 1,2,3,4,5,6
For variable 2
PROSPER MANUAL
12 - 172 Appendix A - Worked Examples
• The long flow line will slow the calculations, so please be patient.
Once the calculation has stopped, click Sensitivity ⏐ Variables and select Oil Rate.
Click Done to display the following plot:
Figure A2.4
System Sensitivity
Note that the production rate is relatively insensitive to the volume of lift gas injection
and that the optimum injection rate has decreased from the optimum found in
Example 1 to around 4 MMscf/day. Click Finish and return to the Calculation ⏐
System menu.
Figure A2.5
Well Pressure and
Temperature Profiles
Note the change of slope of the pressure gradient at the depth of injection. The fluid
temperature approaches that of the surroundings about halfway along its length.
The pressure gradient in the flowline rapidly increases over its last third. This is due
to high flow velocities as ever increasing volumes of gas breaks out of solution.
Increased frictional pressure losses in the flowline account for the decrease in
optimum lift gas injection rate observed in this example.
This example shows how PROSPER's Enthalpy Balance temperature model can be
used to predict the wellhead flowing temperature (WHFT) of a high pressure / high
temperature oil well.
The objective of this example is to determine the WHFT profile versus time.
PROSPER MANUAL
14 - 172 Appendix A - Worked Examples
Next, enter the PVT data. Only basic PVT data from the exploration well is available.
Click PVT ⏐ Input data and enter the following:
• Solution GOR 1500 scf/STB
• Oil Gravity 45 API
• Gas Gravity 0.6 specific gravity
• Water Salinity 100000 ppm
• Mole Percent H2S 0
• Mole Percent CO2 0
• Mole Percent N2 0
 The validity of these correlations for this type of fluid behaviour has
been assumed for the purpose of this example only.
Enter the well equipment details. Click System ⏐ Equipment ⏐ All ⏐ Edit and type in
the following deviation survey data:
Bottom MD (ft) TVD (ft)
0 0
14000 14000
Next, enter the surface environment (Offshore) data:
• Air temperature 50 degrees F
• Humidity 60 percent
• Mean sea level WRT origin 100 ft
• Sea bed WRT origin 400 ft
• Air velocity 4 ft/sec
• Sea velocity 3 ft/sec
The user can enter a sea temperature gradient in the enthalpy balance model. We
are going to assume a linear change of temperature from the sea level (50 degree F)
to seabed (42 degree F). Hence, enter the following in the Sea Temperature
Gradient Table:
 The above data describes a drilling rig with a rotary table 100 ft
above sea level located in 300 ft of water.
Define the drilling and completion by entering the drilling and completion data as
shown on the table below. This describes a well with all casing strings hung off at
the sea bed and the well is tied back to surface using a 30" riser.
Figure A3.1
Drilling and Completion
Input
Here, we are assuming that the annulus is filled with mud. The users can also
customise their own completion liquid or gas type if the appropriate fluid data is
available.
PROSPER MANUAL
16 - 172 Appendix A - Worked Examples
Define the lithology by entering the data shown on the screen below:
Figure A3.2
Litho logy Input
• Xmas tree 0 ft
• tubing type mild steel tubing
• measured depth 13600 ft
• Inside diameter 4.778"
• Outside diameter 5.5"
• Roughness 0.0006
Click | Summary to check the data input before returning to the main screen.
Define the reservoir inflow model by clicking System ⏐ Inflow performance. Select PI
Entry IPR and enter the following:
• Reservoir pressure 6100 psig
• Reservoir temperature 290 degrees F
• Water cut 0%
• Click on the | Input Data button and enter a PI of 8 BOPD/psi
Click | Calculate and an AOF around 28660 STB/day will be calculated. Click Main
and return to the Main menu.
 In order to predict the FWHT and FWHP for a given rate, the Unconstrained
System option should be used.
• In order to see the effects of rate and time on WHFP, make the following
calculations.
• Generate a temperature gradient plot using the Unconstrained Gradient
option.
To do this, click Unconstrained System from the main menu and make the following
selections:
Once the calculation is finished click | Plot. Select Tubing head temperature as the
sensitivity variable and click | Done to display the following plot.
PROSPER MANUAL
18 - 172 Appendix A - Worked Examples
Figure A3.3:
Temperature Sensitivity
Plot
From the plot it can be seen that at 10000 STB/d the wellhead flowing temperature
(WHFT) has reached around 146 degrees F after 5 days of flowing so the design test
sequence is OK.
• It also shows that the well could be flowed at up to 15000 STB/d for 100 days
and the WHFT would not reach the limiting 200 degrees F.
• The calculated WHFT for 100 days production shows that high temperature
well head equipment will be required for long term production rates above
10000 stb/d.
Click | Continue, then select Time since production started as the sensitivity variable
and enter 1,5 and 1000 days. Leave the other sensitivity variables blank. Click |
Continue ⏐ Calculate to start the calculations. Once the calculation has finished click
Plot and the following temperature gradient plot will be displayed:
Figure A3.4
Temperature Gradients
To plot the heat transfer coefficient along the well, click | Variables ⏐ Extended and
select Heat Transfer Coefficient. Click | Done to display the following plot:
Figure A3.5
Heat Transfer Coefficient
Plot
PROSPER MANUAL
20 - 172 Appendix A - Worked Examples
Figure A4.1
ESP - Down hole
Equipment
• Set the tubing O.D. to 4.5 inches and the casing I.D. to 6.184 inches.
• Return to the main menu.
• Lower the reservoir pressure by clicking on System ⏐ Inflow Performance
and setting the reservoir pressure to 4500 psig.
• Change the water cut (WCT) to 80% and total GOR to 300 scf/stb. Leave the
other parameters at their original values.
• Return to the main menu.
• Import the motor characteristics and the cables data in the same manner.
• Note that motor files are arranged by manufacturer.
• Append the individual motor files if you want to work with motors from more
than one supplier.
For designing a new ESP installation, do not enter any ESP System data - go
directly to Design | Electrical Submersible Pump | Design
PROSPER MANUAL
22 - 172 Appendix A - Worked Examples
Figure A4.2
ESP - Design Duty
Click | Done and | Design and PROSPER will display the ESP Design screen.
Figure A4.3
ESP - Pump Selection
For this example, select the REDA GN5600 pump from the list of suitable pumps.
The pump needs 115 stages and will require 215 HP at the design rate.
From the list of suitable motors, select a 240 HP REDA 540 Series 91 - Standard
motor with 2210 Volt windings.
Select a #1 Copper cable. (A smaller cable would pass the current - you can select
any cable large enough for the service).
Click Plot to display the design operating point superimposed on the pump
performance curve:
Figure A4.4
GN5600 Operating Point
PROSPER MANUAL
24 - 172 Appendix A - Worked Examples
The pump is being run a little close to its maximum output, perhaps the next biggest
pump would be a better choice, especially if the pump is expected to handle a
greater lift duty due to e.g. increasing water cut during the pump's run life.
Return to the design screen and select a GN7000 pump. The same 240 HP motor is
suitable for this pump also. Select a #1 Copper cable and plot the results:
Figure A4.5
GN7000 Operating Point
This pump is operating close to its optimum efficiency and has some excess head
capacity.
Once the calculations have been completed, click Solution Details, select the
design case variables of 80% water cut, 4500 psi reservoir pressure and 60 Hz
operating frequency by clicking on the variable arrows. The calculated liquid off-take
rate is close to 6000 STB/day. When the calculated rate is slightly higher than the
design rate, this is to the number of stages having being rounded up to the nearest
integer.
Now, increase the water cut to 90% - the off-take rate drops to around 5480
STB/day. Plot the sensitivities by clicking Pump Plot from the pump solution screen
as follows. From the plot following conclusions can be made
• With 90% water cut, can the design off-take of 6000 BFPD be achieved by
increasing the operating frequency. Select 70 Hz. The production rate
increases to around 7080 BFPD. By interpolation, this pump should be
capable of lifting 6000 BFPD at an operating frequency of around 63.5 Hz.
Figure A4.6
ESP Sensitivities
To find the required motor horsepower, return to the sensitivity screen and click on |
Combinations. Input the data shown on the following screen to set up 2 scenarios:
PROSPER MANUAL
26 - 172 Appendix A - Worked Examples
Figure A4.7
ESP Combinations
Calculate the sensitivities then click | Solution Details to inspect the results for each
Case.
For a 90% water cut, the GN7000 pump can lift 6035 STB/day, provided that the
motor can supply the additional horsepower at 63.5 Hz. The horsepower
requirement increases from 225 to 272 HP (+21%), so a larger motor than the
original selection would be required for this service. Before finalising the design,
more extensive sensitivities should be run and the manufacturer's specifications
must be checked to ensure that the specified pump can withstand the additional
shaft torque and that the housing pressure rating is not exceeded.
• Click Options and select Lift method – Hydraulic Drive Down hole
Pump
• Make sure that the Artificial lift type is set to – Commingle Annular
Supply
• Lower the GOR (and the well's ability to naturally flow) by clicking PVT
⏐ Input data and lowering the GOR from 820 to 300 scf/STB
• Enter the Power fluid (water) salinity as 10000 ppm.
• Revert to unmatched PVT correlations by clicking Correlations ⏐ Reset
All. Return to the main menu by clicking | Done twice.
• Edit the System ⏐ Equipment (Tubing) description to include the
annulus dimensions as per the following input screen:
Figure A5.1
HSP Down hole equipment
• Set the tubing O.D. to 4.5 inches and the casing I.D. to 6.184 inches.
• Return to the main menu.
• Lower the reservoir pressure by clicking on | System ⏐ Inflow performance
and setting the reservoir pressure to 4500 psi.
• Change the water cut and Total GOR to 80% and 300 scf/stb respectively.
• Leave the other parameters at their original values and return to the main
menu.
For designing a new HSP installation, do not enter any HSP System data - go
directly to | Design | Hydraulic Pump | Design and enter the following design
specifications:
PROSPER MANUAL
28 - 172 Appendix A - Worked Examples
Figure A5.2
HSP Design duty
Click | Done and | Design and PROSPER will display the HSP Design screen.
Figure A5.3
HSP - Pump Selection
For this example, select the Weir TP115AH(4250-12325) rpm from the list of suitable
pumps. The pump needs 69 stages and will require 284 HP at the design rate.
From the list of suitable turbines, select a weir T55-B.
Click Plot to display the design operating point superimposed on the pump
performance curve:
Figure A5.4
Weir TP115-AH
PROSPER MANUAL
30 - 172 Appendix A - Worked Examples
Figure A5.5
HSP – System Calculation
• Click | System and enter a top node pressure of 50 psi and a water cut of
80%
• Check that Dukler Flannigan has been selected for surface equipment and
Petroleum Experts 2 is selected for the vertical lift correlation
• Select User Selected rates and Generate 10 rates between 10 and 10,000
BFPD.
• Click | Continue and enter the following sensitivity variables:
For variable 1
− Select Water cut
Enter 80, 95
For variable 2
− Reservoir Pressure
Enter 4000, 4500
For variable 3
− Select pump speed
Enter 5000-6000-7000
Click | Continue | Calculate to perform the sensitivity calculations.
Once the calculations have been completed, click | Solution Details, select the
design case variables of 80% water cut, 4500 psi reservoir pressure and 6000 rpm
pump speed by clicking on the variable arrows. The calculated liquid off-take rate is
close to 6100 STB/day.
Plot the sensitivities by clicking | Pump Plot from the pump solution screen as
follows:
Figure A5.6
HSP – Sensitivity
To find the required motor horsepower, return to the sensitivity screen and click on |
Combinations. Input the data shown on the following screen to set up 2 scenarios:
Figure A5.7
HSP Combination
Calculate the sensitivities then click | Solution Details to inspect the results for each
Case.
PROSPER MANUAL
32 - 172 Appendix A - Worked Examples
For 90% water cut, reservoir pressure of 4000 psig and pump speed of 7000
rpm, the HSP pump can lift about 7000 STB/day, provided that the turbine can
supply the additional power. Before finalising the design, more extensive
sensitivities should be run and the manufacturer's specifications must be
checked to ensure that the specified HSP will work under different scenarios.
The Jet pump design section calculates the pump duty required to achieve a given
design rate. According to the input data such as power fluid information the program
calculates the ratio between the nozzle and throat area and calculates the nozzle
diameter and throat diameter. A pump is then selected from the user-defined
database of jet pump characteristics
• Design
• Jet Pump Database
This section allows the input and maintenance of manufacturer's jet pump
characteristics. The user can either modify existing data or add new jet pump data to
the database via the PROSPER main tool bar Design | Database option.
Set the correct tubing Flow Type, for this case Annular Flow is required to coincide
with the tubing injection – annular production jet pump selection (Figure A6.1).
Figure A6.1
Defining the PROSPER
options menu
PROSPER MANUAL
34 - 172 Appendix A - Worked Examples
Figure A6.2
PVT section defining
water as the power fluid
In this example the power fluid is 30 API oil with 20cp viscosity at standard
conditions.
• Select Other Fluid in the drop list box and enter the density of the power fluid
in the input box (Figure A6.3).
Figure A6.3
Defining oil as the power
fluid
GOR: 0 scf/stb
Oil Gravity: 30 API (power fluid density)
Gas gravity: 0.7 (It is not used since GOR=0)
Water salinity: 100,000 ppm (Not used)
• Match data input screen. In this section enter the viscosity of the power fluid
at the measured temperature. (Up to 5 tables for different temperatures can
be input).
Figure A6.4
Power fluid match data
• Perform a regression to match all the viscosity correlations with the match
data.
• Review and select the viscosity correlation that needs the least corrections
factors (Multiplier and shift). For this particular case Beal et.al. required the
least correction 0.98 and -0.21.
PROSPER MANUAL
36 - 172 Appendix A - Worked Examples
Figure A6.6
Generate power fluid
properties
• Enter the range of temperature and pressure data then click Generate to
calculate the table values (Figure A6.7)
Figure A6.7
Power fluid
properties section
• Click Plot to visualize the power fluid viscosities vs. pressure at different
temperatures (Figure A6.8)
Figure A6.8
Power fluid properties
Plot showing power fluid
viscosity vs. pressure
at different temperatures
• Once the viscosities tables for the power fluid have been generated, the
regression parameters must be reset. To do this, select Regression
|Parameters | Reset all (Figure A6.9)
Figure A6.9
Regression parameters
• In the PVT input parameter section the properties of the oil must be entered
as per the following table. Complete the PVT matching as for previous
examples
PROSPER MANUAL
38 - 172 Appendix A - Worked Examples
Figure A6.10
Oil Input parameters
• Click Match Data and enter the PVT match data shown in the following table
Oil
Pressure GOR Oil FVF viscosity
psig scf/stb rb/stb cp
820 100 1.08 11.1
A6.11
PVT match data
• Perform the regression analysis and select the correlations that need the least
correction. In this particular case Standing for bubble point, solution GOR and
formation volume factor and Petrosky et al for the oil viscosity.
For the geothermal gradient a surface temperature of 60F has been used.
In this section the user has to define the measured pump depth, the maximum OD of
the pump, the liquid rate for the design, the water cut, total GOR, well head pressure.
The power fluid surface injection rate and injection pressure must also be entered
(Figure A6.12).
PROSPER MANUAL
40 - 172 Appendix A - Worked Examples
Figure A6.12
Jet pump design input
screen
Click Calculate | Calculate. The program will calculate the pump duty required
based on the inflow performance relationship, the pressure losses in the tubing and
the entered well head pressure. Based on the power fluid injection rate and
pressure PROSPER will calculate ‘R’ (ratio between nozzle and throat area), the
diameter of the throat and the diameter of the nozzle.
Figure A6.13
Calculation results from the
jet pump design
The next step is to choose a jet pump that best-fits the calculated data, select Done |
Design (Figure A6.14)
The column labelled Desired (Figure A6.14) shows the calculated jet pump design
results. The selected jet pump calculated values from the defined user database
(selected from the drop list box) must closely match the theoretical calculated
results.
Figure A6.14
Jet pump design
After the jet pump design has been completed a system analysis calculation can be
performed (Figure A6.15).
Click Continue | Continue | Calculate and to plot the system analysis result click
Plot
From the plot main menu bar select Variable and then: VLP curve, Pump discharge
pressure and Pump intake pressure for the plotted variables (Figure A6.15).
PROSPER MANUAL
42 - 172 Appendix A - Worked Examples
Figure A6.15
System analysis plot
To set up this problem, firstly clear the existing calculations by clicking File ⏐ New.
Recall the system data from the convergence pressure example by clicking File ⏐
Open ⏐ Analysis (.OUT) and double clicking on the filename of the previously saved
convergence pressure example (CONDEX.OUT).
Options Menu
Click | Done, then PVT Input to display the PVT input screen:
Figure A7.1
EOS PVT Input
• The EOS input data is intended to be loaded from an external PVT simulation
program file using the Import button.
 In case you want to use volume shift, you can enter the volume shift in the
form of S parameter and click on “ Use Vol. Shift” in the input screen
shown in Figure A-7.3.
To ensure that all the data has been correctly entered, and to check the type of fluid
described by the pseudo components entered.
PROSPER MANUAL
44 - 172 Appendix A - Worked Examples
You can do so by pressing the Phase Envelope button and hitting plot. The phase
envelope calculation screen shows the fluid type as shown follows:
Figure A7.2
EOS Calculated Fluid Type
Figure A7.3
EOS Calculated Phase
Envelope
Once the input data has been specified, the user has the option of selecting
Calculation type. The options are:
o Calculated From EOS Model
In this option PROSPER will calculate the fluid properties from
the EOS data entered, using flash process, whenever it needs it.
o Interpolated From Generated Tables
In this case the user generates the tables from the EOS in
PROSPER and then PROSPER during calculations, uses these
tables for property evaluation. This makes the calculations
faster.
o Interpolated From Imported Tables.
In case, the user has elected to import all the properties as a
*.pvx file, it will use the imported tables for property evaluation.
THIS IS FOR CASES WHEN THE USER DOES NOT WANT
TO USE THE EOS OF PROSPER.
For this example, we selected the first option.
In order to use the entered EOS to generate tables, enter a range of pressures and
temperatures.
Click on Generate and | Calculate again check the EOS PVT values.
The saturation pressure at 300 degrees F should be 4596 psig.
 Click Properties, and PROSPER will display the equivalent Black Oil
PVT properties for the reservoir fluid (Figure A7.4)
Figure A7.4
EOS Black Oil
properties
PROSPER MANUAL
46 - 172 Appendix A - Worked Examples
Figure A7.5
EOS Correlation
Comparison
 The Duns and Ros Modified bottom hole pressure for the correlation
comparison case is:
• Approx. 6972 psig, Predicted by the EOS method.
Figure A7.6
EOS System Solution
• How the data input for black oil condensate PVT works
• Comparison of the solution results from the other PVT methods.
To set up this problem, firstly clear the existing calculations by clicking File ⏐ New.
Recall the condensate example by clicking File ⏐ Open ⏐ and double clicking on the
filename of the previously saved condensate example (CONDEX.OUT).
PROSPER MANUAL
48 - 172 Appendix A - Worked Examples
Click | Done, then commence entry of the PVT data by clicking | PVT ⏐ Input data.
Figure A7.7
Black Oil Condensate PVT
Input
Note that the above properties have been derived from an EOS calculation.
Figure A7.8
Black Oil Condensate
Gradient Comparison
 The Duns and Ros Modified bottom hole pressure for the correlation
comparison case is:
• Approx. 7010 psig, Predicted by the EOS method.
• Approx. 7020 psig, Predicted by the Condensate Black Oil
Method.
This is in close agreement with that obtained from compositional modelling - even
though the liquid dropout values have not been matched in the Black Oil model.
For condensate wells, the black oil PVT method can be recommended for:
• Accuracy of mixture density calculations
• Simplicity
• Speed of calculation
• Accuracy of pressure calculations
Proceed to the calculation screen and click Calculate. The solution rates are shown
on the following plot:
PROSPER MANUAL
50 - 172 Appendix A - Worked Examples
Figure A7.9
Black Oil Condensate
System Solution
The above condensate example has shown how to set up the PROSPER calculations
for the different condensate PVT methods. It also illustrates that the Black Oil PVT
method is capable of accurate well pressure prediction and is more computationally
efficient than more complex PVT methods.
Select the Lee et al gas viscosity correlation, then click | Done to return to the main
menu.
Bottom MD TVD
(ft) (ft)
0 0
10000 10000
• Enter NO surface equipment.
• Enter the tubing string details as follows under down hole section:
PROSPER MANUAL
52 - 172 Appendix A - Worked Examples
Bottom MD ID Roughness
(ft) (ins) (ins)
Xmas tree 0
Tubing 500 3.958 0.0006
SSSV 3
Tubing 9800 3.958 0.0006
Casing 10000 8.681 0.0006
Click on the | Input data button on the top right hand corner of the window. In the
reservoir model data entry screen, enter the following:
• Reservoir permeability 300 mD
• Reservoir thickness 100 ft
• Drainage area 640 acres
• Dietz shape factor 31.6
• Well bore radius 0.51 ft
• Perforation interval 50 ft
• Reservoir Porosity 0.2 fraction
• Time 100 days
• Connate water saturation 0.2 fraction
• Non-Darcy coefficient Calculated
• Permeability entered Total permeability
Then click on the | Mech./ Geom. skin tab and enter the following:
• Perforation diameter 0.5 ins
• Shots per foot 6 1/ft
• Perforation length 12 ins
• Damaged zone thickness 12 ins
• Damaged zone permeability 150 mD
• Crushed zone thickness 0.2 ins
• Crushed zone permeability 75 mD
• Shot phasing 60 degrees
• Vertical permeability 30 mD
Click on the | Gravel pack tab and define the gravel pack parameters as follows:
• Gravel pack perm 40000 mD
• Gravel pack length 1.3 ins
• Perforation efficiency 1
Click | Calculate and the program will calculate an AOF of 116 MMscf/day display the
IPR on a plot. Click | Main and return to the main menu.
• perforation density
• gravel pack permeability
Select Dukler Flannigan as the surface equipment correlation and Duns and Ros
Modified for the VLP correlation.
Leave the rate method set to Automatic linear and click OK.
Set the top node pressure to 1200 psig and the water/gas ratio to 4 bbl/ MMscf.
Click OK again to display the sensitivity variables screen.
PROSPER MANUAL
54 - 172 Appendix A - Worked Examples
• From the calculation screen select Sensitivity (Figure A8.1) to plot the sensitivity
data select Variables and select dP Completion as the Y-axis variable, Shots per
foot for the X-axis and gravel pack permeability for the parameter variable.
• Plot the results for 1200 psi top node pressure. A graph similar to Figure A8.2 will
be displayed:
Figure A8.1
Sensitivity calculation
Figure A8.2
Gravel Pack Sensitivity
 Note that when the sand face pressure drops below the dew point,
liquid dropout occurs. The Petroleum Experts IPR reduces the relative
permeability to gas when liquids are being produced.
• In this producing area, field trials and lab tests have established that gravel pack
failure should not occur provided that the total pressure drop across the
completion is less than 400 psi (for purposes of illustration only)
• By inspection, the above sensitivity plot shows that 12 shots per foot perforations
and a gravel pack permeability of 40 Darcies will be required to ensure that the
well will not have to be choked back unnecessarily.
Return to the calculation screen and click on | Solution Detail, then select the
solution for
From the solution summary, we know that the pressure drop across the completion
is almost all due to the gravel pack. In excess of 85 MMscf/day can be safely
produced with this completion design.
Make a sensitivity plot with dP completion on the Y-axis, First node pressure on the
X-axis and Gravel Pack Permeability as the parameter variable.
Figure A8.3
Gravel Pack Sensitivity
Assume that the gravel pack has 40000 mD permeability. Zoom on curve 1 (8 SPF)
near where it is around 400 psi dP completion and read off the First Node Pressure.
You should get around 2500 psi.
To calculate the gas production rate for 400 psi dP completion, use the
Combinations option on the Select variables screen. Enter the following for
combination Case 1:
PROSPER MANUAL
56 - 172 Appendix A - Worked Examples
Leave the rate field blank. Click | Continue and then | Calculate. PROSPER will
calculate the system solution. Click | Solution details and check that the well can
flow at 63 MMscf/day with a THP of 2500 and a dP across the completion of 410 psi.
Note that the allowable rate at 8 shots per foot is more than 20 MMscf/day lower
than the allowable with 12 shots per foot.
Figure A8.4
IPR liquid sensitivity
Note the effect of Separator GOR on both VLP and IPR pressures. Note that
increasing liquid production increases the completion dP.
Click | Main to return to the main menu. Save the file as GRAVEL.OUT if desired.
The example shows how to set up the input data for a Horizontal well - Friction dP
IPR model. It is based on the OILWELL example file.
• Note that the reservoir permeability must be increased from 50 in the base
example to 500 millidarcies in order to see the friction pressures drop along the
well bore.
PROSPER MANUAL
58 - 172 Appendix A - Worked Examples
• This well has alternating perforated and blank sections, which are identical.
• We will enter the data for two only two zones, one blank one producing.
• Then we will use the editing features to copy identical data to the other zones.
• For the first zone enter the following:
Zone Type Perforated
Skin Method By Hand
Gravel Pack This will be automatically skipped
Zone Length 100 feet
Zone Permeability 500 mD
Flowing Radius 0.15 feet
Zone Roughness 0.001 inches
Figure A9.1
Horizontal well - dP Friction
IPR input
• These calculations also calculate the pressure loss along the well bore and allow
the user to display the pressure profiles.
 All the IPR input must have been defined before performing the
coning calculations.
Click | Calculate, and the breakthrough time and critical rate estimates will be
displayed.
PROSPER MANUAL
60 - 172 Appendix A - Worked Examples
Figure A9.2
Horizontal well – Coning
Calculations Screen
To calculate and display the horizontal well pressure profile and production
contribution from each zone for the entered rate, click Plot. PROSPER will display a
graph similar to the following:
Figure A9.3
Horizontal well - dP Friction
Well pressure profile
The source of inflow can be plotted by clicking Variables and selecting Rate per Unit
Length. As shown in the following plot, more production enters at the heel of the well
than the toe:
Figure A9.4
Horizontal well - Rate per
Unit Length
Once the Horizontal well dP friction IPR, has been calculated, System calculations
can be carried out as normal. If you need to calculate a wide range of sensitivity
cases, the dP friction model could be used to prepare a table of test data points to be
entered in one of the fast-calculating multi-rate IPR models.
PROSPER MANUAL
62 - 172 Appendix A - Worked Examples
Click on | Input data, and the layer data entry screen will be displayed.
Figure A10.1
Multi-Layer data Input
The following description shows how to set up a well model with two layers
separated by 100 feet.
Click the Layer PVT data button and enter the following:
Layer formation GOR 820 scf/STB
Layer oil gravity 34 API
Layer gas gravity 0.7 s.g.
Layer water cut 0 percent
Click | Done.
Click the | Layer PVT data button and enter the following:
PROSPER MANUAL
64 - 172 Appendix A - Worked Examples
Click | Done | Calculate and PROSPER will calculate the composite IPR at the intake
node.
The IPR plot shows the layer contributions and the combined IPR as in the following
example:
Figure A10.2
Multi-layer dP pressure loss
Click Results to see the layer pressures and production contributions. Crossflow into
a layer appears as a negative production value as in the following example:
Figure A10.3
Multi-layer dP pressure
loss Results Screen
A11.1 Introduction
Multi-lateral wells are being recognized as a potential option when developing new
oil and gas fields. Often, these types of wells are drilled to save the costs of drilling,
this may occur if drilling individual targets is sub - economic or the platform is
constrained. Sometimes they are not beneficial.
Co-mingling the flow from two targets (branches) may result in higher outflow
performance in the event that a larger tubing size can be specified; this leads to a
lower frictional pressure drop than in obtained in each individual well. But
sometimes, co-mingling fluids may result in greater frictional pressure drop than
expected, so poorer outflow performance than two individual wells will result, it
means that well productivity depends on interference effects in both reservoir and
well bore. Cross flow might represent another potential problem if targets for several
branches are chosen without any proper study.
This is where modelling work can add most of the value: multilateral wells are
different to single wells because they have a variable structure. Both the number of
branches and the way that they are connected is variable, and also the interaction
between each branch should be taken in to account. Hence, a flexible way to model
must be used to understand the behaviour of this type of wells.
PROSPER MANUAL
66 - 172 Appendix A - Worked Examples
This example can be found in the samples directory under the name of
MULTILAT1.OUT file. However, following the steps indicated below, you would be
able to generate the model from scratch.
Figure A11.1
Well Sketch that displays
the drilling program
Figure A11.2
System Summary
Inflow type: Multilateral
1. Begin by starting the program. From the PROSPER main menu, select File ⏐
New to reinitialise the program input and output files. The ‘New’ menu item
under File is only available if a file has already been loaded. If there is no
file loaded skip this step and go to next step.
Then click Done to exit this screen. This completes the system setup and reinitialises
the program and governs the inputs that the user will be required to enter.
PROSPER MANUAL
68 - 172 Appendix A - Worked Examples
Figure A11.3
PVT Input Screen
Click Done on the above screen to exit. This marks the end of defining the PVT
behaviour
Measured True
Depth Vertical
(feet) Depth
(feet)
0 0
9700 8800
Figure A11.4
Equipment
Input Screen
PROSPER MANUAL
70 - 172 Appendix A - Worked Examples
• Click Done to advance to the geothermal data entry screen. Once on the screen,
enter the following temperature profile:
Measured Formation
Depth Temperature
(feet) (deg F)
0 60
9700 200
Enter an overall heat transfer coefficient of 8 Btu/hr/ft2/F. Click | Done to exit the
screen.
• This takes you to the default heat capacity screen. Let it remain as it is. Click on
Done to go to the next screen.
Figure A11.5
Geothermal Gradient
When satisfied that the well equipment is correct, click Main to return to the
PROSPER main
Top layer:
Reservoir Pressure 3900 psig
Reservoir Temperature 218 degrees F
Oil Gravity 34 API
Gas Gravity 0.67 sp. Gravity
Water Salinity 120000 ppm
Water Cut 56 percent
Total GOR 720 scf/STB
Horizontal Permeability 10 md
Formation Thickness 150 feet
Drainage Area 150 acres
Depth of Reservoir Top 8770 feet
Vertical Permeability 10 md
Bottom Layer:
Reservoir Pressure 3200 psig
Reservoir Temperature 210 degrees F
Oil Gravity 34 API
Gas Gravity 0.67 sp. gravity
Water Salinity 120000 ppm
Water Cut 56 percent
Total GOR 720 scf/STB
Horizontal Permeability 10 md
Formation Thickness 100 feet
Drainage Area 175 acres
Depth of Reservoir Top 8950 feet
Vertical Permeability 10 md
According to the drilling program, the tie point will be considered at measured depth
of 9700 ft m (8800 ft vertical depth). The deviation survey of the original well and the
side track are indicated below.
Completion 1
PROSPER MANUAL
72 - 172 Appendix A - Worked Examples
Side track
The user interface consists of a framework window that contains several child
windows, as well as the menu and toolbar from which commands are issued. The
child windows include the network windows that contain the system network drawing,
the navigator window that can assist in the viewing of large networks and up to three
visualisation windows, which can show the multilateral network drawn to scale from
three orthogonal points of view.
Figure A11.6
PROSPER
Multilateral
Network
To start drawing your multilateral system considering the well sketch, start selecting
the tie point, junction, completion (1) and Completion (side track) as well as the top
and bottom reservoir.
Figure A11.7
Adding the
completion and
reservoirs
Once you have the basic drawing according to your well sketch and drilling program,
then you can use the button (add link) to finish with this part.
To enter the required data for each section all you have to do is to double click on
each icon. It is recommended to start from the tie point to the reservoir according to
the well sketch.
 The tie point defined, is the point above which everything will be a part
of wellbore sketch and thus the pressure loss etc in that section will be a
part of VLP. Everything below the tie point is a part of the IPR and
pressure losses in this section will be evaluated in IPR calculations.
Figure A11.8
Linking the tie point
with the joint,
completion and
reservoir.
PROSPER MANUAL
74 - 172 Appendix A - Worked Examples
If you double click on the tie point enter the measured depth and true vertical depth
as indicated previously. The tie point is the node where the IPR is solved and is
located at the top of the system (in vertical depth). Hence, the tie-point can only be a
start point.
The Junction point will be a branching node. It can only have one link into it (from a
tie-point or a completion).
Once these two points have been defined, then, Deviation Survey and Down hole
Equipment and Perforation Details can be entered. In the case of the deviation
survey there is an additional azimuth entry.
When the user put the information respectively for each branch the calculations can
be performed.
Tie point:
Measured depth of 9700 ft m, 8800 ft vertical depth
Junction 1:
The tubing information entry is a two-step process. First we define the model for
pressure loss calculations. We will also be using the following model:
The screens for entering the tubing flow model are as shown below:
Figure A11.9
Tubing Model Selection
screen
Once the model is entered, if on the above screen you Press the Input Data button, it
takes you to the next screen where you enter the deviation survey of this path of the
completion including the azimuth.
Figure A11.10
Tubing deviation survey
Input Screen
Once the deviation survey is entered, we will need to enter the equipment
information like the tubing diameters etc, in the next screen. This screen is accessed
by clicking on the TAB called EQUIPMENT in the bottom left hand corner of the
screen shown above.
PROSPER MANUAL
76 - 172 Appendix A - Worked Examples
Figure A11.11
Tubing description Input
Screen
Completion 1
Select the information required such as vertical flow model, well bore radius, and
Dietz shape factor.
For this example the Petroleum Experts 2 correlation will be used, a well bore radius of
0.43 ft and Dietz shape factor of 30 will be considered.
Figure A11.12
Completion 1,
Calculation options
screen.
When your press the option Input Data, you will see that there are three tabbed
dialogs in this data input screen, which allow the entry of a deviation survey,
equipment descriptions and completion information. The first two dialogs contain
tables very similar to the ones encountered by selecting System | Equipment from
the PROSPER main menu, and then the ‘Deviation Survey’ and ‘Down hole
Equipment’ push buttons. In the case of the deviation survey there is an additional
azimuth entry.
Figure A11.13
Completion 1
Deviation Survey
Screen
Once you enter the deviation survey, select the equipment and select tubing
according to the deviation survey, the tubing in the completion 1 has been run down
to 13900 ft and has a diameter of 3 in.
Figure A11.14
Completion 1
Equipment
PROSPER MANUAL
78 - 172 Appendix A - Worked Examples
According to the drilling program, this completion has been perforated between
11855 ft and 13900 ft.
Figure A11.15
Completion 1
Perforation details
Finally double click on the reservoir and enter the PVT data as well as the
information required to calculate the inflow performance based on the Darcy Model.
The information has been provided at the beginning of this example.
Figure A11.16
Bottom Reservoir
PVT Data
Press Input to continue and enter the information for the reservoir.
Figure A11.17
Bottom Reservoir
Inflow data based
on
Darcy Reservoir
Model
Once finished with the first completion, you can go on entering the correspondent
information for the multilateral section. So just double click on the side track
completion.
Select the information required such as vertical flow model, well bore radius, and
Dietz shape factor.
In this case the Petroleum Experts 2 correlation will be used, a well bore radius of 0.43 ft
and Dietz shape factor of 30 will be considered.
Figure A11.18
Sidetrack
Input Data
PROSPER MANUAL
80 - 172 Appendix A - Worked Examples
Figure A11.19
Sidetrack
Deviation Survey
Once you enter the deviation survey, select the equipment and select tubing,
according to the deviation survey, the tubing in the side track has been run down to
10700 ft and has a diameter of 3 in.
Figure A11.20
Sidetrack
Equipment
According to the drilling program, this completion has been perforated for 700 ft,
from 10000 ft to 10700 ft.
Figure A11.21
Side Track
Perforation
details
Finally double click on the reservoir and enter the PVT data, as well as the
information required to calculate the inflow performance based on the Darcy Model.
Figure A11.22
Top Layer
PVT Data
Press Input Data to continue and enter the information for the reservoir.
PROSPER MANUAL
82 - 172 Appendix A - Worked Examples
Figure A11.23
Top Layer
Inflow data based
on
Darcy Reservoir
Model
Once entered the information for the two branches (completion 1 and side track),
from PROSPER – Multilateral Network Menu, select the option Visualise all:
Figure A11.24
Visualise All
The Calculate screen gives the option of calculating one IPR point or a curve.
Also, calculations can be switched between infinite and finite conductivity modes of
calculation. In the latter case (finite) the pressure drop in the tubing is taken into
account
Figure A11.25
Calculate
The Finite conductivity solution takes in account the pressure drop and
interference, whilst the Infinite conductivity considers equal pressure and constant
production rate at all times. The flow distribution is used then to calculate the
pressure around the source.
The Details button is used to display pressure and rate-related parameters with
respect to the measured and vertical tubing depths of each branch. If a curve has
been calculated, these details pertain to the last point in the curve.
PROSPER MANUAL
84 - 172 Appendix A - Worked Examples
Figure A11.26
Details
To visualise the results press Plot, and from the menu toolbar select Variables.
Figure A11.27
Plot results
True Vertical Depth
vs. Rate per unit
length and
pressure
Figure A11.28
Results
Considering Infinite
conductivity
PROSPER MANUAL
86 - 172 Appendix A - Worked Examples
Figure A11.29
Results
Considering
Finite
Conductivity
References:
50 ft
150 ft 100 ft 100 ft 100 ft 100 ft
100 ft ID=6.969”
ID=4.778”
PROSPER MANUAL
88 - 172 Appendix A - Worked Examples
Figure A12.1
System Summary
 The solution GOR is the gas dissolved in the oil at the original bubble
point pressure. If the well also produces free gas, it should not be
included here.
Figure A12.2
PVT input screen
Click Done to return to main. This completes the PVT input section.
PROSPER MANUAL
90 - 172 Appendix A - Worked Examples
Measured True
Depth Vertical
(feet) Depth
(feet)
0 0
10000 10000
Figure A12.3
Deviation survey
The down hole equipment screen will then appear. Note that the Xmas tree elevation
has been taken to be the same as the deviation survey reference.
The well has 4.778" ID tubing down to 10,000 ft. Click on the Type cells to get a
combo box of options and enter the following down hole equipment:
Descriptive information about the downhole equipment can be written in the label
fields as reminder.
Figure A12.4
Down hole equipment
Click Done to advance to the flowing temperature profile screen and enter the
following:
Measured Fluid
Depth Temperature
(feet) (deg F)
0 60
10000 250
Overall heat transfer coefficient: 8 BTU/hr/ft2/F
PROSPER MANUAL
92 - 172 Appendix A - Worked Examples
Figure A12.5
Geothermal gradient
Click | Done.
The Average Heat Capacities screen will then appear. Click Done to accept the
default value.
This completes the equipment input for the well.
Click Summary and check that the equipment input data is consistent. As a further
check click Draw Down hole. When satisfied that the well equipment is correct, click
Main to return to the PROSPER main screen (status screen).
A multilateral network construction window will appear, which looks like the figure
display below:
Figure A12.6
Multilateral network
construction window
From the diagram of the completion, in terms of the flow connection, the completion
can be simplified as below
Annular flow,
Tubing flow Fluid flowing in
from reservoir
As can be seen, the flow network is consisted of two sections, the first section
consists of annular flow with fluid flowing in from the reservoir and the second
section consists of tubing flow.
Two completions can be set up, with one connected to the other, representing the
flowing sections mentioned in the previous paragraph.
The user can introduce the tie point, junctions, completions and reservoir and their
connection into the network from the tool bar in the multilateral network window.
Figure A11.7
Tool bar from the
multilateral network window
PROSPER MANUAL
94 - 172 Appendix A - Worked Examples
For this particular smart well completion, a flow network can be constructed as
shown below
Figure A12.8
Construction of the flow
network
The tie point represents the end of the downhole equipment that is specified in the |
System | Equipment section. The item labelled T1 represents the 5 ½” tubing that is
shown in the smart well completion structure. The item (a completion) labelled
Tubing represents the section where tubing flow occurs. Junction1 connects the 5 ½”
tubing and the tubing flow section. The item (a completion) labelled Annular
represents the section where annular flow occurs. The reservoir is connected to the
Annular. Fluid is flowing from the reservoir to the Annular, then to the Tubing via
Junction2, then to the tie point via Junction1 and T1.
After constructing the general network diagrammatically, the next step will be to
describe the network items. We start from the tie point by double-clicking on the item
on the network window. A network item data entry screen for the tie point will be
displayed.
Figure A12.9
Tie point data entry
Since we have a vertical well and the TVD for the tie point is at 10,000 ft, the
measured depth of the tie point is at 10,000 ft as well. Hence, enter the following
data for the tie point position:
Next, we are going to specify the data for item T1. To bring up the data entry screen
for item T1, simply click on the item on the equipment screen on the right. The
following screen will be seen:
Figure A12.10:
Tubing T1 data entry
screen
PROSPER MANUAL
96 - 172 Appendix A - Worked Examples
This only specifies the general model of tubing T1. More information is needed, e.g.
the deviation, the tubing length and diameter, etc. These data can be entered in the
Input Data section by clicking on the Input Data button on the top right hand corner
of the screen.
Figure A12.11
Tubing T1 data entry
screen
We first describe the deviation. Since the smart well completion is perfectly
horizontal, the true vertical depth remains at 10000 ft. This section of the tubing is 50
ft long. Hence, the measured depth should be 10050 ft. We assume that this section
of the well is extending in the direction of positive x, hence, the azimuth is 0 degree.
In short, enter the following data in this screen:
Next, we proceed on to specify the tubing length, diameter, etc. These data can be
entered in the Equipment section, by clicking the tab labelled ‘Equipment’.
Figure A12.12
Tubing T1 data entry
screen
This section of the tubing has an internal diameter of 4.778” for its whole length of 50
ft. Hence, input the following data:
This completes the definition for tubing T1. Next, we proceed on to Junction1. The
position of Junction1 is totally dependent on the specification of the items upstream.
It’s position, i.e. measured and true vertical depths are calculated. To see the
calculated position, simply click on Junction1 on the equipment window on the right.
Figure A12.13
Junction1 data entry
screen
PROSPER MANUAL
98 - 172 Appendix A - Worked Examples
Next we proceed on to specify the completion labelled tubing. We first specify the
general model of the completion:
Figure A12.14
Completion data entry
screen – Tubing flow
To enter the deviation, the tubing length and diameter, etc. Click on the Input Data
button on the top right hand corner of the screen.
Figure A12.15
Completion data entry
screen – Tubing flow
We first describe the deviation. Since the smart well completion is perfectly
horizontal, the true vertical depth remains at 10000 ft. This section of the completion
is 650 ft long. Hence, the measured depth should be 10700 ft. Again, we assume
that the well is extending in the direction of positive x, hence, the azimuth is 0
degree. In short, enter the following data in this screen:
Next, we proceed on to specify the tubing length, diameter, etc. These data can be
entered in the Equipment section, by clicking the tab labelled ‘Equipment’.
Figure A12.16
Completion data entry
screen – Tubing flow
PROSPER MANUAL
100 - 172 Appendix A - Worked Examples
This section of the tubing has an internal diameter of 2.041” for its whole length of
650 ft. Hence, input the following data:
Figure A12.17
Completion data entry
screen – Tubing flow
Since this section of the completion is meant for tubing flow only, i.e. no production
or inflow from reservoir, we can specify this section of the completion by introducing
a very high skin, say 5000, so that the production is negligible. The corresponding
true vertical depths of the perforation interval will be calculated automatically. In
short, enter the following:
Figure A12.18
Junction2 data entry
screen
• The flow type of this completion is annular flow instead of tubing flow
• The description of the deviation of this completion is different because it is no
longer extending towards the positive x direction. Contrary, it extends towards
the negative x direction. Hence, we have to adjust the value of the azimuth to
model this situation
• The perforation of this completion is divided into three segments
Figure A12.19
Completion data entry
screen – Annular flow
PROSPER MANUAL
102 - 172 Appendix A - Worked Examples
To enter the deviation, the tubing length and diameter, etc. Click on the Input Data
button on the top right hand corner of the screen.
Figure A12.20
Completion data entry
screen – Annular flow
We first describe the deviation. Since the smart well completion is perfectly
horizontal, the true vertical depth remains at 10000 ft. This section of the completion
is 500 ft long. Hence, the measured depth should be 11200 ft. But this time the well
is extending in the negative x direction, hence, the azimuth is 180 degree for this
completion. In short, enter the following data in this screen:
Next, we proceed on to specify the tubing length, diameter, etc. These data can be
entered in the Equipment section, by clicking the tab labelled ‘Equipment’.
Figure A12.21
Completion data entry
screen – Annular flow
This section of the casing has a internal diameter of 6.969”, tubing has an internal
diameter of 2.041” and an external diameter of 2 3/8”. Hence, input the following
data:
Figure A12.22
Completion data entry
screen – Annular flow
PROSPER MANUAL
104 - 172 Appendix A - Worked Examples
Since this section of the completion has three sections of perforation, the following
data is entered. The local skin is assumed to be zero.
This completes the definition for completion ‘Annular’. Next, we proceed on to define
the reservoir by clicking on the reservoir item on the equipment window on the right.
Figure A12.23
Reservoir data entry
screen
Enter the following for the reservoir model type and reservoir fluid properties:
Next, we need to define the reservoir parameter. This can be done by clicking on the
‘Input Data’ button on the top right hand corner of the screen.
Figure A12.24
Reservoir data entry
screen
• Reservoir Permeability: 20 mD
• Reservoir Thickness: 50 feet
• Drainage Area: 500 acres
• Reservoir Top Depth: 9975 feet
• Vertical Permeability: 5 mD
This basically completes the model specification. Click | Done to leave the data entry
screen.
To visualise the model constructed, from the PROSPER multilateral network window,
we click on | Visualise | Front to see the front view of the completion. The windows
can be arranged nicely by clicking on | Window | Tile.
Figure A12.25
Network view and Front
view of the model
PROSPER MANUAL
106 - 172 Appendix A - Worked Examples
Figure A12.26
Multilateral calculation
screen
The Multilateral calculation screen will appear. Set the calculation option to One
Point. Since we are going to specify the tie point pressure, we set the Pressure or
Rate Option to ‘Rate from Pwf’. To see the production rate at 3000 psig tie point
pressure, enter a value of 3000 psig in the Pressure entry box in the One point
results section.
Then click on | Calculate. PROSPER will now do the calculation iteratively to find a
solution. This will take some time dependent on the speed of the computer.
Once the calculation is completed, the user can see the solution results by clicking
the button | Details under the One point results section.
Figure A12.27
Multilateral calculation -
branch and layer results
The overall production for a tie point pressure of 3000 psig will be around 9950
STB/day. The user can view the results for each branch, by selecting the branch of
interest in the Select Branch combo box. The results can be plotted by clicking on
the | Plot button. To see the pressure drop along the branches, in the plot window,
click in | Variables. Then select all three branches, set the Y-axis as measured depth
and the X-axis as Pressure.
Figure A12.28
Pressure along the
branches
PROSPER MANUAL
108 - 172 Appendix A - Worked Examples
It can be seen that the pressure drop along the Annulus is negligible if compared to
the pressure drop along the tubing. If the casing size is fixed, then there is a
possibility of increased production by increasing the tubing size. By increasing the
tubing size, the pressure drop in the tubing might be reduced significantly, and hence
the production increased.
Due to the restriction of the tubing used in the well bore (5 ½” OD, 4.778” ID), the
maximum tubing size that can be used in the completion is 3 ½” OD tubing. Below is
a summary of the tubing sizes that can be used.
In order to see the effect of different tubing sizes, we have to change the model.
Double click on the Tubing completion and change the tubing ID to 2.922”:
Figure A12.29
Changing the
tubing ID
We also need to change the tubing ID and OD in the annular section. Click on the
completion ‘Annular’ in the equipment list on the right and change the tubing ID to
2.922” and OD to 3.5”.
Figure A12.30
Changing the tubing ID
and OD
PROSPER MANUAL
110 - 172 Appendix A - Worked Examples
Figure A12.31
Calculating a IPR curve
Under the Curve Calculation section, set the Minimum Pressure as 10 psig and the
Number of Points as 10. Click on | Calculate to start the IPR calculation. The
calculation will take some time, dependent on the speed of the computer. Click on |
Plot to see the IPR after the calculation has finished.
Figure A12.32
IPR curve for the smart
well completion
System Calculation
Once the inflow performance has been generated, it can be used to determine the
production rate given a wellhead pressure.
Exit the PROSPER Multilateral Network window by clicking on | Finish | Done. In the
PROSPER main screen, click on | Calculation | System (IPR + VLP).
PROSPER MANUAL
112 - 172 Appendix A - Worked Examples
Figure A12.33
System calculation
We are going to determine the production rate for a wellhead pressure of 200 psig.
Set the following data in the System calculation screen:
Click on | Continue. We are not going to do any sensitivity studies. However, note
that in System Calculation for multilateral option, only the sensitivity variables that
are affecting the lift curve can be chosen. Those sensitivity variables that are
affecting both the IPR and VLP cannot be chosen since multilateral IPR model is
much more complex than the ordinary single branch IPR.
Click on | Continue | Calculate to start the calculation. Click on | Plot to see the
solution. The calculation shows that a production of around 13000 STB/day can be
achieved.
Figure A12.34
System calculation
PROSPER MANUAL
114 - 172 Appendix A - Worked Examples
This example can be found in the samples directory under the name of
MULTILAT3.OUT file. However following the steps indicated below, you would be
able to generate the model from scratch.
Figure A13.1
Sketch of the TIE POINT @ 13000
Completion
Reservoir 1 Top
@ 13103 feet
Reservo
Reservoir 2 Top
@ 15206 feet
Reservo
Tubing ID=4.67”
Tubing OD=5.5”
Casing ID=8.5”
• The well is a straight hole completion with injection catering to two different
reservoirs, separated from each other by approximately 100 feet.
• The flow paths are as drawn by the arrows.
• The flow comes through the 5.5” tubing and at 13103 feet TVD it splits into two
parts one going through the top choke into the annulus and subsequently into the
top reservoir.
• The rest of the tubing flow continues downwards, and goes through the bottom
choke from tubing to annulus and to bottom reservoir.
 The tie point defined at 13000 feet of TVD is the point above which
everything will be a part of well bore sketch and thus the pressure
loss etc in that section will be a part of VLP. Everything below the tie
point is a part of the IPR and pressure losses in this section will be
evaluated in IPR calculations.
Then click Done to exit this screen. This completes the system setup and reinitialises
the program and governs the inputs that the user will be required to enter.
PROSPER MANUAL
116 - 172 Appendix A - Worked Examples
Figure A13.2
PVT Input Screen
For this case we are using Lee et.al as the correlation to predict gas
viscosities. We also are not matching to any laboratory data.
Click Done on the above screen to exit. This marks the end of defining the PVT
behaviour
Measured True
Depth Vertical
(feet) Depth
(feet)
0 0
13000 13000
PROSPER MANUAL
118 - 172 Appendix A - Worked Examples
Figure A13.3
Down hole Equipment
Input Data Screen
• The well has 4.67" ID tubing down to 13000 ft, which is the tie point.
• Click on the Type cells to get a combo box of options and enter the
following down hole equipment:
Type Measured IDs Roughness
Depth
(feet) (ins) (ins)
Xmas tree 0
Tubing 13000 4.67 0.0006
• Click Done to advance to the geothermal data entry screen. Once on the
screen, enter the following temperature profile:
Measured Formation
Depth Temperature
(feet) (deg F)
0 60
13000 270
Enter an overall heat transfer coefficient of 3 Btu/hr/ft2/F. Click | Done to exit
the screen.
• This takes you to the default heat capacity screen. Let it remain as it is.
Click on Done to go to the next screen.
• Now enter the injected fluid temperature as 135 F in the next screen.
Figure A13.4
Equipment Input Screen
Click Summary and check that the equipment input data is consistent. As a further
check click Draw Down hole.
Figure A13.5
Well Bore Sketch
When satisfied that the well equipment is correct, click Main to return to the
PROSPER main.
PROSPER MANUAL
120 - 172 Appendix A - Worked Examples
Or
• Double-click on the ‘IPR DATA’ area
When entering the IPR section, the first entry screen that appears asks for the
injected fluid PVT data. Supply the following data:
Figure A13.7
Multi-lateral Network
screen
Based on the sketch in Figure A.13.1, the flow path will have the following equipment
in the well:
Figure A13.8
Down hole network
System Drawing
The next task is to define the various components as drawn in the above screen. We
will start from the tie point and work our way towards the reservoirs.
PROSPER MANUAL
122 - 172 Appendix A - Worked Examples
Figure A13.9
Tie point Input data
screen
 Please note that on the right hand side of the input screen there is a
window that has all the components of the drawing listed in it. You
can proceed with data by clicking the next piece of equipment on this
window. This window will be always available during the whole
process of data entry.
The junction is the point where the fluids from the two reservoirs
commingle; it is at a depth of (13100, 13100) and is connected to the
tubing with a 4.67” ID tubing.
The screens for entering the tubing flow model are as shown below:
Figure A13.10
Tubing Model Selection
screen
Once the model is entered, if on the above screen the Input Data button is pressed,
the next screen is displayed, where the deviation survey, including the azimuth, is to
be entered.
PROSPER MANUAL
124 - 172 Appendix A - Worked Examples
Figure A13.11
Tubing deviation survey
Input Screen
 Note that for all the pieces of downhole equipment where the
deviation survey needs to be specified, PROSPER will calculate the
measured depth and TVD of the starting point automatically. For
example in this the starting point is at (13000,13000).
Once the deviation survey is entered we will need to enter the equipment
information, like the tubing diameters etc, in the next screen. This screen is
accessed by clicking on the TAB called EQUIPMENT in the bottom left hand corner
of the screen shown above.
Figure A13.12
Tubing description Input
Screen
Figure A13.13
Junction Data Screen
 Note that for this screen the TVD and measured depth have
automatically been picked up from the last point entered for the
tubing, which is (13100,13100).
PROSPER MANUAL
126 - 172 Appendix A - Worked Examples
The information for this part of the input for top completion is as follows
Figure A13.14
Top Completion Model
Input Screen
Figure A13.15
Top Completion
Deviation Survey Input
Screen
The Equipment
Start 13100
Casing 13103 4.67 0.0006
 Note that we have defined the main flow type as annular but have
tubing flow from 13100 to 13103. This is done by using the casing in
that bit of the equipment description
Figure A13.16
Top Completion
equipment description
Input Screen
PROSPER MANUAL
128 - 172 Appendix A - Worked Examples
Perforation Details
In the completion section, the additional piece of data entered is the detail of
the perforations. We need to define the measured depth\ TVD where the
completion has been perforated. For the top completion we have perforations
all along the reservoir thickness of 100 feet.
This data is entered in the perforation details screen, which is accessed by clicking
on the PERFORATION DETAILS Tab as shown above.
Figure A13.17
Top Completion
Perforation Input Screen
• To enter the skin data scroll towards the right hand side of the data entry
screen, by using the bottom scroll bar
Figure A13.18
Perforation Input Screen
 i) You could use the various skin models to calculate the local
geometric and Non-Darcy skin on this screen, by changing the
Skin Model / Non Darcy entry Method choice from enter by
hand to the applicable one.
ii) If we had selected the Gravel Pack option in the main option
screen in step1 of this example, the gravel pack entry screen
would be available as well.
The local is zero for the top completion. To calculate the Non-Darcy factor, hit
on the ‘Calculate’ button. Enter the reservoir permeability (50 mD) and click on
‘Done’ to calculate the Non-Darcy factor. The calculated value will be
displayed on the screen.
The next step is defining the top reservoir. To go to the reservoir data entry
screen, click on the top reservoir in the right hand window of the above
screen.
PROSPER MANUAL
130 - 172 Appendix A - Worked Examples
Figure A13.19
Top reservoir Model Input
Screen
The next step is specify the reservoir characteristics. This is done by pressing
the INPUT DATA button on the above screen.
Figure A13.20
Top reservoir Input
Screen
Figure A13.21
Bottom Completion
Model Input Screen
PROSPER MANUAL
132 - 172 Appendix A - Worked Examples
Figure A13.22
Bottom Completion
Deviation Survey Input
Screen
The Equipment
 Note that we have defined the main flow type as annular but have
tubing flow from 13100 to 15206. This is done by using the casing in
that bit of the equipment description
Figure A13.23
Bottom Completion
Equipment description
Input Screen
Perforation Details
For the bottom completion we have perforations all along the bottom reservoir
thickness of 100 feet.
Figure A13.24
Bottom Completion
Perforation Input Screen
To enter the skin data, scroll towards the right hand side of the data entry screen by
using the bottom scroll bar.
The local is zero for the bottom completion. To calculate the Non-Darcy factor, hit on
the ‘Calculate’ button. Enter the reservoir permeability (50 mD) and click on ‘Done’ to
calculate the Non-Darcy factor. The calculated value will be displayed on the screen.
PROSPER MANUAL
134 - 172 Appendix A - Worked Examples
Figure A13.25
Perforation Input Screen
Figure A13.26
Bottom Reservoir
Model Input Screen
Figure A13.27
Bottom reservoir
Input Screen
This completes data entry. Click on Done to exit to the main drawing of the system.
The next step is to visualise the system defined. To see the system defined on the
main drawing screen click on, VISUALISE | ALL as shown in the figure below.
PROSPER MANUAL
136 - 172 Appendix A - Worked Examples
Figure A13.28
Invoking Visualisation
of the System
Once this is done, we can see the Top, Side and Front view of the completion
system defined as shown in the following figure.
Figure A13.29
Different views of the
completions
Once we have established that the system is okay, we need to generate the IPR for
the system. This is done by clicking on ANALYZE | CALCULATE on the above
screen. Once this is done the calculate screen appears as shown below:
Figure A13.30
IPR Calculation
Option screen
On this screen, there are various Calculation options; we will select the following
options and hit Calculate.
PROSPER MANUAL
138 - 172 Appendix A - Worked Examples
Figure A13.31
IPR of the
Injection Well
On the IPR Plot Click Main to take you to the multi-lateral drawing. Click | Finish |
Done to come to main PROSPER screen.
• Click on Calculation
• Click on System (VLP + IPR)
• Enter the following data
Figure A13.32
System Calculation
Input Data screen
Figure A13.33
Sensitivity Variable
Selection screen
PROSPER MANUAL
140 - 172 Appendix A - Worked Examples
• As soon as you select this variable. Enter the five values in this from 7000 Psig to
7800 Psig as shown below
Figure A13.34
Sensitivity Variable
value Input screen
Figure A13.35
System Solution
Calculation Screen
• Once the calculations are finished on the calculation screen, hit on Sensitivity.
The sensitivity plot is shown. On this plot click on Variable and select the Gas
Rate as variable. This gives us the plot of gas injection rate versus the well head
pressures:
Figure A13.36
Gas Injection
Rate versus well
head pressure
If we want to look at the pressure and production profiles, in the completion for one
of the cases, On the main calculation screen shown below press on Solution Details:
Figure A13.37
Accessing
Solution Details
Once the solution details is pressed the following screen with the details of the
solution comes up. This screen gives the details of pressure temperature, density etc
at the well head and tie point.
PROSPER MANUAL
142 - 172 Appendix A - Worked Examples
Figure A13.38
Solution Details
On the solution details screen, we can go into further details of the inflow, if we press
Inflow Layer Details button as shown above.
Figure A13.39
Inflow Layer
Details
On this screen Press on Plot. On the plot screen, by going to variable screen, we
can select the completions, and variables we want to see. Following are some of
these plots.
Figure A13.40
Top Completion
Pressure and
reservoir
pressure
variation
Figure A13.41
Bottom
Completion Rate
per segment
PROSPER MANUAL
144 - 172 Appendix A - Worked Examples
 i) You can plot the details for other completions, tubing etc as well
by selecting the appropriate variables by going to the top section
of the plot.
ii) If you want to do sensitivity on various inflow variables like
down-hole choke sizes, reservoir pressures, perforation intervals
etc, go back to the IPR section, make the changes and
regenerate the whole IPR curve, before doing sensitivities again.
 Note: To be able to build this model, the user must set the pump and
the rod database first. To learn how to set up the correspondent
database for Progressive Cavity Pumps the user must refer to
Chapter 11 section 11.7.1 of PROSPER manual.
Figure A14.1
Figure A14.2
System Summary
Inflow type: Multilateral
Begin by starting the program. From the PROSPER main menu, select File ⏐ New to
reinitialise the program input and output files.
The ‘New’ menu item under File is only available if a file has already been
loaded. If there is no file loaded skip this step and go to next step.
PROSPER MANUAL
146 - 172 Appendix A - Worked Examples
Then click Done to exit this screen. This completes the system setup and
reinitialises the program and governs the inputs that the user will be required
to enter.
Figure A14.3
PVT Input Screen
Click Done on the above screen to exit. This marks the end of defining the PVT
behaviour
The next task is to define the well bore itself and surface lines (if any). This is done in
the following steps.
Measured True
Depth Vertical
(feet) Depth
(feet)
0 0
4000 4000
While entering the deviation survey, PROSPER calculates automatically the
cumulative displacement and the angle of the well.
PROSPER MANUAL
148 - 172 Appendix A - Worked Examples
Figure A14.4
Equipment Input Screen
• Click Done to advance to the geothermal data entry screen. Once on the
screen, enter the following temperature profile:
Measured Formation
Depth Temperature
(feet) (deg F)
0 60
4000 159
Enter an overall heat transfer coefficient of 8 Btu/hr/ft2/F. Click | Done to exit the
screen.
• This takes you to the default heat capacity screen. Let it remain as it is.
Click on Done to go to the next screen.
Figure A14.5
Geothermal Gradient
PROSPER MANUAL
150 - 172 Appendix A - Worked Examples
Bottom Layer
Reservoir Pressure 2000 psig
Reservoir Temperature 160 degrees F
Oil Gravity 13 API
Gas Gravity 0.67 sp. gravity
Water Salinity 10000 ppm
Water Cut 0 percent
Total GOR 100 scf/STB
Horizontal Permeability 210 md
Formation Thickness 200 feet
Drainage Area 400 acres
Depth of Reservoir Top 4200 feet
Vertical Permeability 210 md
According to the drilling program, the tie point will be considered at measured depth
of 9700 ft (8800 ft vertical depth). The deviation survey of the original well and the
side track are indicated below.
Side Track
Vertical
section
The user interface consists of a framework window that contains several child
windows, as well as the menu and toolbar from which commands are issued. The
child windows include the network windows that contain the system network drawing,
the navigator window that can assist in the viewing of large networks and up to three
visualisation windows, which can show the multilateral network drawn to scale from
three orthogonal points of view.
Figure A14.6
PROSPER
Multilateral
Network
To start drawing your multilateral system according to the well sketch, start selecting
the tie point, junction, Completion (1) and Completion (side track) as well as the top
and bottom reservoir.
Figure A14.7
Adding the
completion and
reservoirs
Once drafted the basic drawing according to your well sketch and drilling program, it
is possible to connect the blocks using the button Add Link.
To enter the required data for each section all you have to do is to double click on
each icon. It is recommended to start from the tie point to the reservoir according to
the well sketch.
PROSPER MANUAL
152 - 172 Appendix A - Worked Examples
 The tie point is the point above which everything will be part of wellbore
sketch and thus the pressure loss etc in that section will be a part of VLP.
Everything below the tie point is a part of the IPR and pressure losses in
this section will be evaluated in IPR calculations.
Figure A14.8
Linking the tie point
with the joint,
completion and
reservoir.
After double clicking on the tie point, enter the measured depth and true vertical
depth as indicated previously. The tie point is the node where the IPR is solved, and
is located at the top of the system (in vertical depth). Hence, the tie-point can only be
a starting point.
The Junction point will be a branching node. It can only have one link into it (from a
tie-point or a completion).
Once these two points have been defined, then Deviation Survey, Downhole
Equipment and Perforation Details can be entered. In the case of the Deviation
Survey, there is an additional azimuth entry.
When the user has entered the information for each branch, the calculations can be
performed.
Tie point :
Data: Measured depth of 4000 ft, True Vertical Depth of 4000 ft
Junction 1:
The tubing information entry is a two step process. First we define the model for
pressure loss calculations. We will also be using the following model:
Completion 1:
The screens for entering the flow model are as shown below:
Figure A14.9
Tubing Model Selection
screen
Once the model is entered, selecting the Input Data button, the following screen is
displayed, where the deviation survey, including the azimuth, can be entered:
PROSPER MANUAL
154 - 172 Appendix A - Worked Examples
Figure A14.10
Tubing deviation survey
Input Screen
Once the deviation survey is entered, we will need to enter the equipment
information like the tubing diameters etc, in the following screen. This screen is
accessed by clicking on the TAB called EQUIPMENT in the bottom left hand corner
of the screen shown above.
Figure A14.11
Tubing description Input
Screen
According to the drilling program, this completion has been perforated from 4200 ft to
4400 ft.
Figure A14.12
Vertical well
Perforation details
Select the information required such as vertical flow model, well bore radius, and
Dietz shape factor.
For this example the Petroleum Experts 2 correlation will be used, a well bore radius of
0.345 ft and Dietz shape factor of 30 will be considered.
Figure A14.13
Re entry 1,
Calculation options
screen.
When pressing the option Input Data, there are three tabbed dialogs in this data
input screen, which allow the entry of a deviation survey, equipment descriptions and
completion information. The first two dialogs contain tables very similar to the ones
encountered by selecting System | Equipment from the PROSPER main menu and
then the ‘Deviation Survey’ and ‘Downhole Equipment’ buttons. In the case of
the deviation survey there is an additional azimuth entry.
PROSPER MANUAL
156 - 172 Appendix A - Worked Examples
Figure A14.14
Re entry
Deviation Survey
Screen
Once entered the deviation survey, select the equipment and select tubing,
according to the deviation survey, the tubing in the completion 1 has been run down
to 4330 ft and has a diameter of 2.89 in.
Figure A14.15
Re entry
Equipment
According to the drilling program, this completion has been perforated from 4100 ft to
4250 ft:
Figure A14.16
Completion 1
Perforation details
Finally double click on the reservoir and enter the PVT data, as well as the
information required to calculate the inflow performance based on the Darcy Model.
The information has been provided at the beginning of this example.
Figure A14.17
Lower sand
PVT Data
Press Input Data to continue and enter the information for the reservoir:
PROSPER MANUAL
158 - 172 Appendix A - Worked Examples
Figure A14.18
Bottom Reservoir
Inflow data based
on
Darcy Reservoir
Model
Now the correspondent data for the second sand can be entered.
Figure A 14.19
Re entry
PVT Data
Figure A14.20
Re entry
Input Data
Press input to continue and enter the information for the reservoir.
Once you enter the information for the two branches (completion 1 and side track),
from PROSPER – Multilateral Network Menu, select the option Visualise all:
Figure A14.21
Visualise All
The Calculate screen gives the option of calculating one IPR point or a curve.
Also, calculations can be switched between infinite and finite conductivity modes of
calculation. In the latter case the pressure drop in the tubing is taken into account.
PROSPER MANUAL
160 - 172 Appendix A - Worked Examples
Figure A14.22
Calculate
The finite conductivity solution takes in account the pressure drop and
interference, whilst the Infinite conductivity considers equal pressure and constant
production rate at all times. The flow distribution is used then to calculate the
pressure around the source.
The pressure of the reservoir approaches a constant value, then if in one particular
branch in the reservoir is surrounded by a constant pressure boundary, the pressure
in the well and the boundary will become constant (steady state pressure), when the
steady state pressure is normalized respect to the flow rate, it provides a measure of
the pressure draw-down required to flow a unit of volume per unit time.
The Details button is used to display pressure and rate-related parameters with
respect to the measured and vertical tubing depths of each branch. If a curve has
been calculated, these details pertain to the last point in the curve.
Figure A14.23
Plot
PROSPER MANUAL
162 - 172 Appendix A - Worked Examples
Figure A14.24
Calculation
IPR+VLP
Figure A14.25
VLP IPR results
Notice that with out the pump and based on the nodal analysis the well can produce
only 90.6 bpd.
Provided the fact that you have the pump database set up according to data
provided by the manufacture then you can set from the main screen the PCP.
Figure A14.26
PCP
Based on the completion program, the pump is to be set at 3900 ft, and it is
expected to produce 700 bpd:
PROSPER MANUAL
164 - 172 Appendix A - Worked Examples
Figure A14.27
PCP
Figure A14.28
PCP
When the calculation is finished, select done and design; form this panel you will be
able to select the pump and rods, the more pumps there are in the database, the
wider is the range of choices.
Figure A14.29
PCP design
For this particular design and pump selection, if one wants to produce 800 bpd at
downhole conditions, 265 RPM of pump speed are required. Also the program will
provide rod stress, etc.
From the main screen select Calculation/ System (IPR+VLP) to perform nodal
analysis considering the pump, it is possible to see that now we will be able to lift
700 bpd:
Figure A14.30
PCP results
In Plot, choose the option Variables. Change the variables, selecting IPR, VLP and
Pump Discharge:
PROSPER MANUAL
166 - 172 Appendix A - Worked Examples
Figure A14.31
PCP results
Black oil modelling is a technique that works back from values of density and GOR
measured at known surface conditions to predict properties at other points in the
system and the technique is fast and accurate when applicable. The black oil
condensate model is preferential to use as the computational time is significantly
faster than using an EOS PVT approach. The matched EOS can be used to validate
the black oil condensate model.
The use of Volume Shift as an EOS match parameter will inevitably cause mass
balance errors in the EOS if used for multiple temperature and pressures (like a
pressure gradient calculation) and will adversely impact the results in PROSPER.
A15.1 Objectives
File: ~/samples/PROSPER/condvalid.out
Figure A15-1
Compositional data
A matched EOS can be passed to PROSPER via the Import…PRP button, from PVTP
for example.
PROSPER will use the EOS data to generate condensate black oil model data.
Select Generate to activate the EOS Calculation Range dialogue (Figure A15-2).
Figure A15-2
EOS calculation
range dialogue
The temperature corresponds to the reservoir temperature and the pressure values
range from initial reservoir to depleted reservoir conditions.
PROSPER MANUAL
168 - 172 Appendix A - Worked Examples
Select Calculate | Calculate to generate the black oil properties (Figure A15-3).
Figure A15-3
Compositional data
The saturation pressure shown in Figure A15-3 is the dew point pressure
required for the black oil model.
Select OK | OK | Properties (Figure A15-4) to generate the black oil fluid properties
from the EOS flashed through the separator stages down to standard conditions. At
this point we have all the properties to build a black oil fluid model.
Figure A15-4
Black oil fluid
properties from
EOS
Figure A15-5
EOS correlation
comparison
No sensitivity variables will be used in the calculation and the Petroleum Experts 4
vertical flow correlation will be used.
PROSPER MANUAL
170 - 172 Appendix A - Worked Examples
Figure A15-6
EOS gradient profile
Figure A15-7
Match point
comparison using the
black oil condensate
model
Zooming in to investigate the off-set gradient point shown in Figure A15-8 shows that
the error is approximately 10.0psig indicating that for this case the black-oil
condensate model is valid with the EOS gradient predictions.
Figure A15-8
Match point using the
black oil condensate
model
PROSPER MANUAL
172 - 172 Appendix A - Worked Examples
Figure A15-8 indicates that for this case the black-oil condensate
 model can be used due to the agreement in the EOS gradient
traverse results.
1. Sutton, R.P. and Farshad, F.F.: ‘Evaluation of Empirically Derived PVT Properties
for Gulf of Mexico,’ SPE Reservoir Engineering, (Feb. 1990), 79-86.
2. Beal, C.: ‘The Viscosity of Air, Water, Natural Gas, Crude Oil and its Associated
Gases at Oil Field Temperatures and Pressures,’ Trans., AIME (1946) 165, 94-98.
3. Beggs, H.D. and Robinson, J.R.: ‘Estimating the Viscosity of Crude Oil Systems,’
JPT (Sept. 1975), 1140-1144.
5. Eilerts et al: ‘Phase Relations of Gas Condensate Fluids,’ Monograph 10, U.S.
Bureau of Mines, Washington D.C. (1957).
6. Brinkman, F.H. and Sicking, J.N.: ‘Equilibrium Ratios for Reservoir Studies’, SPE
(Nov. 1959), SPE reprint series No. 15, 240-246.
7. Katz, D.L. and Kurata, F.: ‘Retrograde Condensation’, Ind. Eng. Chem. (June,
1940) 32, No. 6, 817-827.
8. Katz, D.L., Monroe, R.R. and Trainer, R.P.: ‘Surface Tension of Crude Oils
Containing Dissolved Gases,’ Trans., AIME (1943), 1624, 285-294.
9. Lee et al: ‘The Viscosity of Natural Gases’, Trans., AIME (1966), 997-1002.
11. Coats, K.H.: ‘An Equation of State Compositional Model’, paper SPE 8284
presented at SPE Annual Technical Conference and Exhibition, Las Vegas,
Nevada, Sept. 23-26, 1979.
12. Nghiem, L.X., Fong, D.K. and Aziz, K.: ‘Compositional Modelling with an Equation
of State’, paper SPE 9306 presented at SPE Annual Technical Conference and
Exhibition, Dallas, Texas, Sept. 21-24, 1980.
13. Winkler, H.W., Eads, P.T.: ‘Algorithm for More Accurately Predicting Nitrogen-
Charged Gas-Lift Valve Operation at High Pressures and Temperatures’, paper
SPE 18871 presented at SPE Production Operations Symposium, Oklahoma City,
Oklahoma, March 13-14, 1988.
14. Peng, D.-Y. and Robinson, D.B.: ‘A New Two-Constant Equation of State’, I.&E.C.
Fundamentals (1976) 15, No.1, 59-64.
2-4 Appendix B - References
B2 IPR Calculations
1. Dietz: ‘Determination of Average Reservoir Pressure From Build Up Surveys,’
Trans., AIME.(1965).
2. Fetkovich M.J.: ‘The Isochronal Testing of Oil Wells,’ paper SPE 4529 presented
at the SPE 1973 Annual Fall Meeting, Las Vegas, Sept. 30-Oct. 3.
4. Goode P.A. and Kuchuk F.J., ‘Inflow Performance of Horizontal Wells,’ SPE
Reservoir Engineering (Aug. 1991) 6, No. 3, 319-323.
5. Jones L.G., Blount, E.M et al: ‘Use of Short Term Multiple Rate Flow Tests to
Predict Performance of Wells Having Turbulence,’ paper SPE 6133 presented at
the 1976 SPE Annual Technical Conference and Exhibition, New Orleans, Oct. 3-6.
6. Vogel J.V.: ‘Inflow Performance Relationships for Solution Gas Drive Wells,’ JPT
(Jan. 1968), 83-92.
7. Houzé, O.P., Horne, R. and Ramey, H.J. Jr.: ‘Infinite Conductivity Vertical Fracture
in a Reservoir with Double Porosity Behaviour’, paper SPE 12778 presented at
SPE Regional Meeting, Long Beach, California, April 11-13, 1984.
9. Dikken, B.J.: ‘Pressure Drop in Horizontal Wells and its Effect on Their Production
Performance’, Journal of Petroleum Technology, November, 1990; Trans., AIME,
289.
10. Chaperon, I.: ‘Theoretical Study of Coning Towards Horizontal and Vertical Wells
in Anisotropic Formations: Subcritical and Sub-Critical Rates’, Paper SPE 15377
presented at the 1986 SPE Annual Technical Conference and Exhibition, New
Orleans, Oct. 5-8.
11. Goode, P.A. and Wilkinson, D.J., : ‘Inflow Performance of Partially Open
Horizontal Wells’, Paper SPE 19341 presented at the 1989 SPE Eastern Region
Meeting, Morgantown, WV, Oct. 24-27. Also Journal of Petroleum Technology,
August 1991, pp 983-985.
12. Papazatacos, P., Herring, T.R., Martinsen, R. and Skjaeveland, S.M.: ‘Cone
Breakthrough Time for Horizontal Wells’, Paper SPE 19822 presented at the 64th
Annual Technical Conference, San Antonio, Texas, Oct. 8-11.
13. Cinco-Ley, H., Samaniego, F. and Dominguez, N.: ‘Transient Pressure Behaviour
for a Well With a Finite-Conductivity Vertical Fracture’, Paper SPE 6014 presented
at the 51st Annual Technical Conference, New Orleans, Louisiana, Oct. 3-6, 1976.
14. Mavor, M.J. and Cinco Ley, H: 'Transient Pressure Behaviour of Naturally
Fractured Reservoirs', Paper SPE 7977 presented at the California Regional
Meeting of the SPE, Ventura, California, April 1979
15. Wong, D., Harrington, A. and Cinco Ley, H: 'Application of the Pressure
Derivative Function in th Pressure Transient testing of Fractured Wells', Paper SPE
13056 presented at the 59th annual Technical Conference, Houston, Texas, Sept.
16-19, 1984
16. Warren, J.E and Root, P.J.: 'The behaviour of Naturally Fractured Reservoirs',
Paper SPE 426, SPEJ (Spet 1963), 245-255
17. Hegre, T.T. and Larsen, L.: 'Productivity of Multifractured Horizontal Wells', Paper
SPE 28845 presented at the European Petroleum Conference of the SPE, London,
UK, October 1994
18. Urbanczyk, C.H, and Wattenbarger, R.A: 'Optimization of Well Rates under Gas
Coning Conditions.', SPE Advanced Technology Series, Vol. 2, No. 2, April 1994.
19. Larsen, L.: 'Productivity Evaluations of Wells in Long Rectangular Drainage Areas.'
2. Ashford, F.E, and Pierce, P.E.: ‘The Determination of Multiphase Pressure Drops
and Flow Capacities in Downhole Safety Valves (Storm Chokes)’, paper SPE 5161
presented at the 1974 SPE Annual Fall Meeting, Houston Oct. 6-9.
3. Beggs, H.D. and Brill, J.P.: ‘A Study of Two Phase Flow in Inclined Pipe,’ JPT
(May 1973), 606-617.
5. Fancher, and Brown, G.G.: ‘Prediction of Pressure Gradients for Multiphase Flow
in Tubing,’ SPE Journal (Mar. 1963), 59-64.
6. Fortunati, ‘Two Phase Flow Through Well-head Chokes,’ paper SPE 3742
presented at 1972 SPE European Spring Meeting, Amsterdam, May 17-18.
8. Mandhane et al, ‘A Flow Pattern Map for Gas-liquid Flow in Horizontal Pipes,’
International Journal Multiphase Flow, 1, 537-541.
9. Moody, ‘Friction Factor for Pipe Flow,’ Trans., AIME (1944), 66, 671-675.
10. Mukherjee, H. and Brill, J.P.: ‘Liquid Holdup Correlations for Inclined Two-Phase
Flow,’ JPT (May 1983), 1003-1008.
11. Oranje, ‘Condensate Behaviour in Gas Pipeline is Predictable,’ Oil and Gas Journal
(July 1973), 39-43.
12. Orkiszewski, ‘Predicting Two Phase Pressure Drop in Vertical Pipes,’ JPT (June
1967), 829-833.
PROSPER MANUAL
4-4 Appendix B - References
13. Duns, H. Jr and Ros, N.C.J.: ‘Vertical Flow of Gas and Liquid Mixtures in Wells,’
Proc., Sixth World Petroleum Congress, Frankfurt (1963) 451.
14. Tansev, E. Startzman, R.A. and Cooper, A.M.: ‘Predicting Pressure Loss and
Heat Transfer in Geothermal Wellbores,’ paper SPE 5584 presented at the 1975
SPE Annual Fall Meeting, Dallas, Sept. 28-Oct. 1.
15. Gould, T.L, Tek, M.R. and Katz, D.L.: ‘Two-Phase Flow Through Vertical, Inclined,
or Curved Pipe,’ JPT, August, 1974, 915-925.
B4 Temperature Calculations
1. Chiu, K. and Thakur, S.C.: ‘Modeling of Wellbore Heat Losses in Directional Wells
Under Changing Injection Conditions,’ paper SPE 22870 presented at the 1991
SPE Annual Fall Meeting, Dallas, Oct. 9-9. pp 517 - 528.
2. Hasan, A.R. and Kabir, C.S.: ‘Heat Transfer During Two-Phase Flow in
Wellbores: Part I - Formation Temperature,’ paper SPE 22866 presented at the
1991 SPE Annual Fall Meeting, Dallas, Oct. 9-9. pp 469 - 478.
3. Hasan, A.R. and Kabir, C.S.: ‘Heat Transfer During Two-Phase Flow in
Wellbores: Part II - Wellbore Fluid Temperature,’ paper SPE 22948 presented at
the 1991 SPE Annual Fall Meeting, Dallas, Oct. 9-9. pp 695 - 708.
4. Carslaw, H.S. and Jaeger, J.C.: ‘Conduction of Heat in Solids,’ Oxford Science
Publications, Oxford, U.K., 1959.
PSEP
TSEP
Total GOR is the total of separator and
γgtot TANK
tank GOR.
Rtot = Rsep + Rtnk
Known Parameters:
γ =
MWmix
lb ( )
lb.mol = 1
×
Total.Mass.of .mixture.entering ⎛ lb ⎞
28.966 lb (
lb.mol
) ⎜ ⎟
⎛ lb ⎞ Total .moles.of .mixture.entering ⎝ lb.mol ⎠
28.966⎜ ⎟
⎝ lb.mol ⎠
Total inlet mass calculation:
⎛ lb ⎞
= 1(SCF ) × γ gt × 0.0764⎜ ⎟
⎝ SCF ⎠
= 0.0764γ gt (lb )
Cu. ft ⎛ lb ⎞
= CGR(STB ) × 5.615 × γ c × 62.43⎜⎜ ⎟⎟
STB ⎝ Cu . ft ⎠
0.0764γ gt (lb )
=
⎛ lb ⎞
γ gt × 28.966⎜ ⎟
⎝ lb.mol ⎠
0.0764
= (lb.mol )
28.966
Petroleum Experts
Appendix C - Equations 3-14
1 Total.Mass.of .mixture.entering ⎛ lb ⎞
γ= × ⎜ ⎟
⎛ lb ⎞ Total.moles.of .mixture.entering ⎝ lb.mol ⎠
28.966⎜ ⎟
⎝ lb.mol ⎠
⎧ ⎫
1 ⎪ 0.0764 × γ gt + 5.615 × 62.43 × CGR × γ c ⎪⎛ lb ⎞
= ×⎨ ⎬⎜ ⎟
⎛ lb ⎞ ⎪ 0.0764 + 5.615 × 62.43 × CGR × γ c ⎪⎝ lb.mol ⎠
28.966⎜ ⎟
⎝ lb.mol ⎠ ⎩ 28.966 Mc ⎭
γ gt + 4588.3 × CGR × γ c
 γ=
γ
1 + 132904 × CGR × c
Mc
This expression thus gives, the average gas gravity of a mixture, which
has a condensate to gas ratio of CGR STB/SCF, with the gas having a
gas gravity of γgt and the condensate having a specific gravity of γc and
molecular weight of Mc.
This also can be used to work out the condensate to gas ratio of a
mixture gas if the gas gravity is known as shown in the following
equation.
PROSPER Manual
4-14 Appendix C - Equations
Based on this formulation based on the separator gas gravity and the average total
gas gravity, the effective CGR vaporised in separator gas is estimated as follows
γ g sep - γ g tot
CGRsep =
4588.3 γ c - 132904 γ g sep γ c /M c
Also assuming that the condensate is above dew point, the initial CGR under
reservoir conditions is,
1
CGRres =
Rsep + Rtnk
γ
gsep
γgtnk
Rsep
P=Psep Rtnk
T=Tsep
γ gres
ρcondsc
Cres
SEPARATOR TANK
• At Separator Conditions:
γ g sep - γ g tot
CGR sep =
4588.3 γ csc - 132904 γ g sep γ csc /M c
NOTE:
γgt > γgsep ⇒ CGRsep negative
Petroleum Experts
Appendix C - Equations 5-14
1
CGRres =
Rsep + Rtnk
The CGR at pressures lower than dew point is estimated by a second degree
polynomial as shown
2
⎛ P f ⎞
CGR = CGRmin + (CGRres − CGRmin )⎜ − ⎟
⎜P f ⎟⎠
⎝ dewpoint 1 −
where
Pmin
f =
Pdew
Pmin being the maximum liquid dropout pressure and a function of the dewpoint
pressure.
i.e. Pmin = F (Pdewpoint )
comp
f 2
⎛ P ⎞
P 1 ⎜ -f⎟
Pdew ⎜ Pdewpo int ⎟
⎜ 1- f ⎟
⎜⎜ ⎟⎟
⎝ ⎠
Mc
γ g tot -
% Gas Mole Fraction = 28.966
Mc
γg-
28.966
7.08
f = 0.15 + + 1.45 * % Condensate (From Eilerts et al)
TRES - 161
Bg
CGRmin = CGRres - Lmax
561.5 Bo
PROSPER Manual
6-14 Appendix C - Equations
Thus we need to estimate Bo and Bg to find CGRmin from the following equation
=
CGR res − Lmax Bg
CGRmin
561.5 Bo
⎛k ∂P ⎞
q o = 2πrh⎜⎜ o ∗ ⎟⎟
⎝ µ o ∂r ⎠
⎛ k g ∂P ⎞
q g = 2πrh⎜ ∗ ⎟
⎜µ ∂ r ⎟
⎝ g ⎠
⎛k ∂P ⎞
q w = 2πrh⎜⎜ w ∗ ⎟⎟
⎝ µ w ∂r ⎠
Total Mass Flow Rate:
⎛ k kg k ⎞ ∂P
mr = 2πrh⎜ ρ o o + ρ g + ρw w ⎟
⎜ µ µg µ w ⎟⎠ ∂r
⎝ o
∂ ⎧⎪ ⎛⎜ k o kg k ⎞ ∂P ⎫⎪ ∂ρ
1 and 2 ⇒ ⎨r ⎜ ρ o + ρg + ρw w ⎟ ⎬ = rφ .......................
∂r ⎪⎩ ⎝ µ o µg µ w ⎟⎠ ∂r ⎪⎭ ∂t
By Definition: 1 ⎛∂ ρ ⎞ ∂r _
C = *⎜ ⎟ or =ρc
ρ ⎜⎝ ∂P ⎟⎠ T
∂P
C = S wC w + S o Co + S g C g
Petroleum Experts
Appendix C - Equations 7-14
Equation 3 becomes:
∂ ⎧⎪ ⎛⎜ ρ o ρg ρ ⎞ ∂P ⎫⎪ _
∂P
⎨r ⎜ k o + kg + kw w ⎟ ⎬ = r φ ρ c
∂r ⎪⎩ ⎝ µ o µg ⎟
µ w ⎠ ∂r ⎪⎭ ∂t
k o ⎛⎜ k g µo k µ ⎞
p
=∫ ρ + ρ + w o ρ w ⎟∂P
µ o ⎜⎝ ko µ g ko µ w ⎟
o g
0 ⎠
k ⎛ ⎞
p
qg q
= ∫ o ⎜⎜ ρ o + ρ g + w ρ w ⎟⎟∂P
0
µo ⎝ qo qo ⎠
k ⎛ ⎞
p
GORout B g WORout Bw
= ∫ o ⎜⎜ ρ o + ρg + ρ w ⎟⎟∂P
0
µo ⎝ Bo Bo ⎠
Combining we get:
∂ ⎛ ∂m( p ) ⎞ rφ r c µ o ∂m( p)
⎜ r ko ⎟= ∗
∂r ⎝ ∂r ⎠ F ∂t
GORout Bg WORout Bw
Where F = ρo + ρg + ρw
Bo Bo
∂ 2 m( p ) 1 ∂m( p) _
µ o ∂m( p)
⇒ + = φ c
∂r 2
r ∂r Bo ∂t
So ρ o + S g ρ g + S w ρ w
C = c
F
For Condensates:
∂ 2 m( p ) 1 ∂m( p) µ g ∂m( p)
+ = φc
∂r 2
r ∂r kg ∂t
So ρo + S g ρg + Sw ρ w
C=c
Fg
Bo CGRout B WGR
Fg = ρo + ρ g + w ρw
Bg Bg
PROSPER Manual
8-14 Appendix C - Equations
C3 Temperature Models
Enthalpy Balance temperature model in PROSPER applies the general energy
equation for flowing fluid:
⎛ mv 2 ⎞ ⎛ mgz ⎞
∆U + ∆⎜⎜ ⎟⎟ + ∆⎜⎜ ⎟⎟ + ∆( pV ) − Q = 0
⎝ 2g c ⎠ ⎝ gc ⎠
In terms of Enthalpy H = U + pV , this is written:
⎛ mv 2 ⎞ ⎛ mgz ⎞
∆H + ∆⎜⎜ ⎟⎟ + ∆⎜⎜ ⎟⎟ − Q = 0
⎝ 2g c ⎠ ⎝ gc ⎠
If heat transfer with the surroundings (Q) is neglected, the usual pressure equation
solved in multiphase flow results. PROSPER solves the general energy equation by
considering the enthalpy balance across an incremental length of pipe. The
enthalpy term includes the effects of pressure (including Joule-Thomson effect) and
phase changes.
Where
∆Q 1V 2
∆H = - + ∆Lcosθ + tot
ρ l ql + ρ g qg 2 g
dt
P2 = P1 − G∆L ; T2 = T1 − ∆L
dz
to give the first estimate
of H2
Petroleum Experts
Appendix C - Equations 9-14
The heat transfer coefficient is used to calculate dQ within the enthalpy balance
iterations and not the temperature.
The heat transfer coefficient is itself a function of the temperature of both the fluid
and the surroundings; therefore iteration is required to find both the heat transfer
coefficient and the enthalpy balance. The formation is a thermal sink at
temperature Te. The temperature profile near the wellbore is dependent upon
producing time and the thermal diffusivity of the formation. The heat diffusivity
equation accounts for localised heating (or cooling) of the formation by the well
fluids.
This integral poses numerical problems as u→0 and is slow. This equation is
evaluated for very early times only.
For intermediate times, PROSPER uses a fit of the TD vs tD generated using the
exact solution. At later times a logarithmic approximation is used:
⎛ αt ⎞⎟ k
f (t ) = 0.982 log ⎜ 1 + 1.81 Where thermal diffusivity α =
e⎜ r ⎟⎠ ρ Cp
⎝ n
This formulation approximates the exact solution with less than 1% error. (From
Kwan-Chu and Subash Thakur).
U TO is the overall heat transfer coefficient.
1 1 1 1 1
= + + +
U TO h f hc hr hco
PROSPER Manual
10-14 Appendix C - Equations
The overall heat transfer coefficient takes into account forced convection inside the
pipe and free convection outside the pipe plus radiation and conduction.
• Conduction ∆Q = 2π k ∆L
(T1 − T2 )
⎛r ⎞
log e ⎜ 2 ⎟
⎝ r1 ⎠
• Forced Convection ∆Q = 2π r2 h f ∆L ( T1 − T2 )
Now, let us examine the components of the overall heat loss coefficient individually:
0.023 k Ren0.8 Pr 3
hf =
rti
Where k is the average conductivity.
k av = k gas (1 − holdup) + k liquid ( holdup)
Petroleum Experts
Appendix C - Equations 11-14
H2
rti H1 P1 , T 1
where σ is the Stefan-Boltzman
constant and ε is emissivity.
rto
rci
rco
rcem
Cp Conductivity Specific
Rock BTU/hr/ft/degF Gravity
BTU/lb/degF
Sandstone 0.183 1.06 2.64
Shale 0.224 0.7 2.4
Limstone 0.202 0.54 2.71
Dolomite 0.219 1.0 2.87
Halite 0.219 2.8 2.17
Anhydrite 0.265 0.75 2.96
Gypsum 0.259 0.75 2.32
Lignite 0.3 2.0 1.5
Volcanics 0.2 1.6 2.65
PROSPER Manual
12-14 Appendix C - Equations
Cp Conductivity
BTU/lb/degF BTU/hr/ft/degF
H2O (Low salinity) 1.0 0.35
H2O (High salinity) 1.02 0.345
Heavy Oil 1.04 0.34
Medium Oil 0.49 0.083
Light Oil 0.5 0.0815
Gas 0.26 0.0215
The dry rock properties are modified to wet rock properties upon the porosity,
permeability and rock consistency.
Petroleum Experts
Appendix C - Equations 13-14
Where:
Ta1 = Ambient temperature at L1
T1 = Fluid temperature at entry
T(x) = Fluid temperature at current location
θ = Deviation angle
m& = Fluid mass flow rate
Cp = Specific heat capacity
U = Overall heat transfer coefficient referred to pipe inside diameter
D = Pipe inside diameter
G = Geothermal gradient
W = Product of phase mass flow rates and heat capacities m& oCpo +
m& wCpw + m& gCpg
C6 Choke Calculation
From Bernoulli:
1 1
P + ρ V2 = P + ρ V2
1 2 1 1 o 2 o 0
From Mass Conservation:
ρ AV =ρ A V
1 1 1 0 0 0
In the throat, the maximum velocity is the speed of sound. Under critical
conditions, the choke becomes independant of the downstream pressure and
temperature.
⎛
n ⎞⎟ ⎜
P ⎛ V 2 ⎞ n + 1⎟⎟⎠ ⎜
⎜
⎝
1 ⎜ ⎛ 1 ⎞ 0 ⎟
= ⎜ 1 + ⎜ n - 1⎟ ⎟
⎜ ⎝ ⎠
ms ⎟⎠
P 2 V
o ⎝
PROSPER Manual
14-14 Appendix C - Equations
λ ρ + λ ρ
V2 =
g g i i
ms λ λ
g l
+
ρ V2 ρ V2
g gs l ls
λ C + λ C
l pl g pg
n =
λ C + λ C
l vl g vg
q
g
λ = ; λ = 1 - λ
g q + q l g
l g
Vms : 2 phase sound velocity from FORTUNATI, Vms will be much lower than the
velocity of either phase. Critical conditions are reached at much lower velocities.
C
p Po g
For a mono phase V 2 = 144
g C ρ
r
− For deviated wells, the Beggs and Brill hold up correction is used.
− To determine interfacial tension, the Parachor technique is used.
− Petroleum Experts correlation uses the Gould et al Flow Map and for the various
flow regimes we use the following:
Petroleum Experts
1-2 APPENDIX D – DIETZ SHAPE FACTORS
1 2.07
30.9
2
1 2.72
31.6 4
1 0.232
27.6 4
1 0.115
27.1 4
60°
1
21.9 3.39
3
1 22.6 1 3.13
2 2
1 5.38 1 0.607
4 2
1 2.36 0.111
1
5
2
4 0.098
12.9 3
In water-drive reservoirs
4.57 19.1
In reservoirs of unknown
1 10.8 production character
25
2
D
Petroleum Experts
Appendix E File Formats
E1 Introduction
This appendix contains examples of some file formats used by PROSPER. For
further details and advice regarding interfacing PROSPER with other applications,
please contact Petroleum Experts Limited customer support.
*
* UNITS for the imported PVT variables must be defined in field units
*
* TABLE IDENTIFIER RECORD
*
* N LINES TEMP BP
*
* N - Table Number
* LINES - Number of lines in the table (max 15)
* TEMP - Table Temperature
* BP - Table Bubble Point Pressure (Dew Point for condensate)
1 3 100 1300
1.21 453 .99 46 2000
1.31 454 .98 47 2010
1.41 455 .97 49 2020
2 3 200 1310
2.21 553 .89 56 3000
2.31 554 .88 57 3010
2.41 555 .87 59 3020
3 3 300 1390
3.21 653 .79 76 4000
3.31 654 .78 77 4010
3.41 655 .77 79 4020
2-6 APPENDIX E - FILE FORMATS
4 3 400 1400
4.21 753 .69 86 5000
4.31 754 .68 87 5010
4.41 755 .67 89 5020
5 3 500 1800
5.21 853 .59 96 6000
5.31 854 .58 97 6010
5.41 855 .57 99 6020
Note:
Import table units must be defined in field units. Once the data has been imported
the PROSPER units system can be used to display the values in any desired units.
E3 Lift Curves
The following is an example of a flowing well lift curve in ECLIPSE format:
-- VFP TABLE for PRODUCER --
VFPPROD
1 10430 'LIQ' 'WCT' 'GOR' /
100 1000 10000 /
114.696 514.696 5014.7 /
0 0.5 0.9 /
0.8 1 5 /
0 /
1 1 1 1 2002.17 1258.71 2733.66 /
1 1 2 1 1479.42 1083.09 2655.25 /
1 1 3 1 413.537 806.953 4503.13 /
1 2 1 1 3948.98 2376.35 3439.27 /
1 2 2 1 3619.42 1985.43 3270.18 /
1 2 3 1 494.134 928.339 3352.16 /
1 3 1 1 4913.94 4485.14 4672.16 /
1 3 2 1 4895.27 4343.38 4563.92 /
1 3 3 1 3925.4 2141.93 3460.48 /
2 1 1 1 3629.53 2559.11 3358.56 /
2 1 2 1 3539.7 2209.16 3216.7 /
2 1 3 1 1098.95 1408.86 4038.35 /
2 2 1 1 4817.47 3863.58 4190.39 /
2 2 2 1 4746.81 3540.81 3985.01 /
2 2 3 1 1916.92 1594.64 3434.72 /
2 3 1 1 5347.77 5166.94 5283.46 /
2 3 2 1 5337.64 5102.83 5210.6 /
2 3 3 1 5138.74 3590 4155.85 /
3 1 1 1 8202.54 8206.84 8494.42 /
3 1 2 1 8081.09 8085.64 8397.43 /
3 1 3 1 7436.73 7142.24 8450.65 /
3 2 1 1 9393.27 9014.22 9196.49 /
3 2 2 1 9308.64 8911.21 9105.01 /
3 2 3 1 8567.24 7774.64 8436.27 /
3 3 1 1 9912.37 9798.83 9952.61 /
3 3 2 1 9906.65 9776.86 9924.11 /
3 3 3 1 9813.74 9404.22 9463.37 /
E4 IPR
*
* This is an example IPR input file
*
The format is pressure, rate, curve value
*
The numbers can be space, tab or comma delimited
* Up to twenty points per curve, up to five curves
*
*Blank lines or lines with an asterisk (*) in the first
* column are ingored.
*
0 5000 1000
1000 4000 1000
2000 3000 1000
3000 2000 1000
4000 1000 1000
5000 0 1000
*
* Next curve
*
0 3000 2000
1000 2000 2000
2000 1000 2000
3000 0 2000
E5 ESP PUMPS
* Blank lines or lines begining with an asterisk are ignored.
* The format for the pump data is
* Line 1 Manufacturer pumpname size (ins) frequency(hz) Min. rte Max. rate No. of Stages
* Line 2 six coefficients for head curve (ft of water)
* Line 3 six coefficients for power curve (HP)
****************************
****************************
****************************
*** CENTRILIFT PUMPS ***
****************************
****************************
****************************
PROSPER MANUAL
4-6 APPENDIX E - FILE FORMATS
E6 ESP MOTORS
*Manufacturer
Reda
2 3450. 60.0
*Series OD
456 4.56
*amps
6.53822E-01 -1.34128E+00 8.86349E-01 -1.06114E-01 5.61883E-01 3.43896E-01 *
*rpm
-6.24718E+01 2.04999E+02 -3.03911E+02 1.45552E+02 -1.15803E+02 3.58291E+03 *
*efficiency
-5.57129E-01 1.60591E+00 -7.30540E-01 -1.98693E+00 2.49918E+00 1.91886E-03 *
* power factor
-5.44220E-01 2.16557E+00 -2.81504E+00 7.11957E-01 1.04810E+00 2.49609E-01 *
*Series OD
540 5.4
*amps
-2.16508E-01 6.79101E-01 -5.79651E-01 3.59379E-01 5.24583E-01 2.26834E-01 *
*rpm
-2.14557E+01 8.55182E+01 -1.66122E+02 9.44086E+01 -1.44510E+02 3.58175E+03 *
*efficiency
3.67150E-01 -1.64327E+00 3.01018E+00 -3.02514E+00 1.72215E+00 4.17187E-01 *
* power factor
4.64765E-01 -2.48102E+00 5.12024E+00 -5.23541E+00 2.71560E+00 2.75835E-01 *
E7 ESP CABLES
* Cable Type
* Volt drop coefficient Maximum ampage
#1 Copper
0.26 115
#2 Copper
0.33 95
#4 Copper
0.53 70
#6 Copper
0.84 55
#8 Copper
1.32 50
#10 Copper
2.08 50
#12 Copper
3.32 50
#1 Aluminium
0.33 95
#2 Aluminium
0.53 70
#4 Aluminium
0.84 55
#6 Aluminium
1.32 50
#8 Aluminium
2.08 50
#10 Aluminium
3.32 50
E8 HSP PUMPS
*
* H Y D R A U L I C D R I V E D O W N H O L E P U M P S
* ================= ========= =============== =========
****************************
****************************
****************************
*** WEIR PUMPS ***
****************************
****************************
****************************
E9 HSP TURBINES
Turbine Manufacturer
WEIR
* Number of Turbines
1
****************
* *
* WEIR T30 *
* *
****************
* Turbine Type
T30
PROSPER MANUAL
6-6 APPENDIX E - FILE FORMATS
* Number of Settings
4