KP 8

Download as pdf or txt
Download as pdf or txt
You are on page 1of 106

KP8, KP8F ___________________

Preface

___________________
Overview 1
Safety instructions and
___________________
approvals 2
SIMATIC HMI
___________________
Planning the use 3
HMI device
KP8, KP8F ___________________
Mount and connect KP8 and
KP8F 4

___________________
Operator controls and
displays 5
Operating Instructions
___________________
Setting the KP8 and KP8F 6

___________________
Operating KP8F in a fail-safe
manner 7

___________________
Maintain and service KP8
and KP8F 8

___________________
Technical specifications 9

___________________
Appendix A

___________________
Abbreviations B

10/2010
A5E03284305-01
Legal information
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.

DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.

CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.

NOTICE
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation for the specific task, in particular its warning notices and
safety instructions. Qualified personnel are those who, based on their training and experience, are capable of
identifying risks and avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:

WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be adhered to. The information in the relevant documentation must be observed.

Trademarks
All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Siemens AG A5E03284305-01 Copyright © Siemens AG 2010.


Industry Sector Ⓟ 10/2010 Technical data subject to change
Postfach 48 48
90026 NÜRNBERG
GERMANY
Preface

Purpose of the operating instructions


This operating manual provides information for manuals derived from the requirements for
mechanical engineering documentation according to DIN EN 62079. This information relates
to the place of use, transport, storage, mounting, use and maintenance.
These operating instructions are intended for:
● Project planning engineers
● Users
● Commissioning engineers
● Maintenance personnel
Pay particular attention to the chapter "Safety Instructions (Page 19)".

Required knowledge
General knowledge of automation technology and process communication is needed to
understand the operating instructions.
It is also assumed that those using the manual have experience in using personal computers
and an understanding of Microsoft operating systems.
You must have knowledge about the STEP 7 software and about safety-related technology.

Scope
The operating instructions applies to the following HMI devices:
● KP8, order number 6AV3688-3AY36-0AX0
● KP8F, order number 6AV3688-3AF37-0AX0

Note
The manual is part of the HMI device and will be required for repeat commissioning.
Retain all enclosed and additional documents for the entire service life of the HMI device.
You must pass on all these documents to future owners of the HMI device.

Registered trademarks
The following designations marked with the protective note ® are registered trademarks of
the Siemens AG:
● HMI®
● SIMATIC®
● WinCC®

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 3
Preface

Notes on fail-safe operation


The following sections of these operating instructions contain important information about the
fail-safe operation of the KP8F:
● Safety instructions and approvals (Page 19)
● Requirements for fail-safe operation (Page 36)
● Connecting the HMI device (Page 42)
● Setting KP8F - STEP 7 (Page 64)
● Operating KP8F in a fail-safe manner (Page 73)
● Sensor evaluation of the fail-safe channels (Page 93)

Documentation for fail-safe systems


● System description "Safety technology in SIMATIC S7"
– Provides general information on the use, structure, and mode of operation of the fail-
safe automation systems S7 Distributed Safety and S7 F/FH Systems
– Contains detailed technical information which can be represented for the fail-safe
technology both in S7-300 and S7-400.
– Contains information about the calculation of monitoring and reaction times of the fail-
safe systems "S7 Distributed Safety" and of "S7 F/FH Systems".
● "S7 Distributed Safety, Configuring and Programming" Manual and Online Help
Describes the configuration of the F-CPU and of the fail-safe I/O and the programming of
the F-CPU in F-FBD or F-LAD
● "Automation System S7-1200, CPU Data" Reference Manual
Describes the standard functions of the CPU 1211C, CPU 1212C and CPU 1214C.
● "Automation System S7-400, CPU Data" Reference Manual
Describes the standard functions of CPU 416F-3 PN/DP, CPU 414-3 PN/DP and
CPU 416-3 PN/DP
● "Automation System S7-300, CPU Data" Reference Manual
Describes the standard functions of CPU 315F-2 PN/DP, CPU 317F-2 PN/DP, CPU 315-
2 PN/DP and CPU 317-2 PN/DP.

KP8, KP8F
4 Operating Instructions, 10/2010, A5E03284305-01
Preface

Style conventions
This manual uses the following style conventions:

Style Convention Scope


"Add screen"  Terminology in the user interface, for example dialog names,
tabs, buttons, menu commands
 Required input, for example, limits, tag values.
 Path information
"File > Edit" Operational sequences, for example, shortcut menu commands
<F1>, <Alt+P> Keyboard operation
Please observe notes labeled as follows:

Note
A note contains important information about the product described in the manual and its use,
or a specific section of the manual to which you should pay particular attention.

Naming conventions
This manual uses the following naming conventions:

Naming convention Applies to


Plant  System
 Machining center
 One or more machines
Actuate  By means of the touch screen on the HMI device
 By means of the button on the HMI device
 By operating a mouse on the HMI device
Switching cabinet  Mounting cabinet
 Switching cabinet
 Switchboard
 Console

Figures
This manual contains illustrations of the described devices. The illustrations can deviate from
the details of the delivered device.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 5
Preface

Technical Support
Technical support for the products covered in the manual is available in the Internet at:
● Technical Support (http://support.automation.siemens.com/WW/view/en/4000024)
● Support Request (http://support.automation.siemens.com/WW/view/en/16605654)
● Service (http://support.automation.siemens.com/WW/view/en/16604318)
● Contacts and office locations (http://www.automation.siemens.com/mcms/aspa-
db/en/Pages/default.aspx)
● Training center (http://sitrain.automation.siemens.com/sitrain/default.aspx?AppLang=en)
Additional information on SIMATIC products is available in the Internet at:
● Industry Portal (http://www.automation.siemens.com/_en/portal/index.htm)
● Overall SIMATIC documentation
(http://www.automation.siemens.com/simatic/portal/html_76/techdoku.htm)

Recycling and disposal


The products described in this manual are recyclable because of the low level of
contaminants in their components. Contact a certified disposal service company for
environmentally sound recycling and disposal of your old devices.

Used batteries and rechargeable batteries


Used batteries and lithium ion batteries are hazardous waste. Always dispose of used
batteries and lithium ion batteries properly in accordance with the regulations in effect.
Identify the container provided for this purpose with the label, "Used batteries and
rechargeables".

Note
Batteries and rechargeables do not belong in the garbage. The user is legally obliged to
return used batteries and rechargeable batteries. You can deposit used batteries and
rechargeables at any public collection site and anywhere batteries or rechargeables of
similar type are sold.

You can also send batteries and rechargeables to the following address:
Siemens AG
Industry Sector
Returns Center
Siemensstr. 2
90766 Fürth
Germany

KP8, KP8F
6 Operating Instructions, 10/2010, A5E03284305-01
Table of contents

1 Overview.................................................................................................................................................. 11
1.1 Product Overview.........................................................................................................................11
1.2 Scope of delivery .........................................................................................................................11
1.3 Design of KP8 and KP8F .............................................................................................................12
1.4 Accessory kit ................................................................................................................................14
1.5 Service packages.........................................................................................................................15
1.6 Performance features ..................................................................................................................15
1.7 Communication and enabled PLCs .............................................................................................16
1.8 Operating KP8F in a fail-safe manner .........................................................................................16
2 Safety instructions and approvals ............................................................................................................ 19
2.1 Safety Instructions .......................................................................................................................19
2.2 Approvals .....................................................................................................................................21
2.3 TÜV certificate..............................................................................................................................23
2.4 Notes about Usage ......................................................................................................................23
2.5 Electromagnetic compatibility ......................................................................................................26
3 Planning the use ...................................................................................................................................... 29
3.1 "Plan use" check list.....................................................................................................................29
3.2 Ambient conditions for storage and transport ..............................................................................29
3.3 Ambient conditions for operation .................................................................................................30
3.4 Mounting Positions and Type of Fixation.....................................................................................32
3.5 Preparing for Mounting ................................................................................................................34
3.6 Insulation resistance, protection class and degree of protection.................................................36
3.7 Requirements for fail-safe operation............................................................................................36
3.7.1 Sensor for 1oo1 mode .................................................................................................................36
3.7.2 Sensor for 1oo2 mode .................................................................................................................38
3.7.3 Cables ..........................................................................................................................................40

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 7
Table of contents

4 Mount and connect KP8 and KP8F.......................................................................................................... 41


4.1 "Mounting and connection of HMI device" checklist ................................................................... 41
4.2 Check the scope of delivery ........................................................................................................ 41
4.3 Mounting the HMI device ............................................................................................................ 41
4.4 Connecting the HMI device ......................................................................................................... 42
4.4.1 Connection sequences and lines ................................................................................................ 42
4.4.2 Ports ............................................................................................................................................ 43
4.4.3 Connecting the power supply...................................................................................................... 44
4.4.4 Connect standard inputs/outputs ................................................................................................ 45
4.4.5 Connect KP8F - fail-safe inputs .................................................................................................. 46
4.4.6 Connecting the PLC .................................................................................................................... 48
4.5 Switching on and testing the HMI device .................................................................................... 50
4.6 Securing the cables..................................................................................................................... 51
5 Operator controls and displays ................................................................................................................ 53
5.1 Front-sided control elements and displays ................................................................................. 53
5.2 Rear operator controls and displays ........................................................................................... 54
5.3 Labeling keys .............................................................................................................................. 55
6 Setting the KP8 and KP8F ....................................................................................................................... 57
6.1 "Setting the KP8 and KP8F" checklist......................................................................................... 57
6.2 Integrating GSD in STEP 7 ......................................................................................................... 57
6.3 Setting controller - communication HMI device........................................................................... 58
6.4 Configuring Media Redundancy Protocol ................................................................................... 61
6.5 Setting KP8F - STEP 7 ............................................................................................................... 64
6.6 Setting PROFIsafe address for KP8F ......................................................................................... 67
6.7 KP8F – Configure Shared Device ............................................................................................... 68
6.8 KP8F – Configure Shared Device for non fail-safe controller ..................................................... 71
7 Operating KP8F in a fail-safe manner...................................................................................................... 73
7.1 Overview ..................................................................................................................................... 73
7.2 Passivate HMI device.................................................................................................................. 74
7.3 Error diagnostics ......................................................................................................................... 75
7.4 Repair error and reintegrate........................................................................................................ 76
7.5 Response times of the PROFIsafe devices ................................................................................ 78
8 Maintain and service KP8 and KP8F ....................................................................................................... 81
8.1 Maintenance and care................................................................................................................. 81
8.2 Spare parts and repairs............................................................................................................... 82

KP8, KP8F
8 Operating Instructions, 10/2010, A5E03284305-01
Table of contents

9 Technical specifications........................................................................................................................... 83
9.1 Dimensional diagram ...................................................................................................................83
9.2 Technical specifications ...............................................................................................................84
9.3 Fail-safe mode .............................................................................................................................86
9.4 Interface description.....................................................................................................................89
9.4.1 Inputs and outputs KP8................................................................................................................89
9.4.2 Inputs and outputs KP8F .............................................................................................................90
9.4.3 PROFINET ...................................................................................................................................91
9.5 Bit assignment in the process image ...........................................................................................91
9.6 Sensor evaluation of the fail-safe channels .................................................................................93
A Appendix.................................................................................................................................................. 95
A.1 ESD guideline ..............................................................................................................................95
B Abbreviations........................................................................................................................................... 97
Glossary .................................................................................................................................................. 99
Index...................................................................................................................................................... 103

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 9
Table of contents

KP8, KP8F
10 Operating Instructions, 10/2010, A5E03284305-01
Overview 1
1.1 Product Overview

Application scenarios of the HMI device


The HMI device shows you operating states of a plant. You can actively control a running
production process based on this information.
The HMI device is designed for mounting in control panels, and replaces keys and LEDs that
are individually mounted. The HMI device is mounted in a mounting cut-out and connects to
a SIMATIC controller via PROFINET. The HMI device can be set for immediate use. In
comparison to conventional wiring, substantially less time is needed for commissioning and
the device provides increase security against failure during runtime.

Fail-safe mode with KP8F


Thanks to the integrated PROFIsafe communication, the HMI device can be used in fail-safe
mode for simple sensor applications. In regards to the safety-relevant signals, safety
categories SIL3, Performance Level e and category 4 are reached.
The KP8 and the KP8F are intended for installation in the following extension units:
● Extension Unit 15", Order number 6AV7674-0KG00-0AA0
● Extension Unit 19" left, order number 6AV7674-0KH00-0AA0
● Extension Unit 19" right, order number 6AV7674-0KJ00-0AA0

1.2 Scope of delivery


The scope of delivery includes:
● 1 KP8 or KP8F
● 1 accessory kit
● 1 data carrier with ATEX handbook

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 11
Overview
1.3 Design of KP8 and KP8F

1.3 Design of KP8 and KP8F

Front view and side view

① Labeling strips
② Oblong holes for a mounting clamp
③ Keyboard

Plan view

KP8, KP8F
12 Operating Instructions, 10/2010, A5E03284305-01
Overview
1.3 Design of KP8 and KP8F

Rear view KP8

① Power supply connection and digital inputs and outputs


② Bar for strain relief
③ Seal
④ PROFINET interfaces

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 13
Overview
1.4 Accessory kit

Rear view KP8F




① Power supply connection and digital inputs and outputs


② Bar for strain relief
③ DIP switch
④ Seal
⑤ PROFINET interfaces

1.4 Accessory kit


The accessory kit for the KP8 contains:
● A 12-pin plug connector
● Four mounting clamps for mounting the HMI device
The accessory kit for the KP8F contains the following:
● A 16-pin plug connector
● Four mounting clamps for mounting the HMI device
The accessory kit can include documents.

KP8, KP8F
14 Operating Instructions, 10/2010, A5E03284305-01
Overview
1.5 Service packages

1.5 Service packages

KP8
This service pack contains:
1 set connector, 12-pin, order number 6AV6671-3XY39-4AX0

KP8F
This service pack contains:
1 set connector, 16-pin, order number 6AV6671-3XY49-4AX0

KP8, KP8F
This service pack contains:
1 set plastic mounting clamps, order number 6AV6671-8XK00-0AX2

1.6 Performance features

Performance features KP8


The HMI device offers a wide range of features that can be used without the need for
programming:
● 8 short-stroke keys with integrated LEDs
The LEDs allow for the display of different colors. The colors red, yellow, blue, green and
white are displayable.
● 8 clamps, rear
The clamps are used as digital inputs or outputs to the connection of external sensors.
● Integrated light and button tests - after turning on the HMI device
● Communication via PROFINET
● SIMATIC design
Through this, the HMI devices can be arranged closely next to each other.

Expansion with external input/output devices


The functionality of the HMI device can be extended using input and output devices, for
example lamps or key switches.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 15
Overview
1.7 Communication and enabled PLCs

Performance features KP8F


The KP8F has the following additional performance features compared to the KP8:
● Fail-safe digital inputs for:
– An EMERGENCY STOP button or alternatively
– Two single-channel evaluations

1.7 Communication and enabled PLCs

Enabled PLCs
The HMI device has been enabled for use with the following type of PLC:
● SIMATIC S7-1200
● SIMATIC S7-400, SIMATIC S7-400F
● SIMATIC S7-300, SIMATIC S7-300F
● WinAC and Embedded Controllers

NOTICE
Safety-related communication
A non fail-safe control does not provide any safety-directed communication.
A SIMATIC S7F PLC is required for fail-safe communication.

Released protocols
The HMI device uses the following protocols for communication with the controller:
● PROFINET IO for standard communication
● PROFIsafe Mode V2.0 for the fail-safe communication of the KP8F

1.8 Operating KP8F in a fail-safe manner

Configuring software
For fail-safe operation of the HMI device, the following software is required:
● STEP 7 V5.5
● SIMATIC S7 Distributed Safety, as of V5.4

KP8, KP8F
16 Operating Instructions, 10/2010, A5E03284305-01
Overview
1.8 Operating KP8F in a fail-safe manner

Fail-safe automation system


Fail-safe automation system (F systems) are used in plants requiring higher levels of safety.
F systems control production processes in such a way that residual error probability is taken
into consideration to achieve a safe operating state when a shutdown occurs. An immediate
shutdown therefore does not pose a danger to people or the environment.

Operating KP8F in a fail-safe manner


The KP8F device is a PROFINET IO device on Industrial Ethernet.
In fail-safe mode the HMI device registers the signal states of compatible emergency stop
buttons and transmits corresponding safety frames to the controller. The controller and the
HMI device communicate with each other using the fail-safe protocol, PROFIsafe.
The HMI device can operate in fail-safe mode corresponding to SIL3, Performance Level e
and category 4 if the safety functions are appropriately configured in STEP 7 with the "S7
Distributed Safety" add-on package.
Fail-safe mode of the HMI devices differs from standard mode essentially in that during
communication, the signals are checked for being error-free (error-safe). In the event of a
fault, the HMI device is placed in a safe state.
The fail-safe connection fulfills the following requirements:
● Single-channel mode with 1oo1 parameterization
– Safety category SIL2 corresponding to IEC 61508:2010
– Safety category Performance Level d corresponding to IEC 13849:2006
– Safety category category 3 corresponding to EN 954:1996
● Two-channel mode with 1oo2 parameterization
– Safety category SIL3 corresponding to IEC 61508:2010
– Safety category Performance Level e corresponding to IEC 13849:2006
– Safety category category 4 corresponding to EN 954:1996
The HMI device can be operated simultaneously in standard mode and fail-safe mode.

Diagnostics function of KP8F


The fail-safe KP8F includes non-configurable diagnostic functions. The diagnostics functions
are always active. The diagnostics result is automatically made available by the HMI device
in STEP 7 and passed on to the fail-safe controller in the event of a fault.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 17
Overview
1.8 Operating KP8F in a fail-safe manner

Example configuration of a F-system with KP8F

6,0$7,&6)31'3
DV352),1(7,2FRQWUROOHU
6WDQGDUG+RVW636 (7b6VWDWLRQ
DV352),1(7,2 ZLWK
FRQWUROOHU ,031

352),1(7

+0,DQG ),2DV .3DV .3)DV


REVHUYDWLRQGHYLFH 352),1(7,2 352),1(7,2 352),1(7,2
'HYLFH 'HYLFH 'HYLFH

The example shows the simultaneous operation of fail-safe and non fail-safe devices.
In the example, each PROFINET IO device communicates with just one PROFINET IO-
controller. The PROFIsafe device communicates here exclusively with the F-PROFINET IO
controller.

KP8, KP8F
18 Operating Instructions, 10/2010, A5E03284305-01
Safety instructions and approvals 2
2.1 Safety Instructions

WARNING
Injury or material damage
If you do not follow precisely the safety guidelines and manuals in this handbook, this may
result in sources of danger and make safety functions ineffective. This can result in
personal injuries or material damage.
Follow the safety guidelines and instructions precisely.

Observe the safety and accident prevention instructions applicable to your application in
addition to the safety instructions given in this manual.

Project security

WARNING
Injury or material damage
The configuration engineer for a system PLC must take precautions so that an interrupted
program can be restarted normally after voltage dips or power failures.
A dangerous operating state must not occur during the entire process of the control
program, also during troubleshooting - also not in the short-run.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 19
Safety instructions and approvals
2.1 Safety Instructions

Safety during commissioning and operation

WARNING
Installation according to the instructions
Commissioning of the HMI device is forbidden until it has been absolutely ensured that the
machine which is to be operated with the HMI device complies with Directive 2006/42/EC.
Before commissioning, check to see if the regulations of the directive 2006/42/EC are
fulfilled.
Open-type resource
The HMI device is an open-type resource. This means that the HMI device may only be
installed in cabinets that allow the device to be operated from the front side.
Access to the control cabinet in which the HMI device is installed should only be possible
by means of a key or tool and only for trained and authorized personnel.
Danger, high voltage
Opening the cabinet will expose high voltage parts. Contact with these parts could be fatal.
Switch off the power supply to the cabinet before opening it.

When operating the HMI device in hazardous areas the following warning applies.

WARNING
Explosion Hazard
Do not disconnect while circuit is live unless area is known to be non-hazardous.
Substitution of components may impair suitability for Class I, Division 2 or Zone 2.

Safety during operation

Note
High frequency radiation, from mobile phones for example, can cause unintentional
operating situations.

Recall

Note
If a safety case occurs for the KP8F, the customer of the KP8F will be immediately informed
by the Siemens sales department they ordered from and told about suitable measures.

KP8, KP8F
20 Operating Instructions, 10/2010, A5E03284305-01
Safety instructions and approvals
2.2 Approvals

2.2 Approvals

Note
The following overview shows possible approvals for the HMI device.
The HMI device itself is certified as shown on the label on its rear panel.

CE mark
The HMI device meets the general and safety-related requirements of the following EU
directives and conforms to the harmonized European standards for programmable logic
controllers published in the official gazettes of the European Union:
● 2004/108/EC "Electromagnetic Compatibility" (EMC Directive)
● 2006/95/EC "Electrical Equipment Designed for Use within Certain Voltage Limits" (Low-
voltage Directive)

EC Declaration of Conformity
The EC Declarations of Conformity are kept available for the responsible authorities at the
following address:
Siemens AG
Industry Sector
I IA AS RD ST PLC
P.O. Box 1963
D-92209 Amberg, Germany

Explosion protection approval


For the HMI device
● EN 60079-0
● EN 60079-15
● EN 61241-0
● EN 61241-1
the following approvals are in place:

II 3 G II 3 G Ex nA II T4
II 3 D Ex tD A22 IP6X T xx °C
– x ... Temperature values, see design examination certificate
The design examination certificate is available at the following Internet address:
Technical Support (http://support.automation.siemens.com/WW/view/en/4000024)

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 21
Safety instructions and approvals
2.2 Approvals

FM approval
"Factory Mutual Research" approval in accordance with Approval Standard Class
Number 3611, 3600, 3810
Approved for use in:
● Class I, Division 2, Group A, B, C, D Tx
● Class I, Zone 2, Group IIC Tx

UL approval
"Underwriters Laboratories Inc." approval in accordance with:
● UL 508 (Industrial Control Equipment)
● CSA C22.2 No. 142, (Process Control Equipment)
or
"Underwriters Laboratories Inc." approval in accordance with:
● UL 508 (Industrial Control Equipment)
● CSA C22.2 No. 142, (Process Control Equipment)
● UL 1604 (Hazardous Location)
● CSA-213 (Hazardous Location)
Approved for use in:
● Class I, Division 2, Group A, B, C, D or
● Class I, Zone 2, Group IIC or
● Non-hazardous locations

Approval for Australia


The HMI device fulfills the requirements of standard AS/NZS 2064 (Class A).
N117

KP8, KP8F
22 Operating Instructions, 10/2010, A5E03284305-01
Safety instructions and approvals
2.3 TÜV certificate

2.3 TÜV certificate


The HMI device is certified according to the following standards. The latest edition of the
standard can be found in the report for the Technical Inspectorate Certificate.

Safety subject Standard


Functional safety IEC 61508:2010
IEC 13849:2006
Basic safety IEC 61131-2:2007
Machine Safety EN 60204-1:2007
NFPA 79:2007
IEC 62061:2005
IEC 61511:2003
ISO 13850:2006
You can obtain a copy of certificates and reports from the Technical Inspectorate at the
following address:
Siemens Aktiengesellschaft
Industry Sector
I IA AS RD ST
P.O. Box 1963
D-92209 Amberg
You can find the certificates from the Technical Inspectorate in the Internet at the following
address:
"Technical Support (http://support.automation.siemens.com/WW/view/en/4000024)"

2.4 Notes about Usage


The HMI device is designed for industrial use, limit class A. The following standards are met:
● Requirements for emissions EN 61000-6-4:2007
● Requirements for interference immunity DIN EN 61000-6-2:2005

Note
The HMI device is not suitable for operation in residential areas: Operation of an HMI
device in residential areas can have a negative impact on radio and TV reception.

If the HMI device is used in a residential area, you must take measures to achieve Limit
Class B conforming to EN 55016 for RF interference.
Suitable measures to achieve Limit Class B for suppression of radio interference include:
● Installation of the HMI device in a grounded control cabinet
● Use of filters in electrical supply lines
Individual acceptance is required.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 23
Safety instructions and approvals
2.4 Notes about Usage

Operation in potentially explosive atmosphere, zone 2 and 22

DANGER
Degree of hazard
There is an explosion hazard when operating an HMI device that does not have explosion
protection.
Operate the HMI device in potentially explosive zones 2 and 22 only if it has been approved
and certified for such environments.

If an HMI device is operated in potentially explosive atmospheres of zone 22, pay attention
to the product information "Use in potentially explosive atmospheres of zones 2 and 22." The
product information is available at the following Internet address:
Technical Support (http://support.automation.siemens.com/WW/view/en/4000024)

WARNING
Personal injury and damage to property
Personal injury and property damage can occur in potentially explosive atmospheres if an
electric connection is disconnected from the HMI device while the system is in operation.
In potentially explosive atmospheres, always turn off power to the HMI device before
disconnecting any electrical connections..

Potentially explosive atmosphere zones 2 and 22


Areas subject to explosion hazard are divided into zones. The zones are differentiated
according to the probability of the existence of an explosive atmosphere.

Zone Degree of hazard Example


2 Explosive gaseous atmosphere occurs only Areas around flanged pipe joints
seldom and for a short period with flat gaskets in closed rooms
22 Area in which a potentially explosive –
atmosphere in the form of a cloud in the air
containing flammable dust does not usually
occur or occurs only briefly during normal
operation .
Safe zone No  Outside zone 2
 Outside zone 22
 Standard applications of
distributed I/Os

KP8, KP8F
24 Operating Instructions, 10/2010, A5E03284305-01
Safety instructions and approvals
2.4 Notes about Usage

Operating conditions for Zones 2 and 22


The following operating conditions apply for Zones 2 and 22:
● The HMI device must be installed in a control cabinet. The control cabinet must meet the
following in accordance with EN 60529:
– Protection type IP54 or higher for Zone 2
– Protection type IP5x or higher for Zone 22 in case of non conductive dust
– Protection type IP6x or higher for Zone 22 in case of conductive dust
You must install the HMI device so that you provide at least protection type IP54 or IP5x
to EN 60529 on the front of the device. Consult the operating instructions of control
cabinet and HMI device for this purpose.
Make allowances for the operating and ambient conditions under which you operate the
HMI device. A manufacturer's declaration must be provided for the control cabinet in
accordance with EC Directive 94/9, stating it is fit for purpose.
● The ambient temperature range is 0 °C ≤ T ≤ 50 °C. Under these conditions, the HMI
device will satisfy temperature class Tx for category 3G and support a maximum surface
temperature of xx °C for category 3D. (x ... Temperature value, see design examination
certificate).
Refer to the operating instructions for details of limitations resulting from the ambient
temperature range.
● In situations where the temperature on the cable at the cable inlet of the control cabinet
exceeds a temperature of 70 °C, or where the temperature on the wire branching point
exceeds 80 °C under operating conditions, the temperature specifications of the cables
must match the actually measured temperatures.
● Put measures in place to ensure the rated voltage is not exceeded.
Any transient interference voltages above the rated value must not exceed 40 %.
● Protect the HMI device from mechanical loads > 4 joule and the display from mechanical
loads > 2 joule.
● Ensure that the atmosphere is not explosive during servicing.
Measures that impair or remove the protection type of the HMI device are not permitted
while the system is in operation.
● If the HMI device was dismantled, check the mounting seal for damage before
reassembling the HMI device. A damaged, porous or used mounting seal no longer
meets the requirements of the protection type. In this case, the mounting seal must be
replaced.
● Turn off the HMI device and the entire electrical installation in the control cabinet, if the
film on the front of the HMI device or the glass of the display on the HMI device are
damaged by a tear or hole or if the front film starts to peel off.
Replace the HMI device. Restart the system again after the device has been exchanged.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 25
Safety instructions and approvals
2.5 Electromagnetic compatibility

2.5 Electromagnetic compatibility


The HMI device fulfils, among other things, the requirements of the EMC laws pertaining to
the European domestic market.

EMC-compliant installation of HMI devices


An EMC-compliant installation of the HMI device and the use of interference-proof cables
form the basis of trouble-free operation. The following documentation applies to the
mounting of the HMI device:
● Description "Directives for interference-free installation of PLCs"
(http://support.automation.siemens.com/WW/view/de/1064706)"
● The manual "PROFINET System Description"

Pulseshaped Interference
The following table shows the electromagnetic compatibility of modules compared to pulse-
shaped interference. These specifications only apply when the HMI device meets the
specifications and directives regarding electrical installation.

Pulse-shaped interference Tested with Corresponds to test


intensity
Electrostatic discharge Air discharge: 8 kV 3
conforming to IEC 61000-4- Contact discharge: 6 kV
2:2008
Bursts 2 KV power supply cable 3
(high-speed transient 2 KV signal cable, > 30 m
interference) 1 KV signal cable, < 30 m
in accordance with IEC 61000-
4-4:2004
High-power surge pulses in accordance with IEC 61000-4-5:2005, external protective circuit required
(refer to manual S7-300 PLC, Installation, chapter "Lightning and overvoltage protection").
Asymmetric coupling 2 kV power cable 3
DC voltage with protective elements
2 KV signal/data cable, > 30 m,
with protective elements as required
Symmetric coupling 1 kV power cable 3
DC voltage with protective elements
1 KV signal cable, > 30 m,
with protective elements as required

KP8, KP8F
26 Operating Instructions, 10/2010, A5E03284305-01
Safety instructions and approvals
2.5 Electromagnetic compatibility

Sinusoidal interference
The table below shows the EMC properties of the modules with respect to sinusoidal
interference. These specifications only apply when the HMI device meets the specifications
and directives regarding electrical installation.

Sinusoidal interference Test values Corresponds


to test
intensity
HF radiation (in  80% amplitude modulation at 1 kHz 3
electromagnetic fields) in with 10 V/m in the range of 80 MHz to 1 GHz
accordance with IEC 61000- with 3 V/m in the range 1.4 GHz to 2 GHz
4-3:2006 with 1 V/m the range 2 GHz to 2.7 GHz
 10 V/m with 50 % pulse modulation at 900 MHz
10 V/m with 50 % pulse modulation at 1.89 GHz
RF interference current on Test voltage 10 V at 80 % amplitude modulation of 3
cables and cable shielding 1 kHz in the range from 9 kHz to 80 MHz
conforming to IEC 61000-4-
6:2008

Emission of radio interference


The table below shows the emission values of electromagnetic interference conforming to
55011:2009, limit value class A, Group 1, measured at a distance of 10 m:

30 to 230 MHz < 40 dB (V/m) quasi-peak


230 to 1000 MHz < 47 dB (V/m) quasi-peak

Note
Before you connect the HMI device to the public power grid, ensure that it is compliant with
Limit Class B in accordance with EN 55022:2006.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 27
Safety instructions and approvals
2.5 Electromagnetic compatibility

KP8, KP8F
28 Operating Instructions, 10/2010, A5E03284305-01
Planning the use 3
3.1 "Plan use" check list
Before deploying the HMI device, you should check that the planned application of the HMI
device complies with the following test steps.

Test step Information Check


Check climatic and mechanical ambient Ambient conditions for storage and
conditions transport (Page 29)
Set mounting position, installation location and Mounting Positions and Type of Fixation
mounting type of the HMI device (Page 32)
Prepare installation cut-out Preparing for Mounting (Page 34)
Check insulation voltage, protection class and Insulation resistance, protection class and
seal tightness degree of protection (Page 36)
Check compliance with the technical data
Select sensors for fail-safe operation Sensor for 1oo1 mode (Page 36)

3.2 Ambient conditions for storage and transport


The shipping conditions of this HMI device exceed requirements in accordance with
IEC 61131-2:2007. The following specifications apply to devices that are shipped and stored
in the original packaging.
The climatic ambient conditions conform to the following standards:
● IEC 60721-3-3:1994, Class 3K7 for storage
● IEC 60721-3-2:1997, Class 2K4 for transportation
The mechanical ambient conditions are compliant with IEC 60721-3-2:1997, Class 2M2.
In the following table, the tests are contained that were checked on the HMI device in
regards to the ambient conditions for transport and storage.

Test Permitted range


Drop test, in transport package ≤1m
Temperature –40 to +70 °C
Air pressure 1080 hPa to 660 hPa,
acc. to IEC 60068-2-13:1983 corresponds to an elevation of –1000 to 3500 m
Switching frequency, max. 2 hPa, between front and rear
Humidity, relative 10% to 95 %, without condensation

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 29
Planning the use
3.3 Ambient conditions for operation

Test Permitted range


Vibration, sinusoidal as per  5 to 8 Hz, 3.5 mm, 10 cycles per axis
IEC 60068-2-6:2007  8 to 500 Hz, 9.8 m/s2, 10 cycles per axis
Test Fc
Shock 250 m/s2, 6 ms, 1000 shocks
as per IEC 60068-2-27:2008
Test Ea

NOTICE
Equipment failure
Moisture and condensation lead to malfunction. Moisture in the form of condensation on or
in the device is formed:
 When transporting a device at low temperatures
 Under extreme temperature variations
Bring the device to room temperature before operating.
Condensation
When condensation is on the device, do not expose the HMI device to direct radiation from
a heater.
If condensation has developed, wait approximately 4 hours until the HMI device has dried
completely before switching it on.

The following points must be adhered to in order to ensure a fault-free and safe operation of
the HMI device:
● Proper transportation and storage
● Proper installation and mounting
● Careful operation and maintenance
The warranty for the HMI device will be deemed void if these stipulations are not heeded.

3.3 Ambient conditions for operation

Mechanical and climatic ambient conditions


The HMI device is designed for use in a location protected from the effects of the weather.
The ambient conditions meet the requirements for IEC 60721-3-3 Edition 2.2:2002:
● Mechanical requirements according to class 3M3
● Climatic requirements according to class 3K3

KP8, KP8F
30 Operating Instructions, 10/2010, A5E03284305-01
Planning the use
3.3 Ambient conditions for operation

Use with additional protective measures


You may only use the HMI device at the following locations with additional protective
measures:
● In locations with a high degree of ionizing radiation
● In locations with difficult operating conditions, for example due to:
– Corrosive vapors, gases, oils or chemicals
– Electrical or magnetic fields of high intensity
● In systems that require special monitoring, for example:
– Elevators
– Systems in especially hazardous rooms

Damping shock and vibration


If the HMI device is subjected to strong shocks or vibrations - as specified in the following
table - you must take appropriate measures to reduce amplitudes or acceleration. In such
situations, use vibration damping or vibration absorber systems for the HMI device and
accessories.

Testing mechanical ambient conditions


In the following table contains tests that were checked on the HMI device in regards to the
ambient conditions for operation.

Test Physical variable Value


Vibrations Vibration 1 octave/min
IEC 60068-2-6:2007 10 cycles per axis
Test Fc Frequency band 5 to 8.4 Hz:
Deflection 3.5 mm
8.4 to 150 Hz
Vibration acceleration 9.8 m/s
Shock Shock form Half sine
IEC 60068-2-27:2008 Acceleration 150 ms-2
Test Ea
Duration 11 ms
Number of shocks 3 per axis
Case Fall height 0.3 m, five times
DIN EN 60068-2-31:2009
Test Ec

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 31
Planning the use
3.4 Mounting Positions and Type of Fixation

Testing climatic ambient conditions


In the following table, contains the tests that were checked on the HMI device in regards to
the climatic ambient conditions for operation.

Ambient condition Permitted range Comment


Operating temperature See Mounting Positions and –
Type of Fixation (Page 32)
Humidity, relative < 95 %, –
IEC 61131-2:2007 No condensation
Humidity, absolute 1 to 25 g/m3 –
Air pressure 1080 to 795 hPa Corresponds to an
IEC 60068-2-13:1983 elevation of –1000 to 2000 m
Hazardous material SO2 < 0.5 vpm, Test: 10 cm3/m3; 10 days
concentration relative humidity < 60%,
IEC 60721-3-3:1994 no condensation
H2S < 0.1 vpm, Test: 1 cm3/m3; 10 days
relative humidity < 60%,
no condensation

3.4 Mounting Positions and Type of Fixation

Mounting position
The HMI device is designed for mounting in:
● Racks
● Cabinets
● Control boards
● Consoles
In the following, all of these mounting options are referred to by the general term "cabinet".
The HMI device is self-ventilated and approved for vertical and inclined mounting in
stationary cabinets.

KP8, KP8F
32 Operating Instructions, 10/2010, A5E03284305-01
Planning the use
3.4 Mounting Positions and Type of Fixation

The following mounting positions are permitted:

ದ 


 

Mounting position Deviation from the vertical operating temperature, permissible


① Inclined < 30° 0 to 45 °C

② Vertical 0° 0 to 55 °C

CAUTION
Impermissible ambient temperatures
Do not operate the HMI device without auxiliary ventilation. If the maximum permissible
ambient temperature is exceeded, it may lead to damage. The approvals and warranties for
the HMI device will become void!
If the maximum permissible ambient temperature is exceeded, only operate the HMI device
with auxiliary ventilation.

Type of fixation
Mounting clamps are provided for mounting the device - see chapter "Accessory kit
(Page 14)".




① Hooks
② Screws
The main dimensions of the HMI device are not exceed by the installation of the mounting
clamps.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 33
Planning the use
3.5 Preparing for Mounting

3.5 Preparing for Mounting

Select the HMI device mounting location


Points to observe when selecting the mounting location:
● Position the HMI device so that it is not subjected to direct sunlight.
● Position the HMI device such that it is ergonomically accessible for the user.
Choose a suitable mounting height.
● Ensure that the air vents are not covered as a result of the mounting.
● Observe the permissible mounting positions for the HMI device.

Configuration of the mounting cut-out


In order to guarantee the protective type corresponding with chapter "Insulation resistance,
protection class and degree of protection (Page 36)", the following must be complied with:
● The material at the mounting cut-out must be distortion-resistant.
● Thickness of material at the installation cut-out for protection class IP65: 2 mm up to
6 mm
● Permitted deviation from plane at the mounting cut-out: ≤ 0.5 mm
This condition must be fulfilled for the mounted HMI device.
● Permissible surface roughness in the area of the seal: ≤ 120 µm (Rz 120)

KP8, KP8F
34 Operating Instructions, 10/2010, A5E03284305-01
Planning the use
3.5 Preparing for Mounting

Dimensions of the mounting cut-out


Multiple HMI devices are installed directly next to or under each other. The following image
shows the dimensions of the mounting cut-out and the required intervals.

 



$OOGLPHQVLRQVLQPP

Mounting Depth
The mounting depth for the HMI device depends on the type of construction of the
PROFINET connector. With angled PROFINET connector, order number 6GK1901-1BB20-
2AB0, the mounting depth is 65 mm.
The mounting depth does not match the external dimensions of the device. Plan for an
adequate bending radius for the cables connected to the HMI device.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 35
Planning the use
3.6 Insulation resistance, protection class and degree of protection

3.6 Insulation resistance, protection class and degree of protection

Insulation resistance of the HMI device


Proof of dielectric strength must be provided in the type test at a test voltage to
IEC 61131-2:2007:

Circuits with a nominal voltage of Ue to Test voltage


other circuits or ground
< 50 V 500 VDC

Protection class of the HMI device

HMI device Protection class according to IEC 60417-DB-HS:2008


Front and rear panel Protection class III

Degree of protection of the HMI device

NOTICE
Degree of protection IP65 for HMI device
If the HMI device is not installed according to this manual, the HMI device does not comply
with the specified protection type.
Make sure the mounting is done properly.

HMI device Degree of protection IEC 60529:2000


Front IP65
Rear IP20

3.7 Requirements for fail-safe operation

3.7.1 Sensor for 1oo1 mode


The following safety categories can be achieved with the HMI device:
● SIL2 corresponding to IEC 61508:2010
● PL d corresponding to IEC 13849:2006
● Category 3 corresponding to EN 954:1996

KP8, KP8F
36 Operating Instructions, 10/2010, A5E03284305-01
Planning the use
3.7 Requirements for fail-safe operation

Note
Have the fail-safe part of the system checked and accepted by a registered company in
regards to the prescribed technical safety controls before commissioning the HMI device.

Sensor Requirements for Fail-Safe Sensors

NOTICE
Qualified sensor
If you do not use any qualified, normed sensors, the safety categories SIL2, PL d and
category 3 will not be reached.
Only use qualified sensors corresponding with IEC 60947.

Note
Our electronics are equipped with such safety engineering features so that 98% of the
maximum permissible probability of hazardous faults is due to all other components of the
safety function. This corresponds to the recommended load division in safety engineering
between sensing devices, actuating devices, and electronic switching for input, processing,
and output.
The probability of hazardous faults and the rate of occurrence of hazardous faults of a safety
function must comply with an upper limit determined by an SIL or PL. For a description of the
HMI device, refer to chapter "Technical specifications (Page 84)".

Proof-test interval
Note the following:
● They have a considerable safety responsibility for the instrumentation with sensors.
● Sensors normally do not survive a proof-test interval of 10 years corresponding with
IEC 61508.
The sensors clearly lose their safety.

Note
In order to reach the safety categories SIL2, PL d and category 3, high-quality sensors
are required. The sensors used must fulfill the standards EN 60947-5-1:2004 and
EN 60947-5-5:1997 (VDE 0660, section 200).
The contacts of the sensors must be weld-resistant in accordance with the standard
IEC EN 60947-5. Ensure that the sensor connection is free of short-circuits.
Define an ideal proof-test interval for the used sensor.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 37
Planning the use
3.7 Requirements for fail-safe operation

Fault detection
Faults can be detected if the following connection errors are present:
● Short-circuit between two sensors
● Short-circuit to DC 24 V

Signal duration
In order to assure accurate detection of the sensor signal by the HMI device, you must
ensure that the minimum duration for the sensor signal is adhered to. Refer to chapter
"Technical specifications (Page 84) ".

See also
Connect KP8F - fail-safe inputs (Page 46)

3.7.2 Sensor for 1oo2 mode


The following safety categories can be achieved with the HMI device:
● SIL3 corresponding to IEC 61508:2010
● PL e corresponding to IEC 13849:2006
● Category 4 corresponding to EN 954:1996

Note
Have the fail-safe part of the system checked and accepted by a registered company in
regards to the prescribed technical safety controls before commissioning the HMI device.

Sensor Requirements for Fail-Safe Sensors

NOTICE
Qualified sensor
If you do not use any qualified, normed sensors, the safety categories SIL3, PL e and
category 4 will not be reached.
Only use qualified sensors corresponding with IEC 60947.

KP8, KP8F
38 Operating Instructions, 10/2010, A5E03284305-01
Planning the use
3.7 Requirements for fail-safe operation

Note
Our electronics are equipped with such safety engineering features so that 98% of the
maximum permissible probability of hazardous faults is due to all other components of the
safety function. This corresponds to the recommended load division in safety engineering
between sensing devices, actuating devices, and electronic switching for input, processing,
and output.
The probability of hazardous faults and the rate of occurrence of hazardous faults of a safety
function must comply with an upper limit determined by an SIL or PL. For a description of the
HMI device, refer to chapter "Technical specifications (Page 84)".
If you operate the HMI device with an EMERGENCY-STOP button, you must use a 2-
channel equivalent sensor switching - see chapter "Connect KP8F - fail-safe inputs
(Page 46)".

Proof-test interval
Note the following:
● They have a considerable safety responsibility for the instrumentation with sensors.
● Sensors normally do not survive a proof-test interval of 10 years corresponding with
IEC 61508.
The sensors clearly lose their safety.

Note
In order to reach the safety categories SIL3, PL e and category 4, high-quality sensors
are required. The sensors used must fulfill the standards IEC EN 60947-5-1:2004 and
IEC EN 60947-5-5:1997 (VDE 0660, section 200).
The contacts of the sensors must be weld-resistant in accordance with the standard
IEC EN 60947-5. Ensure the short-circuit-free connection of the emergency-stop button.
Define an ideal proof-test interval for the used sensor.

Fault detection
Faults can be detected if the following connection errors are present:
● When non-equivalent sensor signals are connected.
● When a single-channel sensor has a redundant connection.

WARNING
No redundant connection of two single-channel break contacts
If sensor signals are connected redundantly (break contacts), a fault will only be
recognized if one of the sensors is triggered.
Ascertain that under no circumstances are two single-channel break contacts
redundantly connected as sensor signals.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 39
Planning the use
3.7 Requirements for fail-safe operation

Signal duration
In order to assure accurate detection of the sensor signal by the HMI device, you must
ensure that the minimum duration for the sensor signal is adhered to. Refer to chapter
"Technical specifications (Page 84) ". The minimum duration is ensured by the usage of
push-to-lock emergency stop buttons.

3.7.3 Cables
The cables used must meet the following requirements:
● The unique assignment of terminals to sensors must be ensured.
● Cables laid outside of the switching cabinet must be laid separately in accordance with
the relevant standards.
Use stable pipes or cable channels in order to avoid short circuits and cross-circuits.

Note
With the connection of an emergency stop button to the fail-safe channels of the HMI
device, the line lengths corresponding with chapter "Technical specifications (Page 84)"
must be complied with.

KP8, KP8F
40 Operating Instructions, 10/2010, A5E03284305-01
Mount and connect KP8 and KP8F 4
4.1 "Mounting and connection of HMI device" checklist
The following steps must be taken when mounting and connecting the HMI device.

Test step Check


Check the scope of delivery (Page 41)
Mounting the HMI device (Page 41)
Connecting the power supply (Page 44)
Connect standard inputs/outputs (Page 45)
Connect KP8F - fail-safe inputs (Page 46)
Connecting the PLC (Page 48)
Switching on and testing the HMI device (Page 50)

4.2 Check the scope of delivery


Check the scope of delivery for completeness and visible signs of transport damage.

NOTICE
Do not use damaged parts
If you use defective parts from the items delivered, you may experience malfunctions.
If you find defective parts in the item delivered, contact your Siemens partner. Only install
undamaged parts.

4.3 Mounting the HMI device

Requirement
● Four mounting clamps.
The mounting clamps are included in the accessory kit.
● The HMI device comes equipped with a mounting seal.
If the mounting seal is damaged, do not mount the HMI device.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 41
Mount and connect KP8 and KP8F
4.4 Connecting the HMI device

Procedure

Note
Always mount the HMI device according to the operating instructions in this manual.
When mounting the HMI device, ensure that the labeling strips do not become jammed
between the mounting cut-out and the HMI device.

1. Insert the HMI device into the mounting cut-out.


2. Insert a mounting clamp into a recess of the HMI device.
3. Fasten each mounting clamp by tightening its screws.
The permitted torque is 0.15 Nm.
4. Repeat step 2 and 3 for all mounting clamps until all required clamps are tightened.

4.4 Connecting the HMI device

4.4.1 Connection sequences and lines

Requirement
● The HMI device must be mounted according to the specifications of these operating
instructions.
● Shielded standard cables
For additional information, refer to the Internet at:
Industry Mall (http://mall.automation.siemens.com)

Connection sequence

Note
Failure to do so may result in damage to the HMI device.

Connect the HMI device in the following sequence:


1. Power supply
2. Controller
Proceed in a reverse direction when disconnecting the connections.

KP8, KP8F
42 Operating Instructions, 10/2010, A5E03284305-01
Mount and connect KP8 and KP8F
4.4 Connecting the HMI device

Connecting the cables


Pay attention to the following when connecting the lines:
● Do not bend contact pins
● The connector is coded to prevent faulty insertion
The setting of the interfaces is described in Chapter "Technical specifications (Page 83)".

4.4.2 Ports
The following figure below shows the interfaces of the KP8:

'LJLWDOLQSXWVRXWSXWV
3RZHUVXSSO\FRQQHFWRU

352),1(7;3
352),1(7;3

In contrast to the KP8, the KP8F has a 16-pin socket for the digital input/output and for
connection to the power supply. For a description of the interfaces, refer to chapter "Interface
description (Page 89)".

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 43
Mount and connect KP8 and KP8F
4.4 Connecting the HMI device

4.4.3 Connecting the power supply

Configuration diagram
The figure below illustrates the connection between the power supply and the HMI device.

0 0

/ / .3

0 0

/ / .3)

Connecting the connector


The plug-in connector for connecting the power supply is contained in the accessory kit and
is designed for cables with a maximum cross-section of 1 mm2. Note the following diagram
when stripping the wire.

PP

If you are using a stranded lead, use wire-end ferrules.

NOTICE
Damage possible
Do not connect the lines if the connector is in the HMI device. You may otherwise damage
the mounting of the HMI device socket.
Always remove the connector to connect the wires.

To open the connectors, press in the opening provided with a screwdriver for slotted screws.
Slide the cable into the connector enclosure and remove the screwdriver. The wire is fixed.

KP8, KP8F
44 Operating Instructions, 10/2010, A5E03284305-01
Mount and connect KP8 and KP8F
4.4 Connecting the HMI device

Do not confuse the wires. Refer to the label for the contact pins on the rear of the HMI
device.

Note
The HMI device is equipped with a polarity reversal protection circuit.

Connecting the power supply

CAUTION
For the 24 VDC supply, use only power supply units with safety isolation complying with
IEC 364-4-41 or HD 384.04.41 (VDE 0100, Part 410), for example according to the
standards, SELV (Safety Extra Low Voltage ) and PELV (Protective Extra Low Voltage).
The supply voltage must be within the specified voltage range. Any other voltage might lead
to failure of the HMI device.
Applies to floating system design:
Connect the connection for GND 24 V from the 24 V power supply output to equipotential
bonding for uniform reference potential. For this purpose, choose a connecting point that is
as close as possible to the center.

4.4.4 Connect standard inputs/outputs


On the back of the HMI device you will find 8 digital inputs/outputs for non fail-safe input and
output devices. Non-fail-safe inputs/outputs are shown in gray in the following illustration.
Unconnected inputs/outputs are automatically set to "0".

,2 ,2 ,2 ,2

.3

,2 ,2 ,2 ,2

,2 ,2 ,2 ,2

.3)

,2 ,2 ,2 ,2

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 45
Mount and connect KP8 and KP8F
4.4 Connecting the HMI device

Procedure

Note
Follow the notes about connectors in chapter "Connecting the power supply (Page 44)".

1. Connect the wires on the connector corresponding with the setting of the socket on the
rear of the HMI device.

4.4.5 Connect KP8F - fail-safe inputs


The KP8F is intended for the use of an emergency stop button and fail-safe sensor. Please
observe the information in Section "Sensor for 1oo1 mode (Page 36)" and "Sensor for 1oo2
mode (Page 38)".

Note
For supplying the fail-safe inputs, only inputs labeled with VS may be used on the HMI
device.
Only connect fail-safe inputs if these are also used. This also applies for disabled fail-safe
inputs.

Follow the notes about connectors in chapter "Connecting the power supply (Page 44)".

Requirement - EMERGENCY STOP connection


● Connectors from the accessory kit
● EMERGENCY-STOP button

Note
If, in STEP 7 HW Config, you selected the option "No evaluation" for the KP8F in the
"Evaluation of the sensor" parameter and no sensor is connected, the value 0 will be
reported to the controller for the sensor values in the process illustration.
See section "Setting KP8F - STEP 7 (Page 64)" and "Bit assignment in the process
image (Page 91)".

KP8, KP8F
46 Operating Instructions, 10/2010, A5E03284305-01
Mount and connect KP8 and KP8F
4.4 Connecting the HMI device

Procedure
1. Connect the EMERGENCY-STOP button as follows to the connector for the fail-safe
digital inputs:
– Sensor supply VS.0 for the FI.0 input
– Sensor supply VS.1 for the FI.1 input

0 0 ,2 ,2 ,2 ,2 ), ),

/ / ,2 ,2 ,2 ,2 96 96

 

 

(PHUJHQF\VWRSEXWWRQ

The EMERGENCY-STOP button must be connected as an equivalent break contact.


Observe the affiliated setting for "Evaluation of the sensor" in the HW config - see chapter
"Setting KP8F - STEP 7 (Page 64)".

Note
External power supply is not permissible for VS.0 and VS.1.

Requirement - sensor connection


● Connectors from the accessory kit
● Button as contact break or closer

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 47
Mount and connect KP8 and KP8F
4.4 Connecting the HMI device

Procedure
The following approach is an example.
1. Connect the button as follows to the connector for the fail-safe digital inputs:
– Sensor supply VS.0 for the FI.0 input
– Sensor supply VS.1 for the FI.1 input

0 0 ,2 ,2 ,2 ,2 ), ),

/ / ,2 ,2 ,2 ,2 96 96

 

%XWWRQb

 

%XWWRQb

Observe the affiliated setting for "Evaluation of the sensor" in the HW config - see chapter
"Setting KP8F - STEP 7 (Page 64)".

Note
External power supply is not permissible for VS.0 and VS.1.

4.4.6 Connecting the PLC


The connection between the HMI device and controller depends on the topology of the
PROFINET network.
● Line
All the communication nodes are connected in series as a bus. The series structure is
implemented with switches that are integrated in the PROFINET devices.
● Star
The communication nodes are connected with a switch, from the Scalance X208 or X204
series for example.
You can find additional information on the topology of PROFINET networks in the system
manual, "PROFINET System Description".

Note
Always use only the approved cables to connect a SIMATIC S7 controller.

KP8, KP8F
48 Operating Instructions, 10/2010, A5E03284305-01
Mount and connect KP8 and KP8F
4.4 Connecting the HMI device

Standard cables are available for the connection. You will find more information in the
SIMATIC NET-catalog IK PI or on the Internet at:
Industry Mall (http://mall.automation.siemens.com)

Configuration diagram for serial configuration


The figure below illustrates the connection between the HMI device and the controller with a
serial configuration.

6,0$7,&6
352),1(7

&RQWUROOHU
352),1(7 (WKHUQHW/$1

&RQWUROOHUIURPGLIIHUHQWSURGXFHU

IXUWKHU
FRPPXQLFDWLRQ
SDUWLFLSDQWV

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 49
Mount and connect KP8 and KP8F
4.5 Switching on and testing the HMI device

Configuration diagram for star configuration


The following figure shows the connection between the HMI device and the controller with a
star configuration.

6,0$7,&6
352),1(7

&RQWUROOHU
352),1(7 (WKHUQHW/$1

6ZLWFKIRUH[DPSOH6FDODQFH
;
&RQWUROOHUIURPGLIIHUHQWSURGXFHU

4.5 Switching on and testing the HMI device

Note
If the KP8F is operated with an EMERGENCY STOP button, check during the fail-safe
operation of the KP8F before each commissioning to see if the required parameters are set
in the HW config. Refer to chapter "Setting KP8F - STEP 7 (Page 64) ".

Procedure
1. Connect the connector on the HMI device.
2. Switch on the power supply.
After starting the HMI device, all LEDs will illuminate corresponding to the setting. The
default illumination time is 5 s.

Note
As long as the light test is executed, no keyboard entry will be transferred to the
connected controller.

If the HMI device does not start, it is possible the wires on the connector have been
crossed. Check the connected wires and change the connections if necessary.

KP8, KP8F
50 Operating Instructions, 10/2010, A5E03284305-01
Mount and connect KP8 and KP8F
4.6 Securing the cables

3. Press each light button after one another.


The LED goes off after pressing light button.
4. Applies for the KP8F:
After connecting the EMERGENCY-STOP button or the buttons, execute a function test.
5. Execute a function test after connecting a sensor.

Switching off the HMI device


You have the following options for switching off the HMI device:
● Switch off the power supply.
In fail-safe mode of the PROFIsafe device, the system goes to a fail-safe state .

4.6 Securing the cables


After the power-on test, use cable ties to secure the connected cables to the marked fixing
elements to ensure strain relief.

)L[LQJHOHPHQWIRUVWUDLQUHOLHI

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 51
Mount and connect KP8 and KP8F
4.6 Securing the cables

KP8, KP8F
52 Operating Instructions, 10/2010, A5E03284305-01
Operator controls and displays 5
5.1 Front-sided control elements and displays

Controls

,OOXPLQDWHGSXVKEXWWRQV

Display elements
There are 8 light buttons on the front of the HMI device. The corresponding bit in the
controller is set as long as the key is pressed.
Surface LEDs are integrated in each key. They can be used to represent bit states of the
connected controller. The LEDs can be displayed in red, green, yellow, blue and white.
The brightness of the LEDs can be set - see chapter "Setting controller - communication HMI
device (Page 58)". The default setting is "normal".

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 53
Operator controls and displays
5.2 Rear operator controls and displays

The following figure shows the numbering of the LEDs:

 

 

 

 

Utilization of the buttons occurs via the process image. Refer to chapter "Bit assignment in
the process image (Page 91) ".

5.2 Rear operator controls and displays


On the rear of the KP8 and the KP8F, you will find the following operator elements and
displays. The DIL switch is only available on the KP8F.

',3VZLWFK

/('JUHHQ
/('\HOORZ

KP8, KP8F
54 Operating Instructions, 10/2010, A5E03284305-01
Operator controls and displays
5.3 Labeling keys

PROFINET interfaces
There are two LEDs on each PROFINET interface. These LEDs display the status of the
PROFINET communication. The following table shows the meaning:

Green LED Yellow LED Meaning


LINK RX/TX
OFF OFF No PROFINET connection
On OFF PROFINET communication possible
On On PROFINET communication runs

5.3 Labeling keys


You can label the keys as required for your project. Use the labeling strips for this purpose.

When installed, the labeling strips can be inserted if the mounting has a material thickness of
< 3.5 mm. With larger material thicknesses, the disassembly of the HMI device is required if
a labeling strip should be changed.

Note
Do not write on the keyboard to label the function keys.

Printing labeling strips


A template for the labeling strips is available as a Word file online under:

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 55
Operator controls and displays
5.3 Labeling keys

"Technical Support
(http://support.automation.siemens.com/WW/llisapi.dll?aktprim=99&lang=en&referer=%2fW
W%2f&func=cslib.csinfo2&siteid=csius&extranet=standard&viewreg=WW)"
Observe the information in this file.
The labeling strips have the following dimensions:

5








9LVLEOHZLQGRZUDQJH[

$OOGLPHQVLRQVLQPP

Procedure
1. Edit the template.
2. Print the template.
You can use printable labels and paper. Always ensure an adequate material stiffness
during the selection. This is needed to insert the labeling strips. The maximum permitted
thickness of the labeling strip is 0.15 mm.
Alternatively, you can also label the strips by hand.

Note
Wait for the printed labeling strips to dry before you insert them.

3. If you print the labeling strips on foil or paper, cut out the labeling strips.
Ensure that the corners are cut according to the corresponding diagram, as this makes it
easier to slide them into the slot.
4. Remove any previously existing labeling strips.
5. Slide the new labeling strips into the guide up to the stop.
The labeling strip will protrude approximately 1 cm out of the guide. The template
dimensions for the labeling strips are designed so that the labeling is correctly placed for
the keys. An interlock is not required for the labeling strips.

KP8, KP8F
56 Operating Instructions, 10/2010, A5E03284305-01
Setting the KP8 and KP8F 6
6.1 "Setting the KP8 and KP8F" checklist
In order to operate the HMI device in a fail-safe manner, the set-up steps in STEP 7 and on
the HMI device are required. Information, such as how to set the F-I/O in STEP 7, can be
found in the Programming and operation manual "S7 Distributed Safety - Configuring and
Programming" (http://support.automation.siemens.com/WW/view/en/22099875) and in the
"Safety Technology in SIMATIC S7" system manual
(http://support.automation.siemens.com/WW/view/en/12490443).

Test step Information Check


Setting slot 0 and 1 Setting controller - communication HMI device
(Page 58)
Setting slot 2 of the KP8F Setting controller - communication HMI device
(Page 58)
Setting KP8F - STEP 7 (Page 64)
Set PROFIsafe target addresses Setting PROFIsafe address for KP8F (Page 67)

6.2 Integrating GSD in STEP 7


If the HMI device is not listed in the hardware catalog of HW Config, you need to integrate a
valid GSD (device database) file for the HMI device in the STEP 7 database.

Requirement
● The GSD is installed.
Information on installing the GSD can be found online at:
Integrating a GSD File (http://support.automation.siemens.com/WW/view/en/22817133)
● STEP 7 applications, for example, the KOP/AWL/FUP editor or the icon table, are closed.
● HW Config opens.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 57
Setting the KP8 and KP8F
6.3 Setting controller - communication HMI device

Display catalog structure


KP8 and KP8F are displayed in the catalog structure of the HW config, "GSD" folder - see
red labeling in the following image.

6.3 Setting controller - communication HMI device


HW Config of the STEP 7 project has to be configured and set to enable communication
between HMI device and controller.

Note
The KP8F can only be configured with a – non fail-safe – standard controller if this standard
controller supports Shared Device.

Set parameters for the slots as follows:


● For the KP8:
– Slot 0
– Slot 1
● For the KP8F:
– Slot 0
– Slot 1
– Slot 2
The fail-safe mode is set with slot 2.
The setting of slots 0 and 1 is the same for the KP8 and KP8F.

KP8, KP8F
58 Operating Instructions, 10/2010, A5E03284305-01
Setting the KP8 and KP8F
6.3 Setting controller - communication HMI device

Requirement
● The SIMATIC Manager opens in "HW Config".
In the following image, the slots that must be set are labeled in red.

The setting described in the following uses KP8 as an example and applies similarly for the
KP8F.

Procedure – Setting slot 0


1. Double click in the station window on the module.
The "Properties – [Name]" dialog box opens.
2. Select the "General" tab.

Parameter Meaning
Device name The IO controller addresses the IO device by its device name. The
device name must be unique within the network.
The device name is connected with the IP-address, which is set for
the HMI device.
Device number You can identify an IO device in the user program with its device
number. STEP 7 assigns the device number.
3. Change the entries, if required.
4. Click "OK".
The entries are saved. The dialog box closes.
You can find additional information about device names and numbers in the manual
"PROFINET System Description".

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 59
Setting the KP8 and KP8F
6.3 Setting controller - communication HMI device

Procedure – Setting slot 1


1. Double click in the properties window on slot 1.
The "Properties – KP8 inputs/outputs" dialog box opens.
2. Open the "Addresses" tab.
In the "Inputs" and "Outputs" groups, the start values of the address areas are set
depending on the controller used.
Parameter Meaning
Inputs > Start Start of address range in which the PROFIsafe inputs/outputs for
the fail-safe HMI device are mapped.
Inputs > Process Image Process image to which the address range belongs.
This parameter cannot be set with controllers of the
SIMATIC CPU 300 type.
Outputs > Start Start of address range in which the PROFIsafe inputs/outputs for
the fail-safe HMI device are mapped.
Outputs > Process Image Process image to which the address range belongs.
This parameter cannot be set with controllers of the
SIMATIC CPU 300 type.
3. Change the entries, if required.
4. Select the "Parameters" tab.
5. Open the "Parameters > Device-specific parameters" folder.

Parameter Meaning
Duration of the light test The value range from 0 to 60 s can be set.
With the value "0", no light test is executed.
Default setting is 5 s.
Brightness Adjustable:
very bright, bright, normal, dark or very dark
Default setting is "normal".
Function of the clamp 0 Adjustable:
Input or output, default setting is input
Function of the clamp 1 Adjustable:
Input or output, default setting is input
Function of the clamp 2 Adjustable:
Input or output, default setting is input
Function of the clamp 3 Adjustable:
Input or output, default setting is input
Function of the clamp 4 Adjustable:
Input or output, default setting is output
Function of the clamp 5 Adjustable:
Input or output, default setting is output
Function of the clamp 6 Adjustable:
Input or output, default setting is output
Function of the clamp 7 Adjustable:
Input or output, default setting is output

KP8, KP8F
60 Operating Instructions, 10/2010, A5E03284305-01
Setting the KP8 and KP8F
6.4 Configuring Media Redundancy Protocol

6. Change the entries, if required.


7. Click "OK".
The entries are saved. The dialog box closes.

Result
The HMI device will now respond in operation according to the new setting. The switch
states of the digital inputs/outputs of the HMI device are stored in the specified address area
of the controller.

6.4 Configuring Media Redundancy Protocol


KP8 and KP8F are designed for MRP.
MRP allows compensation for individual failures in a simple ring topology. Meshed topology
is not supported, MRP is deterministic.
MRP is based on a ring topology and guarantees recovery times between 200 ms and
500 ms. MRP uses a redundancy manager that closes the ring. In normal mode, the
redundancy manager checks the continuity of the ring through test packets.

NOTICE
Response time
If the response monitoring time is less than the response time of the MRP, then MRP will
not work with the KP8F. The controller will see the HMI device as "failed" in the short-term.
The response monitoring time must be greater than the response time of the MRP. Refer to
chapter "Response times of the PROFIsafe devices (Page 78) ".

Requirement
● "HW Config" is open in the SIMATIC Manager.
In the following image, the module to be configured is labeled in red.

The following procedure is an example and also applies for the KP8F.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 61
Setting the KP8 and KP8F
6.4 Configuring Media Redundancy Protocol

Procedure
1. Double-click the "X2" slot in the station window.

The following dialog appears.

2. Select the "Media Redundancy" tab.


The "X317-2" controller can perform three different roles in MRP.
Parameter Meaning
Not in the ring The "X317-2" controller is not a node of the MRP
Manager (Auto) The "X317-2" controller is the Manager of the MRP
Client The "X317-2" controller is the Client of the MRP
3. Select "Manager (Auto)".
4. Click "OK".
The entry is saved. The dialog box closes.
5. Select KP8 again in the station window.

KP8, KP8F
62 Operating Instructions, 10/2010, A5E03284305-01
Setting the KP8 and KP8F
6.4 Configuring Media Redundancy Protocol

6. Double-click the "X1" slot in the station window.


The following dialog appears.

7. Select the "Media Redundancy" tab.


8. Select the marked entry from the "Role" list box.

Parameter Meaning
Not not in the ring The KP8 is not a node of the MRP
Client The KP8 is a client of the MRP
9. Select "Client".
10.Click "OK".
The entry is saved. The dialog box closes.
11.Double-click the "X1 P1" slot in the station window.
The following dialog appears. The partner port entries are examples.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 63
Setting the KP8 and KP8F
6.5 Setting KP8F - STEP 7

12.Select the required partner port from the "Partner port" list box.
The selected partner is therefore defined as the next partner of the MRP. If you select
"Any partner", MRP will not work. A message is displayed.
Parameter Meaning
Any partner Any device is partner of the MRP
317F_2\(11) X317-2-KP8F The device 317F_2\(11) X317-2-KP8F\Port 2 (X1 P2) is the next
partner of the MRP
13.Click "OK".
The entry is saved. The dialog box closes.

Result
The KP8 is configured for the MRP This is illustrated by the following topology view with the
Master CPU "KP8" and three Clients in a ring structure. The KP8F is a client in this case.

6.5 Setting KP8F - STEP 7


This chapter applies for the setting of the fail-safe slot 2 of the KP8F.

Requirement
● The password for the security program must be known.
● The SIMATIC Manager opens in "HW Config".

KP8, KP8F
64 Operating Instructions, 10/2010, A5E03284305-01
Setting the KP8 and KP8F
6.5 Setting KP8F - STEP 7

In the following image, the slot that must be set is labeled in red.

Procedure
1. Double click in the properties window on slot 2.
The "Properties – F-DI" dialog box opens.
2. Open the "Addresses" tab.
In the "Inputs" and "Outputs" groups, the start values of the address areas are set
depending on the controller used. The signals of the F channels of the HMI device are
mapped in these address ranges.
Parameter Meaning
Inputs > Start Start of address range in which the safety-relevant usage data of
the HMI device are mapped.
Inputs > Process Image Process image to which the address range belongs.
This parameter cannot be entered with a controller of the
SIMATIC CPU 300 type.
Outputs > Start Start of address range in which the safety-relevant usage data of
the HMI device are mapped.
Outputs > Process Image Process image to which the address range belongs.
This parameter cannot be entered with a controller of the
SIMATIC CPU 300 type.
3. Check the default entry of the addresses for "Start".
If necessary, change the address range.
4. Select the "Parameters" tab.
5. Open the "Parameters > Device-specific Panels > Evaluation of the Sensor" directory.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 65
Setting the KP8 and KP8F
6.5 Setting KP8F - STEP 7

6. In the list, select:


– Not activated
"Not activated" is the default entry.
– 1oo2 (2v2)-evaluation, EMERGENCY STOP
– 1oo1 (1v1)-evaluation, single-channel
The selection is based on the connection corresponding with chapter "Connect KP8F -
fail-safe inputs (Page 46)".

Note
Make sure that the sensor is monitored corresponding with its connection.

7. Click "OK".
The entries are saved. The dialog box closes.
8. Open the "PROFIsafe" tab.
If no access rights exist, the following dialog box will be shown.

9. Enter the password that was assigned when the safety program was created in
Distributed Safety.
10.Click "OK".
The dialog box closes.
11.If necessary, change the "F_Dest_Add" parameter.
To do this, use the "Change value" button. Assign a network and station-wide unique
address.
12.Change the monitoring time "F_WD_Time" if needed.
13.Click "OK".
The entries are saved. The dialog box closes.

Result
The HMI device will now respond in operation according to the new setting. The switch
states of the digital inputs of the HMI device are stored in the specified address area of the
controller.

KP8, KP8F
66 Operating Instructions, 10/2010, A5E03284305-01
Setting the KP8 and KP8F
6.6 Setting PROFIsafe address for KP8F

6.6 Setting PROFIsafe address for KP8F


A PROFIsafe target address is assigned when you add the HMI device in the HW Config of
the STEP 7 project. The PROFIsafe target address is the value of the "F_Dest_Add"
parameter - see chapter "Setting KP8F - STEP 7 (Page 64)".
Then you must set the same PROFIsafe target address using the DIP switch on the back of
the HMI device.

Note
Ensure that the HMI device is disconnected from the power before setting the PROFIsafe
target address with the DIP switches.

Requirement
● The DIP switch of the HMI device is accessible.
● The value of the "F_Dest_Add" parameter is known.

Note
The PROFIsafe target address of the HMI device must be unique throughout the
communication network and station. You can assign a maximum of 1022 PROFIsafe
target addresses in a single system.
If you change the STEP 7 program in a way that changes the PROFIsafe target address,
you need to change the switch settings on the HMI device's DIP switch accordingly.

Example
In the HW Config of the STEP 7 project, set the binary address for "383" as the PROFIsafe-
target address:
Corresponding setting on the DIP switch: 0101111111
● 1 = switch setting "ON"
● 0 = switch setting "OFF".

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 67
Setting the KP8 and KP8F
6.7 KP8F – Configure Shared Device

Set the DIP switch on the back of the KP8F as follows:

2)) 21 6ZLWFK %LWQXPEHU :HLJKWLQJ $GGUHVV


   
   
   
   
   
   
   
   
   
   



The illustrated switch settings correspond with the binary address 383.

Result
The HMI device can be uniquely identified by the configured PROFIsafe target address.

6.7 KP8F – Configure Shared Device


KP8F is designed for shared device.
Shared Device is the parallel and independent access from two different controllers to the
same HMI device. A fixed assignment of the different modules that are used in an
automation device must be configured to a select controller. The unique assignment of the
module to the controller is always guaranteed and visible for the user.

Requirement
● A shared device is created in the project.
Information on the configuration of Shared Device can be found in the online help
"STEP 7 Version 5.5".
● The Shared Device is now inserted in the PROFINET IO system.
Coupling with the controllers of the station is carried out automatically.
● "HW Config" is open in the SIMATIC Manager.

KP8, KP8F
68 Operating Instructions, 10/2010, A5E03284305-01
Setting the KP8 and KP8F
6.7 KP8F – Configure Shared Device

In the following image, the module to be configured is labeled in red.

Procedure
1. Double-click in the station window on the marked device.
The following dialog appears.

2. Select the "Shared" tab.


The buttons are gray as long as no device is selected.
3. In the "Devices which can be coupled" group, select the device to be coupled to the
KP8F.
4. Click "Couple".
The Shared Device connection is established. The coupled device is displayed in the
"Coupled devices" group. See red marking.
5. If you want to decouple a Shared Device connection, select the device in question.
6. Click "Uncouple".
The Shared Device connection is terminated. The decoupled device is displayed in the
"Devices which can be coupled" group.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 69
Setting the KP8 and KP8F
6.7 KP8F – Configure Shared Device

7. If there are several Shared Device connections, you must select a device for full access.
The following dialog appears:

8. Select the required device for the access type "Full".


9. Click "OK".
The entry is saved. The dialog box closes.
10.Select the "Access" tab.
The following dialog appears:

11.Select the Shared Device connection for which you want to change the access.

Parameter Meaning
Full Read and write access by the controller
... No access by the controller
12.Select the required parameter.
13.Click "OK".
The entry is saved. The dialog box closes.

Result
Shared Device is configured for the KP8F.

KP8, KP8F
70 Operating Instructions, 10/2010, A5E03284305-01
Setting the KP8 and KP8F
6.8 KP8F – Configure Shared Device for non fail-safe controller

6.8 KP8F – Configure Shared Device for non fail-safe controller


You can also operate the KP8F with a non fail-safe controller. The non fail-safe controller
must support Shared Device in this case.

Requirement
● "HW Config" is open in the SIMATIC Manager.
In the following image, the module to be configured is labeled in red.

Procedure
1. Perform steps 1 to 9 as described in section "KP8F – Configure Shared Device
(Page 68)".
2. Select the "Access" tab.
The following dialog appears:

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 71
Setting the KP8 and KP8F
6.8 KP8F – Configure Shared Device for non fail-safe controller

3. Select "…" for the Shared Device connection.


The parameter indicates that there is no access by the controller.
4. Click "OK".
The entry is saved. The dialog box closes.

Result
Shared Device is configured for the KP8F and for a non fail-safe controller.

KP8, KP8F
72 Operating Instructions, 10/2010, A5E03284305-01
Operating KP8F in a fail-safe manner 7
7.1 Overview

Fail-safe mode
You can use the HMI device in standard mode and fail-safe mode simultaneously.
In fail-safe mode the HMI device recognizes signal states from suitable fail-safe sensors and
sends corresponding safety telegrams to the fail-safe controller where the safety program
runs. The fail-safe controller and the HMI device communicate with each other using the fail-
safe protocol "PROFIsafe".

Safety functions
During fail-safe mode, safety functions are activated in both HMI and the fail-safe controller
which recognize faults and react to them.
In the following cases, the fitting system unit must be run in a secure operating state:
● The EMERGENCY STOP button is pressed.
● A sensor was confirmed.
● A diagnosable error has occurred.

Reaction to pressed EMERGENCY STOP buttons or activation of sensor


If the EMERGENCY-STOP button was pressed or sensor was activated, the related BIT is
sent to the controller in a safety-directed manner. The controller program analyzes if the
EMERGENCY STOP button was pressed or sensor was activated.

Note
Which reactions this bit activates in the controller and thus, in the system, is the task of the
user. Tasks include:
 Configuring required responses appropriate for the EMERGENCY STOP in the controller
 Setting measures to repair the cause of an EMERGENCY STOP
 Configuring the startup behavior after an EMERGENCY STOP
The response to an EMERGENCY STOP or activation of the sensor, measures and startup
behavior must be described in the system documentation.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 73
Operating KP8F in a fail-safe manner
7.2 Passivate HMI device

Responses to faults in the system


In the case of a failure,the F channels of the HMI device are passivated. This means "0" will
be recognized at all fail-safe digital inputs.
The system must be configured so that the required safe operating mode can occur. Which
measures must be implemented for failure analysis and repairs must be provided by the
user.

Note
The HMI device may first be integrated into the control process after the causes for the
failure have been repaired.

After integration, the process values for the digital fail-safe inputs are available again.

7.2 Passivate HMI device

Passivation
As soon as the HMI device recognizes a fault in fail-safe mode, all fail-safe channels are
switched to the safe operating state. Through this, the fail-safe channels of this HMI device
are passivated.

Note
If the HMI device is passivated, instead of the queued process values, the fail-safe value "0"
is always assigned to all the fail-safe digital inputs. You cannot configure the fail-safe value.

Detected faults are entered in the diagnostic buffer of the fail-safe controller and reported to
the safety program in the fail-safe controller.
The HMI device cannot permanently save the fault. When you switch off the HMI device and
switch it on again, only one of the existing faults will continue to be detected after startup. If
you want to save the faults, program your safety program accordingly.
The HMI device is passivated in the following situations:
● When the HMI device is started (startup)
● With a setting error
Errors in the PROFIsafe parameters, for example "F_WD_TIME" (F_monitoring time) too
short.
● When an error occurs in the PROFIsafe communication between the fail-safe controller
and HMI device
● With a hardware error
Error, for example, through wire break, short-circuit, discrepancy errors, internal errors of
the HMI device.

KP8, KP8F
74 Operating Instructions, 10/2010, A5E03284305-01
Operating KP8F in a fail-safe manner
7.3 Error diagnostics

Determining passivation
If you want to determine if the HMI device is passive or not, address the "PASS_OUT"
variable of the F-I/O. The variable can be assigned the following values:
● 0 = HMI device not passive
● 1 = HMI device passive

Reintegrating KP8F
After passivation of the HMI device, the fault must be diagnosed and rectified. Afterwards,
the HMI device can be reintegrated.

7.3 Error diagnostics

Diagnostic functions
Diagnostic functions , in other words displays and messages, are not critical to safety and
therefore are not designed to be safety-related functions. They are therefore not tested
internally.

Diagnostic function the HMI device


The fail-safe HMI device includes a non-configurable diagnostic function. The diagnostics
are always activated and are automatically made available by the HMI device in STEP 7 and
passed on to the controller in the event of a fault.
The diagnostics function passes the following diagnostics information to the controller:
● Communication error
The communication between the HMI device as the IO-device and the controller as the
IO-controller is disrupted.
● Configuration error
Error in the PROFIsafe configuration

Reading diagnostic information


If you wish to locate the cause of an error, open the module diagnostics in STEP 7. You can
find detailed information in the online help for STEP 7.
The following table shows the diagnostic functions of the HMI device. The diagnostic
functions are assigned either to one channel or to the entire module.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 75
Operating KP8F in a fail-safe manner
7.4 Repair error and reintegrate

Diagnostics function Error code Scope of diagnostics functions


Short-circuit 0x01 Channel
Configuration error 0x10 Module
Communication error 0x13 Module
Discrepancy error 0x19 Channel
Non-permissible sensor evaluation 0x1C Module
PROFIsafe address deviation 0x1D Module
Serious error 0x1E Module
Version conflict 0x1F Module
You have the option of reading the diagnostics functions in the standard program by calling
SFB 52 or SFB 54. For detailed information, refer to the "System and Standard Functions"
reference manual.

Diagnostics of PROFIsafe errors


When diagnosing PROFIsafe errors, address the "DIAG" variable of the F-I/O DB. Detailed
information about the F-I/O-DB can be found in the Programming and operation manual "S7
Distributed Safety - Configuring and Programming"
(http://support.automation.siemens.com/WW/view/en/22099875)".

HMI device with a serious error


If a serious error in the HMI device leads to its failure, the HMI device reacts as follows:
● The connection to PROFINET will be interrupted and the fail-safe channels will be
rendered passive.
● No diagnosis will be transmitted from the HMI device.
In STEP 7 in module diagnostics, the standard diagnosis "Module interrupted" or "Module
missing" will be reported.

7.4 Repair error and reintegrate

Remedy
The error correction of the HMI device should be undertaken depending on the type of error
recognized:

Error Possible causes of error Remedy


Short-circuit Short-circuit in the sensor Eliminate the short-circuit.
Cross-circuit in the sensor Eliminate the cross-circuit.
Internal error Replace the HMI device.

KP8, KP8F
76 Operating Instructions, 10/2010, A5E03284305-01
Operating KP8F in a fail-safe manner
7.4 Repair error and reintegrate

Error Possible causes of error Remedy


Serious error Internal error in the HMI device Replace the HMI device.
Discrepancy error The process signal is faulty. Check the process signal.
(1oo2 evaluation) The sensor is defective. Replace the sensor if needed.
Short-circuit between the sensor line Eliminate the short-circuit.
and the sensor voltage supply line.
Configuration error The HMI device does not match the Correct the configuration.
configuration. Check the communication paths.
Configuration incorrect Correct the configuration.
PROFIsafe address The PROFIsafe address on the HMI Set the same PROFIsafe address in
deviation device is set incorrectly. the SIMATIC manager, HW config and
on the device. This address must be
unique. Refer to chapter "Setting
PROFIsafe address for KP8F
(Page 67) ".
Communication error The communication between the Check the PROFINET cable.
fail-safe controller and HMI device is
interrupted, for example, due to a
defective PROFINET connection or
EMI.
The PROFIsafe monitoring time set Increase the value of the
too low. "F_WD_Time" parameter in the
SIMATIC Manager, HW Config.
The configuration of the HMI device Compile the safety program again.
does not match the safety program. Then download the configuration and
the safety program to the fail-safe
controller.
Non-permissible An invalid value was transferred for Check the setting. Check the version
sensor evaluation the setting "Evaluation of the of your GSDML-file. Load a new
sensor". GSDML file.
Version conflict The HMI device recognized an Update the device firmware
invalid combination of firmware. completely and bring it to the current
state.

End passivation
When you have eliminated an error that lead to a passivation of the HMI device, you have to
reintegrate the HMI device. A user acknowledgement in the safety program may be required
for the reintegration of the HMI device. After reintegration, the pending process values at the
HMI device's fail-safe channels are provided again for the safety program.
More information about the reintegration of F-I/O and for creating a user acknowledgement
in the safety program can be found in the Programming and operation manual "S7
Distributed Safety - Configuring and Programming"
(http://support.automation.siemens.com/WW/view/en/22099875).

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 77
Operating KP8F in a fail-safe manner
7.5 Response times of the PROFIsafe devices

7.5 Response times of the PROFIsafe devices

Response time of KP8F


The response time of the HMI device enters into the calculation of the response time of the
F-system.
● Response times of the fail-safe channels
The response time is the time that is required between a signal change on the digital
input and the safe loading of the safety message frame to PROFINET.
● Response time of the HMI device
The actual response time is somewhere between the shortest and longest response time.
When planning a system, the longest response time must always be anticipated.
Information about the response time can be found in the chapter "Technical specifications
(Page 84)".
The following image shows where response times can be expected.

6,0$7,&6)31'3
DV352),1(7,2FRQWUROOHU
(7b6VWDWLRQ
ZLWK
,031

352),1(7

5HVSRQVHF\FOH

.3)DV
352),1(7,2'HYLFH

IDLOVDIHVHQVRU
IDLOVDIHVHQVRU

KP8, KP8F
78 Operating Instructions, 10/2010, A5E03284305-01
Operating KP8F in a fail-safe manner
7.5 Response times of the PROFIsafe devices

Calculating response time


Information about the response times of the IO controller can be found in the manual of the
IO controller used.
The "S7 Distributed Safety" add-on package contains an Excel file "s7fcotia.xls" for
calculating maximum response times. You can find the current version of this table on the
Internet at the following address:
"Support Request (http://support.automation.siemens.com/WW/view/en/16605654)", Entry -
ID 19138505
Detailed information for the calculation of the response time of the F-system can be found in
the "Safety Technology in SIMATIC S7" system manual
(http://support.automation.siemens.com/WW/view/en/12490443)".

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 79
Operating KP8F in a fail-safe manner
7.5 Response times of the PROFIsafe devices

KP8, KP8F
80 Operating Instructions, 10/2010, A5E03284305-01
Maintain and service KP8 and KP8F 8
8.1 Maintenance and care
Observe the safety instructions during maintenance and care found in chapter "Safety
Instructions (Page 19)".

Scope of maintenance
The HMI device is designed for maintenance-free operation. Cyclic maintenance work is not
required.

Scope of care
The scope of care includes:
● Cleaning keyboard overlay

Cleaning procedure

CAUTION
Damage possible
Using compressed air or steam cleaners, or aggressive solutions or scouring agents will
damage the HMI device.
Use a cleaning cloth dampened with a cleaning agent to clean the equipment. Only use
water with a little liquid soap or a screen cleaning foam.

Proceed as follows:
1. Switch off the HMI device.
2. Spray the cleaning solution onto a cleaning cloth.
Do not spray directly onto the HMI device.
3. Clean the HMI device.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 81
Maintain and service KP8 and KP8F
8.2 Spare parts and repairs

8.2 Spare parts and repairs


If the unit needs to be repaired, ship the HMI device to the Return Center in Fürth.
The address is:
Siemens AG
Industry Sector
Returns Center
Siemensstr. 2
90766 Fürth
Germany
You can find more detailed information on the Internet at Spare parts and repairs
(http://support.automation.siemens.com/WW/view/en/16611927).

KP8, KP8F
82 Operating Instructions, 10/2010, A5E03284305-01
Technical specifications 9
9.1 Dimensional diagram





  


 

$OOGLPHQVLRQVLQPP

You can find more images on the Internet at:


Image database (http://www.automation.siemens.com/bilddb)

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 83
Technical specifications
9.2 Technical specifications

9.2 Technical specifications

Weight

KP8, including connector and mounting clamps, 270 g


without packaging
KP8F, including connector and mounting clamps, 280 g
without packaging

Power supply

Nominal value +24 VDC


Range, permissible +20,4 V … +28,8 V (–15 %, +20 %)
Value for t < 0.5 s 35 V
Current consumption, maximum 0.3 A without load
Electrical isolation No
Short-circuit protection Yes
Transients, maximum permissible 35 V, 500 ms
Time between two transients, minimum 50 s
Fuse, internal 4A

encoder

Signal duration, minimum 50 ms

KP8, KP8F
84 Operating Instructions, 10/2010, A5E03284305-01
Technical specifications
9.2 Technical specifications

KP8 - digital inputs/outputs

Connectable Keys, switches


Number of digital inputs/outputs, standard mode 8
Electrically isolated from internal logic No
Input voltage
 Nominal value  +24 VDC
 With "0" signal  0 … +5 V
 With "1" signal  15 … 30 V
Input current for signal "1" Typically 5 mA for 24 V
Delay in the digital inputs/outputs 0.3 ms
Connection mechanical switches Yes
Bounce time ≤ 10 ms
 Permitted resistive loads  0,1 A
 Lamp load, permissible  2W
Energy, inductive ( max.) 200 mWs
Output voltage
 With "0" signal  Max. 2 V no load
 With "1" signal  Min. supply voltage –3 V
Output current
 With "0" signal  Max. 1 mA
 With "1" signal  Cumulative current for all outputs 800 mA
Switching frequency, max. at
 Resistive load  100 Hz
 Lamp load  8 Hz

KP8 - fail-safe digital inputs/outputs


Additionally, with KP8F, the following applies for the fail-safe digital inputs:

Number of fail-safe digital inputs 2


Number of fail-safe outputs Corresponding to PROFIsafe process values
Cable length
 Unshielded cable, maximum  1m
 Shielded cable, maximum  3m
Response time for 6 to 22 ms
1oo1 and 1oo2 if there are no faults
Response time for 10 to 27 ms
1oo1 and 1oo2 in the event of a fault
Acknowledgment time in safety mode 15 to 35 ms
Signal duration, minimum 22 ms

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 85
Technical specifications
9.3 Fail-safe mode

9.3 Fail-safe mode

KP8F internal
The block diagram of the KP8F:

,QSXW ,QSXWXQLW &RQWUROOHU %ODFNFKDQQHO 2XWSXW

3RZHUVXSSO\

The relevant values of the individual blocks are shown in the following.

Note
All values for the following data are based on the SN 29500:2005 and an ambient
temperature of 60 °C.

Input unit – 1oo1 mode

Parameter Value Comment


Hardware Fault Tolerance 0 –
Classification A –
Architecture 1oo1D –
Failure mode Dangerous process value Due to failures in the input circuit
 Detected  5.50 FIT
 Undetected  0.34 FIT
Failure Mode Diagnostic No error signaling or no safe Calculation according
values IEC13849:2006 CAT4
 Detected  0 FIT
 Undetected  0 FIT
Diagnostic Coverage 94.15 % –
Diagnostic test interval 15 ms Errors detected in each firmware
cycle
Safe Failure Fraction 99.19 % –

KP8, KP8F
86 Operating Instructions, 10/2010, A5E03284305-01
Technical specifications
9.3 Fail-safe mode

Input unit – 1oo2 mode

Parameter Value Comment


Hardware Fault Tolerance 1 –
Classification A –
Architecture 1oo2D 1st detected failure leads to the safe
state
Failure mode Dangerous process value Due to failures in the input circuit
 Detected  5.78 FIT One channel
 Undetected  0.06 FIT One channel
Failure Mode Diagnostic No error signaling or no safe Calculation according
values IEC13849:2006 CAT4
 Detected  0 FIT
 Undetected  0 FIT
Diagnostic Coverage 99.00 % –
Diagnostic test interval 15 ms Errors detected in each firmware
cycle
Safe Failure Fraction 99.86 % –
Common Cause Factor 2% –

Controller

Parameter Value Comment


Hardware Fault Tolerance 1 –
Classification B –
Architecture 1oo2D 1st detected failure leads to the safe
state
Failure mode Dangerous process value Due to failures in the processing unit
 detected  174,00 FIT  One channel
 undetected  1,68 FIT  One channel
Failure Mode Diagnostic No error signaling or no safe Calculation according
values IEC13849:2006 CAT4
 Detected  0 FIT
 Undetected  0 FIT
Diagnostic Coverage 99.04 % –
Diagnostic test interval 15 ms Errors detected in each firmware
cycle
Safe Failure Fraction 99.23 % –
Common Cause Factor 2% –

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 87
Technical specifications
9.3 Fail-safe mode

Power supply

Parameter Value Comment


Hardware Fault Tolerance 0 –
Classification A –
Architecture 1oo1D –
Failure mode Dangerous process value Due to failures in the power supply
 Detected  22.50 FIT
 Undetected  0.22 FIT
Failure Mode Diagnostic No error signaling or no safe Calculation according
values IEC13849:2006 CAT4
 Detected  0 FIT
 Undetected  0 FIT
Diagnostic Coverage 99.03 % –
Diagnostic test interval < 10 ms Voltage monitoring in hardware
Safe Failure Fraction 99.84 % –

Fail-safe mode for 1oo1 evaluation


● In accordance with IEC 61508:2010

Systematic Capability SIL3


Mode of operation High and low demand mode
Meantime to Restoration (MTTR) 100 h
Probability of a dangerous failure per hour 5.95 × 10–10 1/h
(PFH)
Probability of a dangerous failure on demand 2.61 × 10–5
(PFD)
Safe Failure Fraction (SFF) 99.19 %
Diagnostic test interval 15 ms
Proof Test Interval 10 y
Lifetime 10 y
● In accordance with IEC 13849:2006

Meantime to Failure (MTTFd) 560 y


Meantime to Restoration (MTTR) 100 h
Diagnostic Coverage (DCavg) 98.90 %
Performance Level d
Category 3
● In accordance with EN 954-1:1996

Category 3

KP8, KP8F
88 Operating Instructions, 10/2010, A5E03284305-01
Technical specifications
9.4 Interface description

Fail-safe mode for 1oo2 evaluation


● In accordance with IEC 61508:2010

Systematic Capability SIL3


Mode of operation High and low demand mode
Meantime to Restoration (MTTR) 100 h
Probability of a dangerous failure per hour 2.55 × 10–10 1/h
(PFH)
Probability of a dangerous failure on demand 1.11 × 10–5
(PFD)
Safe Failure Fraction (SFF) 99.23 %
Diagnostic test interval 15 ms
Proof Test Interval 10 y
Lifetime 10 y
● In accordance with IEC 13849:2006

Meantime to Failure (MTTFd) 560 y


Meantime to Restoration (MTTR) 100 h
Diagnostic Coverage (DCavg) 99.04 %
Performance Level e
Category 4
● In accordance with EN 954-1:1996

Category 4

9.4 Interface description

9.4.1 Inputs and outputs KP8


X60, connector, 12-pin

0 0 ,2 ,2 ,2 ,2

/ / ,2 ,2 ,2 ,2

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 89
Technical specifications
9.4 Interface description

PIN Assignment
M Ground
M Ground
L+ +24 VDC
L+ +24 VDC
IO.0 digital input/output 0
IO.1 digital input/output 1
IO.2 digital input/output 2
IO.3 digital input/output 3
IO.4 digital input/output 4
IO.5 digital input/output 5
IO.6 digital input/output 6
IO.7 digital input/output 7

9.4.2 Inputs and outputs KP8F


X60, connector, 16-pin

0 0 ,2 ,2 ,2 ,2 ), ),

/ / ,2 ,2 ,2 ,2 96 96

PIN Assignment
M Ground
M Ground
L+ +24 VDC
L+ +24 VDC
I0.0 digital input/output 0
I0.1 digital input/output 1
I0.2 digital input/output 2
I0.3 digital input/output 3
I0.4 digital input/output 4
I0.5 digital input/output 5
I0.6 digital input/output 6
I0.7 digital input/output 7
FI.0 Fail-safe digital input 0
FI.1 Fail-safe digital input 1
VS.0 Sensor supply 1 for FI.0
VS.1 Sensor supply 2 for FI.1

KP8, KP8F
90 Operating Instructions, 10/2010, A5E03284305-01
Technical specifications
9.5 Bit assignment in the process image

9.4.3 PROFINET
RJ45 plug connector, 8-pin

 

PIN Assignment
1 RxP Receive data +
2 RxN Receive data –
3 TxP Transmit data +
4 GND n. c.
5 GND n. c.
6 TxN Transmit data –
7 GND n. c.
8 GND n. c.

9.5 Bit assignment in the process image


The signal states of HMI device digital inputs/outputs that are used in standard mode are
saved in their own process images independently from the signal states of the fail-safe
channels.

Input area of the controller


The keys and digital inputs of the HMI device are mapped to the bits in the input area of the
controller as follows:

Bit 7 Bit6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Description Input byte
K7 K6 K5 K4 K3 K2 K1 K0 Keys 0 to 7 0
DI 7 DI 6 DI 5 DI 4 DI 3 DI 2 DI 1 DI 0 Digital inputs 0 to 7 1

K= Key
DI = Digital input
The numbering refers to the specifications in the chapter "Front-sided control elements and
displays (Page 53)".

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 91
Technical specifications
9.5 Bit assignment in the process image

Output area of the controller


Each of the three questions has its own output byte. The LEDs are assigned to the bits in the
output area of the controller as follows:

Bit 7 Bit6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Description Output byte
R7 R6 R5 R4 R3 R2 R1 R0 LEDs 0 to 7, 0
red
G7 G6 G5 G4 G3 G2 G1 G0 LEDs 0 to 7, 1
green
B7 B6 B5 B4 B3 B2 B1 B0 LEDs 0 to 7, 2
blue
DO 7 DO 6 DO 5 DO 4 DO 3 DO 2 DO 1 DO 0 Digital outputs 3
0 to 7

R= Red
G= Green
B= Blue
DO = Digital output
For the output bytes 0 to 2, the bit combinations of the bit x are illustrated in the following
table.

Bit R x (red, byte 0) Bit G x (green, byte 1) Bit B x (blue, byte 2) LED
1 0 0 Red
0 1 0 Green
0 0 1 Blue
1 1 0 Yellow
1 1 1 White
0 0 0 OFF
1 0 1 OFF
0 1 1 OFF

KP8, KP8F
92 Operating Instructions, 10/2010, A5E03284305-01
Technical specifications
9.6 Sensor evaluation of the fail-safe channels

9.6 Sensor evaluation of the fail-safe channels

Note
For digital inputs that are reserved with a fail-safe channel, the process image described in
the chapter "Bit assignment in the process image (Page 91)" is not used.

The fail-safe channels occupy the following address areas in the process image of the fail-
safe controller:

Input area Output area


x + 0 to x + 4 x + 0 to x + 3

x The start address for the input and output range.


The address was entered on the "Addresses" tab in the HW Config in the object
properties of the module "KP8F, Slot 2".
The first byte in the process image describes the switch state of the connected sensors or a
connected EMERGENCY-OFF button. The setting is described in the section "Setting KP8F
- STEP 7 (Page 64)".

Note
The unused bits in the byte 0 are always "0".

The following evaluations are possible:


● No evaluation
Slot 2 was not set. No evaluation occurs.
6,/ 6,/
%LW %LW %LW %LW %LW %LW %LW %LW )LUVWE\WH

● 1oo1 evaluation
The slot 2 was set with "1oo1 (1v1)-evaluation, one-channel". The connected sensor is
evaluated.
), ),

6,/ 6,/
%LW %LW %LW %LW %LW %LW %LW %LW )LUVWE\WH

Bits 4 and 5 determine if the respective sensor contact is open or closed. The bits may
take on the following values:
– 0 = Open sensor contact
– 1 = sensor contact closed

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 93
Technical specifications
9.6 Sensor evaluation of the fail-safe channels

● 1oo2 evaluation
The slot 2 was set with "1oo2 (2v2)-evaluation, EMERGENCY STOP". The
EMERGENCY STOP button is evaluated.
),
),

6,/ 6,/
%LW %LW %LW %LW %LW %LW %LW %LW )LUVWE\WH

Bit 0 determines whether or not the EMERGENCY STOP button was pressed. The bit
can take on the following values:
– 0 = EMERGENCY STOP button pressed or error
– 1 = EMERGENCY STOP button not pressed

KP8, KP8F
94 Operating Instructions, 10/2010, A5E03284305-01
Appendix A
A.1 ESD guideline

What does ESD mean?


An electronic module is equipped with highly integrated electronic components. Due to their
design, electronic components are highly sensitive to overvoltage and thus to the discharge
of static electricity. Such electronic components are labeled as electrostatic sensitive devices
(ESD).
The following abbreviations are commonly used for electrostatic sensitive devices:
● ESD – Electrostatic Sensitive Device
● ESD – Electrostatic Sensitive Device (internationally recognized term)

Electrostatic charge

CAUTION
Electrostatic charge
ESDs may be destroyed by voltages far below the level perceived by human beings. If you
are not discharged electrostatically, the voltage that you transfer when touching a
component or the contact points of a module can already cause damage.
The damage to an ESD caused by overvoltage is usually not recognized immediately. The
damage only becomes apparent after a long period of operation.
Discharge any electrostatic charge of your body before you touch the ESD.

Anyone who is not connected conductively to their surroundings is subject to electrostatic


charge.
The following diagram shows the maximum voltage values to which a person can be
charged electrostatically. The values depend on the material and humidity. The shown
values are in conformity with the specifications of EN 61000-4-2.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 95
Appendix
A.1 ESD guideline

9ROWDJH
>N9@








 




 


 


           >@
5HODWLYHKXPLGLW\

① Synthetic materials
② Wool
③ Antistatic materials such as wood or concrete

Protective measures against discharge of static electricity

CAUTION
Grounding measures
There is no equipotential bonding without grounding. An electrostatic charge is not
discharged and may damage the ESD.
When working with electrostatic sensitive devices, make sure that the person and the
workplace are properly grounded.

Note the following:


● Only touch the ESD if it is absolutely necessary.
● When you touch ESD modules, avoid touching the pins or the PCB tracks.
This precaution reduces the risk of damaging an ESD.
● Discharge electrostatic electricity from your body if you are performing measurements on
an ESD.
To do so, touch a grounded metal object before you carry out the measurement.
● Always use grounded measuring instruments.

KP8, KP8F
96 Operating Instructions, 10/2010, A5E03284305-01
Abbreviations B
CPU Central Processing Unit
DC Direct Current
DIL Dual-in-Line
DP Distributed I/O
ESD Electrostatic Discharge, the components and modules endangered by
such
EMC Electromagnetic Compatibility
EN European standard
ESD Electrostatic Sensitive Device
F-CPU Fail-safe Central Processing Unit
GND Ground
GSD Device master file
HF High Frequency
HMI Human Machine Interface
IEC International Electronical Commission
LED Light Emitting Diode
MTTR Meantime to Restoration
MRP Media Redundancy Protocol
MS Microsoft
PELV Protective Extra Low Voltage
PFD Probability of a dangerous Failure on Demand
PFH Probability of a dangerous Failure per Hour
PL Performance Level
RSTP Rapid Spanning Tree Protocol
SELV Safety Extra Low Voltage
SIL Safety Integrity Level
TIA Totally Integrated Automation
UL Underwriter’s Laboratory

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 97
Abbreviations

KP8, KP8F
98 Operating Instructions, 10/2010, A5E03284305-01
Glossary

Automation system (AS)


is a controller of the SIMATIC S7 series such as a SIMATIC S7-1200.

Controller
General term for devices and systems with which the HMI device communicates, e.g.
SIMATIC S7.

Diagnostics
Diagnostics enable you to determine if the signals are being correctly registered in the fail-
safe HMI device.

EMC
Electromagnetic compatibility (EMC) refers to a state in which technical equipment does not
disturb other equipment with unwanted electrical or electromagnetic effects. Electromagnetic
compatibility deals with technical and regulatory questions of undesired, mutual influence in
electrical engineering.

Failsafe
Capability of a technical system to remain in a safe state or switch to another safe state
immediately in the event of a failure or fault.

Fail-safe system, F system


A fail-safe system is used to control production processes in which immediate shutdown
results in a safe system status. This means that a fail-safe systems control processes that do
not present a danger to people or the environment if a direct shutdown of the plant occurs.
Fail-safe systems are used in plants with high safety requirements.

GSD
The GSD file contains all the properties of a DP slave or IO device. STEP 7 requires a GSD
file for each DP slave and for each IO device to allow the DP slave or IO device to be
selected in the module catalog of HW Config.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 99
Glossary

Passivation
If the F-I/O detects a fault/error, it switches the affected channel or all its channels to the safe
state. In other words, channels of this F-I/O are passivated. The F-I/O reports the detected
error to CPU via the slave diagnostics. With an F-I/O with inputs, passivation is performed by
the the F system by making available substitute values (0) to the safety program instead of
the process values queued at the fail-safe inputs. With an F-I/O with outputs, passivation is
performed by the the F system by sending substitute values (0) to the fail-safe outputs
instead of the output values provided by from the safety program.

PROFINET
Within the framework of Totally Integrated Automation (TIA), PROFINET represents an
enhancement of the following bus systems:
● PROFIBUS DP as well-established field bus
● Industrial Ethernet as the communication bus for the cell level
The experience gained from both systems has been and continues to be integrated in
PROFINET. PROFINET as an Ethernet-based automation standard from PROFIBUS
International (PROFIBUS Nutzerorganisation e.V.) defines a vendor-independent
communication and engineering model.

PROFINET IO controller
Device used to address the connected IO devices. That is: The IO controller exchanges
input and output signals with assigned field devices. The IO controller is often the controller
on which the automation program runs.

PROFINET IO device
A PROFINET IO device is a decentralized field device that is assigned to one of the IO
controllers (e.g., remote IO, valve terminals, frequency converters, switches)

PROFINET IO
As part of PROFINET, PROFINET IO is a communication concept that is used to implement
modular, distributed applications.
PROFINET IO allows you to create automation solutions of the type with which you are
familiar from PROFIBUS.
PROFINET IO is implemented by the PROFINET standard for automation devices on the
one hand, and on the other hand by the STEP 7 engineering tool.
This means that you have the same application view in STEP 7 regardless of whether you
configure PROFINET devices or PROFIBUS devices. Programming your user program is
essentially the same for PROFINET IO and PROFIBUS DP if you use the extended blocks
and system status lists for PROFINET IO.

PROFIsafe
Fail-safe bus profile of PROFINET for communication between the safety program and the
F-I/O in an F system.

KP8, KP8F
100 Operating Instructions, 10/2010, A5E03284305-01
Glossary

PROFIsafe address
Every F-I/O has a PROFIsafe address. This address is used to receive safety frames from
the fail-safe CPU or send safety frames to the fail-safe CPU.

Proof-test interval
The proof-test interval is the time period after which a component must be put into fail-safe
state. That is, it is replaced by an unused component or it is proven to be completely fault-
free.

Reintegration
Once a fault/error has been eliminated, the F-I/O must be reintegrated (depassivated).
Reintegration (switching from substitute values to process data) takes place either
automatically or following user acknowledgment.
For an F-I/O module with inputs, the process data queued at the failsafe inputs are made
available again to the safety program after reintegration. For an F-I/O module with outputs,
the output values for fail-safe outputs are sent again by the system to the fail-safe outputs.

Safe state
State of a unit in which safety is assured. In other words, the risk is acceptably low because
it has been established that safety-related malfunctions do not occur or because of the
safety measures taken to prevent possible safety-related malfunctions.
The basic principle of the safety concept in a fail-safe system is the existence of a safe state
for all process variables.

Safety class
Safety integrity level according to IEC 61508 and prEN 50129. The higher the safety integrity
level, the sharper the measures taken to avoid systematic errors and to control systematic
errors and random hardware failures.

Safety function
Safety function is a mechanism integrated in fail-safe CPUs and I/Os, enabling them to be
used in fail-safe systems. According to IEC 61508: A safety function is implemented by a
safety system to ensure that the system is kept in a safe state or brought into a safe state in
the event of a particular fault (user safety function).

Safety mode
Operating mode of the HMI device in which safety-related communication can be performed
via safety frames.

safety-related communication
Communication used to exchange fail-safe data.

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 101
Glossary

Sensor evaluation
Two types of sensor evaluation:
● 1oo1 evaluation
Sensor signal is read once.
● 1oo2 evaluation
The sensor signal is read twice by the same F-I/O and compared internally.

Standard mode
Operating mode of an HMI device in which only standard communication is possible and
safety-related communication cannot be performed via safety frames.

STEP 7
Programming software SIMATIC S7, SIMATIC C7 and SIMATIC WinAC controllers.

KP8, KP8F
102 Operating Instructions, 10/2010, A5E03284305-01
Index

Setting the KP8F, 57


Climatic
1 Transport conditions, 29
Communication error, 75
1oo1 evaluation
Condensation, 30
encoder, 93
Conductor cross-section, 44
1oo1-parameterization, 17
Configuration diagram
1oo2 evaluation
Connecting the controller, 49, 50
EMERGENCY-STOP button, 94
Connecting the power supply, 44
1oo2 parameterization, 17
Configuration error, 75
connecting
Connection sequence, 42
A
HMI device, 42
Address range, 93 Connecting
Ambient condition Controller, 49, 50
Climatic, HMI device, 32 EMERGENCY-STOP button, 47
Mechanical, HMI device, 31 non fail-safe input/output, 46
Ambient temperature Plug connector, 44
Impermissible, 33 Connecting the connector, 44
Approval Connecting the controller
Australia, 22 Configuration diagram, 49, 50
FM, 22 Connection
Protection against explosion, 21 1oo1, 47
UL, 22 1oo2, 47
Area of application EMERGENCY STOP, 46
Operating instructions, 3 Connection sequence, 42
Contact person, 6
Controller
B Input, 91
Output, 92
Battery
Convention
Used, 6
Style, 5
Term, 5
C
Cable D
Request, 40
Degree of protection, 34, 36
Calculating
Design examination certificate, 25
Response time, 79
Diagnostics, 75
Care, 81
Reading, 75
CE mark, 21
Diagnostics function, 75
Channel
Reading, 75
Fail-safe, 93
digital input/output, 85
Charge
DIP switch, 67
Electrostatic, 95
Disposal, 6
Check list
Documentation
Mounting and connecting, 41
SIMATIC complete, 6
Planning the use, 29

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 103
Index

E Input/output
non fail-safe, 46
EC Declaration of Conformity, 21
Input/output device
Electrostatic charge, 95
External, 15
EMERGENCY STOP connection, 46
Installation cut-out, 35
EMERGENCY-STOP button
Dimensions, 35
Bit assignment, 94
Installation location, 34
connect fail-safe, 47
insulation resistance, 36
Response to, 73
Interference
Emission, 23
Pulse-shaped, 26
encoder
Sinusoidal, 27
Bit assignment, 93
Response to, 73
K
F Key
Labeling, 55
Fail-safe
Knowledge
Operation enabled, 73
Required, 3
fail-safe channel, 93
KP8
Fail-safe mode
Main dimensions, 83
Technical specifications, 88, 89
Scope of delivery, 11
Fault detection, 38, 39
KP8F
Main dimensions, 83
Scope of delivery, 11
G
GSD, 57
L
Labeling
H
Key, 55
Hardware update, 57 Labeling strips, 55
HMI device
connecting, 42
EMC-compliant mounting, 26 M
mounting, 33, 42
Main dimensions
Mounting position, 32
KP8, 83
Serious error, 76
KP8F, 83
Switching off, 51
Maintenance, 81
Switching on, 50
Maintenance personnel, 3
Testing, 50
Mechanical
with Ex approval, 24
Transport conditions, 29
HW Config, 58
Module diagnostics, 75
moisture protection, 36
mounting
I
EMC-compliant, 26
Identification HMI device, 33, 42
CE, 21 Mounting clamp, 33
Illustration, 5 Mounting Depth, 35
Industry Portal, 6 Mounting position
Input unit HMI device, 32
1oo1 mode, 86 MRP, 61
1oo2 mode, 87 MTTR, 88, 89

KP8, KP8F
104 Operating Instructions, 10/2010, A5E03284305-01
Index

N Protective measure
Static electricity, 96
Notice of protected rights, 3
Protocol, 16

O R
Office location, 6
Radio interference, 23
Operating
Reading
Safety, 20
Diagnostics function, 75
Operating instructions
Rechargeable battery
Scope, 3
Used, 6
Operation
Recycling, 6
In industry, 23
Registered trademark, 3
In potentially explosive atmospheres, 24
Request
In residential areas, 23
Cable, 40
Operation enabled
Response time, 79
Dual-channel, 17
Fail-safe, 73
Single-channel, 17
S
Safety function, 73
P Scope of delivery, 11
KP8, 11
Parameterizing
KP8F, 11
Slot 0, 59
Sensor connection, 47
Slot 1, 60
Serious error, 76
Slot 2, 65
Service, 6
Passivation, 74
SFB 52, 76
Performance Characteristic
SFB 54, 76
KP8, 15
Shock, 31
KP8F, 16
Signal duration, 38, 40
PFD, 88, 89
SIMATIC S7, 16
PFH, 88, 89
Slot 0
Pin assignment
Parameterizing, 59
Plug connector, 89, 90
Slot 1
RJ45, 91
Parameterizing, 60
PLC, 16
Slot 2
Potentially explosive atmosphere, 24
Parameterizing, 65
Power supply, 84
Static electricity
Conductor cross-section, 44
Protective measures, 96
Configuration diagram, 44
STEP 7
connecting, 45
HW Config, 58
Connecting the connector, 44
Support
Prescribed usage, 20
Technical, 6
Process image, 93
Support Request, 6
PROFIsafe, 16
Switching cabinet
PROFIsafe target address, 67
Working on, 19
Proof-test interval, 37, 39
Switching off
Protected trademark, 3
HMI device, 51
Protection against explosion, 21
Switching on
Protection against ingress of solid foreign bodies, 36
HMI device, 50
Protection class
HMI device, 36

KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01 105
Index

T
Technical specifications
Fail-safe mode, 88, 89
KP8, 85
KP8F, 85
Plug connector, 89, 90
Power supply, 84
Response time, 79
RJ45, 91
Weight, 84
Technical support, 6
Technical Support, 6
Test
Climatic conditions, 32
Mechanical conditions, 31
Testing
HMI device, 50
Trademark, 3
Training center, 6
Transport conditions, 29
Transport damage, 41
Type of fixation, 33

U
Usage
Prescribed usage, 20
With protective measures, 31

V
Vibration, 31

W
Weight, 84

Z
Zones 2 and 22
Operating conditions, 25
Potentially explosive atmosphere, 24

KP8, KP8F
106 Operating Instructions, 10/2010, A5E03284305-01

You might also like