Electrical Load Schedule

This document provides a load distribution schedule for a proposed ground shed project. It details the electrical loads to be distributed from two meter cabinets fed from the local utility (DEWA). Meter Cabinet 1 and Meter Cabinet 2 each have an incomer rated for 300A and 400A respectively. From these, electricity will be distributed to various distribution boards and a static meter distribution board to power the site loads. The total connected load is estimated to be 348.78kW.

Uploaded by

ritesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views13 pages

Electrical Load Schedule

This document provides a load distribution schedule for a proposed ground shed project. It details the electrical loads to be distributed from two meter cabinets fed from the local utility (DEWA). Meter Cabinet 1 and Meter Cabinet 2 each have an incomer rated for 300A and 400A respectively. From these, electricity will be distributed to various distribution boards and a static meter distribution board to power the site loads. The total connected load is estimated to be 348.78kW.

Uploaded by

ritesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

PROJECT: PROPOSED GROUND SHED LOAD DISTRIBUTION SCHEDULE

PLOT NO :- 5310279
SUMMARY CLIENT: ALEX RENNER MOTOR GARAGE
LOCATION :- SAIH SHUAIB 2
FEED FROM : DEWA CONSULTANT: ALGAFRY CONSULTING ARCHITECTS ENGINEERS

RATING-AMPS CABLE SIZE CONNECTED LOAD - KW PROPOSED TYPE &


PVC/* XLPE REMARKS
FAULT Length No. OF kwh Meters
CIRCUIT/ FEEDER
SP/TP DUTY of Cable ECC SIZE 1C mm2
DB NO. MCCB / 1-PH 3-PH LV/HV
F/S ISO. KA SWA/ PVC 2/4/ X 1C mm2 2/3/ X 4C mm2 (Mtrs.) R-PH KW Y-PH KW B-PH KW TOTAL KW
ACB (1) (2) CT (4)

INCOMER 117.98 114.36 116.43 348.78 2

METER CAB. 1 4P 300A 50 By Dewa 2x1Cx150mm2 58.02 56.76 56.27 171.05 1 300/5A CT

METER CAB. 2 4P 400A 50 By Dewa 2x1Cx150mm2 59.96 57.60 60.16 177.73 1 400/5A CT

MDB CONNECTED TO:DEWA LV DB/Transf. SMDB


TOTAL CONNECTED LOAD PER PHASE: 117.98 114.36 116.43 348.78 2 TOTAL
CONNECTED TO: MDB:

DEMAND FACTOR: 0.9 MAX. DEMAND 313.90 kW TOTAL CONNECTED LOAD (3 PH): 348.78

TYPE OF METER (RATING OF INCOMER) : (1) Upto 60A - 1 Phase (2) Upto 100A - 3 Phase (3) 125 - 160A - 3Phase (4) LV CT ……./…..A / HV CT…../…..A

113
PROJECT: PROPOSED GROUND SHED LOAD DISTRIBUTION SCHEDULE
PLOT NO :- 5310279
MDB-01 CLIENT: ALEX RENNER MOTOR GARAGE
LOCATION :- SAIH SHUAIB 2
FED FROM : METER CAB.1 CONSULTANT: ALGAFRY CONSULTING ARCHITECTS ENGINEERS

RATING-AMPS CABLE SIZE CONNECTED LOAD - KW PROPOSED TYPE &


PVC/* XLPE REMARKS
FAULT Length of No. OF kwh Meters
CIRCUIT/ FEEDER
SP/TP DUTY Cable ECC SIZE 1C mm2
DB NO. MCCB / 1-PH 3-PH LV/HV
F/S ISO. KA SWA/ PVC 2/4/ X 1C mm2 2/3/ X 4C mm2 (Mtrs.) R-PH KW Y-PH KW B-PH KW TOTAL KW
ACB (1) (2) CT (4)

INCOMER-1 300A 50 XLPE/SWA/PVC 4C 240MM2 1C 120MM2 58.02 56.76 56.27 171.05

OUT GOING:
DB-01 TP 63A 25 XLPE/SWA/PVC 4C 25MM2 1C 16MM2 5.95 6.10 6.10 18.15

DB-01 A TP 40A 25 XLPE/SWA/PVC 4C 16MM2 1C 10MM2 4.62 4.50 4.38 13.50

DB-02 TP 40A 25 XLPE/SWA/PVC 4C 16MM2 1C 10MM2 4.22 4.63 3.88 12.72

DB-04 TP 63A 25 XLPE/SWA/PVC 4C 25MM2 1C 16MM2 6.75 6.75 6.58 20.08

DB-04 A TP 63A 25 XLPE/SWA/PVC 4C 25MM2 1C 16MM2 7.78 7.78 8.33 23.90

SMDB-E TP 200A 35 XLPE/SWA/PVC 4C 120MM2 1C 70MM2 28.70 27.00 27.00 82.70

CAP. BANK 1 TP 160 25 XLPE/SWA/PVC 4C 70MM2 1C 35MM2 65KVAR CAPACITOR BANK


MDB CONNECTED TO:DEWA LV DB/Transf. SMDB
TOTAL CONNECTED LOAD PER PHASE: 58.02 56.76 56.27 171.05 TOTAL
CONNECTED TO: MDB:

DEMAND FACTOR: 0.9 MAX. DEMAND 153.95 kW TOTAL CONNECTED LOAD (3 PH): 171.05 kW

TYPE OF METER (RATING OF INCOMER) : (1) Upto 60A - 1 Phase (2) Upto 100A - 3 Phase (3) 125 - 160A - 3Phase (4) LV CT ……./…..A / HV CT…../…..A
PROJECT: PROPOSED GROUND SHED LOAD DISTRIBUTION SCHEDULE
PLOT NO :- 5310279
MDB-02 CLIENT: ALEX RENNER MOTOR GARAGE
LOCATION :- SAIH SHUAIB 2
FED FROM : METER CAB.2 CONSULTANT: ALGAFRY CONSULTING ARCHITECTS ENGINEERS

RATING-AMPS CABLE SIZE CONNECTED LOAD - KW PROPOSED TYPE &


PVC/* XLPE REMARKS
FAULT Length of No. OF kwh Meters
CIRCUIT/ FEEDER
SP/TP DUTY Cable ECC SIZE 1C mm2
DB NO. MCCB / 1-PH 3-PH LV/HV
F/S ISO. KA SWA/ PVC 2/4/ X 1C mm2 2/3/ X 4C mm2 (Mtrs.) R-PH KW Y-PH KW B-PH KW TOTAL KW
ACB (1) (2) CT (4)

INCOMER-1 400A 50 XLPE/SWA/PVC 4C 300MM2 1C 150MM2 59.96 57.60 60.16 177.73

OUT GOING:
DB-03 TP 40A 25 XLPE/SWA/PVC 4C 10MM2 1C 10MM2 4.63 4.88 5.49 15.01

DB-OFF/LL TP 63A 25 XLPE/SWA/PVC 4C 25MM2 1C 16MM2 10.09 7.65 9.78 27.52

DB- EXT TP 32A 25 XLPE/SWA/PVC 4C 10MM2 1C 10MM2 2.64 2.47 2.29 7.40

DB-ECBS TP 32A 25 XLPE/SWA/PVC 4C 10MM2 1C 10MM2 1.00 1.00 1.00 3.00

SMDB-AC TP 250A 35 XLPE/SWA/PVC 4C 150MM2 1C 70MM2 41.60 41.60 41.60 124.80

CAP. BANK 2 TP 160 25 XLPE/SWA/PVC 4C 70MM2 1C 35MM2 65KVAR CAPACITOR BANK


MDB CONNECTED TO:DEWA LV DB/Transf. SMDB
TOTAL CONNECTED LOAD PER PHASE: 59.96 57.60 60.16 177.73 TOTAL
CONNECTED TO: MDB:

DEMAND FACTOR: 0.9 MAX. DEMAND 159.95 kW TOTAL CONNECTED LOAD (3 PH): 177.73 kW

TYPE OF METER (RATING OF INCOMER) : (1) Upto 60A - 1 Phase (2) Upto 100A - 3 Phase (3) 125 - 160A - 3Phase (4) LV CT ……./…..A / HV CT…../…..A

313
PROJECT: PROPOSED GROUND SHED LOAD DISTRIBUTION SCHEDULE
PLOT NO :- 5310279
SMDB - E CLIENT: ALEX RENNER MOTOR GARAGE
LOCATION :- SAIH SHUAIB 2
FED FROM : MDB-01 CONSULTANT: ALGAFRY CONSULTING ARCHITECTS ENGINEERS

RATING-AMPS CABLE SIZE CONNECTED LOAD - KW PROPOSED TYPE &


PVC/* XLPE REMARKS
FAULT Length of No. OF kwh Meters
CIRCUIT/ FEEDER
SP/TP DUTY Cable ECC SIZE 1C mm2
DB NO. MCCB / 1-PH 3-PH LV/HV
F/S ISO. KA SWA/ PVC 2/4/ X 1C mm2 2/3/ X 4C mm2 (Mtrs.) R-PH KW Y-PH KW B-PH KW TOTAL KW
ACB (1) (2) CT (4)

INCOMER-1 200A 35 XLPE/SWA/PVC 4C 120MM2 1C 70MM2 28.70 27.00 27.00 82.70

OUT GOING:
FIRE PUMP TP 160A 25 XLPE/SWA/PVC 4C 95MM2 1C 50MM2 21.67 21.67 21.67 65.00 ELS+ALARM

JOCKEY PUMP TP 20A 25 XLPE/SWA/PVC 2C 6MM2 1C 4MM2 1.50 1.50 30mA ELCB

DIESEL PUMP TP 20A 25 XLPE/SWA/PVC 2C 6MM2 1C 4MM2 0.20 0.20 30mA ELCB

WATER PUMP TP 32A 25 XLPE/SWA/PVC 4C 10MM2 1C 10MM2 2.00 2.00 2.00 6.00

LIFT TP 32A 25 XLPE/SWA/PVC 4C 10MM2 1C 10MM2 3.33 3.33 3.33 10.00


MDB CONNECTED TO:DEWA LV DB/Transf. SMDB
TOTAL CONNECTED LOAD PER PHASE: 28.70 27.00 27.00 82.70 TOTAL
CONNECTED TO: MDB:

DEMAND FACTOR: 0.9 MAX. DEMAND 74.43 kW TOTAL CONNECTED LOAD (3 PH): 82.70 kW

TYPE OF METER (RATING OF INCOMER) : (1) Upto 60A - 1 Phase (2) Upto 100A - 3 Phase (3) 125 - 160A - 3Phase (4) LV CT ……./…..A / HV CT…../…..A
PROJECT: PROPOSED GROUND SHED LOAD DISTRIBUTION SCHEDULE
PLOT NO :- 5310279
SMDB - AC CLIENT: ALEX RENNER MOTOR GARAGE
LOCATION :- SAIH SHUAIB 2
FED FROM : MDB-02 CONSULTANT: ALGAFRY CONSULTING ARCHITECTS ENGINEERS

RATING-AMPS CABLE SIZE CONNECTED LOAD - KW PROPOSED TYPE &


PVC/* XLPE REMARKS
FAULT Length of No. OF kwh Meters
CIRCUIT/ FEEDER
SP/TP DUTY Cable ECC SIZE 1C mm2
DB NO. MCCB / 1-PH 3-PH LV/HV
F/S ISO. KA SWA/ PVC 2/4/ X 1C mm2 2/3/ X 4C mm2 (Mtrs.) R-PH KW Y-PH KW B-PH KW TOTAL KW
ACB (1) (2) CT (4)

INCOMER-1 250A 35 XLPE/SWA/PVC 4C 150MM2 1C 70MM2 41.60 41.60 41.60 124.80

OUT GOING:
AHU-01 TP 63A 25 XLPE/SWA/PVC 4C 25MM2 1C 16MM2 8.77 8.77 8.77 26.30

AHU-02 TP 63A 25 XLPE/SWA/PVC 4C 25MM2 1C 16MM2 8.77 8.77 8.77 26.30

AHU-03 TP 63A 25 XLPE/SWA/PVC 4C 25MM2 1C 16MM2 7.77 7.77 7.77 23.30

AHU-04 TP 63A 25 XLPE/SWA/PVC 4C 25MM2 1C 16MM2 7.77 7.77 7.77 23.30

FAHU TP 63A 25 XLPE/SWA/PVC 4C 25MM2 1C 16MM2 8.53 8.53 8.53 25.60


MDB CONNECTED TO:DEWA LV DB/Transf. SMDB
TOTAL CONNECTED LOAD PER PHASE: 41.60 41.60 41.60 124.80 TOTAL
CONNECTED TO: MDB:

DEMAND FACTOR: 0.9 MAX. DEMAND 112.32 kW TOTAL CONNECTED LOAD (3 PH): 124.80 kW

TYPE OF METER (RATING OF INCOMER) : (1) Upto 60A - 1 Phase (2) Upto 100A - 3 Phase (3) 125 - 160A - 3Phase (4) LV CT ……./…..A / HV CT…../…..A

513
PROJECT: PROPOSED GROUND SHED LOAD DISTRIBUTION SCHEDULE
PLOT NO : - 5310279
DB NO : DB-OFF/LL CLIENT: ALEX RENNER MOTOR GARAGE
LOCATION :- SAIH SHUAIB 2
FED FROM : MDB-02 CONSULTANT: ALGAFRY CONSULTING ARCHITECTS ENGINEERS

CONNECTED LOADS / POINTS LOAD PER CIRCUIT - WATT


RATING OF

RATING OF
INCOMER

CCT ECT
MCB
ELCB
SL. CIR WIRE WIRE WATT/
RTG IN ROOM / AREA 13A 20A 40A WAT. UNIT
REMARKS
NO. NO. SIZE SIZE C. EX. SH 13A 16A HD/ 45A W SPLIT
AMPS
mm2 mm2
LTG TW W/H WP WP PUM FCU OTHER R Y B
FAN FAN S/O S/O ISO WM CCU A/C A/C P
S/O ISO ISO

1 R1 10 2.5 2.5 RECEPTION 7 30 210

2 Y1 10 2.5 2.5 RECEPTION 7 30 210

40 A 4P 3 B1 10 2.5 2.5 SALES MGR 2 40 80


100mA
(1) 4 R2 10 2.5 2.5 AFTER SALES 2 40 80

5 Y2 10 2.5 2.5 CORRIDOR 6 52 312

6 B2 10 2.5 2.5 ACCOUNTS 2 40 80

7 R3 10 2.5 2.5 IT ROOM 2 40 80

8 Y3 10 2.5 2.5 ACCOUNTS MANAGER 2 40 80

40 A 4P 9 B3 10 2.5 2.5 CONFERENCE ROOM 2 40 80


100mA
(2) 10 R4 10 2.5 2.5 SERVER ROOM 2 40 80

11 Y4 10 2.5 2.5 MD ROOM 8 30 240

12 B4 10 2.5 2.5 STORE ROOM 2 40 80

13 R5 10 2.5 2.5 PRAYER ROOM 2 40 80

14 Y5 10 2.5 2.5 MD ROOM COVE LIGHT 1 100 100

40 A 4P 15 B5 10 2.5 2.5 RECEPTION COVE LIGHT 1 100 100


100mA
(3) 16 R6 10 2.5 2.5 FEMALE TOILET 3 18 54

17 Y6 10 2.5 2.5 DINING AREA 6 40 240


63A TP ISOLATOR

18 B6 10 2.5 2.5 MALE TOILET 4 18 72

19 R6 10 2.5 2.5 TOILET 3 18 54


40 A 4P
100mA 20 Y6 10 2.5 2.5 TOILET 4 18 72
(4)
21 B6 10 2.5 2.5 ELECTRICAL ROOM 1 36 36

22 R7 20 4 4 TOILET 1 400 400

23 Y7 20 4 4 DINING AREA 2 400 800


PRAYER ROOM &
40 A 4P 24 B7 20 4 4 2 200 400
RECEPTION
30mA
(5) 25 R7 20 4 4 PRAYER ROOM 1 400 400

26 Y7 20 4 4 RECEPTION 4 400 1600

27 B7 20 4 4 SALES MGR 3 400 1200

28 R8 20 4 4 ACCOUNTS 3 400 1200

29 Y8 20 4 4 AFTER SALES 3 400 1200

30 B8 20 4 4 IT ROOM 3 400 1200

31 R8 20 4 4 ACCOUNTS MANAGER 3 400 1200


40 A 4P
30mA 32 Y8 20 4 4 CONFERENCE ROOM 4 400 1600
(6)
SERVER ROOM & STORE
33 B8 20 4 4 2 400 800
ROOM
34 R9 20 4 4 MD ROOM 2 400 800

35 Y9 20 4 4 MD ROOM 3 400 1200

36 B9 20 4 4 MD ROOOM 1 200 200

37 R9 32 6 6 RECEPTION & PRAYER 1 5450 5450


40 A 4P
100mA 38 Y9 32 6 6 SPACE
(7)
39 B9 32 6 6 OFFICES AREA 1 5450 5450

TOTAL 10088 7654 9778 27520


CABLE SIZE: 1X 4C 25mm2 Cu./PVC-XLPE/SWA/PVC & 1x 1C 16mm2 Cu, G/Y PVC, ECC W/H =Water Heater, 'A/C' = FCU, W/M=WASHING MACHINE, FR-FRIDGE
PROJECT: PROPOSED GROUND SHED LOAD DISTRIBUTION SCHEDULE
PLOT NO : - 5310279
DB NO : DB-01 CLIENT: ALEX RENNER MOTOR GARAGE
LOCATION :- SAIH SHUAIB 2
FED FROM : MDB-01 CONSULTANT: ALGAFRY CONSULTING ARCHITECTS ENGINEERS

CONNECTED LOADS / POINTS LOAD PER CIRCUIT - WATT


RATING OF

RATING OF
INCOMER

CCT ECT
MCB
ELCB
SL. CIR WIRE WIRE WATT/
RTG IN ROOM / AREA 13A 20A 40A WAT.
UNIT
REMARKS
NO. NO. SIZE SIZE C. EX. SH 13A 16A HD/ 45A 20A SPLIT
AMPS LTG TW W/H WP WP PUM FCU OTHER R Y B
mm2 mm2 FAN FAN S/O SO ISO WM CCU ISO A/C P
SO ISO ISO

1 R1 10 2.5 2.5 FERRARI+OTHER BRANDS 3 150 450


40 A 4P
100mA 2 Y1 10 2.5 2.5 FERRARI+OTHER BRANDS 4 150 600
(1)
3 B1 10 2.5 2.5 FERRARI+OTHER BRANDS 4 150 600

4 R2 20 4 4 FERRARI+OTHER BRANDS 1 1000 1000


40 A 4P
30mA 5 Y2 20 4 4 FERRARI+OTHER BRANDS 1 1000 1000
(2)
6 B2 20 4 4 ROLLING SHETTER 1 1000 1000

7 R3 32 6 6 1000
40 A 4P
30mA 8 Y3 32 6 6 FERRARI+OTHER BRANDS 1 3000 1000 CAR LIFT
63A TP ISOLATOR

(3)
9 B3 32 6 6 1000

10 R4 32 6 6 1000
40 A 4P
30mA 11 Y4 32 6 6 FERRARI+OTHER BRANDS 1 3000 1000 CAR LIFT
(4)
12 B4 32 6 6 1000

13 R5 32 6 6 1000
40 A 4P
30mA 14 Y5 32 6 6 FERRARI+OTHER BRANDS 1 3000 1000 CAR LIFT
(5)
15 B5 32 6 6 1000

16 R6 32 6 6 1000
40 A 4P
30mA 17 Y6 32 6 6 FERRARI+OTHER BRANDS 1 3000 1000 CAR LIFT
(6)
18 B6 32 6 6 1000

19 R7 32 6 6 500
40 A 4P
30mA 20 Y7 32 6 6 FERRARI+OTHER BRANDS 1 1500 500 CAR LIFT
(7)
21 B7 32 6 6 500

TOTAL 5950 6100 6100 18150


CABLE SIZE: 1X 4C 25mm2 Cu./PVC-XLPE/SWA/PVC & 1x 1C 16mm2 Cu, G/Y PVC, ECC W/H =Water Heater, 'A/C' = FCU, W/M=WASHING MACHINE, FR-FRIDGE
PROJECT: PROPOSED GROUND SHED LOAD DISTRIBUTION SCHEDULE
PLOT NO : - 5310279
DB NO : DB-01 A CLIENT: ALEX RENNER MOTOR GARAGE
LOCATION :- SAIH SHUAIB 2
FED FROM : MDB-01 CONSULTANT: ALGAFRY CONSULTING ARCHITECTS ENGINEERS

CONNECTED LOADS / POINTS LOAD PER CIRCUIT - WATT


RATING OF

RATING OF
INCOMER

CCT ECT
MCB
ELCB
SL. CIR WIRE WIRE WATT/
RTG IN ROOM / AREA 13A 20A 40A REMARKS
NO. NO. SIZE SIZE C. EX. SH 13A 16A HD/ 45A 20A SPLIT WAT. UNIT
AMPS LTG TW W/H WP WP FCU OTHER R Y B
mm2 mm2 FAN FAN S/O SO ISO WM CCU ISO A/C PUMP
SO ISO ISO

1 R1 10 2.5 2.5 ENGINE BUILDING ROOM 8 40 320


40 A 4P
100mA 2 Y1 10 2.5 2.5 SPARE PARTS DISTRIBUTION 5 40 200
(1)
3 B1 10 2.5 2.5 OFFICE 2 40 80

4 R2 20 4 4 ENGINE BUILDING ROOM 2 400 800


40 A 4P
30mA 5 Y2 20 4 4 SPARE PARTS DISTRIBUTION 2 400 800
(2)
6 B2 20 4 4 OFFICE 2 400 800
40A TP ISOLATOR

7 R3 32 6 6 1000
40 A 4P
30mA 8 Y3 32 6 6 FERRARI+OTHER BRANDS 1 3000 1000 CAR LIFT
(3)
9 B3 32 6 6 1000

10 R4 32 6 6 1000
40 A 4P
30mA 11 Y4 32 6 6 FERRARI+OTHER BRANDS 1 3000 1000 CAR LIFT
(4)
12 B4 32 6 6 1000

13 R5 32 6 6 500
40 A 4P
30mA 14 Y5 32 6 6 FERRARI+OTHER BRANDS 1 1500 500 CAR LIFT
(5)
15 B5 32 6 6 500

16 R6 32 6 6 1000
40 A 4P
30mA 17 Y6 32 6 6 FERRARI+OTHER BRANDS 1 3000 1000 CAR LIFT
(6)
18 B6 32 6 6 1000

TOTAL 4620 4500 4380 13500


CABLE SIZE: 1X 4C 16mm2 Cu./PVC-XLPE/SWA/PVC & 1x 1C 10mm2 Cu, G/Y PVC, ECC W/H =Water Heater, 'A/C' = FCU, W/M=WASHING MACHINE, FR-FRIDGE
PROJECT: PROPOSED GROUND SHED LOAD DISTRIBUTION SCHEDULE
PLOT NO : - 5310279
DB NO : DB-02 CLIENT: ALEX RENNER MOTOR GARAGE
LOCATION :- SAIH SHUAIB 2
FED FROM : MDB-01 CONSULTANT: ALGAFRY CONSULTING ARCHITECTS ENGINEERS

CONNECTED LOADS / POINTS LOAD PER CIRCUIT - WATT


RATING OF

RATING OF
INCOMER

CCT ECT
MCB
ELCB
SL. CIR WIRE WIRE WATT/
RTG IN ROOM / AREA 13A 20A 40A REMARKS
NO. NO. SIZE SIZE C. EX. SH 13A 16A HD/ 45A W SPLIT WAT. UNIT
AMPS LTG TW W/H WP WP FCU OTHER R Y B
mm2 mm2 FAN FAN S/O SO ISO WM CCU A/C A/C PUMP
SO ISO ISO

1 R1 10 2.5 2.5 BODY SHOP 3 150 450

2 Y1 10 2.5 2.5 BODY SHOP 4 150 600

40 A 4P 3 B1 10 2.5 2.5 BODY SHOP 3 150 450


100mA
(1) 4 R2 10 2.5 2.5 CAR WASH 2 150 300

5 Y2 10 2.5 2.5 SPARE PARTS STORE 4 40 160

6 B2 10 2.5 2.5 SPARE PARTS STORE 4 40 160


40A TP ISOLATOR

7 R3 20 4 4 SPRAY BOOTH 3 400 1200

8 Y3 20 4 4 CAR WASH 2 400 800

40 A 4P 9 B3 20 4 4 ROLLING SHETTER 1 1000 1000


30mA
(2) 10 R4 20 4 4 SPACE

11 Y4 20 4 4 SPARE PARTS STORE 2 400 800

12 B4 20 4 4 SPACE

13 R5 32 6 6 1000
40 A 4P
30mA 14 Y5 32 6 6 BODY SHOP 1 3000 1000 CAR LIFT
(3)
15 B5 32 6 6 1000

16 R6 20 6 6 1267
40 A 4P
100mA 17 Y6 20 6 6 SPARE PARTS STORE 1 3800 1267 AC
(4)
18 B6 20 6 6 1267
TOTAL 4217 4627 3877 12720
CABLE SIZE: 1X 4C 16mm2 Cu./PVC-XLPE/SWA/PVC & 1x 1C 10mm2 Cu, G/Y PVC, ECC W/H =Water Heater, 'A/C' = FCU, W/M=WASHING MACHINE, FR-FRIDGE
PROJECT: PROPOSED GROUND SHED LOAD DISTRIBUTION SCHEDULE
PLOT NO : - 5310279
DB NO : DB-03 CLIENT: ALEX RENNER MOTOR GARAGE
LOCATION :- SAIH SHUAIB 2
FED FROM : MDB-02 CONSULTANT: ALGAFRY CONSULTING ARCHITECTS ENGINEERS

CONNECTED LOADS / POINTS LOAD PER CIRCUIT - WATT


RATING OF

RATING OF
INCOMER

CCT ECT
MCB
ELCB
SL. CIR WIRE WIRE WATT/
RTG IN ROOM / AREA 13A 20A 40A
UNIT
REMARKS
NO. NO. SIZE SIZE C. EX. SH 13A 16A HD/ 45A W SPLIT WAT.
AMPS LTG TW W/H WP WP FCU OTHER R Y B
mm2 mm2 FAN FAN S/O SO ISO WM CCU A/C A/C PUMP
SO ISO ISO

1 R1 10 2.5 2.5 BODY SHOP 6 150 900


40 A 4P
100mA 2 Y1 10 2.5 2.5 BODY SHOP 5 150 750
(1)
3 B1 10 2.5 2.5 OFFICE 1 & PAINT MIXING RM 4 40 160

4 R2 20 4 4 BODY SHOP 1 400 400


40 A 4P
30mA 5 Y2 20 4 4 OFFICE 1 & PAINT MIXING RM 2 400 800
40A TP ISOLATOR

(2)
6 B2 20 4 4 BODY SHOP 2 1000 2000

7 R3 32 6 6 500
40 A 4P
30mA 8 Y3 32 6 6 BODY SHOP 1 1500 500 CAR LIFT
(3)
9 B3 32 6 6 500

10 R4 32 6 6 500
40 A 4P
30mA 11 Y4 32 6 6 BODY SHOP 1 1500 500 CAR LIFT
(4)
12 B4 32 6 6 500

13 R5 32 6 6 2333
40 A 4P
30mA 14 Y5 32 6 6 PAINT BOOTH 1 7000 2333
(5)
15 B5 32 6 6 2333

TOTAL 4633 4883 5493 15010


CABLE SIZE: 1X 4C 16mm2 Cu./PVC-XLPE/SWA/PVC & 1x 1C 10mm2 Cu, G/Y PVC, ECC W/H =Water Heater, 'A/C' = FCU, W/M=WASHING MACHINE, FR-FRIDGE
PROJECT: PROPOSED GROUND SHED LOAD DISTRIBUTION SCHEDULE
PLOT NO : - 5310279
DB NO : DB-04 CLIENT: ALEX RENNER MOTOR GARAGE
LOCATION :- SAIH SHUAIB 2
FED FROM : MDB-01 CONSULTANT: ALGAFRY CONSULTING ARCHITECTS ENGINEERS

CONNECTED LOADS / POINTS LOAD PER CIRCUIT - WATT


RATING OF

RATING OF
INCOMER

CCT ECT
MCB
ELCB
SL. CIR WIRE WIRE WATT/
RTG IN ROOM / AREA 13A 20A 40A REMARKS
NO. NO. SIZE SIZE C. EX. SH 13A 16A HD/ 45A W SPLIT WAT. UNIT
AMPS LTG TW W/H WP WP FCU OTHER R Y B
mm2 mm2 FAN FAN S/O SO ISO WM CCU A/C A/C PUMP
SO ISO ISO

1 R1 10 2.5 2.5 PORSCHE SECTION 3 150 450


40 A 4P
100mA 2 Y1 10 2.5 2.5 PORSCHE SECTION 3 150 450
(1)
3 B1 10 2.5 2.5 OFFICE-02 2 40 80

4 R2 20 4 4 PORSCHE SECTION 2 400 800


40 A 4P
30mA 5 Y2 20 4 4 OFFICE-02 2 400 800
(2)
6 B2 20 4 4 ROLLING SHETTER 1 1000 1000

10 R4 32 6 6 1000
40 A 4P
30mA 11 Y4 32 6 6 PORSCHE SECTION 1 3000 1000 CAR LIFT
(3)
12 B4 32 6 6 1000
63A TP ISOLATOR

13 R5 32 6 6 1000
40 A 4P
30mA 14 Y5 32 6 6 PORSCHE SECTION 1 3000 1000 CAR LIFT
(4)
15 B5 32 6 6 1000

16 R6 32 6 6 1000
40 A 4P
30mA 17 Y6 32 6 6 PORSCHE SECTION 1 3000 1000 CAR LIFT
(5)
18 B6 32 6 6 1000

19 R7 32 6 6 500
40 A 4P
30mA 20 Y7 32 6 6 PORSCHE SECTION 1 1500 500 CAR LIFT
(6)
21 B7 32 6 6 500

16 R6 32 6 6 1000
40 A 4P
30mA 17 Y6 32 6 6 PORSCHE SECTION 1 3000 1000 CAR LIFT
(7)
18 B6 32 6 6 1000

19 R7 32 6 6 1000
40 A 4P
30mA 20 Y7 32 6 6 PORSCHE SECTION 1 3000 1000 CAR LIFT
(8)
21 B7 32 6 6 1000

TOTAL 6750 6750 6580 20080


CABLE SIZE: 1X 4C 25mm2 Cu./PVC-XLPE/SWA/PVC & 1x 1C 16mm2 Cu, G/Y PVC, ECC W/H =Water Heater, 'A/C' = FCU, W/M=WASHING MACHINE, FR-FRIDGE
PROJECT: PROPOSED GROUND SHED LOAD DISTRIBUTION SCHEDULE
PLOT NO : - 5310279
DB NO : DB-04 A CLIENT: ALEX RENNER MOTOR GARAGE
LOCATION :- SAIH SHUAIB 2
FED FROM : MDB-01 CONSULTANT: ALGAFRY CONSULTING ARCHITECTS ENGINEERS

CONNECTED LOADS / POINTS LOAD PER CIRCUIT - WATT


RATING OF

RATING OF
INCOMER

CCT ECT
MCB
ELCB
SL. CIR WIRE WIRE WATT/
RTG IN ROOM / AREA 13A 20A 40A REMARKS
NO. NO. SIZE SIZE C. EX. SH 13A 16A HD/ 45A 20A W SPLIT WAT. UNIT
AMPS LTG TW W/H WP WP FCU OTHER R Y B
mm2 mm2 FAN FAN S/O SO ISO WM CCU ISO A/C A/C PUMP
SO ISO ISO

1 R1 10 2.5 2.5 PORSCHE SECTION 3 150 450


40 A 4P
100mA 2 Y1 10 2.5 2.5 PORSCHE SECTION 3 150 450
(1)
3 B1 10 2.5 2.5 SPACE

4 R2 20 4 4 PORSCHE SECTION 1 1000 1000


40 A 4P
30mA 5 Y2 20 4 4 PORSCHE SECTION 1 1000 1000
(2)
6 B2 20 4 4 ROLLING SHETTER 2 1000 2000

7 R3 32 6 6 1000
40 A 4P
30mA 8 Y3 32 6 6 PORSCHE SECTION 1 3000 1000 CAR LIFT
(3)
9 B3 32 6 6 1000
63A TP ISOLATOR

10 R4 32 6 6 1000
40 A 4P
30mA 11 Y4 32 6 6 PORSCHE SECTION 1 3000 1000 CAR LIFT
(4)
12 B4 32 6 6 1000

13 R5 32 6 6 500
40 A 4P
30mA 14 Y5 32 6 6 PORSCHE SECTION 1 1500 500 CAR LIFT
(5)
15 B5 32 6 6 500

16 R6 32 6 6 1000
40 A 4P
30mA 17 Y6 32 6 6 PORSCHE SECTION 1 3000 1000 CAR LIFT
(6)
18 B6 32 6 6 1000

19 R7 32 6 6 1000
40 A 4P
30mA 20 Y7 32 6 6 PORSCHE SECTION 1 3000 1000 CAR LIFT
(7)
21 B7 32 6 6 1000

19 R7 32 6 6 1833
40 A 4P
30mA 20 Y7 32 6 6 PORSCHE SECTION 1 5500 1833
(8)
21 B7 32 6 6 1833

TOTAL 7783.33 7783.33 8333.33 23900


CABLE SIZE: 1X 4C 25mm2 Cu./PVC-XLPE/SWA/PVC & 1x 1C 16mm2 Cu, G/Y PVC, ECC W/H =Water Heater, 'A/C' = FCU, W/M=WASHING MACHINE, FR-FRIDGE
PROJECT: PROJECT G+M SHED LOAD DISTRIBUTION SCHEDULE
PLOT NO : - 5310279
DB NO : DB-EXT CLIENT: ALEX RENNER MOTOR GARAGE
LOCATION :- SAIH SHUAIB 2
FED FROM : MDB-02 CONSULTANT: ALGAFRY CONSULTING ARCHITECTS ENGINEERS

CONNECTED LOADS / POINTS LOAD PER CIRCUIT - WATT


RATING OF

RATING OF
INCOMER

CCT ECT
MCB
ELCB
SL. CIR WIRE WIRE WATT/
RTG IN ROOM / AREA 20A 40A REMARKS
NO. NO. SIZE SIZE C. EX. SH 16A HD/ 45A W SPLIT WAT. UNIT
AMPS LTG W/H WP WP FCU OTHER R Y B
mm2 mm2 FAN FAN S/O ISO WM CCU A/C A/C PUMP
ISO ISO

1 R1 10 2.5 2.5 BOUNDARY WALL 9 60 540

2 Y1 10 2.5 2.5 BOUNDARY WALL 9 60 540

3 B1 10 2.5 2.5 BOUNDARY WALL 9 60 540

4 R2 10 2.5 2.5 BOUNDARY WALL 9 60 540


40 A 4P
100mA 5 Y2 10 2.5 2.5 BOUNDARY WALL 9 60 540
(1)
6 B2 10 2.5 2.5 BOUNDARY WALL 9 60 540

7 R3 10 2.5 2.5 STREET LIGHT 2 250 500

8 Y3 10 2.5 2.5 EXTERNAL WALL 8 36 288


32A TP ISOLATOR

9 B3 10 2.5 2.5 EXTERNAL WALL 8 36 288

10 R4 10 2.5 2.5 EXTERNAL WALL 8 36 288

11 Y4 10 2.5 2.5 EXTERNAL WALL 9 36 324

40 A 4P 12 B4 10 2.5 2.5 CAR PARKING 3 36 108


100mA
(2) 13 R5 10 2.5 2.5 CAR PARKING 3 36 108

14 Y5 10 2.5 2.5 CAR PARKING 3 36 108

15 B5 10 2.5 2.5 CAR PARKING 4 36 144

16 R6 20 4 4 333
40 A 4P
30mA 17 Y6 20 4 4 ENTRANCE NAME BOARD SIGN 1 1000 333
(3)
18 B6 20 4 4 333

19 R7 20 4 4 333
40 A 4P
30mA 20 Y7 20 4 4 ENTRANCE NAME BOARD SIGN 1 1000 333
(4)
21 B7 20 4 4 333
TOTAL 2643 2467 2287 7396
CABLE SIZE: 1X 4C 10mm2 Cu./PVC-XLPE/SWA/PVC & 1x 1C 10mm2 Cu, G/Y PVC, ECC W/H =Water Heater, 'A/C' = FCU, W/M=WASHING MACHINE, FR-FRIDGE