0% found this document useful (0 votes)
84 views11 pages

A Method of Line Fault Location Based On Traveling Wave Theory

Uploaded by

Đặng Ẩn
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
84 views11 pages

A Method of Line Fault Location Based On Traveling Wave Theory

Uploaded by

Đặng Ẩn
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/297729659

A Method of Line Fault Location Based on Traveling Wave Theory

Article  in  International Journal of Control and Automation · February 2016


DOI: 10.14257/ijca.2016.9.2.25

CITATION READS

1 129

4 authors, including:

Gang Ma
Nanjing Normal University
19 PUBLICATIONS   34 CITATIONS   

SEE PROFILE

All content following this page was uploaded by Gang Ma on 28 July 2016.

The user has requested enhancement of the downloaded file.


International Journal of Control and Automation
Vol.9, No.2 (2016), pp.261-270
http://dx.doi.org/10.14257/ijca.2016.9.2.25

A Method of Line Fault Location Based on Traveling Wave


Theory

Gang Ma1, 2, Linru Jiang1, Kaihua Zhou1 and Guchao Xu1


1. School of Electric & Automation Engineering, Nanjing Normal University,
Nanjing 210042, China
2. Electrical Engineering, Southeast University, Nanjing 210096, China
[email protected]

Abstract
This paper combines traveling wave distance measuring principle with the wavelet
transform and applies it to the detection and localization of power system short-circuit
fault to avoid the severity and multiple of line short-circuit fault. Firstly, according to the
current or voltage traveling wave signals detected by traveling wave detection devices put
on the bus bar ends, we take traveling wave distance measuring principle as
the theoretical basis to extract signals. Then, using wavelet transform to process the
signal in order to extract the singular points. Also, traveling wave fault location is
established by using B-type double-terminal traveling wave fault location algorithm.
Finally, in order to locate the fault precisely and make simulation on different fault types
and different sampling frequencies to come to a conclusion, we make wavelet transform of
the transient fault signals and make further simulation about the location of single-phase
grounding fault.

Keywords: fault location, traveling wave fault location, wavelet transform, grounding
fault, simulation

1. Introduction
Power system is a pillar of the country’s energy, also the economic lifeline.
Determining the location of the failure point quickly and accurately after the transmission
line failure can not only reduce the workload of line workers, but also help to clear the
fault rapidly, which will ensure the stability of the power supply system [1]. Nowadays,
the size of the grid is expanding, and operating conditions are becoming more and more
complex. As a result, it is not easy to check out when failure occurs on the line. Thus, we
need a method to locate the fault point quickly, efficiently and accurately. With the
development of the traveling wave theory and modern mathematics, there has been some
progress on the study of line failure based on traveling wave theory in recent years both at
home and abroad.
The entire power grid cannot run without the power transmission lines of distribution
network. Transmission line is a key to power transmission, also the point which causes
the most times of mistakes in the entire power system. Long-distance transmission line
and the variety of geography environment bring a lot of difficulties to trouble shooting.
So, it is important to take an effective method to find the point of failure quickly,
accurately, and reliably after a line failure [2-5].
Literature [6] proposed a fault location method which is based on impedance method.
This method gets the distance to the failure point by calculating the AC impedance before
and after the line fault happens, but it can be affected seriously by uncertain factors.
Literature [7] proposed a ranging method of nonlinear frequency characteristics analysis,
which uses nonlinear output frequency response function to analyze system domain
characteristics. This paper proposes a dual-side traveling wave method based on traveling

ISSN: 2005-4297 IJCA


Copyright ⓒ 2016 SERSC
International Journal of Control and Automation
Vol.9, No.2 (2016)

wave theory and wavelet transform theory, which gets the location of fault by analyzing
the singular point of current or voltage traveling wave signal.

2. Double-ended Traveling Wave Principle


Voltage jump will occur on the fault point when ground fault occurs on the
transmission line. The high-frequency current which is produced by voltage
mutation on the line is defined as fault transient traveling wave on the transmission
lines, whose speed is close to the speed of light. So we can take advantage of
double-ended traveling principle to determine the point of failure.

Figure 1. Schematic Diagram of Double Terminal Method

Double-ended power supply system is shown in Figure 1. The traveling waves


produced by the fault point will spread to both ends of the line when ground fault
occurs on the transmission line. We can calculate the distance to fault point by using
the time difference of traveling-wave arrival at the line ends. Point K in the figure is
the point of failure, t a1 and t b1 are the initial times for transient traveling wave
reaching A-side and B-side of line respectively. The velocity of traveling wave is  ,
the total length of the line is L AB , the fault location can be expressed as:
LAB  v(tb1  t a1 )
DAK 
2

LAB  v(tb1  ta1 ) (1)


DBK 
2
Double terminal method uses the traveling wave produced by line fault to locate
the fault point. In this paper, we use traveling wave recording device which is
mounted on the bus side of the transformer to capture and record the initial traveling
wave. Then, analyze the time when initial traveling wave arrives at the bus side of
transformer by using computer wavelet transform. This method converts the
complex problem of locating line fault to a relatively simple physical problem about
distance.

3. Double Terminal Method of Traveling Wave Fault Location


The method of locating fault point based on two-terminal traveling wave theory is
different from the method based on two-terminal electrical quantities [8], which measures
and locates point by the change of voltage, current and other parameters on both ends of
the line. Double-terminal traveling wave method only needs the time of fault traveling
wave reaching both ends of the line, and the speed of light is approximate to the velocity
of the traveling wave. As a result, it has advantage on simplified calculation.

262 Copyright ⓒ 2016 SERSC


International Journal of Control and Automation
Vol.9, No.2 (2016)

3.1 Extraction of Traveling-wave Signal


The key to realize two-terminal traveling wave method lies in the ability of
capturing the traveling wave when it reaches both ends of the transmission line.
When transmission line fault occurs, we can find the change of voltage and current
obvious on the primary side, then line wave surge generates, which contains lots of
information about the line fault. It is important to choose a simple and economical
way to survey the fault traveling wave signals from the secondary side of the
transformer because we need to survey it.
Only after the cutoff frequency of current and voltage transformer is higher than
10KHZ has been confirmed can we collect the slightly distorted signal while the
frequency of fault traveling wave is high. Also, it is better for traveling wave
distance measuring device to share transformers with other protection devices such
as distance protection and differential protection, or it will be difficult to promote
due to its poor economy. In order to meet the demand of accuracy within 1km, the
rising edge time of the signal on the secondary side should be less than a few
microseconds [11]. According to the experiment, the high-voltage transformer is
unable to meet this requirement, while transient response speed of current
transformers can meet the measurement request of high-frequency fault traveling
waves.
It is necessary to determine the arrival time of the initial surge by analyzing the
traveling wave signal after the signal acquisition conditions are met. The signal is of
singularity at that point if a signal or a derivative is off somewhere; If the signal is
unlimited derivative in its domain of definition, then the signal is none of
singularity, a mutant signal must be singular at its mutant point.[12]
The traveling wave signals from the line fault are almost mutant signals. The
waveform will change to be intermittent when fault happens. The key to determining
the time of fault occurs is to find the singular point of the signal. In order to analyze
the traveling wave signal, this paper takes the method of wavelet transform, which
is sensitive to frequency when processing the discrete signal. When the frequency of
wave signal mutates, the wavelet transform will change. The arrival time of initial
surge traveling wave at both ends can be known according to the changes, the
sampling frequency and the starting and ending time. Then we can calculate
absolute time difference by using time synchronization devices on both ends .

3.2 Synchronization of Two-side Fault Signal


The key to the method which is used in this paper is to determine absolute time
difference for initial surge of current traveling wave on both ends of the
transmission line to reach the bus. So, it is necessary to build a communication
channel which can meet request of speed and unconditional simultaneity on both
ends of line. With the development of global positioning system (GPS),
synchronous sampling on both ends of line has become a reality.
The transmission line is equipped with GPS synchronization device and
communication equipment based on wireless base station on both ends, which can
make sure that data will be analyzed accurately in real time. In order to meet
sampling frequency of the traveling wave signals, we can take the technology of
GPS synchronized sampling to ensure a high degree of synchronous sampling,
whose maximum error is less than 1us. The GPS synchronized sampling device is
shown in Figure 2 [13].

Copyright ⓒ 2016 SERSC 263


International Journal of Control and Automation
Vol.9, No.2 (2016)

Figure 2. Synchronized Sampling Device

As we can see in Figure 2, the device is equipped with a PC bus, which can
transform analog quantity collected by transformer based on GPS synchronization
technique to digital quantity by converter, then input the signal to the computer
through the plug-in unit, so we can get clock synchronized fault signals on both
ends.

4. Algorithm for Double Terminal Theory of Traveling Wave

4.1 Fixed Wave Velocity


Specific steps of the algorithm are shown in Figure 3:

Figure 3. Double-ended Traveling Wave Flow Chart

Set up the head and the end of the fault line as A-side and B-side. When a fault
occurs, the time of initial traveling wave reaching A-side and B-side are t a1 and t b1
respectively.  is traveling wave velocity, then the fault location can be figured out
by using equation(1).
According to the equation, the distance of transmission fault is determined by the
wave velocity, the total length of the line and the time difference of initial traveling
wave surge arriving between both ends of the line. Double terminal method of
traveling wave fault location uses fixed traveling wave velocity to measure the
distance, also the real length of the line is L AB . As a result, the deviation of
calculation is almost determined by the deviation of initial surge of traveling wave
arrival time difference between the two ends of the line.

264 Copyright ⓒ 2016 SERSC


International Journal of Control and Automation
Vol.9, No.2 (2016)

4.2 Improve the System to Reduce Velocity’s Impact


The traveling wave velocity in equation (1) is fixed. In fact, the unit inductance
and capacitance of line will change when considering the impact result from
topography and climate changes. According to the equation of velocity   1 / L  C ,
the actual wave velocity may change. At the same time, it is difficult to select the
velocity directly for the reason that the velocities of traveling wave in the line are
different at different frequencies. Based on the above reasons, we can see that there
are great uncertainties over the velocity of traveling wave. So, it is important to
determine the velocity of wave if we want to improve the accuracy of the method of
traveling wave fault location.
In order to reduce the effect of wave velocity, we use a double terminal method
of traveling wave fault location based on the real-time measured wave velocity in
this paper. Because of the method we use, the line in measuring area is uniform, the
wave velocity in measuring area is determined by the equipment based on the
double terminal method and line out of measuring area.
When a grounding fault occurs on the line out of the measuring area, the wave
velocity from the fault point can run through the power line in measuring area.
Assume l as the total length of the line, t1 and t 2 are assumed as the time of initial
fault traveling wave out of the measuring area to reach the traveling wave recording
devices on both ends of the bus, so we can define the velocity of traveling wave in
measuring area is:
l
v (2)
t2  t1
When fault location outside the measuring area is too far or there is too much
attenuation of signal in the process of transmission, a large error will occur in the
recording traveling data. Now, compare the measured velocity with the theoretical
velocity. If the error is in the scope allowed, then we should take this data, otherwise
we should abandon it and do not modify the last record. So we can not only ensure
the accuracy of the wave velocity and realize the measurement of velocity online,
but also improve the economy so that we don’t need to add equipment.
Actual measurement of velocity can also be measured by injecting signal in
offline mode when the line is under construction. The measured velocity is more
close to theoretical velocity, however, there must be some deviation because the
noise is added in actual operations.
Substitute equation (2) into equation (1), then we can get the formula of the fault
distance:

l  t a1  tb1 
DAM   1   (3)
2  t 2  t1 
According to the sag rate of power line and the fault distance calculated by the
above formula, we can find the tower number of the fault line accurately, and the
affection of tower location which is caused by wave velocity can be eliminated in
some ways.

5. Simulation
In this experiment, we use Simulink in Matlab to create a simulation system.
Assume the length of a 10kV double terminal power line as 500km, now the A-

Copyright ⓒ 2016 SERSC 265


International Journal of Control and Automation
Vol.9, No.2 (2016)

phase grounding fault occurs at 100km from the start point of the line. We can see
the model of the line distributed parameter in Figure 4.

Figure 4. The Model of 10kV Double Terminal Power Supply

Use powerlib, one of the power system modules in Simulink toolbox to build
model transmission line model, which is shown in Figure 5.

Figure 5. 10kV Transmission Line Simulation Module

As we can see in Figure 5, the three-phase power supply in the system is set as
10kV, 50Hz and neutral grounding. The wiring structure of the transformer is Y/Yg.
The parameters of line are as follows:
r1  0.0127  / km , l1  0.934  10 3 H / km , c1  12.74  10 9 F / km ,
r0  0.384 / km , l0  4.126  10 3 H / km , c0  7.75  10 9 F / km , the total length
of line is 500km.
In order to meet the accuracy of time to complete the simulation, we set the
powergui parameter in the figure as discrete sampling mode and set the sampling
frequency as 1MHz.

5.1 Single-phase Grounding Fault Simulation


Make a single-phase grounding fault simulation at the point which is 100km far
away from the point A, then we can see fault current waveform from the
transformers at both ends of the transmission line, such as Figure6 (a),(b).

266 Copyright ⓒ 2016 SERSC


International Journal of Control and Automation
Vol.9, No.2 (2016)

(a) A Terminal Waveform (b) B Terminal Waveform


Figure 6. The Current Waveform of Single-Phase Grounding Short Circuit

Based on wavemenu wavelet transform module in Matlab, five layers of discrete


dyadic wavelet transform is made on the collected discrete fault current signal by
using db5 as wavelet function. We can see the waveforms shown in Figure 7 (a , b).

(a) A Terminal Signal Waveform (b) B Terminal Signal Waveform


Figure 7. The Traveling Waveform of Single-phase Fault

The initial time of transient traveling wave reaching A-side and B-side of the line
is easy to get according to the waveform after transformation, which is the time of
waveform distortion point on the positioning line shown in waveform. We can see
that t a is 22369 in Figure 7(a) and t b is 23373 in Figure 7(b).
We can calculate the fault location by using equation (1):
t a1  22369 10 6 s

tb1  23373 10 6 s

t  tb1  ta1  23373 106  22369 106  1004 106 s

LAB  v(tb1  ta1 ) 500  3 105 1004 106


DAK    99.4 km
2 2
The distance from then fault point to a terminal measurement point is 99.4km, the
absolute error of this simulation is 600m and the relative error is 0.6%.
Make the same simulation experiment to the fault point which is 300km away, we
can see that t a is 23022 and t b is 22691 by using traveling wave extraction and
wavelet transformation.
According to equation (1), we get the fault location:
t a1  23022 10 6 s

tb1  22691 10 6 s

t  tb1  ta1  22691106  23022 106  -331106 s

Copyright ⓒ 2016 SERSC 267


International Journal of Control and Automation
Vol.9, No.2 (2016)

LAB  v(tb1  ta1 ) 500  3 105 (- 33110 6)


DAK    299.65 km
2 2
The distance from fault point to A terminal measure point is 299.65km. The
absolute error is 350m and the relative error is 0.117%.
The above simulation shows that double terminal method of traveling wave fault
location is effective to the single-phase grounding fault in 10kV double terminal
power supply system. The method can locate the fault points effectively, and the
range of error to the fault location is small.
In order to test and verify the effectiveness of the method of traveling wave fault
location which is mentioned in this paper, we select the distance to the fault
randomly to verify the effectiveness and accuracy of the method when single-phase
short circuit, phase-to-phase short circuit or three-phase short circuit happens. The
result of simulation is shown in table 1.

Table 1. The Result of Fault Simulation

Time Fault
Fault Absolute Relative
Fault type difference/ distance/k
distance/km error/m error/%
μs m
80 1135 79.75 250 0.25
One-phase
230 135 229.75 250 0.25
80 1130 80.5 500 0.5
Two-phase
230 129 230.65 650 0.65
80 1131 80.35 350 0.35
Three-phase
230 130 230.5 500 0.5
According to the data from the above table we can find that, the method of
traveling wave fault location we use in this paper is also an effective way to locate
fault point in other types of fault.

5.2 Impact Made by Sampling Frequency to the Ranging Error


The sampling frequency of fault traveling wave has a deep effect on the result of
calculation according to the principle of traveling wave fault location. When the
sampling frequency is high, if the period of sampling become shorter, the accuracy
of t will improve and then accuracy of calculation result will also rise.
In order to test the influence of frequency on the measuring error, we choose
different sampling frequency such as 1MHz, 5MHz and 10MHz to make simulation
of traveling wave fault location respectively. The specific results can be found in
Table 2.

Table 2. The Effect of Sampling Frequency on Simulation Results


Single-phase 1MHz 5MHz 10MHz
grounding fault 80 230 80 230 80 230
Time 1134. 1133.
1135 135 132.8 133.5
difference/μs 2 7
Fault 229.7 230.0 79.94 229.9
79.75 79.87
distance/km 5 8 5 75
Absolute
250 250 130 80 55 25
error/m
Relative
0.25 0.25 0.13 0.08 0.055 0.025
error/%

268 Copyright ⓒ 2016 SERSC


International Journal of Control and Automation
Vol.9, No.2 (2016)

From the data in the table we can see that the effect of sampling fr equency on
simulation results. When the sampling frequency increases, the accuracy of location
also increases. For example, the sampling error is 300m when the frequency is
1MHz, the sampling error is 100m when the frequency is 5MHz and the sampling
error is down to 50m when the frequency is up to 10MHz.
The increase of sampling frequency may improve the accuracy of the method in
some ways. However, with the increase of sampling frequency, the strong hardware
is needed. The requirement of sampling channel, fault-tolerant processing and
database will increase, and the huge sampling data will make calculation become
more complicated. So, we should take different factors into account and determine a
reasonable sampling frequency to meet the actual error requirement.

6. Conclusion
This paper presents a double terminal method of traveling wave fault location to
find the fault point when line fault occurs, and uses simulation software to do some
simulation experiments, which proves that the method can locate the fault point
effectively, precisely, and feasibly. The method can work out the distance to the
fault point by determining the times of initial traveling wave reaching both ends of
line. Therefore, the excessive resistances, grounding resistance, the reflection and
refraction of traveling wave have no effect on the method, so it has the
characteristics of high accuracy and small calculation. It can theoretically reduce or
even eliminate the effect of wave velocity on the accuracy of measurement by using
double terminal method to measure velocity.

Acknowledgements
This research was supported by NSF of Jiangsu Province of China (Grant no.
BK20141452), Program of Natural Science Research of Jiangsu Higher Education
Institutions of China (Grant no. 14KJB470006), High level talents in Nanjing
Normal University research start-up research project (Grant no. 2014111XGQ0078)
and Jiangsu province post-doctoral research funding scheme (Grant no. 1402216C).

References
[1] Y.H. Bao, “Study on Full Parallel AT Power Supply Mode Protection and Fault Location Plan”, Electric
Railway, vol. 2, (2010), pp. 15-19.
[2] Z. Li, Z. Feng and L. Jun, “Fault locating based on single-end traveling waves for T-type transmission
lines”, Electric Power Automation Equipment, vol. 30, no. 4, (2010), pp. 46-50.
[3] X. Fei, D. Xinzhou and W. Bin, “Combined single-end fault location method of transmission line and its
experiments”, Electric Power Automation Equipment, vol. 34, no. 4, (2014), pp.37-42.
[4] Z. Zhou, L. Yanping and W. Jie, “A new two-terminal traveling wave fault location method based on
wavelet transform”, Power System Technology, vol. 34, no. 1, (2010), pp.203-207.
[5] S. Xue, J. He and Y. Li, “Analysis of Unified Traveling Wave Theory for Transmission Lines”,
Automation of Electric Power System, vol. 31, no. 20, (2007), pp. 32-35.
[6] R. Zheng, X. Lin and F. Zhao, “Fault location based on global search of minimum phase difference for
high voltage transmission lines”, Electric Power Automation Equipment, vol. 32, no. 3, (2012), pp. 58-61.
[7] C. Minyou, S. Feng and Z. Jinqian, “The online monitoring method of power transmission line fault
based non-linear frequency response function”, Journal of Chongqing University, vol. 33, no. 1, (2010),
pp. 54-60.
[8] H. Shu, C. Cheng and W. Zhaoet, “Accurate traveling-wave front detection based on morphology and
HHT”, Electric Power Automation Equipment, vol. 29, no. 7, (2009), pp.1-7.
[9] Q. Jian, “Study on single terminal travelling wave fault location of transmission line”, Power System
Technology, vol. 29, no. 15, (2005), pp. 65-70.
[10] W. Geng, M. Huaning, “Fault location methods based on travelling wave theory for high voltage power
transmission lines”, High Voltage Apparatus, vol. 4, no. 2, (2005), pp. 135-138.
[11] S. Hongchun, L. Yi and X. Yingxia, “Discussions on the single ended approach based on travelling wave
to fault location that can avoid the effect of wave speed”, Relay, vol. 34, no. 8, (2006), pp. 1-2.

Copyright ⓒ 2016 SERSC 269


International Journal of Control and Automation
Vol.9, No.2 (2016)

[12] J. Yu, J. Yanjun and W. ZengPing, “New Principle of Fault Phase Selection Based on Wavelet Filter and
Its Derived Filter”, Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific. IEEE,
(2012), pp.1-4.
[13] S. Zhenhong, Z. Ju and T. Jie, “Fault location based on dual-terminal voltage measurement”, Electric
Power Automation Equipment, vol. 26, no. 6, (2006), pp. 27-29.

Author

Gang Ma, He is a lecturer in School of Electric & Automation


Engineering, Nanjing Normal University. He received the Ph.D.
degrees from North China Electric Power University. His
research interests include renewable energy, power system
analysis & simulation and Smart Grid.

270 Copyright ⓒ 2016 SERSC

View publication stats

You might also like