Ee 1
Ee 1
Ee 1
1. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL SYMBOL DESCRIPTION
CODE, THE RULES AND REGULATIONS OF THE AUTHORITIES THAT HAVE JURISDICTION OVER THE PROJECT, AND WITH THE POLICIES OF THE LOCAL POWER SERVICE ENTRANCE
TELECOMMUNICATION SERVICE ENTRANCE
UTILITY COMPANIES FOR ELECTRICAL AND FOR COMMUNICATION.
ENCLOSED CIRCUIT BREAKER IN NEMA-1/3R ENCL.
PROPOSED TRANSPORT
2.
AIR CIRCUIT BREAKER (FREE-STANDING)
TERMINAL PHASE 2
AUTOMATIC TRANSFER SWITCH
3. WIRING METHOD SHALL BE DONE IN THE FOLLOWING MANNER: MANUAL TRANSFER SWITCH GREENFIELD CITY,
A. RIGID STEEL CONDUIT (RSC) - AS SPECIFIED IN THE PLANS, IF ANY. MECHANICAL AND ELECTRICAL INTERLOCK FOR ATS STA. ROSA, LAGUNA
B. POLYVINYL CHLORIDE (PVC) PIPE - FOR PRIMARY AND SECONDARY POWER SERVICE ENTRANCE, TELEPHONE SERVICE ENTRANCE POWER PANEL BOARD
AND LAYOUT EMBEDDED IN THE CONCRETE/SLAB FOR POWER & LIGHTING. BUSBAR/CB GUTTER & ECB
C. FLEXIBLE METAL CONDUIT - FOR CONNECTION BETWEEN JUNC. BOX INSIDE TO LIGHTING OUTLET OF FIXTURES AT DROP CEILING. CIRCUIT HOME RUN
D. ELECTRICAL METALLIC TUBING - FOR INSTALLATION LAYOUT INSIDE DROP CEILING, EXPOSED AND DOUBLE WALL PARTITION,
4. ALL ELECTRICAL MATERIALS/EQUIPMENTS TO BE USED SHALL BE NEW AND OF THE APPROVED TYPE FOR BOTH LOCATION AND PURPOSE. JUNCTION BOX( PULL BOX/TAPPING POINT)
5. GENERAL USE RECEPTACLE SHALL BE RATED 15A, 250V, GROUNDING TYPE WITH PARALLEL SLOTS. SPECIAL PURPOSE OUTLETS SHALL BE OF THE FLOOR SINGLE CONVENIENCE OUTLET
TYPE AND RATING APPROPRIATE FOR THE EQUIPMENT TO BE SERVED. SINGLE CONVENIENCE OUTLET
6. SWITCHES FOR LIGHTS SHALL BE RATED 10A, 230V, AC RATED ONLY. DUPLEX CONVENIENCE OUTLET
PULLBOX(POWER PROVISION)
7. ALL OUTDOOR INSTALLATIONS SHALL BE OF THE WEATHERPROOF TYPE. S SINGLE GANG SWITCH
8. 2Sab 2 GANG SWITCH
3Sabc 3 GANG SWITCH
9. WHERE SPARE CIRCUITS ARE INDICATED IN THE SCHEDULE OF PANELBOARD, THE CONTRACTOR SHALL PROVIDE AN EMPTY CONDUIT S3W 3 WAY SWITCH
2S3Wab 2 GANG 3 WAY SWITCH
STUBBED-OUT INSIDE THE CEILING AND CAPPED.
RU/RD RISER UP/RISER DOWN
10. OUTLET BOXES SHALL BE 1.35MM THICK AND AS FOLLOWS: SB SWITCH BANK
A. CEILING LIGHT OUTLET - 100MM X 100MM X 55MM DEEP OCTAGONAL BOX FOR 1 OR 2 RACEWAY ENTRIES; EMERGENCY LIGHTS W/ SINGLE CONVENIENCE OUTLET
B. LIGHT SWITCHES - 100MM X 100MM X 55MM DEEP SQUARE BOX FOR 3 OR MORE RACEWAY ENTRIES. EXIT LIGHTS SIGNAGE
C. WALL MOUNTED CONVENIENCE - 50MM X 100MM X 55MM DEEP UTILITY BOX HAND DRYER
ACU, TELEPHONE OUTLET, ETC
D. CONVENIENCE OUTLET - 100MM X 100MM X 55MM DEEP SQUARE BOX WITH SPECIAL TYPE RAISED COVER
(FLOOR-MOUNTED) POP-UP 10W LED RECESSED MOUNTED ADJUSTABLE DOWNLIGHT;
E. OTHERS - AS REQUIRED BY EQUIPMENTS SERVED. 59 DEG BEAM SPREAD: 3000k; IP20
32W LED UP AND DOWNLIGHT WALL SCONCE
11. MOUNTING HEIGHTS SHALL BE AS FOLLOWS:CEILING LIGHT OUTLET
1X 20W LED LAMP; BOX-TYPE POWDERCOATED
A. PANELBOARDS, CABINETS & - 1400MM ABOVE FLOOR FINISH ON CENTER OR AS REQUIRED BY FIELD CONDITION 1225mm X 45mm X 20mm; 6500k
DISCONNECTING SWITCHES
B. LIGHT CONTROL SWITCHES - 1400MM ABOVE FLOOR FINISH ON CENTER
C. DESK TOP CONVENIENCE OUTLET - 300MM ABOVE FLOOR FINISH ON CENTER
D. CHIME & FIRE ALARM BELL - 250MM BELOW CEILING @ CENTER
E. OTHERS - AS REQUIRED BY EQUIPMENTS SERVED. 32W LED RECESSED DOWNLIGHT WITH 59 DEG BEAM SPREAD: 3000k
12. THE ENTIRE ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER DIRECT SUPERVISION OF A COMPETENT REGISTERED ELECTRICAL ENGINEER. 32W UPLIGHT, VERIFY DETAIL
PROVISION FOR DATA, PROVIDE 2 - 1 CORE SINGLE MODE FIBER
13. PROVIDE AN ADEQUATE AND EFFECTIVE GROUNDING SYSTEM. IN THE ABSENCE OF GI WATER PIPE IN SERVICE,
14. MOUNTING HEIGHTS OF ALL TYPES OF WRING DEVICES SHALL BE SUBJECT TO PRIOR APPROVAL BY THE ARCHITECT. TELEPHONE PROVISION, PROVIDE 1-4PAIR CAT6 CABLE
RISER UP TO
GENSET/EE ROOM
JOSE L. SERRANILLA,PEE
MH MH MH
E
1