GRP Relay Settings
GRP Relay Settings
(UNIT # 5)
REVISION NO. 0
GENERATOR PARAMETERS
RATING : 25 MVA
IMPEDANCE : 8.6%, + 10% TOL. AT PRINCIPAL TAP
VOLTAGE RATIO : 21/6.9 kV
TAP CHANGER RANGE : + 10% TO -10% in steps of 1.25%
VECTOR GROUP : Dyn1
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-312-510-E004
FOR GRP REV NO. : 0 DATE : 19.10.2011
KORBA WEST TPP SHEET : 2 OF 14
SETTING RANGE
ZONE-1, Z<1 SETTING : 2/In – 120/In
TIME, Z<1 TIME DELAY : 0 – 100 SECONDS
ZONE-2, Z<2 SETTING : 2/In – 120/In
TIME, Z<2 TIME DELAY : 0 – 100 SECONDS
IMPEDANCE OF GT (ZT) = (13.97*0.95)%
= 0.1327 P.U.
21x 21
= 0.1327 OHM
621
= 0.0942 OHM
CT RATIO = 20000 / 5 A
VT RATIO =
21000 / 3
V
110 / 3
IMPEDANCE ZONE Z1 = 70% OF ZT
CT RATIO
= 0.7 x Z
T VT RATIO
20000 110 / 3
= 0.7 x 0.0942 x
5 21000 / 3
= 1.3816 Ω
SELECTED Z1 = 7.0/In Ω
TIME DELAY OF ZONE Z1 = 1.00 SECOND (*)
IMPEDANCE ZONE Z2 = 100% OF ZT
CT RATIO
= Z
T VT RATIO
20000 110 / 3
= 0.0942 x
5 21000 / 3
= 1.973 Ω
SELECTED Z2 = 9.9/In Ω
TIME DELAY OF ZONE Z2 = 2.00 SECOND (*)
* : THE ABOVE TIME SETTING SHALL BE COORDINATED AT SITE.
VT RATIO : (21000/√3)/(110/√3) V
UNDER VOLTAGE SETTING RECOMMENDED : 70% OF VT SECONDARY VOLTAGE
VT SECONDARY VOLTAGE 110V
VOLTAGE SETTING RANGE : 10.0 – 120.0V
TIME SETTING RANGE : 0 – 100 SECOND
VOLTAGE SETTING : 77V
TIME SETTING : 0 SECONDS
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-312-510-E004
FOR GRP REV NO. : 0 DATE : 19.10.2011
KORBA WEST TPP SHEET : 3 OF 14
CT RATIO : 20000/5 A
VT RATIO : (21000/√3)/(110/√3) V
RATED RELAY CURRENT, In : 5A
SETTING RANGE, -P>1, -P>2 : 1.0 x In – 300 x In W
POWER1 TIME DELAY : 0 – 100 SECOND
0.5% OF RATED POWER = (0.5/100) x 500000000 W
= 2500000 W
0.5% POWER REFFERED TO RELAY = 2500000 x (5/20000) x (110/√3)/(21000/√3) W
= 3.27 W
= 0.654 x In W
SETTINGS SELECTED :
RECOMMENDED POWER SETTING,
-P>1, -P>2 : 1.0 x In W
TIME SETTING : T1= 2sec with turbine trip
T2= 10sec without turbine trip
CT RATIO : 20000/5 A
VT RATIO : (21000/√3)/(110/√3) V
RATED RELAY CURRENT, In : 5A
SETTING RANGE, -P>1, -P>2 : 1.0 x In – 300 x In W
POWER1 TIME DELAY : 0 – 100 SECOND
0.5% OF RATED POWER = (0.5/100) x 500000000 W
= 2500000 W
0.5% POWER REFFERED TO RELAY = 2500000 x (5/20000) x (110/√3)/(21000/√3) W
= 3.27 W
= 0.654 x In W
SETTINGS SELECTED :
RECOMMENDED POWER SETTING,
P<1, P<2 : 1.0 x In W
TIME SETTING : T1= 2sec with turbine trip
T2= 10sec without turbine trip
CT RATIO : 20000/5 A
VT RATIO : (21000/√3)/(110/√3) V
RATED RELAY CURRENT, In : 5A
SETTING RANGE, FFAIL1 –Xa1 : 0/In – 40/In Ω
FFAIL1 Xb1 : 25/In – 325/In Ω
FFAIL1 TIMEDELAY : 0 – 100 SECOND
SETTING RANGE, FFAIL2 –Xa2 : 0/In – 40/In Ω
FFAIL2 Xb2 : 25/In – 325/In Ω
FFAIL2 TIMEDELAY : 0 – 100 SECOND
BASE IMPEDANCE OF THE GENERATOR = kV2/MVA Ω
= 212/588 Ω
= 0.75 Ω
BASE IMPEDANCE OF THE GENERATOR
20000 110 3
REFERRED TO CT & VT SECONDARY = 0.75 x x Ω
5 21000 3
= 15.71 Ω
TRANSIENT REACTANCE OF THE GENERATOR = 24.1%
(SATURATED) (Xd’)
24.1
= 15.71 Ω
100
= 3.78 Ω
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-312-510-E004
FOR GRP REV NO. : 0 DATE : 19.10.2011
KORBA WEST TPP SHEET : 4 OF 14
8 16166
I2>2 CURRENT SET =
100 20000
= 0.064 In A
SETTING RANGE
DEAD MACH I> : 0.08 In – 4 In A
DEAD MACH V< : 10 – 120 V
DEAD MACH tPU : 0 – 10 SECOND
DEAD MACH tDO : 0 – 10 SECOND
CT RATIO : 20000/5 A
VT RATIO : (21000/√3)/(110/√3) V
SETTING RANGE
I>1 CURRENT SET : 0.08 In – 4 In A
I>1 TIME DELAY : 0 – 100 SECOND
CT RATIO : 20000/5 A
GENERATOR CURRENT : 16166 A
CT SECONDARY CURRENT CORRESPONDING TO = 16166 x5
16166 A A
20000
= 4.04 A
GENERATOR OVERLOAD CAPABILITY : 10% FOR 3 MINUTES
RECOMMENDED SETTING = 4.44 A
I>1 CURRENT SET = 0.89 In A
I>1 TIME DELAY = 2.0 SECOND
VT RATIO : (21000/√3)/(110/√3) V
SETTING RANGE
V>1, V>2 VOLTAGE SET : 60 – 185 V
V>1, V>2 TIME DELAY : 0 – 100 SECOND
V>1(Stage-1) VOLTAGE SET : 115.5 V
V>1 TIME DELAY (ALARM) : 2.0 SECOND
V>2 (Stage-2) VOLTAGE SET : 154 V
V>2 TIME DELAY (TRIP) : 0 SECOND
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-312-510-E004
FOR GRP REV NO. : 0 DATE : 19.10.2011
KORBA WEST TPP SHEET : 6 OF 14
VT RATIO : (21000/√3)/(110/√3) V
SETTING RANGE
V>1, V>2 VOLTAGE SET : 60 – 185 V
V>1, V>2 T ME D LAY : 0 – 100 SECOND
V>1(Stage-1) VOLTAGE SET : 121 V
V>1 TIME DELAY (TRIP) : 6.0 SECOND
V>2 (Stage-2) VOLTAGE SET : 154 V
V>2 INSTANTANEOUS (TRIP) : 0 SECOND
Pickup Value of earth fault detection = (100% - 95 %)xVT SEC VOLTAGE / TRVD
100%
= (100% - 95%)x220x(200/500) V (As TRVD=500/200)
100%
= 4.4V
VN Input : MEASURED
VN>1 VOLTAGE SET : 4.4 V
VN>1 TIME DELAY : 0.2 SECOND
SETTING RANGES
ALARM STAGE, 64R R<1 ALM SET : 1000 – 80000 OHM
64R R<1 ALM DELAY : 0 – 600 SECONDS
TRIPPING STAGE, 64R R<2 TRIP SET : 1000 – 80000 OHM
64R R<2 TRIP DELAY : 0 – 600 SECONDS
ALARM SETTING, 64R R<1 ALM SET : 80 KOHM
64R R<1 ALM DELAY : 10SECONDS
TRIP SETTING, 64R R<2 TRIP SET : 5 KOHM
64R R<2 TRIP DELAY : 1 SECOND
SETTING RANGES
FORWARD IMPEDANCE REACH, PSlip Za Forward : 0.5/In – 350/In Ω
REVERSE IMPEDANCE REACH, PSlip Zb Reverse : 0.5/In – 350/In Ω
LENS ANGLE : 90o – 150o
TIMER1, PSlip Timer T1 : 0 – 1 SECOND
TIMER1, PSlip Timer T2 : 0 – 1 SECOND
BLINDER ANGLE : 20o – 90o
PSlip Zc : 0.5/In – 350/In Ω
CT RATIO : 20000/5 A
VT RATIO : (21000/√3)/(110/√3) V
TRANSFORMER RATIO : 21 kV/ 420kV
FAULT LEVEL AT GRID : 40 kA FOR 1 SECOND
BASE POWER : 588 MVA
BASE VOLTAGE : 21 kV
SYSTEM IMPEDENCE ANGLE : 80 DEG. (assumed)
BASE IMPEDANCE = 212/588 Ω
= 0.75 Ω
MAXIMUM GT IMPEDANCE (XT) = 1.05 x (0.1397 x (621/588)) x 0.75
= 0.116 Ω
SYSTEM IMPEDANCE (X1) = 212/ 27712
= 0.0159 Ω
GENERATOR TRANSIENT IMPEDANCE (Xd’) = 1.15x0.241 x 0.75 Ω
= 0.207 Ω
PSLIP Za FORWARD = XT +X1
= (0.116 + 0.0159) x 5/In Ω
= 0.66/In Ω
PSLIP Zb REVERSE = 2 x Xd’
= 2 x 0.207 x 5/In Ω
= 2.07/In Ω
PSLIP Zc = 90% OF GT REACTANCE
= 0.9 x 0.116 x 5/In Ω
= 0.52
/In Ω
PSLIP TIMER T1 = 0.015 SECOND
PSLIP TIMER T2 = 0.015 SECOND
LENS ANGLE, = 90o
BLINDER ANGLE = 80o
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-312-510-E004
FOR GRP REV NO. : 0 DATE : 19.10.2011
KORBA WEST TPP SHEET : 8 OF 14
VT RATIO : (21000/√3)/(110/√3) V
SETTING RANGE
F<1, F<2 SETTING : 45 – 65 Hz
F<1, F<2 TIME DELAY : 0.1 – 100 SECOND
FIRST STAGE – ALARM
F<1 SETTING : 48.5 Hz
F<1 TIME DELAY : 2.5 SECOND
SECOND STAGE – TRIPPING
F<2 SETTING : 47.5 Hz
F<2 TIME DELAY : 2.0 SECOND
SELECTED SETTING
Is1 : 0.2 In
Is2 : 1.0 In
k1 : 0%
k2 : 20%
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-312-510-E004
FOR GRP REV NO. : 0 DATE : 19.10.2011
KORBA WEST TPP SHEET : 9 OF 14
In case of single turn inter turn fault, unbalance produced in faulty phase
leads to a voltage 0.908 p.u. in the faulty phase, with other two phase
voltages being normal.
Voltage across open delta secondary
VOD = ( VR VY VB ) N,
where, N is inverse of the transformation ratio of IVT1
1
IVT1 ratio = 110 73.33=
N
3 3
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-312-510-E004
FOR GRP REV NO. : 0 DATE : 19.10.2011
KORBA WEST TPP SHEET : 10 OF 14
V = 110/3 V
VOD = 0.092 x [110/3] x [(73.33/3)/(110/3)]
= 3.89 V
VOLTAGE SETTING : 4V
TIME SETTING : 0.10 SECOND
: 1
Iref
0.1397
: 7.15 Iref
SELECTED SETTING
Idiff> : 0.2 Iref
Idiff>> : 7.5 Iref
m1 : 0.20
m2 : 0.80
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-312-510-E004
FOR GRP REV NO. : 0 DATE : 19.10.2011
KORBA WEST TPP SHEET : 11 OF 14
: 1
Iref
0.086
: 11.62 Iref
SELECTED SETTING
Idiff> : 0.2 Iref
Idiff>> : 12 Iref
m1 : 0.20
m2 : 0.80
: 1
Iref
0.1397
: 7.158 Iref
SELECTED SETTING
Idiff> : 0.2 Iref
Idiff>> : 7.5 Iref
m1 : 0.20
m2 : 0.80
TITLE : DOCUMENT NO.
RELAY SETTING CALCULATIONS PE-DC-312-510-E004
FOR GRP REV NO. : 0 DATE : 19.10.2011
KORBA WEST TPP SHEET : 14 OF 14
CT RATIO : 1000/1 A
RCT : 5 OHMS