BE YLAA Spec Engineering Guide B50Hz
BE YLAA Spec Engineering Guide B50Hz
BE YLAA Spec Engineering Guide B50Hz
72-EG8 (115)
Nomenclature
Y L A A 0320 S E 50 X A B
DEVELOPMENT
LEVEL = B (BPHX)
S = STANDARD EFFICIENCY
H = HIGH EFFICIENCY
A = AMERICAS
A = AIR COOLED
L = SCROLL COMPRESSOR
Y = YORK CHILLER
Approvals
• ASME Boiler and Pressure Vessel Code – Section Vlll Division 1.
2 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
Table Of Contents
NOMENCLATURE.................................................................................................................................................... 2
APPROVALS............................................................................................................................................................ 2
TABLE OF CONTENTS............................................................................................................................................ 3
INTRODUCTION....................................................................................................................................................... 5
EQUIPMENT OVERVIEW......................................................................................................................................... 8
UNIT COMPONENTS............................................................................................................................................. 15
DESIGN PARAMETERS......................................................................................................................................... 20
ISOLATOR LOCATIONS........................................................................................................................................ 30
ELECTRICAL NOTES............................................................................................................................................ 32
WIRING LUGS........................................................................................................................................................ 34
WIRING DIAGRAM................................................................................................................................................. 38
NOTES.................................................................................................................................................................... 42
APPLICATION DATA.............................................................................................................................................. 44
GUIDE SPECIFICATIONS...................................................................................................................................... 46
JOHNSON CONTROLS 3
FORM 150.72-EG8 (115)
4 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
Introduction
Johnson Controls, the building efficiency leader, is proud to present the YORK Model
YLAA Air-Cooled Scroll Chiller.
Installation
The YLAA weighs less and has s smaller footprint than other chillers in its class. In fact, it
is 20-35% lighter weight than the market average chiller. When the chiller is roof-mounted
in new construction, the cost of the support structure can be reduced. In building retrofits,
the YLAA can provide the largest capacity in a given space and existing structure.
Power hook-up could not be any easier with the standard single-point connection. A ter-
minal block, disconnect switch or circuit breaker is provided to meet the unique needs of
every project and minimize installation time and labor. The factory-installed control trans-
former steps down the power voltage to the control voltage.
Chilled-water piping is also simple. The water connections are factory-piped to the out-
side of the unit, for ease of access. Factory-cut grooves, or optional flanges, make pip-
ing connections simple. Optional factory-installed pump kits eliminate the time, cost, and
mechanical-equipment room space necessary to install chilled-water pumps.
Press the start button with confidence – your YLAA has been run-tested at the factory to
ensure that you will have a successful start-up.
Reliability
The YLAA chiller is proven and reliable, designed to reduce service calls. The scroll com-
pressors have logged hundreds of thousands of operating hours in numerous different
applications. The corrosive-resistant condenser heat exchangers have been specifically
designed for stationary HVAC applications and have undergone extensive laboratory and
field testing to extend chiller life and improve performance. They are also more rigid than
standard condenser coils, making them less susceptible to damage during rigging, lifting,
and installation of the chiller.
Efficiency
JOHNSON CONTROLS 5
FORM 150.72-EG8 (115)
Introduction (Cont'd)
YLAA high-efficiency chillers, with their innovative control algorithms, offer industry-lead-
ing energy efficiency. Real-world energy efficiency is measured by IPLV (off-design) per-
formance, and YLAA chillers provide some of the best IPLVs in their class.
YLAA also offers an efficiency choice. In addition to the high-efficiency units, YLAA chill-
ers are available in standard efficiency models with smaller footprints and lower capital
costs.
Only pay for the chiller you need – the multi-efficiency levels of the YLAA allow you to
decide the best investment for the job.
Flexibility
The YLAA chiller offers a number of options designed to operate reliably across a wide
range of customer needs. It can cool glycol down to 10°F (-12°C). It can provide heat
recovery up to 140°F (60°C), with up to 85% of total heat rejection captured.
When factory-mounted pump kits are considered, there are now more pump sizes to
choose from. The optional kits come standard with valves, pressure ports, flow switch,
and strainer for quick hook-up, and frost protection to prevent freeze-up. There are also
more pump options available: variable-speed drives, dual pumps, service shut-off valves,
expansion tanks, and additional test ports for temperature and pressure sensing.
Standard low sound and multiple sound attenuation options allow flexibility in locating the
chiller, and reduce the cost for field-constructed barriers.
Sustainability
The YLAA makes you a leader in sustainability through innovation, not added cost. With
the combination of R-410A refrigerant, which has no ozone-depletion potential, and state-
of-the-art heat exchanger technology that allows refrigerant charge to be reduced by as
much as 30%, the YLAA chiller provides the most ecologically friendly equipment. Part-
nered with its low-sound properties for noise pollution prevention, this chiller is a true
earth-friendly offering.
Communications
The YLAA chiller comes standard with native communication capability for BACnet (MS/
TP), Modbus, and N2, with optional capabilities available for LON. The standard unit ca-
pabilities include built-in-scheduling, remote start-stop, remote water temperature reset
and up to two steps of demand (load) limiting depending on model. The standard control
panel can be directly connected to a Johnson Controls Building Automated System via the
standard factory-installed RS232 communication port.
6 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
Introduction (Cont'd)
Serviceability
JOHNSON CONTROLS 7
FORM 150.72-EG8 (115)
Equipment Overview
The 50 - 150 Ton (180 - 530 kW) YLAA models are shipped complete from the factory
ready for installation and use.The unit is pressure-tested, evacuated, and fully charged
with a zero Ozone Depletion Potential Refrigerant R-410A and includes an initial oil charge.
After assembly, a complete operational test is performed with water flowing through the
evaporator to assure that the refrigeration circuit operates correctly.
The unit structure is heavy-gauge, galvanized steel. This galvanized steel is coated with
baked-on powder paint, which, when subjected to ASTM B117 1000 hour, salt spray test-
ing, yields a minimum ASTM 1654 rating of “6”. Units are designed in accordance with
NFPA 70 (National Electric Code), ASHRAE/ANSI 15 Safety code for mechanical refrig-
eration, ASME and rated in accordance with AHRI Standard 550/590.
COMPRESSORS
The chiller has suction-gas cooled, hermetic scroll compressors. The YLAA compressors in-
corporate a compliant scroll design in both the axial and radial direction. All rotating parts are
statically and dynamically balanced. A large internal volume and oil reservoir provides greater
liquid tolerance. Compressor-crankcase heaters are also included for extra protection against
liquid migration.
LD18425
The compact, high efficiency Brazed Plate Heat Exchanger (BPHE) is constructed with
316L stainless steel corrugated channel plates with a filler material between each plate. It
offers excellent heat transfer performance with a compact size and low weight, reducing
structural steel requirements on the job site.
8 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
LD18426
Water inlet and outlet connections are 3” in diameter and are grooved for compatibility
with field supplied ANSI/AWWA C-606 couplings.
A factory-wired flow switch is standard, installed in a pipe section at the outlet of the
evaporator.
JOHNSON CONTROLS 9
FORM 150.72-EG8 (115)
Reference Table 1 for YLAA brazed plate evaporator Canadian Registration Numbers
(CRN) for all Canadian Provinces. Since all YLAA brazed plate evaporators are catego-
rized as pressure “H” fittings per CSA-B51, a CRN label or marking is not provided on the
evaporator. According to the Canadian Standards Association’s Boiler, pressure vessel,
and pressure piping code B-51 (2009 version), a product registered as a category “H” fit-
ting does not require a label or marking displaying the CRN.
CONDENSER
Coils - Condenser coils are made of a single material to avoid galvanic corrosion due
to dissimilar metals. Coils and headers are brazed as one piece. Integral sub cooling is
included. The design working pressure of the coil is 650 PSIG (45 bar). Condenser coil is
easily washable with clear water up to 100 psi (7 bar).
LD18427
Fans – The condenser fans are composed of corrosion resistant aluminum hub and glass-
fiber-reinforced polypropylene composite blades molded into a low-noise airfoil section.
They are designed for maximum efficiency and are statically and dynamically balanced for
vibration-free operation. They are directly driven by independent motors, and positioned
for vertical air discharge. The fan guards are constructed of heavy-gauge, rust-resistant,
coated steel. All blades are statically and dynamically balanced for vibration-free opera-
tion.
10 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
LD18428
Motors – The fans are driven by Totally Enclosed Air-Over, squirrel-cage type, current pro-
tected motors. They feature ball bearings that are double-sealed and permanently lubricated.
The YLAA chiller is designed with an intelligent control system that operates the chiller
automatically with maximum reliability, safety and ease of use. The controls are factory
tested and with as little user input as a chilled liquid setpoint the chiller will operate to meet
the load demand.
The control system includes native BACnet MS/TP, Modbus and N2 communications, with
LON protocol served through an optional eLink communications card.
DISPLAY
KEYPAD
ON/OFF
SWITCH
MICROBOARD
TERMINAL CONTROL
BLOCK TRANSFORMER
LD18429
FUSES
The operating program is stored in non-volatile memory (EPROM), so power failures and
battery discharge will not require reprogramming the chiller. Programmed setpoints are
retained in lithium battery-backed RTC memory for 5 years minimum.
JOHNSON CONTROLS 11
FORM 150.72-EG8 (115)
Maximum reliability is achieved through intelligent control. Run hours and starts are av-
eraged across all compressors automatically, and between both pumps of the optional
dual pump hydro-kit. When compressors are cycled off, an anti-recycle timer ensures
the motors have time to cool before starting again, for the maximum service life. At unit
shutdown, the unit pumps down automatically to prevent liquid refrigerant from entering
the compressors at restart, which can cause premature bearing wear and other compres-
sor damage.
Liquid temperature sensors provide feedback to the controller, and logic predicts when
additional capacity will be required based on how quickly the unit has loaded or unloaded
in the past. This prevents unnecessary compressor cycling and helps maintain setpoint
accurately.
If there is a problem that prevents the unit operating properly, the controls are designed to
allow the unit to operate safely while making as much capacity as possible. For example,
if airflow to the condenser coil is diminished due to a dirty coil, the chiller will unload slightly
to provide maximum capacity possible while remaining within the unit operating envelope.
If a fault prevents the unit from starting or causes it to shutdown, the chiller will attempt to
restart three times. If it cannot start, a manual reset is required to alert the operator about
the fault condition. The fault history is stored in the unit controller RTC memory for the
last six fault shutdown conditions. An RS-232 port provides capability to print hard copy
reports (printer available separately).
All controls are contained in a NEMA 3R cabinet with a hinged outer door and includes a
liquid crystal display (LCD) with light emitting diode (LED) backlighting for outdoor view-
ing. There are two display lines, each with twenty text characters per line, and a color
coded 12-button non-tactile keypad with sections for display, entry and printing.
• Ambient temperature
• Number of compressors
12 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
• Set time
In addition, the microprocessor control center is capable of displaying the following data
points:
• Holiday status
JOHNSON CONTROLS 13
FORM 150.72-EG8 (115)
COMMUNICATIONS
In addition to native BACnet, Modbus and N2, the YLAA chiller accepts a 4-20 milliamp
or 0-10VDC input to reset of the leaving chilled liquid temperature. The standard unit ca-
pabilities include remote start-stop, remote water temperature reset via up to two steps of
demand (load) limiting depending on model. The standard control panel can be directly
connected to a Johnson Controls Building Automated System via the standard on-board
RS232 communication port. (Factory- installed)
POWER PANEL
The power wiring is routed through liquid-tight conduit to the compressors and fans.
FAN
FAN DISCONNECT FAN FAN FAN
FUSE CONTACTORS SWITCH CONTACTORS FUSE CONTACTORS
FAN
CONTACTORS
XTBF1
14 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
Unit Components
MICROCHANNNEL
FAN DECK
COILS COIL
HEADERS
HYDRO-KIT
PUMPS AND CONTROL
MOTORS AND POWER
(OPTIONAL) PANELS
COMPRESSORS
FORMED STEEL
BASE RAILS BRAZED PLATE
EVAPORATOR
LD18426
JOHNSON CONTROLS 15
FORM 150.72-EG8 (115)
POWER OPTIONS:
Single-Point Circuit Breaker – A unit mounted circuit breaker with external, lockable
handle (in compliance with NEC Article 440-14), can be supplied to isolate the power volt-
age for servicing. (This option includes the Single-Point Power connection.)
Multiple Point Supply With Individual System Circuit Breakers – Two unit-mounted
circuit break- ers, with external lockable handles (in compliance with NEC Article 440-14),
can be supplied to isolate the power voltage for servicing. (SQ only)
Control Transformer – Converts unit power voltage to 115-1-60 (0.5 or 1.0 kVA capac-
ity). Factory mounting includes primary and secondary wiring between the transformer
and the control panel. (Factory installed)
Power Factor Correction Capacitors – Will correct unit compressor power factors to a
0.90-0.95. (Factory installed)
CONTROL OPTIONS:
High Ambient Kit – Allows units to operate when the ambient temperature is above 46°C
(115°F). Includes sun shield panels and discharge pressure transducers.
Low Ambient Kit – Standard units will operate to -1°C (30°F). This accessory includes
all necessary components to permit chiller operation to -18°C (0°F). (This option includes
the discharge pressure transducer/readout capability option.) For proper head pressure
control in applications below -1°C (30°F) where wind gusts may exceed 8 kph (5 mph),
it is recommended that optional condenser louvered enclosure panels also be included.
(Factory installed)
Language LCD And Keypad Display – Spanish, French, German, and Italian unit LCD
controls and keypad display available. Standard language is English.
16 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
Chicago Code Relief Valves – Unit will be provided with relief valves to meet Chicago
code requirements. (Factory installed)
Service Suction Isolation Valve – Service suction discharge (ball-type) isolation valves
are added to unit per system (discharge service ball-type isolation valve is standard on
each circuit). (Factory installed)
Hot Gas By-Pass – Permits continuous, stable operation at capacities below the mini-
mum step of compressor unloading to as low as 5% capacity (depending on both the unit
and operating conditions) by introducing an artificial load on the evaporator. Hot gas by-
pass is installed on only refrigerant system #1. (Factory installed)
Thermal Dispersion Flow Switch – A thermal dispersion type flow switch provides ac-
curate, low maintenance flow proving and is included standard. It is factory wired and in-
stalled in the extension pipe between evaporator outlet and edge of chiller. The extension
pipe is secured to the chiller frame for shipping to avoid risk of damage to evaporator and
is easily attached to the evaporator at startup using the supplied ANSI/AWWA C-606 con-
nector. The flow switch can be deleted if alternate or existing flow switch is field supplied.
Evaporator Nozzle Extension Kit – Pipe and ANSI/AWWA C-606 fittings to extend the
evaporator connections to the outside of the chiller. Includes the Thermal Dispersion Flow
Switch. Provided as standard on all chillers but can be deleted if alternate or existing pip-
ing and flow switch is field supplied. The extension pipe is secured to the chiller frame for
shipping to avoid risk of damage to evaporator and is easily attached to the evaporator at
startup using the supplied ANSI/AWWA C-606 connector. A support bracket for the exten-
sion kit or field piping is standard on all chillers.
Hydro-Kit – Factory installed Hydro-Kit suitable for water glycol systems with up to 35%
glycol at leaving temperatures down to 20°F. The hydro-kit option is available in a single
or dual configuration (dual as standby duty only), with totally enclosed permanently lubri-
cated pump motors.
The hydro-kit option comes standard with a balancing valve, discharge check valve, dis-
charge shutoff valve, thermal dispersion flow switch, pressure ports, inlet wye-strainer,
bleed and drain valves and frost protection.
Service shut off valves, additional pressure ports and expansion tanks are optional within
the hydro-kit option.
JOHNSON CONTROLS 17
FORM 150.72-EG8 (115)
Post-Coated Condenser Coils – The unit is built with electrostatic post-coated condens-
er coils. This is the choice for corrosive applications (with the exception of strong alkalies,
oxidizers and wet bromine, chlorine and fluorine in concentrations greater than 100 ppm).
Wire Panels (Full Unit) – Consists of welded wire-mesh guards mounted on the exterior
of the unit. Prevents unauthorized access, yet provides free air flow. (Factory installed)
Wire/Louvered Panels – Consists of welded wire-mesh panels on the bottom part of unit
and louvered panels on the condenser section of the unit. (Factory- mounted).
Louvered Panels (Condenser Coil Only) – Louvered panels are mounted on the sides
and ends of the condenser coils for protection. (Factory installed)
Louvered Panels (Full Unit) – Louvered panels surround the front, back, and sides of
the unit. They prevent unauthorized access and visually screen unit components. Un-
restricted air flow is permitted through generously sized louvered openings. This option
is applicable for any outdoor design ambient temperature up to 46°C (115°F). (Factory
installed)
Coil End Hail Guard – Louvered panel attached to exposed coil end. (Factory installed)
18 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
One or both of the following sound attenuation options are recommended for residential
or other similar sound sensitive locations.
Ultra Quiet Fans – Lower RPM, 8-pole fan motors are used with steeper-pitch fans. (Fac-
tory installed)
VIBRATION ISOLATION
Vibration Isolators – Level adjusting, spring type 1” (25.4mm), 2” (50.8 mm) deflection,
or neoprene isolators for mounting under unit base rails. (Field installed)
JOHNSON CONTROLS 19
FORM 150.72-EG8 (115)
Design Parameters
20 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
500
C
WATER PRESSURE DROP (kPa) E
A
50
F
B
D
5
5 50
LD18455
JOHNSON CONTROLS 21
FORM 150.72-EG8 (115)
YLAA
REFRIGERANT R-410A
STANDARD EFFICIENCY UNITS
GENERAL UNIT DATA 0180SE 0210SE 0241SE 0286SE 0320SE 0360SE 0400SE 0435SE 0485SE
Nominal Tons, R-410A 53.9 57.3 62.1 76.9 86.3 97.6 109.2 118.4 132.0
COP 2.99 2.34 2.78 2.61 2.37 2.66 2.55 2.70 2.55
IPLV 4.66 3.84 4.25 4.45 4.16 4.40 4.28 4.40 4.31
Length (mm) 2912 2912 2912 2912 2912 3614 3614 3614 3614
Width (mm) 2242 2242 2242 2235 2235 2242 2242 2242 2242
Height (mm) 2397 2397 2397 2397 2397 2397 2397 2397 2397
Number of Refrigerant
2 2 2 2 2 2 2 2 2
Circuits
Refrigerant Charge, Operating
21/15 25/15 24/23 26/24 26/26 30/26 31/29 31/29 32/30
R-410A, Ckt1 / Ckt2, kg
Oil Charge, Ckt1 / Ckt2, liters 9/6 11/6 9/9 9/11 11/11 16/9 16/11 16/14 16/16
Shipping Weight (kg) 1668 1702 1768 1831 1995 2781 2834 2604 2705
Operating Weight (kg) 1689 1723 1789 1857 2028 2814 2873 2642 2755
Compressors, scroll type
Compressors Per Circuit 3/2 2/2 3/3 3/2 2/2 3/3 3/2 3/3 3/3
Condenser
Total Face Area m2 7 7 10 10 10 13 13 15 15
Number of Rows 1 1 1 1 1 1 1 1 1
Condenser Fans
Number of Fans, Ckt1 / Ckt2 2/2 2/2 2/2 2/2 2/2 3/2 3/2 3/3 3/3
Fan hp 2 2 2 2 2 2 2 2 2
Fan RPM 950 950 950 950 950 950 950 950 950
Total Chiller m3/sec 20 20 28 28 28 35 35 42 42
Evaporator
Water Volume, liters 20.4 20.4 20.4 25.4 33.3 33.3 37.9 37.9 50.0
Maximum Water Side
10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3
Pressure, bar
Maximum Refrigerant Side
31 31 31 31 31 31 31 31 31
Pressure, bar
Water Connections Size, inch 3 3 3 3 3 3 3 3 3
NOTES:
1. Standard Rating Conditions per AHRI Standard 550/590.
2. COP = Chiller COP (includes power from compressors, fans, and the control panels).
3. Rated in accordance with AHRI Standard 550/590 at an air on condenser temperature of 95°F and a leaving chilled water temperature of
44°F.
4. Additional rating information can be provided by your local Johnson Controls Sales Office.
22 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
YLAA
REFRIGERANT R-410A
HIGH EFFICIENCY UNITS
GENERAL UNIT DATA 0195HE 0221HE 0261HE 0300HE 0350HE 0390HE 441HE 456HE 516HE
Nominal TONs, R-410A 56.3 60.1 70.5 87.8 98.1 109.5 121.5 127.6 147.4
COP 3.11 3.22 3.11 3.11 3.11 3.02 3.02 3.05 3.05
IPLV 4.92 4.84 4.75 4.57 4.48 4.63 4.60 4.63 4.84
Length (mm) 2912 2912 2912 3614 3614 3614 4731 4731 4731
Width (mm) 2242 2242 2242 2235 2235 2242 2242 2242 2242
Height (mm) 2397 2397 2397 2397 2397 2397 2393 2393 2393
Number of Refrigerant
2 2 2 2 2 2 2 2 2
Circuits
Refrigerant Charge,
Operating R-410A, Ckt1 / 24/17 25/23 25/25 28/24 29/29 33/28 38/28 37/36 40/40
Ckt2, kg
Oil Charge, Ckt1 / Ckt2, liters 9/6 9/6 9/9 12/10 11/11 16/9 16/11 16/14 16/16
Shipping Weight (kg) 1688 1700 1822 2137 2301 2458 3294 3444 3561
Operating Weight (kg) 1714 1725 1855 2170 2339 2508 3344 3482 3615
Compressors, scroll type
Compressors Per Circuit 3/2 3/2 3/3 2/2 2/2 3/3 3/2 3/3 3/3
Condenser
Total Face Area m2 7.4 10 10 12.6 15.1 15.1 17.6 20.1 20.1
Number of Rows 1 1 1 1 1 1 1 1 1
Condenser Fans
Number of Fans, Ckt1 / Ckt2 2/2 2/2 2/2 3/2 3/3 4/2 4/3 4/4 4/4
Fan hp 2 2 2 2 2 2 2 2 2
Fan RPM 950 950 950 950 950 950 950 950 950
Total Chiller m3/sec 20 28 28 35 42 42 49 56 56
Evaporator
Water Volume, liters 25.4 25.4 33.3 33.3 37.9 50.0 50 37.9 54
Maximum Water Side
10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3
Pressure, bar
Maximum Refrigerant Side
31 31 31 31 31 31 31 31 31
Pressure, bar
Water Connections Size, inch 3 3 3 3 3 3 4* 4* 4*
* Side extension kit (standard), evaporator nozzle remains 3”
NOTES:
1. Standard Rating Conditions per AHRI Standard 550/590.
2. COP = Chiller COP (includes power from compressors, fans, and the control panels).
3. Rated in accordance with AHRI Standard 550/590 at an air on condenser temperature of 95°F and a leaving chilled water temperature
of 44°F.
4. Additional rating information can be provided by your local Johnson Controls Sales Office.
JOHNSON CONTROLS 23
FORM 150.72-EG8 (115)
Unit Dimensions
YLAA0180SE, 0210SE, 0195HE
LD18445
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Controls’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2m (6'); rear to wall – 2m (6’); control panel to end wall
– 1.2m (4'0''); top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the
unit.
24 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
LD18446
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Controls’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2m (6'); rear to wall – 2m (6’); control panel to end wall
– 1.2m (4'0''); top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the
unit.
JOHNSON CONTROLS 25
FORM 150.72-EG8 (115)
LD18447
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Controls’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2m (6'); rear to wall – 2m (6’); control panel to end wall
– 1.2m (4'0''); top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the
unit.
26 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
LD18448
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Controls’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2m (6'); rear to wall – 2m (6’); control panel to end wall
– 1.2m (4'0''); top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the
unit.
JOHNSON CONTROLS 27
FORM 150.72-EG8 (115)
LD18449
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Controls’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2m (6'); rear to wall – 2m (6’); control panel to end wall
– 1.2m (4'0''); top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the
unit.
28 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
LD18450
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Controls’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2m (6'); rear to wall – 2m (6’); control panel to end wall
– 1.2m (4'0''); top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the
unit.
JOHNSON CONTROLS 29
FORM 150.72-EG8 (115)
Isolator Locations
LD18451
LD18452
30 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
LD18453
JOHNSON CONTROLS 31
FORM 150.72-EG8 (115)
Electrical Notes
NOTES:
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the
largest motor plus 100% of the rated load amps for all other loads included in the cir-
cuit, per N.E.C. Article 430‑24. If the optional Factory Mounted Control Transformer
is provided, add the following MCA values to the electrical tables for the system
providing power to the transformer: -50 = 380/415-3-50, add 1 amps.
2. The minimum recommended disconnect switch is based on 115% of the rated load
amps for all loads included in the circuit, per N.E.C. Article 440.
3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor
plus 100% of the rated load amps for all other loads included in the circuit to avoid
nuisance trips at start‑up due to lock rotor amps. It is not recommended in applica-
tions where brown outs, frequent starting and stopping of the unit, and/or operation
at ambient temperatures in excess of 35ºC (95ºF) is anticipated.
4. Maximum fuse size is based upon 225% of the rated load amps for the largest mo-
tor plus 100% of the rated load amps for all other loads included in the circuit, per
N.E.C. Article 440-22.
5. Circuit breakers must be UL listed and CSA certified and maximum size is based
on 225% of the rated load amps for the largest motor plus 100% of the rated load
amps for all other loads included in the circuit. Otherwise, HACR‑type circuit break-
ers must be used. Maximum HACR circuit breaker rating is based on 225% of the
rated load amps for the largest motor plus 100% of the rated load amps for all other
loads included in the circuit.
6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can
be accommodated by the unit wiring lugs. The (2) preceding the wire range indi-
cates the number of termination points available per phase of the wire range speci-
fied. Actual wire size and number of wires per phase must be determined based on
the National Electrical Code, using copper connectors only. Field wiring must
also comply with local codes.
9. Field Wiring by others which complies to the National Electrical Code & Local Codes.
32 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
LEGEND
VOLTAGE CODE
-50 = 380/415-3-50
JOHNSON CONTROLS 33
FORM 150.72-EG8 (115)
Wiring Lugs
LUGS
MODEL
VOLT HZ ETL TB ETL NFDS ETL CB
YLAA
1XX 2XX 3XX
0180SE 400 50 (1) #6 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL (1) #6 AWG - 350 kCMIL
0210SE 400 50 (1) #6 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0241SE 400 50 (1) #6 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0286SE 400 50 (1) #6 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0320SE 400 50 (1) #6 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0360SE 400 50 (1) #6 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0400SE 400 50 (1) #6 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0435SE 400 50 (2) #6 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0485SE 400 50 (2) #6 - 500 kCMIL (2) 250 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL
0195HE 400 50 (1) #6 - 500 kCMIL (1) #6 AWG - 350 kCMIL (1) #6 AWG - 350 kCMIL
0221HE 400 50 (1) #6 - 500 kCMIL (1) #6 AWG - 350 kCMIL (1) #6 AWG - 350 kCMIL
0261HE 400 50 (1) #6 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL (1) #6 AWG - 350 kCMIL
0300HE 400 50 (1) #6 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL (1) #6 AWG - 350 kCMIL
0350HE 400 50 (1) #6 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0390HE 400 50 (1) #6 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0441HE 400 50 (2) #6 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0456HE 400 50 (2) #6 - 500 kCMIL (2) 250 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL
0516HE 400 50 (2) #6 - 500 kCMIL (2) 250 - 500 kCMIL (2) #3/0 AWG - 250 kCMIL
34 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
LUGS
MODEL
VOLT HZ ETL NFDS W/ INDIVIDUAL CE NFDS CE NFDS W/
YLAA
SYSTEM CBS 4XX W/ MMS MMS & SS
0180SE 400 50 (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL N/A
0210SE 400 50 (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL N/A
0241SE 400 50 (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL N/A
0286SE 400 50 (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0320SE 400 50 (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0360SE 400 50 (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0400SE 400 50 (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0435SE 400 50 (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0485SE 400 50 (2) 250 - 500 kCMIL (2) 250 - 500 kCMIL (2) 250 - 500 kCMIL
0195HE 400 50 (1) #6 AWG - 350 kCMIL (1) #6 AWG - 350 kCMIL (1) #6 AWG - 350 kCMIL
0221HE 400 50 (1) #6 AWG - 350 kCMIL (1) #6 AWG - 350 kCMIL (1) #6 AWG - 350 kCMIL
0261HE 400 50 (1) #6 AWG - 350 kCMIL (1) #6 AWG - 350 kCMIL (1) #6 AWG - 350 kCMIL
0300HE 400 50 (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0390HE 400 50 (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL (2) #3/0 AWG - 250 kCMIL
0441HE 400 50 (2) #3/0 AWG - 250 kCMIL N/A (2) #3/0 AWG - 250 kCMIL
0456HE 400 50 (2) 250 - 500 kCMIL N/A (2) 250 - 500 kCMIL
0516HE 400 50 (2) 250 - 500 kCMIL N/A (2) 250 - 500 kCMIL
JOHNSON CONTROLS 35
FORM 150.72-EG8 (115)
NOTES:
1. Reference PIN 59 for pump models.
2. Use this table along with Pump Electrical Data to determine electrical data of the unit plus the pump.
3. Does not include the Control Transformer.
36 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
NOTES:
1. Reference PIN 59 for pump models.
2. Use this table along with Pump Electrical Data to determine electrical data of the unit plus the pump.
3. Does not include the Control Transformer.
JOHNSON CONTROLS 37
FORM 150.72-EG8 (115)
Wiring Diagram
38 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
JOHNSON CONTROLS 39
FORM 150.72-EG8 (115)
A-
INTERNAL WIRING TO OPTIONAL REMOTE TEMP. RESET BOARD
A+
14
FLOW SWITCH
13
50
13
21
REMOTE UNLOAD STEP 1
13
20
PWM REMOTE TEMP RESET
13
19 INTERNAL WIRING TO 2-KCR CONTROL RELAY
13
18 INTERNAL WIRING TO 1-KCR CONTROL RELAY
13
51
REMOTE START / STOP
13
XTBC1
LD13130
LD13130
40 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
XTBC2
LD13242
JOHNSON CONTROLS 41
FORM 150.72-EG8 (115)
Notes
42 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
Notes (Cont'd)
JOHNSON CONTROLS 43
FORM 150.72-EG8 (115)
Application Data
UNIT LOCATION
The YLAA chillers are designed for outdoor installation. When selecting a site for installa-
tion, be guided by the following conditions:
1. For outdoor locations of the unit, select a place having an adequate supply of fresh
air for the condenser.
4. The condenser fans are the propeller-type, and are not recommended for use with
duct work in the condenser air stream.
In installations where winter operation is intended and snow accumulations are expected,
additional height must be provided to ensure normal condenser air flow.
Recommended clearances for units are given in Dimensions. When the available space is
less, the unit(s) must be equipped with the discharge pressure transducer option to permit
high pressure unloading in the event that air recirculation were to occur.
FOUNDATION
The unit should be mounted on a flat and level foundation, ground or roof, capable of sup-
porting the entire operating weight of the equipment. Operating weights are given in the
PHYSICAL DATA tables.
Roof Locations – Choose a spot with adequate structural strength to safely support the
entire weight of the unit and service personnel. Care must be taken not to damage the roof
during installation. If the roof is “bonded”, consult the building contractor or architect for
special installation requirements. Roof installations should incorporate the use of spring-
type isolators to minimize the transmission of vibration into the building structure.
44 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
For ground level installations, precautions should be taken to protect the unit from tam-
pering by or injury to unauthorized persons. Screws on access panels will prevent casual
tampering; however, further safety precautions, such as unit enclosure options, a fenced-
in enclosure, or locking devices on the panels may be advisable. Check local authorities
for safety regulations.
The chilled liquid piping system should be laid out so that the circulating pump discharges
into the evaporator. The inlet and outlet evaporator liquid connections are given in DI-
MENSIONS.
Hand stop valves are recommended for use in all lines to facilitate servicing. Drain con-
nections should be provided at all low points to permit complete drainage of the evapora-
tor and system piping. Additionally, a strainer (20 mesh) is recommended for use on the
INLET line to the evaporator.
Pressure gauge connections are recommended for installation in the inlet and outlet wa-
ter lines. Gauges are not furnished with the unit and are to be furnished by other suppliers.
The chilled liquid lines that are exposed to outdoor ambients should be wrapped with a
supplemental heater cable and covered with insulation. As an alternative, ethylene glycol
should be added to protect against freeze-up during low ambient periods.
A flow switch is available as an accessory on all units. The flow switch (or its equivalent)
must be installed in the leaving water piping of the evaporator and must not be used to
start and stop the unit.
JOHNSON CONTROLS 45
FORM 150.72-EG8 (115)
Guide Specifications
PART 1 – GENERAL
1.01 SCOPE
A. The requirements of this Section shall conform to the general provisions of the Con-
tract, including General and Supplementary Conditions, Conditions of the Contract,
and Contract Drawings.
4. Manufacturer Start-Up
A. Products shall be Designed, Tested, Rated and Certified in accordance with, and In-
stalled in compliance with applicable sections of the following Standards and Codes:
1. AHRI 550/590 – Water Chilling Packages Using the Vapor Compression Cycle
5. ASHRAE 90.1 – Energy Standard for Buildings Except Low-Rise Residential Build-
ings
10. Conform to Intertek Testing Services for construction of chillers and provide ETL/
cETL Listed Mark
B. Factory Run Test: Chiller shall be pressure-tested, evacuated and fully charged with re-
frigerant and oil, and shall be factory operational run tested with water flowing through
the vessel.
46 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
D. Warranty: Manufacturer shall Warrant all equipment and material of its manufacture
against defects in workmanship and material for a period of eighteen (18) months from
date of shipment or twelve (12) months from date of start-up, whichever occurs first.
A. Unit shall be delivered to job site fully assembled with all interconnecting refrigerant
piping and internal wiring ready for field installation and charged with refrigerant and
oil by the Manufacturer.
B. Provide protective covering over vulnerable components for unit protection during
shipment. Fit nozzles and open ends with plastic enclosures.
PART 2 - PRODUCTS
A. General: Install and commission, as shown on the schedules and plans, factory as-
sembled, charged, and tested air cooled scroll compressor chiller(s) as specified
herein. Chiller shall be designed, selected, and constructed using a refrigerant with
Flammability rating of “1”, as defined by ANSI/ASHRAE STANDARD 34 Number Des-
ignation and Safety Classification of Refrigerants. Chiller shall include not less than
two refrigerant circuits above 50 tons (200kW), scroll compressors, direct-expansion
type evaporator, air-cooled condenser, refrigerant, lubrication system, interconnecting
wiring, safety and operating controls including capacity controller, control center, mo-
tor starting components, and special features as specified herein or required for safe,
automatic operation.
C. Operating Characteristics: Provide low and high ambient temperature control options
as required to ensure unit is capable of operation from -1°C to 46°C (30°F to 115°F)
ambient temperature. [Optional: -18°C to 52°C (0°F to 125°F) ambient.]
D. Service Isolation valves: Discharge (ball type) isolation valves factory installed per
refrigerant circuit. Includes a system high-pressure relief valve in compliance with
ASHRAE15.
1. Discharge Pressure Transducers: Permits unit to sense and display discharge pres-
sure.
2. Suction Pressure Transducers: Permits unit to sense and display suction pressure.
3. High Ambient Control: Allows units to operate when the ambient temperature is
above 46°C (115°F). Includes discharge pressure transducers.
JOHNSON CONTROLS 47
FORM 150.72-EG8 (115)
2. Refrigerant flow through the compressor with 100% suction cooled motor.
3. Large suction side free volume and oil sump to provide liquid handling capability.
5. Annular discharge check valve and reverse vent assembly to provide low-pressure
drop, silent shutdown and reverse rotation protection.
10. Compressor Motor overloads capable of monitoring compressor motor current. Pro-
vides extra protection against compressor reverse rotation, phase-loss and phase-
imbalance
Each refrigerant circuit shall include: a discharge service ball type isolation valve, high
side pressure relief, liquid line shutoff valve with charging port, low side pressure relief
device, filter-drier, solenoid valve, sight glass with moisture indicator, thermostatic expan-
sion valves [Option: electronic expansion valves], and flexible, closed-cell foam insulated
suction line and suction pressure transducer.
A. Evaporator :
3. Exterior surfaces shall be covered with 19mm (3/4”), flexible, closed cell insulation,
thermal conductivity of 0.26k ([BTU/ HR-Ft2 -°F]/in.) maximum.
4. Water nozzles shall be provided with grooves for field provided ANSI/AWWA C-606
mechanical couplings.
5. Evaporator shall include vent and drain fittings and thermostatically controlled heat-
ers to protect to -29°C (-20°F) ambient in off-cycle.
48 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
2. Low Sound Fans: Shall be dynamically and statically balanced, direct drive, corro-
sion resistant glass fiber reinforced composite blades molded into a low noise, full-
airfoil cross section, providing vertical air discharge and low sound. Each fan shall
be provided in an individual compartment to prevent crossflow during fan cycling.
Guards of heavy gauge, PVC (polyvinyl chloride) coated or galvanized steel shall
be factory installed.
3. Fan Motors: High efficiency, direct drive, 6 pole, 3 phase, insulation class “F”,
current protected, Totally Enclosed Air-Over (TEAO), rigid mounted, with double
sealed, permanently lubricated, ball bearings.
2.05 CONTROLS
A. General: Automatic start, stop, operating, and protection sequences across the range
of scheduled conditions and transients.
B. Power/Control Enclosure: Rain and dust tight NEMA 3R powder painted steel cabi-
net with hinged, latched, and gasket sealed door.
2. Remote water temperature reset via 0-10 VDC or 4-20 mA input signal or up to two
steps of demand (load) limiting.
4. Forty character liquid crystal display, descriptions in English (or Spanish, French,
Italian, or German), numeric data in English (or Metric) units. Sealed keypad with
sections for Setpoints, Display/Print, Entry, Unit Options & clock, and On/Off Switch.
JOHNSON CONTROLS 49
FORM 150.72-EG8 (115)
6. Display Data: Return and leaving liquid temperatures, low leaving liquid tempera-
ture cutout setting, low ambient temperature cutout setting, outdoor air tempera-
ture, English or metric data, suction pressure cutout setting, each system suction
pressure, discharge pressure (optional), liquid temperature reset via a 4-20milliamp
or 0-10 VDC input, anti-recycle timer status for each compressor, anti-coincident
system start timer condition, compressor run status, no cooling load condition, day,
date and time, daily start/stop times, holiday status, automatic or manual system
lead/lag control, lead system definition, compressor starts/operating hours (each),
status of hot gas valves, evaporator heater and fan operation, run permissive sta-
tus, number of compressors running, liquid solenoid valve status, load & unload
timer status, water pump status.
7. System Safeties: Shall cause individual compressor systems to perform auto shut
down; manual reset required after the third trip in 90 minutes. System Safeties in-
clude: high discharge pressure, low suction pressure, high pressure switch, and
motor protector. Compressor motor protector shall protect against damage due to
high input current or thermal overload of windings.
8. Unit Safeties: Shall be automatic reset and cause compressors to shut down if
low ambient, low leaving chilled liquid temperature, under voltage, and flow switch
operation.
9. Alarm Contacts: Low ambient, low leaving chilled liquid temperature, low voltage,
low battery, and (per compressor circuit): high discharge pressure, and low suction
pressure.
D. Manufacturer shall provide any controls not listed above, necessary for automatic
chiller operation. Mechanical Contractor shall provide field control wiring necessary to
interface sensors to the chiller control system.
A. Power Panels:
1. NEMA 3R raintight, powder painted steel cabinets with hinged, latched, and gasket
sealed outer doors. Provide main power connection(s), control power connections,
compressor and fan motor start contactors, current overloads, and factory wiring.
2. Power supply shall enter unit at a single location, be 3 phase of scheduled voltage,
and connect to individual terminal blocks per compressor. Separate disconnecting
means and/or external branch circuit protection (by Contractor) required per appli-
cable local or national codes.
B. Compressor, control and fan motor power wiring shall be located in an enclosed panel
or routed through liquid tight conduit.
50 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
Some accessories and options supercede standard product features. Your Johnson Con-
trols representative will be pleased to provide assistance.
1. Low Ambient Control: Permits unit operation to -17.8°C (0°F) ambient. Standard
unit controls to -1.1°C (30°F) ambient.
2. High Ambient Control: Permits unit operation above 46°C (115°F) ambient.
1. Single Point Power Supply: Single point Terminal Block for field connection and
interconnecting wiring to the compressors. Separate external protection must be
supplied, by others, in the incoming power wiring, which must comply with the Na-
tional Electric Code and/or local codes.
3. Single Point Circuit Breaker: Single point Terminal Block with Circuit Breaker and
lockable external handle (in compliance with Article 440-14 of N.E.C.) can be sup-
plied to isolate power voltage for servicing. Incoming power wiring must comply with
the National Electric Code and/or local codes.
D. Control Power Transformer: Converts unit power voltage to 120-1-60 (500 VA ca-
pacity). Factory-mounting includes primary and secondary wiring between the trans-
former and the control panel.
2. Wire Panels (full unit): Heavy gauge, welded wire- mesh, coated to resist corro-
sion, to protect con- denser coils from incidental damage and restrict unauthorized
access to internal components.
3. Louvered Panels (full unit): Painted steel as per re- mainder of unit cabinet, to pro-
tect condenser coils from incidental damage, visually screen internal components,
and prevent unauthorized access to internal components.
JOHNSON CONTROLS 51
FORM 150.72-EG8 (115)
5. End Louver (hail guard): Louvered steel panels on external condenser coil faces
located at the ends of the chiller.
H. Thermal Dispersion Flow Switch (Factory installed and wired in piping extension
kit): Normally open, 30bar pressure rating, stainless steel 316L construction, IP67,-
20°C to 70°C (-4°F to 158°F) ambient rating.
I. Evaporator options:
J. Hot Gas By-Pass: Permits continuous, stable operation at capacities below the mini-
mum step of unloading to as low as 5% capacity (depending on both the unit & operat-
ing conditions) by introducing an artificial load on the evaporator. Hot gas by-pass is
installed on only one refrigerant circuit.
K. Thermal Storage: Leaving chilled liquid setpoint range for charge cycle from -3.9°C to
-6.7°C (25°F to 20°F) minimum, with automatic reset of the leaving brine temperature
up to 4.4°C (40°F) above the setpoint.
L. Low Temperature Process Glycol: Leaving chilled liquid setpoint range -12°C to
10°C (10°F to 50°F)
1. Elastomeric Isolators.
2. 1” Deflection Spring Isolators: Level adjustable, spring and cage type isolators for
mounting under the unit base rails.
52 JOHNSON CONTROLS
FORM 150.72-EG8 (115)
3.01 INSTALLATION
A. General: Rig and Install in full accordance with Manufacturers requirements, Project
drawings, and Contract documents.
C. Components: Installing Contractor shall provide and install all auxiliary devices and
accessories for fully operational chiller.
D. Electrical: Co-ordinate electrical requirements and connections for all power feeds
with Electrical Contractor (Division 16).
E. Controls: Co-ordinate all control requirements and connections with Controls Contrac-
tor.
F. Finish: Installing Contractor shall paint damaged and abraded factory finish with touch-
up paint matching factory finish.
JOHNSON CONTROLS 53
Printed on recycled paper
Form 150.72-EG8 (115) Supersedes: 150.72-EG8 (914)
© 2015 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201 Printed in USA
www.johnsoncontrols.com
Issued on 1/12/2015