MiCOM C264-P
Feeder Protection and
Control Solution
MiCOM C264-P enables innovative automation & protection schemes thanks to an extremely fast
(event driven) engine and robust topological processing. Combining any data available on the
10/100 Mbps IEC61850 Ethernet network eliminates conventional wiring and facilitates cost versus
dependability decisions within a substation.
OPTIMIZED ENGINEERING
VERSUS CONVENTIONAL DESIGNS
Customer Benefits
The multifunctional capabilities of MiCOM C264-P optimize system engineering as fewer devices
• Independent Protection result in less wiring, training and maintenance. Its modern XML and SCL configuration interfaces allow
module information to be shared between the various configuration tools used in the project, thus reducing the
• Advanced real-time overall engineering time.
Automation & Control
capabilities
REDUCE TROUBLE SHOOTINGS
• Optimized engineering
versus conventional AND MAINTENANCE COST
designs Thanks to this modular architecture with all card withdrawable construction, the MiCOM C264-P
• Reduce troubleshooting minimize replacement time and provides via the integrated WEB server all detailed necessary
time and maintenance maintenance information to the local or remote maintenance team.
costs
• Integration of today's and
tomorrow's
communication protocols
AREVA T&D
INTEGRATION OF TODAY’S AND > Wattmetric (32N)
TOMORROW’S COMMUNICATION The wattmetric protection protects the element against
PROTOCOLS a forward and reverse ground fault wether the earthing
is resistif, capacitif or inductif (Peterseen Coil). DMT
MiCOM C264-P is fully compatible with modern and IDMT tripping characteristic allows protection
communication standards IEC61850, IEC60870-5-104, coordination of elements over the network.
DNP3 over IP, IEC60870-5-101/103 and MODBUS,
while its modular design will make it easy to upgrade in
line with future advances in communication technology. > Under and Over Voltage (27, 59, 59N)
The MiCOM C264-P provides two independent under-
voltage stages and two independent over-voltage
PROTECTION FEATURES stages. They are definite time elements. Each stage
can be configured to operate in single-phase mode or
The MiCOM C264-P ensures feeder management and three phase mode.
bay control using powerfull protection and fast
An additional residual over-voltage stage that can be
automation feature providing an efficient single box
used for generic earth faults detection, particularly in
solution for HV and MV applications such as :
insulated neutral system or as backup at busbar level.
• MV feeder lines,
• Overhead lines and underground cables
(back-up protection on HV systems), > Broken conductor detection (37)
• Insulated, solid or resistance earthed and The definite time undercurrent protection of the MiCOM
Petersen coil earthed neutral system, C264-P allows typicaly simple broken conductor
• MV subscribers, Industry, Transport, detection or loss of load.
• Generator and transformer schemes.
> Thermal overload (49)
MiCOM C264-P supports the following protection The thermal overload protection is mainly dedicated for
functions : lines and transformers and includes a thermal replica
• Phase & earth Overcurrent (50/51, 50N/51N), element based on the true RMS value of the current, up
• Phase & earth Directional Overcurrent (67, 67N), to 10th harmonic. Alarm and overload thresholds and
• Wattmetric (32N), time constant are fully programmable to match each
application requirement.
• Negative sequence overcurrent (46).
• Undercurrent (37),
> Over and Under Frequency (81O, 81U)
• Undervoltage (27) and Over-voltage(59)
MiCOM C264-P Frequency protection supports 6
and residual Over-voltage (59N)
thresholds linked to 6 timers (definite time
• Over and Under-frequency (81O/81U), characteristic). Each threshold could be set to under
• Rate of frequency change (81R) frequency or over frequency. Protection frequency runs
• Thermal overload (49) each signal period.
• Breaker failure (50BF)
> Rate of Frequency changes (81R)
> Phase and Earth Overcurrent (50/51, 50N/51N) This protection supports 6 stages, based on average of
Three independent stages are available for phase and instantaneous rate of range, derived from the instantaneous
earth fault protection. For the first and second stage the frequency calculated each period. Each threshold is settable
user may independently select definite time delay or as over or under rate of frequency change.
inverse time delay with different type of curves (IEC,
IEEE/ANSI, RI). The third stage can be configured for > Auto-recloser (79)
peak detection and with definite time only. The IDMT MiCOM C264-P manages an integrated auto-recloser
stages have definitive or IDMT reset timer to reduce operating in single and/or three pole mode. Up to four
clearance times when intermittent faults occur. auto-reclosing shots are available and the delay for
Dedicated EPATR A, B, C curves are available with each is independently configurable. Auto recloser can
dedicated Earth CT. be initiated either internally in the bay unit or via
external protection devices using digital inputs.
> Phase and Earth Directional Overcurrent (67, 67N)
Each phase overcurrent stage of MiCOM C264-P can Substation LAN
be independently configured as directional protection IEC 61850
Ethernet LAN (10/100 Mbps)
with specific characteristic angle (RCA) and boundaries.
Each directional stage provides instantaneous reverse
(mirror) information.
2>3
> Trip circuit supervision (50BF) FEEDER BAY MANAGEMENT
The purpose of this function is to supervise the
continuity of the trip circuit of a circuit breaker by a > Binary Input processing
dedicated undercurrent threshold. MiCOM C264-P offers five types of Binary Input
The circuit breaker failure function can be activated by processing (Single point, Double points, Multiple points,
trip of a generic protection or/and external command. System Input and Logic Input), all acquired and time-
The circuit breaker failure stamped at 1 ms accuracy and discrimination.
protection can be used for tripping upstream circuit
Furthermore, C264-P contains multiple base BIs
breakers.
processing options, such as toggle filtering, persistence
Two options are available: two wires or four wires.
filtering, motion filtering, undefined state filtering,
The two-wire option permits verification of the trip manual suppression, substitution, forcing of invalid BIs
circuit continuity only when the circuit breaker is closed. and faulty indications.
The four-wire option permits verification of the Combining IEC61850 protocol on the substation LAN,
continuity in either position. BIs are transmitted on a client/server basis.
> Cold Load Pickup IEC61850 GOOSE mode is used to transmit BIs data
MiCOM C264P allows automatic or manual blocking or extremely quickly on the substation LAN to create
raising of trip settings for a period after the breaker is reflex automation schemes.
closed, avoiding unexpected trips.
> Digital outputs
> Protection setting groups Digital outputs are used to apply a switching voltage to
2 separate groups of protection settings are available an external device in order to execute single or dual,
within the MiCOM C264P and can be activated via an transient or permanent controls. MiCOM C264-P
IEC61850 command, a manual action or any physical contains multiple security and self-checks, such as
input. relay coil energizing, relay command, relay coil biasing,
relay driving registers.
> Derived values
A multitude of values are derived from the direct Furthermore, during configuration, a control may be set
primary measurements (currents and voltages), such to one of the following modes:
as: • Select Before Operate
• RMS currents and voltages • Direct Execute (DE)
• Network frequency and Phase angles
• Active, reactive and apparent powers > Measurement inputs processing
(P, Q – total), power factor MiCOM C264-P offers five types of measurement from:
• Sequence components • Analogue inputs (AI)
(positive and negative sequence for I and U) • Digital measurement (DM)
• Currents and phase-phase voltage magnitudes • Protection-value acquisition (CT/VT)
(direct or derived) • Derived values
• Communication network
> Disturbance recording
MiCOM C264-P provides Disturbance file recording
> Analogue inputs processing
initiated by:
Analogue inputs are voltage or current DC values,
• Change of state of binary digital inputs/outputs
representing an external value, delivered by
• Protection threshold crossing transducers. Measurements can be received through
• Operator's request the communication network as periodical messages or
as changes of state (variation, threshold, and invalidity)
The record length (pre and post time) and the number
in various formats including floating, binary, BCD and
of records is user ajustable.
others.
MiCOM C264-P
(80TE and 40TE)
front panels
> Analog outputs processing > Event logging
Analogue outputs are used to interface auxiliairy The MiCOM C264-P allows the storage of events in
devices requiring analog inputs (eg. Measurement non-volatile ring memory. The events are archived with
viewers, Generators, Motors, etc..). The Analog outputs their time stamp in chronological order. Up to 2000 of
are issued from Analog setpoints values received or the latest events are stored.
generated by the MiCOM C264-P. A quality indication is
available with the Read Inhibit output relays associated > IED Gateway
to each analog output. The Analog output values are MiCOM C264-P provides a cost-effective method for
secured via an external power supply (48VDC) keeping interfacing data already wired on legacy devices (IEDs)
the value even if the MiCOM C264-P power supply is to a substation automation system (such as DCS).
shut-down. IED’s data integration can be done via Ethernet-based
links or via several serial links.
> Digital measurement processing
The digital measurement (DM) inputs are acquired via > Local control, operation with LCD display
digital input boards. MiCOM C264-P allows the The control of switching devices is possible using the
acquisition of a digital value coded on N wired BI. Each MiCOM C264-P front panel LCD. Operating actions are
BI represents part of the DM value, and can be either performed in a simple and intuitive way, directly from
one of two values (low or high). These DM values are “Mimic “ views for the devices control and on dedicated
used to process measurements and tap indications. panels for data monitoring (i.e. measurements, events
Acquisition may be carried out either in BCD-coded list, alarms, etc.) and maintenance.
form, binary, Gray, decimal, or 1 among N. The operator panel can be mounted separately from
the rack (up to five/fifteen meters), if required, to
> Protection value acquisition provide a high level of flexibility in mounting positions.
Four currents (3 phase CTs & 1 earth CT) and four Access barriers protect the enter mode to guard
voltages (3 phase VTs & 1 neutral VT) derived from the against inadvertent or unauthorized changes to
direct primary measures are monitored and sampled at parameters or triggering of control functions.
32 samples/cycle.
Cases Max.
C264-P (40TE) C264-P (80TE) IOs
3 free slots 13 free slots per
type
Table key: I/O modules D E F G H I J K L M N O P Q
4>5
> Time Synchronization
The MiCOM C264-P internal clock can be
synchronised :
• by an operator
• by an IRIG–B GPS clock (via the IRIG-B input)
• by an Ethernet SNTP server,
• by a time telegram message issued by
remote Scada (DNP3.0, IEC60870-5-101 or
IEC60870-5-104).
> EMC
• IEC61000-4-12:1995 (IEC255 Part 22-1) –
High frequency disturbance: Class III (2.5 kV)
• IEC61000-4-2:2002(IEC60255-22-2) –
Electrostatic discharge: Level 4
(8kV contact, 15kV air)
• IEC61000-4-3:2002 (IEC60255-22-3) –
Radiated immunity: Level 3 (10 V/m-1GHz) and
IEEE C37.90.2 (35 V/m- 1GHz)
• IEC61000-4-4:2001 (IEC60255-22-4) –
Fast transient or burst: level 4
• IEC61000-4-5:2001–Surge immunity: Level 4
• EC61000-4-6:2003–
High frequency conducted immunity: Level 3
> Redundancy • IEC61000-4-8:1993 –
At substation level and/or bay level an optional Power frequency magnetic field immunity: Level 5
redundant MiCOM C264-P can be offerd to secure all (100A/m for 1mn; 1000A/m for 3s)
the critical functions at these levels. • IEC61000-4-9:1993 – Impulse magnetic field
immunity: Level 5 (1000 A/m pulses)
> Multi-bay management
MiCOM C264-P manages up to 12 independent bay
panel mimics with a maximum of 8 animated devices
on the local LCD.
MiCOM C264-P
40 TE and 80 TE
rear view
6>7
• IEC61000-4-10:2001 – Damped oscillatory > Protection CT & VT inputs
magnetic field immunity: Level 5 • Nominal frequency (FNOM): 50/60 Hz
(100 A/m at 100 kHz and 1 MHz) • Operating range: 45 to 66 Hz
• IEC61000-4-16:1998 – Power frequency • Sampling rate: 64 samples per cycle
immunity: CM 500 V/DM 250 V via 0.1µF • Voltage (resp. Current) accuracy : 0.5% at Vn
• EN 55022:2003 (CISPR 22) – Conducted (resp In)
emission: Gr. I, class A (from 0.15 to 30 MHz) • phase angles : ± 1° accuracy
• EN 55022:2003 (CISPR 22) – Radiated emission: • Pass band 10th harmonic
Gr. I, class A (from 30 to 1000 MHz, 10m)
> Protection CT : phase input
> Insulation
• Nominal current: 1A or 5A (ΙN)
• IEC 60255-5:2000
– High voltage impulse test: 5 kV (1.2/50 µs), 0.5J • Operating range: 0.1-40 ΙN
– Insulation voltage test: 2 KV rms, 1minute • Nominal consumption per phase input:
0.05 VA (at ΙN =1A) ; < 1,25 VA (at ΙN = 5A).
• Load rating per phase input : 4 ΙN in continuous,
30 ΙN for 10s, 100 ΙN for 1s
TECHNICAL DATA
• Surge current: 250 ΙN
> Design • Compatibility with external transformer : 5VA 5P10
Surface mounting cases (4 U, 40/80T) are included,
suitable for flush mounting on 19” cabinets and panels. > Protection CT : earth input
Natively, Ethernet connection and four serial • Nominal current: 1A or 5A (ΙON)
communication links (configurable) are available.
• Operating range :
0.01- 8 ΙON , 0.002-1 ΙON or 0.1-40 ΙON
Internal rugged Ethernet switch board (for simple star,
• Nominal consumption earth input
or switch for redundant Ethernet ring -SNMP managed,
< 0.008 VA at 0.1 ΙON (rating 1A);
or switch for dual physical star- SNMP managed)
< 0.175 VA at 0.1 ΙON (rating 5A)).
allows construction of multiple applications using fewer
• Load rating earth: 4 ΙON in continuous, 30 ΙON for
devices and demanding a high level of EMC immunity.
10s, 100 ΙON for 1s
> Degree of protection: • Surge current: 250 ΙON
• IP20 for the MiCOM C264-P case body 80TE • Compatibility with external transformer : 5VA 5P10
• IP50 for the MiCOM C264-P case body 40 TE
> Protection VT inputs:
• Front panel (LCD or Leds): IP 52 for both cases
• Nominal voltage: 50 to 130 V (option 220 to 480 V)
• Nominal consumption per phase: < 0.5 VA at 130 V
> Power Supply
Nominal Auxiliary Voltage: • Thermal heating : 2 VN phase-neutral permanent,
• VA, nom: 24 VDC, 48-60 VDC, 110-125 VDC, and 2.6 VN phase-neutral for 10 s
220 VDC, and 230 VAC 50/60 Hz, ±20%, and
40W max. admissible consumption DIMENSIONAL DRAWINGS
> IRIG-B interface 413.2
10
156.5
155.5
177
172.2
172.2
3 3
10.8
All dimensions in
30
413.2
206
O I L/R
200
17.7
10
12
All dimensions in mm
172.2
157.5
177
30
> DC Analogue inputs (AI) > DC Analogue outputs
• Range (independently configurable): • Range (independently configurable):
• ±1.25, ±2.5, ±5 and ±10V (AIU201 only) • ±5 mA and 0-5 mA
• ±1, ±5, ±10 and ±20 mA • ±10 mA and 0-10 mA
• 0-1, 0-5, 0-10, 0-20 and 4-20 mA • ±20 mA, 0-20 mA and 4-20 mA
• A/D converter resolution:15 bits + sign • Accuracy at 25°C full scale: 0.1%
• Accuracy at 25°C: • Deviation: < 100ppm/1°C
• Better than 0.1% in voltage • Output stabilization: < 100ms
(full scale at 25 °C) • AOU Watchdog relay:
• Better than 0.1% in current • Continuous current: 2,5 A
(full scale at 25 °C)
• Short-duration current: 30A for 500ms, 100A for 30ms
MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - PDF ONLY - SONOVISION-ITEP
Dual Attachment:
• 2 to 6 mA, maximum power dissipation is 0,45 W 4 x Tx ports (RJ45)
±20% per input + 2 Fx single or multi-mode ports for ring
• Trip and Control output relays redundancy;
• Operating voltage: 24 to 300 VDC or 250 VAC SNMP Managed.
• Continuous current: 5 A
• Short-duration current: 30A for 500ms, 100A for 30ms
• Breaking capacity:
AUTOMATION-L3-C264P-BR-05.08-1826-GB - © - AREVA - 2008. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
DC: 100W resistive,
ENVIRONMENTAL CONDITIONS
30W inductive (L/R=40ms) • Operating temperature:
AC: 1250 VA resistive, 1250VA inductive -25°C to +70°C (-13°F to +158°F)
(cosϕ= 0,7) • Storage temperature:
-40°C to +70°C (-40°F to +158°F).
> Digital inputs (DI)
• Nominal wetting voltage:
• Vn,nom: 24 VDC, 48-60 VDC,
110/125 VDC and 220 VDC, ±20%
• or Multi-voltage (24- 250V)
on the DIU210 board
• 1ms time stamping resolution