Annexure‐F Technical Specifications.

1KVA ONLINE UPS & Voltage regulator


Compliance to
Actual Technical Compliance If
MGVCL Technical
Sr. Minimum MGVCL Technical Specifications Specifications of (NO) mention
Specifications
No. [A] Offered by Bidder deviation
(YES/NO)
[B] * [D] *
[C] *
1 Approved Brand /Make APC/EMRSON/ HIRel Hitachi/Numeric
2 Model Any (Must be specified by Bidder)
3 Power Capicity 800 Watts minimum(1000VA) ONLINE UPS
SPWM, IGBT/MOSFET (for more than 72 DC volt
4 Technology
IGBT preferred)
5 Input
a Power Factor ≥ 0.99 at full load and nominal input Voltage
b Nominal Input 230VAC
c Input Voltage Range 170‐282VAC
d Input Phase Single Phase with Ground
6 Output
a Nominal Output Voltage 230VAC
b Output Voltage Regulation + / ‐ 1%
c Output Voltage THD: < 3% (linear load) and < 5% (non‐linear load)
d Output Crest Factor 3:01
e Output power factor 0.8 Lagging
f Output Overload 105% ‐ 110% for 10 minutes,111% ‐ 130% for 1 minute,131% ‐ 150% for 10 Seconds
7 Battery
a Battery connection Should be Internal only
b On Battery Output Voltage Pure Sine wave output at 230VAC
c Battery type 12 V Sealed Lead Acid Maintenance Free
d Battery Dc Voltage 36 VDC or higher
e Battery TOTAL VAH ‐ Minimum 432(12V,12Ah*3Nos) or higher
f Battery Make Exide/Quanta/Panasonic/Rocket
g Battery Backup Time 30 minutes at full load or higher
LCD Display & Indication,Input Voltage,Output Voltage,Input Frequency,Output
8 User display Frequency,Battery Charging / Discharging Level,Load Level,Input High / Normal / Low /
Fail,Output Overload ,Output Short Circuit,Output Fault
9 Audible Alarms Mains Failure alarm,Low Battery Alarm,Overload and Fault
Advanced electronic protection for device,safety backed with MCBs,Fast acting fuses,
10 Protections
High speed pulse blanking,Electronic overvoltage / undervoltage
11 ByPass Static bypass
12 Standard IEC 62040 ‐ 1 Safety ,IEC 62040 ‐ 2 (EMI / EMC)
13 Communication interface
a Standard RS 232 port for software interface
b Optional USB for Software interface SNMP/RS485/As400 Card
14 Certifications Should be ISO 9001 & 14001 certified
15 Transient Voltage Surge Suppressor
a Nominal Operating Voltage 120‐240 VAC, Single Phase, 2W+G
b Maximum Continuous Operating Voltage (MCOV) 320 VAC
15A per UL & CSA (IEC Connector rating)
v Maximum Load Rating
10A per VDE (IEC Connector rating)
d Operating Frequency Range 47 ‐ 63 Hz
e Connection Type 2 Port
f Phase Configuration 2 Wire + Gnd
g Indication of Suppression Status Monitoring – Green LED
h Input Connection (Line) IEC C14 Socket (Inlet)
i Output Connection (Load) IEC C13 Plug (Outlet)
Annexure‐F Technical Specifications.
1KVA ONLINE UPS & Voltage regulator
Compliance to
Actual Technical Compliance If
MGVCL Technical
Sr. Minimum MGVCL Technical Specifications Specifications of (NO) mention
Specifications
No. [A] Offered by Bidder deviation
(YES/NO)
[B] * [D] *
[C] *
j Enclosure High Impact Plastic
k Modes Of Protection L‐N, N‐G
l Peak Surge Current Capability (8 x 20 s)
m Line to Neutral (L‐N) 10kA
n Neutral to Ground (N‐G) 10kA
o Clamping Voltage (L‐N, N‐G) 845V @ 100 Amps
p Response Time < .5 ns Normal mode
03(Three) Year National Warranty including Parts & Labor. During warranty period, all
16 Warranty parts including UPS ,battery and circuit etc. to be replaced / repaired by vendor
irrespective of type of damage occurred.
Bidder/SI should have a back‐end / back‐to‐back support
contract/agreement/arrangement specifically for this tender no. for services including
supply of spare parts, expertise requirements etc. with the Original Equipment
17 OEM Undertaking Letter Manufacturers (OEMs) which includes the post sales support activities to meet the
Service Level Agreement (SLA) mentioned for the entire warranty period.
The OEM undertaking/Authorisation letter on OEM Letter Head in this regard should be
submitted along with the bid mentioning this tender no.

Note : * Columns‐B,C & D must be filled by Bidder. Partially filled/Unfilled bid will be outrightly rejected
Signature of Tenderer Company’s Round Seal