Ground Fault UL
110395 LR80793
Model GFM (Sensor )
1.5 to 65 Amp Trip Currents
OPERATING RANGE: INSULATION LEVEL:
Trip currents from 600 Volt, 10 kV BIL full wave.
1.5 -7.5 to 15 - 65 Amperes. Terminals are brass studs
No. 8-32.
FREQUENCY: 50/60 Hz. Only for use with GFM relays.
TOROIDAL SENSORS RECTANGULAR SENSORS
• Ground Fault Current Sensors type GFM, are available in three different case styles, a variety of sizes and trip current ranges - to match the GFM Relay.
The physical size of the sensor window should be carefully determined by the physical size and conf iguration of the power conductors. The Ground Fault
Sensor will respond only to ground faults which occur between the position of the senor and the load.
MODEL TRIP SENSOR DIMENSIONS MODEL TRIP SENSOR DIMENSIONS
NUMBER CURRENT NUMBER CURRENT
“A1 ” “A2” “A3” “B1” “B2” “B3” “A1 ” “A2” “A3” “ B1” “ B2” “ B3”
GFM 094 2.0 TO 8.5 0.94 N/A 2.67 N/A 2.75 2.38 GFM 041 X 071 6 TO 30 4.1 6.4 7.3 7.1 10.0 10.9
GFM 125 2.7 TO 14 1.25 N/A 2.67 N/A 2.75 2.38 GFM 080 X 117SC 15 TO 65 8.0 9.5 11.1 11.7 14.5 15.4
*
GFM 156 4.5 TO 18 1.56 N/A 3.53 N/A 3.77 2.15 GFM 080 X 141 9 TO 39 8.0 9.5 11.1 14.1 17.0 17.9
GFM 200 3.5 TO 14.5 2.00 3.19 4.00 N/A 4.00 1.75
* Model GFM 080 X 117SC is split core (take-apart style) for assembly to existing
GFM 250 3.5 TO 11 2.50 3.75 4.63 N/A 5.10 3.00 electrical installations without the need for dismantling the primary bus or
GFM 350 4 TO 12 3.75 4.75 5.96 4.75 6.31 3.00 cables.
GFM 375D * 3.75 4.75 5.96 4.75 6.31 3.00 CAUTION:
Proper safety precautions must be followed during installation by a trained
GFM 425 5 TO 18 4.25 5.44 6.73 5.43 6.73 1.28
electrician. It is recommended that the incoming power de-energized before
GFM 462 4 TO 12 4.62 5.75 7.00 5.75 7.12 4.00 installation. The sensor must have its secondary terminals short circuited or
the relay connected, before energizing the primary circuit .
GFM 813 4 TO 12 8.13 8.50 11.10 8.50 11.47 3.00
*Dual trip current ranges 3.5 to 11 and 10 to 36.
Mounting bracket kits are available for all
toroidal sensors except the Model GFM 094,
GFM 125, and GFM 156, which have molded
mounting feet . 3 HOLE SENSORS
GMF 094 GMF 156
GMF 125 MODEL BRACKET
NUMBER KIT
GFM 200 0221B01976
MODEL TRIP SENSOR DIMENSIONS
GFM 250 0221B00541
NUMBER CURRENT
GFM 375 0221B00259 “A1 ” “A2” “A3” “B1 ” “B2” “B3”
GFM 375D 0221B00259 GFM 3P205 X 050 4.5 TO 16 * 7.60 8.50 3.70 2.00 2.75
GFM 425 0221B00187 GFM 3P208 5 TO 20 2.08 8.24 9.00 3.94 2.00 2.75
GFM 462 0221B01525 GFM 3P212 7 TO 25 2.12 11.72 12.80 4.87 2.63 4.00
GFM 813 0221B00259
* The Model GFM 3P205 X 050 has a rectangle window 2.05 ” X 0.50”.
USA, Canada, Asia, Latin America Europe, Middle East , Africa
Tel: +1-800-547-8629 Tel: +34-94-485-88-00
Fax: +1-905-201-2455 Fax: +34-94-485-88-45
4 Electronic Products Please refer to our website www.GEMultilin.com for more detailed contact information CS00A40767 Rev.
Pick-Up
Pick-Up and
and Time
Time Delay
Delay Characteristics
Characteristics
ITI GFM sensors are assigned a current range to indicate a pick-up current level.
The GFM relay has a range select from “A” to “D”. “A” is the lowest current
magnitude pick-up and “D” is the highest . The pick up level is dependent on the
energy in a ground fault wave shape; therefore tripping initiation depends on the
wave shape and regularity of the fault current .
In general, the relay will pick up before 150% of the low end of the sensor
current range on the “A” setting with a sinusoidal signal, and will pick up before
150% of the high end of the sensor range on the “D” setting. The relay is
adjustable continuously from “A” to “D” so that identical sensors can be
coordinated.
The ITI GFM ground fault system has inverse time current trip characteristics.
As the fault current increases, the trip time delay gets shorter. The GFM-252,
GFM-353, GFM-453 relays do not have adjustable trip time delay, while the
GFM-262, GFM-363, GFM-463 relays have adjustable trip time delay.
Trip time on Models with f ixed time delay, may exceed a one second delay at
the pick up threshold. Trip time on Models with adjustable time delay, may
exceed a one second delay at the pick up threshold, however the inverse time
curve can be modif ied to vary trip time at multiples of over current with an
ordinal “1” to “4” is scale where “1” is faster and “4” is slower.
The pick up time delay on the f ixed time delay relays can be as fast as 0.02
seconds on the “A” setting, and 0.1 seconds on the “D” setting at high fault
currents.
For the adjustable time delay relays, a time delay of “1” in the “A” scale can
produce a time delay of under 0.15 seconds at a 600% sinusoidal fault . A time
delay setting of “4” will result in a time delay approximately 0.2 seconds slower
than the “1” setting. Time delay will be greater for smaller fault current .
Similarly, a time delay setting of “1” in the “D” scale can produce a time delay
of under 0.4 seconds at a 600% sinusoidal fault . A time delay setting of “4” will
result in a time delay approximately 0.2 seconds slower than the “1” setting.
Time delay will be greater for smaller fault current .
www.GEMultilin.com 5
FIXED DELAY TYPES
GFM Test Procedure
A Simulated fault current can be applied by the above test circuit.
An appropriate value of R1 should be selected to apply a minimum of 1.5 times maximum trip rating of the sensor.
1. Assure that the GFM relay is in “ NORMAL ” (reset) position.
2. Close switch S1, and check for reset for response. Relay handle will move to the tripped position.
3. Open S1, reset the relay and remove the test circuit from the system. System is now back to normal.
THE ABOVE TEST PROCEDURES SHOULD BE PERFORMED BY QUALIFIED PERSONNEL ONLY.
HOW TO ORDER RELAYS
GFM X X X
CASE STYLE WEIGHT
2- P.B Style-Door mtg. 6 oz.
3- Panel mount 14 oz. OUTPUT CONTACTS
4- Door mount 16 oz. 2- I0A form C contacts
(case style 2 only)
3- 10A form C contacts
TIME DELAY
plus 30A N.O. contacts
5- Instantaneous
(on case styles 3 & 4 only)
6- Adjustable time delay,
up to 36 36 cycles.
USA, Canada, Asia, Latin America Europe, Middle East , Africa
Tel: +1-800-547-8629 Tel: +34-94-485-88-00
Fax: +1-905-201-2455 Fax: +34-94-485-88-45
6 Electronic Products Please refer to our website www.GEMultilin.com for more detailed contact information CS00A40767 Rev.