Capacity Evaluation of Precast Driven Pile: Considerations

This document evaluates the capacity of a precast driven pile for a 2x660 MW power plant project. It analyzes soil core samples from 4 soil layers down to a depth of 21 meters. It determines the ultimate skin resistance from the soil layers is 962 kN and the ultimate tip resistance is 353 kN, for a total capacity of 1315 kN. It provides the final pile capacities in both kN and tonnes with factor of safety values for compression and tension loading.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
276 views6 pages

Capacity Evaluation of Precast Driven Pile: Considerations

This document evaluates the capacity of a precast driven pile for a 2x660 MW power plant project. It analyzes soil core samples from 4 soil layers down to a depth of 21 meters. It determines the ultimate skin resistance from the soil layers is 962 kN and the ultimate tip resistance is 353 kN, for a total capacity of 1315 kN. It provides the final pile capacities in both kN and tonnes with factor of safety values for compression and tension loading.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Capacity Evaluation of Precast Driven Pile

''CONFORMING AASHTO LRFD 2007''

PROJECT TITLE: 2X660 MW MAITREE STPP BOREHOLE ID: DESIGN SPT


CLIENT & OWNER: BHEL/BIFPCL ANALYSED BY: PRIODEEP

Considerations
GWT: 0 m
γw: 9.8 kN/m3
CUT-OFF LEVEL: 0.00 m

EVALUATION OF ULTIMATE SKIN RESISTANCE

Corrected SPT (Hammer Eff.)

Corrected SPT (Overburden

Ultimate Skin Res. @ Each


Unit Skin Resistance , fs
Unit Weight, γt
Depth of Mid

SOIL TYPE

layer, fsAs
Field SPT

Press.)
Layer

Layer
Thick

Depth (m)

# Start End (m) (m) Type (kN/m3) N N60 N160 (kPa) (kN)
1 0 6 6 3 S 17 3 4 6 0.0 0.0
2 6 14 8 10 C 17 2 3 3 15.8 177.2
3 14 19 5 16.5 C 17 16 21 20 70.8 495.9
4 19 21 2 20 S 17 27 36 31 67.1 188.0
Total Pile Length 21.00 (m) Ultimate Skin Resistance 861

Ultimate Tip Resistance for Driven Pile


Layer Depth N Type N60 N160 qp (kPa) Qpr (kN)

4 2 27 S 36 6 2880 353

Capacity of a Single Precast Pile-SUMMARY

Size: 0.35 m Compression Tension

Component Ult (kN) F.S. Safe (kN) F.S. Safe(kN)


Skin Friction 861 3.00 287 5.00 172
End Bearing 353 3.00 118 NA 0
Total (kN) 1214 Safe 405 Safe 172 DEVELOPMENT CONSTRUCTIONS LTD.
Total (Ton) 121.39 Safe 40.46 Safe 17.22

Capacity Estimation of Precast Pile// LRFD Page 1/1 #Version:17.8 8/11/2018 [Time]
Capacity Evaluation of Precast Driven Pile
''CONFORMING AASHTO LRFD 2007''

PROJECT TITLE: 2X660 MW MAITREE STPP BOREHOLE ID: DESIGN SPT


CLIENT & OWNER: BHEL/BIFPCL ANALYSED BY: PRIODEEP

Considerations
GWT: 0 m
γw: 9.8 kN/m3
CUT-OFF LEVEL: 1.00 m

EVALUATION OF ULTIMATE SKIN RESISTANCE

Corrected SPT (Hammer Eff.)

Corrected SPT (Overburden

Ultimate Skin Res. @ Each


Unit Skin Resistance , fs
Unit Weight, γt
Depth of Mid

SOIL TYPE

layer, fsAs
Field SPT

Press.)
Layer

Layer
Thick

Depth (m)

# Start End (m) (m) Type (kN/m3) N N60 N160 (kPa) (kN)
1 0 6 6 3 S 17 3 4 6 0.0 0.0
2 6 14 8 10 C 17 2 3 3 15.8 177.2
3 14 19 5 16.5 C 17 16 21 20 70.8 495.9
4 19 22 3 20.5 S 17 27 36 31 68.8 289.1
Total Pile Length 21.00 (m) Ultimate Skin Resistance 962

Ultimate Tip Resistance for Driven Pile


Layer Depth N Type N60 N160 qp (kPa) Qpr (kN)

4 3 27 S 36 6 2952 362

Capacity of a Single Precast Pile-SUMMARY

Size: 0.35 m Compression Tension

Component Ult (kN) F.S. Safe (kN) F.S. Safe(kN)


Skin Friction 962 3.00 321 5.00 192
End Bearing 362 3.00 121 NA 0
Total (kN) 1324 Safe 441 Safe 192 DEVELOPMENT CONSTRUCTIONS LTD.
Total (Ton) 132.38 Safe 44.13 Safe 19.24

Capacity Estimation of Precast Pile// LRFD Page 1/1 #Version:17.8 8/11/2018 [Time]
Capacity Evaluation of Precast Driven Pile
''CONFORMING AASHTO LRFD 2007''
PROJECT TITLE: 2X660 MW MAITREE STPP BOREHOLE ID: DESIGN SPT
CLIENT & OWNER: BHEL/BIFPCL ANALYSED BY: PRIODEEP

Considerations
GWT: 0 m

γw: 9.8 kN/m3


CUT-OFF LEVEL: 0 m

EVALUATION OF ULTIMATE SKIN RESISTANCE

Corrected SPT (Hammer Eff.)

Corrected SPT (Overburden

Ultimate Skin Res. @ Each


Unit Skin Resistance , fs
Unit Weight, γt
Depth of Mid

SOIL TYPE

layer, fsAs
Field SPT

Press.)
Layer

Layer
Thick

Depth (m)

# Start End (m) (m) Type (kN/m3) N N60 N160 (kPa) (kN)
1 0 6 6 3 S 17 3 4 6 0.0 0.0
2 6 14 8 10 C 17 2 3 3 15.8 227.8
3 14 19 5 16.5 C 17 16 21 20 70.8 637.5
4 19 22 3 20.5 S 17 27 36 31 68.8 371.7
5 22 26 4 24 S 17 30 40 32 80.6 580.2
Total Pile Length 26 (m) Ultimate Skin Resistance 1817

Ultimate Tip Resistance for Driven Pile


Layer Depth N Type N60 N160 qp (kPa) Qpr (kN)

5 4 30 S 40 6 3456 700

Capacity of a Single Precast Pile

Size: 0.45 m Compression Tension


Component Ult (kN) F.S. Safe (kN) F.S. Safe(kN)
Skin Friction 1817 3.00 606 5.00 363
End Bearing 700 3.00 233 NA 0 DEVELOPMENT CONSTRUCTIONS LTD.
Total (kN) 2517 Safe 839 Safe 363
Total (Ton) 251.70 Safe 83.90 Safe 36.34

Capacity Estimation of Precast Pile// LRFD Page 1/1 #Version:17.8 8/11/2018 [Time]
Capacity Evaluation of Precast Driven Pile
''CONFORMING AASHTO LRFD 2007''
PROJECT TITLE: 2X660 MW MAITREE STPP BOREHOLE ID: DESIGN SPT
CLIENT & OWNER: BHEL/BIFPCL ANALYSED BY: PRIODEEP

Considerations
GWT: 0 m
γw: 9.8 kN/m3
CUT-OFF LEVEL: 1.00 m

EVALUATION OF ULTIMATE SKIN RESISTANCE

Corrected SPT (Hammer Eff.)

Corrected SPT (Overburden

Ultimate Skin Res. @ Each


Unit Skin Resistance , fs
Unit Weight, γt
Depth of Mid

SOIL TYPE

layer, fsAs
Field SPT

Press.)
Layer

Layer
Thick

Depth (m)

# Start End (m) (m) Type (kN/m3) N N60 N160 (kPa) (kN)
1 0 6 6 3 S 17 3 4 6 0.0 0.0
2 6 14 8 10 C 17 2 3 3 15.8 227.8
3 14 19 5 16.5 C 17 16 21 20 70.8 637.5
4 19 22 3 20.5 S 17 27 36 31 68.8 371.7
5 22 27 5 24.5 S 17 30 40 32 82.3 740.3
Total Pile Length 26.00 (m) Ultimate Skin Resistance 1977

Ultimate Tip Resistance for Driven Pile


Layer Depth N Type N60 N160 qp (kPa) Qpr (kN)

5 5 30 S 40 6 3528 714

Capacity of a Single Precast Pile

Size: 0.45 m Compression Tension


Component Ult (kN) F.S. Safe (kN) F.S. Safe(kN)
Skin Friction 1977 3.00 659 5.00 395
End Bearing 714 3.00 238 NA 0
Total (kN) 2692 Safe 897 Safe 395 DEVELOPMENT CONSTRUCTIONS LTD.
Total (Ton) 269.18 Safe 89.73 Safe 39.55

Capacity Estimation of Precast Pile// LRFD Page 1/1 #Version:17.8 8/11/2018 [Time]
Evan and Duncan Analysis

Geotechnical Capacity of 450x450mm Precast Driven R.C.C. pile.

Input Values Output Values


Support condition= Free head
Pile shape (SQ, Cir)= SQ
A Charecteristic parameter dependent on the soil's behavior, λ= 1 Modulus of Elasticity, E= 25743 Mpa
Least dimension of Pile, B= 0.45 m Representative passive pressure of soil, σp= 126.00 kPa
Concrete Strength at 28 days, f'c= 30 Mpa Moment of Inertia, I= 0.00342
Moment of Inertia ratio, Ri= 1.7 Passive pressure factor, Cp= 3
Axial strain at which 50 percent of soil pressure mobilised, ε50= 0.02 Charecteristic Shear Load,Vc= 3443.36 kN
an Exponent, m= 0.683 Charecteristic Moment Load,Mc= 3987.91
an Exponent, n= -0.22 V/Vc 0.0116
Undrain shear strength at depth of 8 pile diameter, Su= 30 kPa From Fig yt/B= 0.0110
Effective friction angle, φ'= 30 deg Lateral Deflection at top of foundation, yt= 0.0050 m
Soil Type (Sand/ Clay) C 5.0 mm
Effective Unit weight of sand, γ= 17
18 kN/m3
Applied Shear at top of pile, V= 40 kN
Applied Moment at top of pile, M=

Hence Safe Lateral Capacity of pile shall be = 40 kN

Ref: Evan and Duncan's Analysis.


Foundation design - D.P Coduto.( 2nd edition, Chap. 16, page 600-611)
Evan and Duncan Analysis

Geotechnical Capacity of 350x350mm Precast Driven R.C.C. pile.

Input Values Output Values


Support condition= Free head
Pile shape (SQ, Cir)= SQ
A Charecteristic parameter dependent on the soil's behavior, λ= 1 Modulus of Elasticity, E= 25743 Mpa
Least dimension of Pile, B= 0.35 m Representative passive pressure of soil, σp= 126.00 kPa
Concrete Strength at 28 days, f'c= 30 Mpa Moment of Inertia, I= 0.00125
Moment of Inertia ratio, Ri= 1.7 Passive pressure factor, Cp= 3
Axial strain at which 50 percent of soil pressure mobilised, ε50= 0.02 Charecteristic Shear Load,Vc= 2083.02 kN
an Exponent, m= 0.683 Charecteristic Moment Load,Mc= 1876.34
an Exponent, n= -0.22 V/Vc 0.0130
Undrain shear strength at depth of 8 pile diameter, Su= 30 From Fig yt/B= 0.0143
Effective friction angle, φ'= 30 deg Lateral Deflection at top of foundation, yt= 0.0050 m
Soil Type (Sand/ Clay) C 5.0 mm
Effective Unit weight of sand, γ= 17
18 kN/m3
Applied Shear at top of pile, V= 27 kN
Applied Moment at top of pile, M=

Hence Safe Lateral Capacity of pile shall be = 27 kN

Ref: Evan and Duncan's Analysis.


Foundation design - D.P Coduto.( 2nd edition, Chap. 16, page 600-611)