This document describes a program that solves the swing equation of a one-machine power system subjected to a three-phase fault. The program uses the modified Euler method to model the system during a fault that is cleared at a specified time, calculating the rotor angle and angular velocity over time.

Uploaded by

Naeem Gul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as TXT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
240 views2 pages

SWINGMEU

This document describes a program that solves the swing equation of a one-machine power system subjected to a three-phase fault. The program uses the modified Euler method to model the system during a fault that is cleared at a specified time, calculating the rotor angle and angular velocity over time.

Uploaded by

Naeem Gul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as TXT, PDF, TXT or read online on Scribd
You are on page 1/ 2

% This program solves the swing equation of a one-machine system

% when subjected to a three-phase fault with subsequent clearance


% of the fault. Modified Euler method
%
% Copyright (c) 1998 H. Saadat
%
function swingmeu(Pm, E, V, X1, X2, X3, H, f, tc, tf, Dt)
%global Pm f H E V X1 X2 X3
clear t
if exist('Pm')~=1
Pm = input('Generator output power in p.u. Pm = '); else, end
if exist('E')~=1
E = input('Generator e.m.f. in p.u. E = '); else, end
if exist('V')~=1
V = input('Infinite bus-bar voltage in p.u. V = '); else, end
if exist('X1')~=1
X1 = input('Reactance before Fault in p.u. X1 = '); else, end
if exist('X2')~=1
X2 = input('Reactance during Fault X2 = '); else, end
if exist('X3')~=1
X3 = input('Reactance after Fault X3 = '); else, end
if exist('H')~=1
H = input('Generator Inertia constant in sec. H = '); else, end
if exist('f')~=1
f = input('System frequency in Hz f = '); else, end
if exist('Dt')~=1
Dt = input('Time interval Dt = '); else, end
if exist('tc')~=1
tc = input('Clearing time of fault in sec tc = '); else, end
if exist('tf')~=1
tf = input('Final time for swing equation in sec tf = '); else, end
Pe1max = E*V/X1; Pe2max=E*V/X2; Pe3max=E*V/X3;
clear t x1 x2 delta
d0 =asin(Pm/Pe1max);
t(1) = 0;
x1(1)= d0;
x2(1)=0;
np=tf /Dt;
Pemax=Pe2max;
ck=pi*f/H;
for k = 1:np
if t(k) >= tc
Pemax=Pe3max;
else, end
t(k+1)=t(k)+Dt;

Dx1b=x2(k);
Dx2b=ck*(Pm-Pemax*sin(x1(k)));
x1(k+1)=x1(k)+Dx1b*Dt;
x2(k+1)=x2(k)+Dx2b*Dt;
Dx1e=x2(k+1);
Dx2e=ck*(Pm-Pemax*sin(x1(k+1)));
Dx1=(Dx1b+Dx1e)/2;
Dx2=(Dx2b+Dx2e)/2;
x1(k+1)=x1(k)+Dx1*Dt;
x2(k+1)=x2(k)+Dx2*Dt;
end
delta=180*x1/pi;
clc
fprintf('\nFault is cleared at %4.3f Sec. \n', tc)
head=[' '
' time delta Dw '
' s degrees rad/s'
' '];
disp(head)
disp([t', delta' x2'])
h=figure; figure(h)
plot(t, delta), grid
title(['One-machine system swing curve. Fault cleared at ', num2str(tc),'s'])
xlabel('t, sec'), ylabel('Delta, degree')
cctime(Pm, E, V, X1, X2, X3, H, f) % Obtains the critical clearing time