Spec - 1250 KVA (Oil Type)
Spec - 1250 KVA (Oil Type)
Spec - 1250 KVA (Oil Type)
6. ELECTRIC PERFORMANCE :
Primary Voltage Secondary Voltage
6-1 Insulation Class : 24 kV 1.1 kV
6-2 Basic Impulse Level : 125 kV - kV
6-3 Applied Voltage Test During 1 Minute : 50 kV 3 kV
6-4 Induced Voltage Test : Apply 2 times of the rate voltage at 350 cycles per second for 18 second
o
6-5 Temperature Rise : The coil temperature rise measured by resistance method will not exceed 65 C
o
and the oil temperature rise will not exceed 60 C
6-6 Losses at Rated Voltage 20 / 0.4 kV
No Load Losses : 2,000 Watt Note : - FR-3 Fluid
Load Losses ( at 75 °C ) : 15,000 Watt
Total Losses : 17,000 Watt
6-7 Efficiency at % Rated Capacity : 100 75 50 25 %
at P.F. = 1,0 : 98.66 98.90 99.09 99.07 %
6-8 Exciting Current / Off load Current at Nominal Voltage : 2.00 % Date of Approval :
6-9 Percent Impedance : 5.50 % PROPOSER :
6 - 10 Voltage Regulation at P.F. = 1,0 : 1.34 %
Voltage Regulation at P.F. = 0.8 : 4.24 % hp
P180949 - Af