Enerlin'X IFE Ethernet Interface For One Circuit Breaker Used Guide
Enerlin'X IFE Ethernet Interface For One Circuit Breaker Used Guide
Enerlin'X IFE Ethernet Interface For One Circuit Breaker Used Guide
1040IB1401-05 07/2017
Enerlin’X IFE
Ethernet Interface for One Circuit Breaker
User Guide
07/2017
1040IB1401-05
www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not intended as
a substitute for and is not to be used for determining suitability or reliability of these products for specific
user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk
analysis, evaluation and testing of the products with respect to the relevant specific application or use
thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information contained herein. If you have any suggestions for improvements or amendments
or have found errors in this publication, please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of this
document on any medium whatsoever without permission of Schneider Electric, given in writing. You also
agree not to establish any hypertext links to this document or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the document or its content, except for a
non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must
be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in
injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2017 Schneider Electric. All Rights Reserved.
2 1040IB1401-05 07/2017
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1 IFE Interface Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Intelligent Modular Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Hardware Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Ecoreach Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Schematics with Masterpact NT/NW and PowerPact P- and R-Frame Circuit Breakers . . . . 20
Schematics with PowerPact H-, J-, and L-Frame Circuit Breakers . . . . . . . . . . . . . . . . . . . . 24
Technical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Firmware Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Schneider Electric Green Premium™ Ecolabel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Chapter 2 IFE Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.1 IFE Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Access to IFE Webpages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
User Interface Layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Webpage Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
2.2 IFE Web Server - Configuration & Settings Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Time Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Ethernet Configuration (Dual Port) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
IP Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Modbus TCP/IP Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Modbus Serial Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Email Server Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Email Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
EcoStruxure Facility Expert . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Device List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Device Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Device Log Export . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
SNMP Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Advanced Services Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Webpage Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
2.3 IFE Web Server - Monitoring Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Real Time Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Device Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
2.4 IFE Web Server - Control Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Device Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Set Device Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
1040IB1401-05 07/2017 3
2.5 IFE Web Server - Diagnostics Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Device Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
IMU Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Read Device Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Communication Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
IO Readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
2.6 IFE Web Server - Maintenance Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Appendix A Appendix A - List of IFE Supported Devices . . . . . . . . . . . . . . . . . . . . . . . . 93
List of IFE Supported Device Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
4 1040IB1401-05 07/2017
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, service, or maintain it. The following special messages may appear throughout
this documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and its installation, and has received safety training to recognize and avoid the
hazards involved.
1040IB1401-05 07/2017 5
FCC Notice
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
to part 15 of the FCC Rules. These limits are designated to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment
in a residential area is likely to cause harmful interference in which case the user will be required to correct
the interference at this own expense.
6 1040IB1401-05 07/2017
About the Book
At a Glance
Document Scope
The aim of this document is to provide the users, installers, and the maintenance personnel with the
technical information and procedure needed to access and maintain the IFE Ethernet interface for one
circuit breaker (IFE interface) web server.
Validity Note
The technical characteristics of the devices described in this document also appear online. To access this
information online:
Step Action
1 Go to the Schneider Electric home page www.schneider-electric.com.
2 In the Search box type the reference of a product or the name of a product range.
Do not include blank spaces in the reference or product range.
To get information on grouping similar modules, use asterisks (*).
3 If you entered a reference, go to the Product Datasheets search results and click on the reference that interests you.
If you entered the name of a product range, go to the Product Ranges search results and click on the product range that interests you.
4 If more than one reference appears in the Products search results, click on the reference that interests you.
5 Depending on the size of your screen, you may need to scroll down to see the data sheet.
6 To save or print a data sheet as a .pdf file, click Download XXX product datasheet.
The characteristics that are presented in this manual should be the same as those characteristics that
appear online. In line with our policy of constant improvement, we may revise content over time to improve
clarity and accuracy. If you see a difference between the manual and online information, use the online
information as your reference.
Related Documents
Masterpact NT/NW, PowerPact P- and R-frame Modbus Communication Guide 0613IB1313 (EN)
0613IB1314 (ES)
0613IB1315 (FR)
0613IB1316 (ZH)
PowerPact H-, J-, and L-Frame Modbus Communication Guide 0611IB1302 (EN)
0611IB1303 (ES)
0611IB1304 (FR)
0611IB1305 (ZH)
ULP System - User Guide 0602IB1503 (EN)
0602IB1504 (ES)
0602IB1505 (FR)
0602IB1506 (ZH)
You can download these technical publications and other technical information from our website at
http://www.schneider-electric.com/en/download
Trademark Notice
All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies
1040IB1401-05 07/2017 7
8 1040IB1401-05 07/2017
Enerlin’X IFE
IFE Interface Presentation
1040IB1401-05 07/2017
Chapter 1
IFE Interface Presentation
1040IB1401-05 07/2017 9
IFE Interface Presentation
Introduction
Overview
The IFE interface enables an intelligent modular unit (IMU), for example a Masterpact™ NT/NW or
PowerPact™ H-, J-, and L-Frame circuit breaker to be connected to an Ethernet network. Each circuit
breaker has its own IFE interface and a corresponding IP address.
NOTE: The built-in switch of IFE interface does not support the ring topology as it does not have the feature
of the loop back protection.
10 1040IB1401-05 07/2017
IFE Interface Presentation
Definition
A modular unit is a mechanical and electrical assembly containing one or more products to perform a
function in a switchboard (incoming protection, motor command, and control).
The circuit breaker with its internal communicating components (Micrologic control unit) and external ULP
modules (IO module) connected to one communication interface is called an intelligent modular unit (IMU).
ULP Module Part Number Masterpact NT/NW or PowerPact H-, J-, and L-frame
PowerPact P- and R-frame with with BSCM Module and/or
BCM ULP Module and Micrologic Trip Unit
Micrologic Control Unit
IFE Ethernet interface for one circuit breaker LV434001 ✓ ✓
IFE Ethernet switchboard server LV434002 ✓ ✓
IFM Modbus-SL interface for one circuit breaker TRV00210 ✓ ✓
IFM Modbus-SL interface for one circuit breaker LV434000 ✓ ✓
FDM121 ULP display for one circuit breaker TRV00121 ✓ ✓
IO input/output application module for one circuit LV434063 ✓ ✓
breaker
UTA maintenance module STRV00911 ✓ ✓
1040IB1401-05 07/2017 11
IFE Interface Presentation
Communication Architecture
12 1040IB1401-05 07/2017
IFE Interface Presentation
1040IB1401-05 07/2017 13
IFE Interface Presentation
Remote Controller
A remote controller is a device that is able to communicate with an IMU using a communication interface,
such as the IFE Ethernet interface. For example, FDM128 Ethernet display for eight devices, supervisor,
PLC, BMS, SCADA system, and so on, are remote controllers.
14 1040IB1401-05 07/2017
IFE Interface Presentation
Hardware Description
Description
For information on installation, consult the instruction sheet available on the Schneider Electric website:
QGH13473.
Mounting
The IFE interface mounts on a DIN rail. The stacking accessory enables the connection of several
IFM interfaces to an IFE server without additional wiring.
NOTE: The stacking feature is available only for the IFE server with the part number LV434002.
1040IB1401-05 07/2017 15
IFE Interface Presentation
16 1040IB1401-05 07/2017
IFE Interface Presentation
Modbus Address
The IFE interface accepts the Modbus address of the IMU to which it is connected.
The Modbus address is 255 and cannot be changed.
Locking Pad
The locking pad on the front panel of the IFE interface enables or disables the ability to send the remote
control commands over the Ethernet network to the IFE interface, and to the other modules of the IMU.
If the arrow points to the open padlock (factory setting), remote control commands are enabled.
If the arrow points to the closed padlock, remote control commands are disabled.
The only remote control command that is enabled even if the arrow points to the closed padlock, is the
set absolute time command.
Test Button
The test button has two functions, according to the duration of the button pressed.
Reset Button
When the reset button is pressed for 1–5 s, it forces the IP acquisition mode to the factory default setting
(DHCP).
1040IB1401-05 07/2017 17
IFE Interface Presentation
18 1040IB1401-05 07/2017
IFE Interface Presentation
Ecoreach Software
Overview
Ecoreach software helps you to manage a project as part of testing, commissioning, and maintenance
phases of the project life cycle. The innovative features in it provide simple ways to configure, test, and
commission the smart electrical devices.
Ecoreach software automatically discovers the smart devices and allows you to add the devices for an
easy configuration. You can generate comprehensive reports as part of Factory Acceptance Test and Site
Acceptance Test to replace your heavy manual work. Additionally, when the panels are under operation,
any change of settings made can be easily identified and hence provides a system consistency during the
operation and maintenance phase.
Ecoreach software enables the configuration of the following devices, modules, and accessories:
Key Features
Ecoreach software performs the following actions for the supported devices and modules:
Create projects by device discovery
Save Ecoreach projects in Ecoreach cloud repository
Upload settings to the device and download settings from the device
Compare the settings between the project and the device
Perform control actions in a secured way
Generate and print the device settings report
Perform a communication wiring test on the entire project and generate and print the test reports
View the communication architecture between the devices in a graphical representation
View the measurements, logs, and maintenance information
Export Waveform capture
View the status of device and IO module
Check the system firmware compatibility status
Upgrade to the latest device firmware
1040IB1401-05 07/2017 19
IFE Interface Presentation
Schematics with Masterpact NT/NW and PowerPact P- and R-Frame Circuit Breakers
Description
Depending on the type of circuit breaker used, connect the IFE interface to the circuit breaker using one of
the following configurations:
Connection of the IFE interface to a fixed manually-operated PowerPact P- or R-frame circuit breaker
with a BCM ULP module.
Connection of the IFE interface to a fixed electrically-operated Masterpact NT/NW or PowerPact P-
frame circuit breaker with a BCM ULP module.
Connection of the IFE interface to a drawout Masterpact NT/NW or PowerPact P-frame circuit breaker
with a BCM ULP module and its respective IO module.
ULP Connection
NOTICE
HAZARD OF EQUIPMENT DAMAGE
Never connect an Ethernet device to a RJ45 ULP port.
The RJ45 ULP ports of IFE interface are for ULP modules only.
Any other use can damage the IFE interface or the device connected to the IFE interface.
To check if a ULP module is compatible with the RJ45 ULP ports of IFE interface, refer to the ULP
System User Guide.
Failure to follow these instructions can result in equipment damage.
20 1040IB1401-05 07/2017
IFE Interface Presentation
Connection of the IFE Interface to a Fixed Manually-Operated PowerPact P- or R-Frame Circuit Breaker
1040IB1401-05 07/2017 21
IFE Interface Presentation
Connection of the IFE Interface to a Fixed Electrically-Operated Masterpact NT/NW or PowerPact P-Frame Circuit Breaker
22 1040IB1401-05 07/2017
IFE Interface Presentation
Connection of the IFE Interface to a Drawout Masterpact NT/NW or PowerPact P-Frame Circuit Breaker
1040IB1401-05 07/2017 23
IFE Interface Presentation
General Description
Depending on the configuration of the PowerPact H-, J-, and L-frame circuit breaker, connect the IFE
interface to the circuit breaker using one of the following configurations:
Connection of the IFE interface to the Micrologic trip unit
Connection of the IFE interface to the BSCM module
Connection of the IFE interface to the BSCM module and to the Micrologic trip unit
ULP Connection
NOTICE
HAZARD OF EQUIPMENT DAMAGE
Never connect an Ethernet device to a RJ45 ULP port.
The RJ45 ULP ports of IFE interface are for ULP modules only.
Any other use can damage the IFE interface or the device connected to the IFE interface.
To check if an ULP module is compatible with the RJ45 ULP ports of IFE interface, refer to the ULP
System User Guide.
Failure to follow these instructions can result in equipment damage.
All connection configurations require the NSX cord. The insulated NSX cord is mandatory for system
voltages greater than 480 Vac.
See the PowerPact H-, J-, and L-Frame Circuit Breakers User Manual for more information regarding the
description and mounting of the PowerPact H-, J-, and L-frame circuit breaker-compliant products
(Micrologic trip unit, BSCM module, NSX cord).
When the second RJ45 ULP port is not used, it must be closed with an ULP line termination.
24 1040IB1401-05 07/2017
IFE Interface Presentation
1040IB1401-05 07/2017 25
IFE Interface Presentation
26 1040IB1401-05 07/2017
IFE Interface Presentation
Connection of the IFE Interface to the BSCM Module and to the Micrologic Trip Unit
1040IB1401-05 07/2017 27
IFE Interface Presentation
Connection of the IFE Interface to a Circuit Breaker for System Voltage Greater Than 480 Vac
28 1040IB1401-05 07/2017
IFE Interface Presentation
Technical Characteristics
Environmental Characteristics
Characteristics Value
Conforming to standards IEC 60950
IEC 60947-6-2
UL508
UL60950
IACS E10
Mechanical Characteristics
Characteristics Value
Shock resistance Conforming to IEC 60068-2-27
15 g/11 ms, 1/2 sinusoidal
Resistance to sinusoidal vibrations Conforming to IEC/EN 60068-2-6
Electrical Characteristics
Characteristics Value
Power supply 24 Vdc, -20%/+10% (19.2–26.4 Vdc)
Consumption Typical 24 Vdc, 120 mA at 20 °C (68 °F)
Maximum with server 19.2 Vdc, 140 mA at 60 °C (140 °F)
Physical Characteristics
Characteristics Value
Dimensions 72 x 105 x 71 mm (2.83 x 4.13 x 2.79 in)
Mounting DIN rail
Weight 187 g (0.41 lb)
Degree of protection of the installed module On the front panel (wall-mounted enclosure): IP4x
Connectors: IP2x
Other parts: IP3x
1040IB1401-05 07/2017 29
IFE Interface Presentation
Characteristics Value
Power supply type Regulated switch type
Rated power 72 W
Input voltage 100–120 Vac for single phase
200–500 Vac phase-to-phase
PFC filter With IEC 61000-3-2
Output voltage 24 Vdc
Power supply output current 3A
30 1040IB1401-05 07/2017
IFE Interface Presentation
Firmware Upgrade
Description
The IFE interface consists of two component types that can be upgraded using the Ecoreach software
(see page 19):
Firmware
Webpage, device supporting file, and data file
It is recommended to use the Ecoreach software for all firmware upgrades. Ecoreach provides a one click
update option that ensures consistency between the firmware and device webpages.
From Smart Panels 1.3, the two component types are upgraded in a single operation through Ecoreach
software.
NOTE:
The Ecoreach software must be used for maintaining the firmware of the device.
Before starting the firmware upgrade, take a backup of the data log files (see page 75).
The Ecoreach software automatically downloads the latest firmware version from the Schneider Electric
server.
If you add or update a device, the firmware has the potential to create inconsistencies. Hence, it is
important to review your firmware upgrade plan with respect to other devices in the system. If the firmware
creates inconsistencies, the system may have some limitations or unexpected behavior.
Firmware Compatibility
The primary reason for updating the system is to obtain the latest system features. The following system
compatibility table shows the firmware versions of the products that are compatible with each other:
Product Part Number Smart Panels 1.0 Smart Panels 1.1 Smart Panels 1.2 Smart Panels 1.3 Smart Panels 1.4
Firmware Firmware Firmware Firmware Firmware Versions
Versions Versions Versions Versions
IO module LV434063 V2.1.4 V2.1.4 V2.1.4 V3.2.2 V3.2.9
IFE interface LV434001 – – – V3.5.3 V3.6.11
IFE server LV434002 – – – V3.5.3 V3.6.11
IFE interface LV434010 Firmware V1.8.4 Firmware V1.9.8 Firmware V3.5.3 V3.6.11
Webpage V1.8.9 Webpage V1.9.9 V1.10.18
Webpage
V1.10.18
IFE server LV434011 Firmware V1.8.4 Firmware V1.9.8 Firmware V3.5.3 V3.6.11
Webpage V1.8.9 Webpage V1.9.9 V1.10.18
Webpage
V1.10.18
IFM interface LV434000 – – – – V3.0.16
IFM interface TRV00210 V2.2.7 V2.2.7 V2.2.9 V2.2.11 V2.2.11
FDM121 display TRV00211 V2.3.5 V2.3.5 V2.3.5 V2.3.5 V2.3.5
FDM128 display LV434128 V5.5.6 V6.1.1 V6.2.2 V6.3.4 V6.3.10
ULP accessories LV4••••• – – – – –
Com’X 200 EBX200 V1.1.20 V1.3.5 V2.2.1 V2.2.1 3.6.3
Com’X 510 EBX510 – – V3.0.6 V3.5.4 3.6.3
BCM ULP module 33106 V4.0.9 V4.0.9 V4.1.4 V4.1.5 V4.1.7
Product data Product data Product data Product data Product data code
code greater code greater than code greater than code greater than greater than or
than or equal to or equal to 14251 or equal to 14251 or equal to 14251 equal to 14251
14251
1040IB1401-05 07/2017 31
IFE Interface Presentation
Product Part Number Smart Panels 1.0 Smart Panels 1.1 Smart Panels 1.2 Smart Panels 1.3 Smart Panels 1.4
Firmware Firmware Firmware Firmware Firmware Versions
Versions Versions Versions Versions
BSCM module Product data V2.2.7 V2.2.7 V2.2.7 V2.2.7 V2.2.7
code greater than
or equal to
3N141810186
Micrologic trip unit for – V8282 V8282 V8282 V8282 V8282
Masterpact NT/NW
and Compact NS
circuit breakers
To manage the device firmware, refer to the device documentation and Ecoreach that assures the feature
set is complete and compatible.
NOTE: The Ecoreach compatibility status is used for PowerPact H-, J-, and L-frame circuit breakers and
Masterpact devices. As a result, the devices that are not part of these product lines (for example, FDM128
display, Com'X, and power meters) need to be manually verified with System Compatibility table.
Updating the Firmware, Webpages, and Device Supporting Files using Ecoreach Software
For more information, refer to the Ecoreach Online Help.
The Ecoreach software is available at www.schneider-electric.com.
32 1040IB1401-05 07/2017
IFE Interface Presentation
Description
Green Premium by Schneider Electric is a label that allows you to develop and promote an environmental
policy while preserving your business efficiency. This ecolabel is compliant with up-to-date environmental
regulations.
Step Action
1 From www.schneider-electric.com, select Support → Additional Links → Green Premium Eco Label.
2 Click Find Green Premium Products to open the search tool webpage.
3 Fill in the fields:
Enter the commercial reference or product range of the product to search for.
Optional: Enter the manufacturing date code of the product with format YYWW. By default, this field is filled with the date of
the search.
4 To search for several products simultaneously, click the Add product button, and then fill in the fields.
5 Click Check product(s) to generate a report of the environmental criteria available for the products with the entered commercial
references.
Environmental Criteria
The Green Premium ecolabel provides documentation on the following criteria about the environmental
impact of the products:
RoHs: European Union Restriction of Hazardous Substances (RoHS) directive.
REACh: European Union Registration, Evaluation, Authorization, and Restriction of Chemicals
regulation.
PEP: Product Environmental Profile.
EoLI: End of Life Instructions.
RoHs
Schneider Electric products are subject to RoHS requirements at a worldwide level, even for the many
products that are not required to comply with the terms of the regulation. Compliance certificates are
available for products that fulfill the criteria of this European initiative, which aims to eliminate hazardous
substances.
REACh
Schneider Electric applies the strict REACh regulation on its products at a worldwide level, and discloses
extensive information concerning the presence of SVHC (Substances of Very High Concern) in all of these
products.
1040IB1401-05 07/2017 33
IFE Interface Presentation
PEP
Schneider Electric publishes complete set of environmental data, including carbon footprint and energy
consumption data for each of the life cycle phases on all of its products, in compliance with the
ISO 14025 PEP ecopassport program. PEP is especially useful for monitoring, controlling, saving energy,
and/or reducing carbon emissions.
EoLI
These instructions provide:
Recyclability rates for Schneider Electric products.
Guidance to mitigate personnel hazards during the dismantling of products and before recycling
operations.
Part identification for recycling or for selective treatment, to mitigate environmental hazards/incompati-
bility with standard recycling processes.
34 1040IB1401-05 07/2017
Enerlin’X IFE
IFE Web Server
1040IB1401-05 07/2017
Chapter 2
IFE Web Server
1040IB1401-05 07/2017 35
IFE Web Server
Section 2.1
IFE Interface
IFE Interface
36 1040IB1401-05 07/2017
IFE Web Server
Browser Version with Version with Windows Vista Version with Windows 7
Windows XP
Internet Explorer IE 9.0 IE 9.0 IE 10.0, IE11.0
Firefox 15.0 20.0 20.0, 45.0
Chrome (recommended) 24.0 and later 24.0 and later 24.0 and later
NOTE: On upgrade of IFE interface before accessing the webpages for the first time, delete the browser
cache.
Step Action
1 Disconnect the PC from the local area network (LAN) and switch off Wi-Fi.
2 Connect an Ethernet cable from the computer to the IFE interface or to the Ethernet switch inside the panel.
3 Open Windows Explorer.
4 Click Network and the IFE-XXYYZZ appears in the list of devices.
NOTE: If the IFE name is not displayed in the list of devices in Windows Explorer, check if the PC and the IFE interface are
not connected through the router.
5 Double-click the selected IFE-XXYYZZ, the login page automatically opens in the browser.
6 Enter Administrator as the user name and Gateway as the password, the home page automatically opens in the
browser.
NOTE: The user name and password are case-sensitive.
7 To locate the IFE-XXYYZZ, select the Configuration & Settings menu, go to General submenu, click
Device Physical Location, and click Blink ON. The ULP LED of the selected IFE-XXYYZZ blinks for 15 seconds (test mode).
8 To name the IFE-XXYYZZ, select the Configuration & Settings menu, go to Device Configuration submenu, click Device List
and then click Name. Click IFE-XXYYZZ to set the IFE name.
9 Write the IFE name on a blank device name label and stick it on the existing one.
NOTE:
XXYYZZ is the last 3 bytes of the MAC address in hexadecimal format.
Check the firewall settings if DPWS is not enabled.
Step Action
1 Disconnect the computer from the local area network (LAN) and switch off Wi-Fi.
2 Connect an Ethernet cable from the computer to the IFE interface.
3 Start the web browser (see page 37).
NOTE: The computer automatically uses the default IP address 169.254.#.# (#=0–255) and the default subnet mask
255.255.0.0.
1040IB1401-05 07/2017 37
IFE Web Server
Step Action
4 In the address text box, enter 169.254.YY.ZZ, where YY and ZZ are the last 2 bytes of the IFE interface MAC address (to
be found on the IFE interface side label), then press Enter: the home page opens in the browser.
Example: For an IFE with MAC address 00-B0-D0-86-BB-F7 or 0-176-208-134-187-247 in decimal, enter 169.254.187.247
in the address text box.
5 Press Enter, the login page automatically opens in the browser.
6 Enter Administrator as the user name and Gateway as the password. The homepage automatically opens in the
browser.
NOTE: The user name and password are case-sensitive.
7 To locate the -XXYYZZ, select the Configuration & Settings menu, go to General submenu, click Device Physical Location,
go to Device Physical Location, and click Blink ON. The ULP LED of the selected -XXYYZZ blinks for 15 seconds.
8 To name the -XXYYZZ, select the Configuration & Settings menu, go to Device Configuration submenu, click Device List and
then click Name to set the IFE name.
9 Write the IFE name on a blank device name label and stick it on the existing one.
NOTE: XXYYZZ is the last 3 bytes of the MAC address in hexadecimal format.
Access to Webpages
Follow the Network Discovery, Name Browsing, and IP Address Browsing process to access the
webpages.
The webpage access depends on the IT infrastructure.
Network Discovery
Follow the below procedure to access the IFE webpages once the IFE name has been configured.
Step Action
1 Connect the IFE interface or the Ethernet switch inside the panel to the local area network (LAN).
2 Connect the computer to the local area network (LAN).
3 Open Windows Explorer.
4 Click Network, the IFE name is displayed in the list of devices.
NOTE: If the IFE name is not displayed in the list of devices in Windows Explorer, check if the PC and the IFE interface are
not connected through the router.
5 Double-click the IFE name which is written on the device label located on the front face of the selected IFE interface, the login
page automatically opens in the browser.
Name Browsing
DNS server is mandatory.
Step Action
1 Connect the IFE interface or the Ethernet switch inside the panel to the local area network (LAN).
2 Connect the computer to the local area network (LAN).
3 Start the web browser (see page 37).
4 In the address text box, enter the IFE name which is written on the device label located on the front face of the selected IFE
interface.
5 Press Enter, the login page automatically opens in the browser.
NOTE: If the IFE interface does not appear in the list of devices in Windows Explorer, check if the PC and the IFE interface
are not connected through the router.
NOTE: The IFE IP address is mapped to the device label in the DNS server.
38 1040IB1401-05 07/2017
IFE Web Server
IP Address Browsing
IP static configuration has to be set.
Step Action
1 Connect the IFE interface or the Ethernet switch inside the panel to the local area network (LAN).
2 Connect the computer to the local area network (LAN).
3 Start the web browser (see page 37).
4 In the address text box, enter IP address given by the IT administrator.
5 Press Enter, the login page automatically opens in the browser.
NOTE: If the login page in the web browser does not open or does not display correctly, check if Internet
Explorer\Tools\Compatibility View Settings\Display Intranet sites in Compatibility View in Internet Explorer is checked.
WARNING
UNAUTHORIZED ACCESS TO CONTROL FUNCTIONS
Immediately change the default password to a new and secure password.
DO NOT distribute the password to unauthorized or otherwise unqualified personnel.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: The password should not contain any personal or obvious information.
1040IB1401-05 07/2017 39
IFE Web Server
Overview
This graphic shows the IFE user interface layout.
A Banner
B Menu tabs
C Subtabs
D Action button
E Display zone
Banner
The banner displays the following information at the top of all the pages.
Main Tabs
The main tabs are:
Monitoring
Control
Diagnostics
Maintenance
Configuration & Settings
Subtabs
The subtabs display the submenus under the selected main tab.
Action Buttons
The action buttons correspond to the selected tab and it varies.
The following table describes the interface buttons:
Button Action
Apply Applies the changes.
Cancel Cancels the modifications to return to the last saved settings.
40 1040IB1401-05 07/2017
IFE Web Server
Display Zone
The display zone shows the selected subtab in detail with all the related fields.
1040IB1401-05 07/2017 41
IFE Web Server
Webpage Description
Monitoring Webpage
Control Webpage
Diagnostics Webpage
Maintenance Webpage
42 1040IB1401-05 07/2017
IFE Web Server
1040IB1401-05 07/2017 43
IFE Web Server
Section 2.2
IFE Web Server - Configuration & Settings Pages
44 1040IB1401-05 07/2017
IFE Web Server
General
1040IB1401-05 07/2017 45
IFE Web Server
Description
The Date and Time page allows you to set the date and time of the slave devices manually. This page
allows you to automatically synchronize the date and time of the slave devices to the IFE time and
periodically check the synchronization at specified interval of time. This page lists the slave devices that
require an external interface to set their date and time.
Parameter Description
Manual Allows you to select the manual date and time setting of slave devices. This
option is disabled when Automatic (SNTP) is selected.
Date Allows you to set the present date manually in the format YYYY-MM-DD.
Time Allows you to set the present time manually in the format hh:mm:ss.
Automatic (SNTP) Allows you to select an external time server (SNTP server) for IFE interface or
IFE server and synchronize the time of its slave devices automatically.
Poll Interval Allows you to enter the poll interval in hours that ranges from 1 through 63.
Obtain Servers Automatically via DHCP/BOOTP Allows you to enable the check box that obtains the server address from DHCP
or BOOTP.
Primary SNTP/NTP server Allows you to enter the primary SNTP server address.
Secondary SNTP/NTP server Allows you to enter the secondary SNTP server address.
Apply Allows you to automatically synchronize the selected device with the IFE time.
Cancel Allows you to clear the synchronization of the selected device.
46 1040IB1401-05 07/2017
IFE Web Server
1040IB1401-05 07/2017 47
IFE Web Server
Time Zone
Step Action
1 From the IFE menu bar, click Configuration & Settings.
2 From the Configuration & Settings menu, in the General submenu, click Time Zone.
3 In Time Zone Configuration webpage, select the time zone of your region from the Time Zone list.
4 Select the Enable check box if you have to set the daylight saving time.
5 Select the beginning and end time of daylight saving from the Daylight Saving Time begins and the Daylight Saving Time ends
list.
6 Click Apply to save the settings.
NOTE: The settings of Time Zone is applicable only when Date and Time is in Automatic mode.
48 1040IB1401-05 07/2017
IFE Web Server
Ethernet
NOTE: Whenever the frame format settings are changed, Auto (Factory setting)
restart the device to implement the changes.
Committed Information Rate Defines the read-only value of the storm protection level. –
1040IB1401-05 07/2017 49
IFE Web Server
IP Configuration
IPv4 Configuration
IPv6 Configuration
DNS
50 1040IB1401-05 07/2017
IFE Web Server
1040IB1401-05 07/2017 51
IFE Web Server
Description
The Modbus TCP/IP Filtering page allows you to define the level of access for Modbus TCP/IP clients
connected to IFE interface.
Block Connections
You can select the maximum number of IP connections allowed, 8 or 16. Each connection can have 12
concurrent transactions simultaneously.
NOTE: When the maximum number of IP connections is changed, a message pops-up on the screen Max
Connection is changed. Restart the Device to Take Effect and prompts to restart the device.
IP Filtering
IP Address Filters the required IP address entered by you. 10 addresses (Maximum allowed IP addresses)
Access level Defines the access level for the corresponding IP Read: The following Modbus TCP/IP function
address. codes are allowed:
1 (0x01)
2 (0x02)
3 (0x03)
4 (0x04)
7 (0x07)
8 (0x08)
11 (0x0B)
12 (0x0C)
17 (0x11)
20 (0x14)
24 (0x18)
43 (0x2B), with subfunction codes 14 (0x0E),
15 (0x0F), and 16 (0x10).
100 (0x64)
Allow Anonymous IP Allows all Modbus TCP/IP clients to have the read- Enabled
only access. Disabled (Factory setting)
52 1040IB1401-05 07/2017
IFE Web Server
Parameter Settings
Baud Rate 9600 bps
19200 bps (Factory setting)
38400 bps
NOTE: When Nb bits of Stop parameter is set to Auto, the actual value is based on the parity chosen.
1040IB1401-05 07/2017 53
IFE Web Server
Introduction
The built-in email alarm notifications are sent through emails when the connected devices trigger an alarm.
The alarms are notifications that occur in response to a status change or when a value exceeds a threshold
value. The administrator selects and configures several alarm notifications. The recipient list is
configurable to notify the several users of the same alarm.
The email alarm notifications require unfiltered Internet access. This level of service is suited for small or
mid-sized non-critical buildings. The device sends the emails when Internet access is available through a
dedicated connection or through a local area network (LAN) with Internet access.
NOTE: The email alarm notifications should not be used if email services are managed internally by a
customer IT domain administrator.
Email Service
Authentication If the SMTP server requires login information, enable the Enabled
Authentication Enable check box. Disabled (factory setting)
SMTP account login Allows you to enter the SMTP account login name. –
SMTP account password Allows you to enter the SMTP account password. –
54 1040IB1401-05 07/2017
IFE Web Server
Email Language
Email Test
The Email Test feature enables connection from the device to the service. If the test emails are not
received, the Internet connection needs to enable the email ports (port 25 or 587 or 2525). The required
setting of the port is done in accordance between the device that sends the email and the site router
settings.
NOTE: The email with custom text that uses characters such as à, è, ù, é, â, ê, î, ô, û, ë, ï, ü, ÿ, and ç are
not shown correctly in the email. However, the generic text message is shown correctly.
1040IB1401-05 07/2017 55
IFE Web Server
Email Events
Description
The Email Events page allows the selection of the events to notify through email among a list of events.
CAUTION
EQUIPMENT INCOMPATIBILITY OR INOPERABLE EQUIPMENT
Do not rely solely on the notification of the emails for maintaining your equipment.
Failure to follow these instructions can result in injury or equipment damage.
The list of event displayed contains only applicable events related to the devices connected to the ULP port
of the IFE interface.
NOTE: If an email SMTP server is not located on the same Ethernet network segment as IFE interface,
ensure that the IFE default gateway is properly configured.
Parameter Description
Events List of events for configuration
Add Event A check box to enable to add events.
Email Recipients Allows you to choose from a list of email recipients.
NOTE: You can choose a maximum of 12 recipients.
Custom Text Allows you to enter a custom text.
NOTE: You can enter a maximum of 63 characters in the custom text area.
Events from PowerPact H-, J-, and L-Frame, PowerPact P- and R-frame, or Masterpact NT/NW Circuit Breakers
56 1040IB1401-05 07/2017
IFE Web Server
1040IB1401-05 07/2017 57
IFE Web Server
58 1040IB1401-05 07/2017
IFE Web Server
Description
The EcoStruxure™ Facility Expert service enables the electricians and the facility manager to stay
connected with their customer assets. The manager in charge of maintaining the electrical installation can
receive the alarms from all the installed IFE interfaces logged in a notebook, and the complete history of
the maintenance is shared within the maintenance staff. You can receive alarms directly in the notification
center of EcoStruxure Facility Expert as it is easy to monitor all the connected panels in the same space.
CAUTION
EQUIPMENT INCOMPATIBILITY OR INOPERABLE EQUIPMENT
Do not rely solely on the notification of the emails for maintaining your equipment.
Failure to follow these instructions can result in injury or equipment damage.
Parameters Description
Enable Configures the EcoStruxure Facility Expert service. You can receive all the alarm emails in the
EcoStruxure Facility Expert notification center.
When you enable EcoStruxure Facility Expert, the following actions are performed:
All the alarm emails are received in the EcoStruxure Facility Expert notification center.
The Email Recipients field is automatically populated with Facility Expert in the Email Events page.
NOTE: When the EcoStruxure Facility Expert service is enabled, the From address configured in
Email Server Configuration page cannot be changed.
Facility expert premium web site Allows you to log into the EcoStruxure Facility Expert account. The EcoStruxure Facility Expert
manages a special page to declare your IFE interface.
An alarm notification is sent to the EcoStruxure Facility Expert premium website on occurrence of an
alarm.
1040IB1401-05 07/2017 59
IFE Web Server
Device List
Description
The Device List page is used to define the list of devices connected to the IFE server (ULP port, serial port)
and remote Modbus/TCP slave devices. In the device list, you can add, delete and/or discover devices.
The list of connected devices is defined by either of the following:
Automatically, by using the device discovery procedure
Manually, by adding the devices one by one.
NOTE: The webpages are supported only for the devices added in the device list.
60 1040IB1401-05 07/2017
IFE Web Server
1040IB1401-05 07/2017 61
IFE Web Server
The table shows the steps to add device using device discovery procedure:
Save Allows you to save the selected device to the Device List. –
IP Address Displays the IP address of the IFE server or the remote device. –
Defined Lists the device type that was defined for this device. –
Assigned Allows you to assign the device type from the drop-down list. –
Name Allows you to enter a custom name for the device. –
Local ID The slave address of the device connected to the IFE server. –
Status Displays the discovery or validation status. Attempting (trying to determine the device
type that matches in the device list.)
Discovering (query attempt of device which is
not in the device list.)
Found (device found but the device type does
not match what is defined in the device list.)
Unknown (device found but the device type is
unknown.)
Valid (device type identified and matches
what is defined in the device list.)
Failed (failed to communicate with the
device.)
62 1040IB1401-05 07/2017
IFE Web Server
Device Logging
Description
Logging is available for the devices which are in the device list (see page 60). The logging contents can
be customized using topics. Topics are the parameters for a device that can be selected to have the
desired logging content. The number of log entries per device is fixed irrespective to the number of topics
selected for that device. The IFE interface can log data received at predefined intervals (5, 10, 15, 20, 30,
and 60 minutes). Below is an explanation of how the IFE interface logs data and how to set up logging for
a device.
NOTE: Device information in the Device List page cannot be edited if the device logging for that device is
selected.
Logging Interval
Many devices in a power monitoring system do not have the ability to record data in non-volatile memory.
The IFE interface provides this data logging at predefined intervals for up to 13 devices.
The features of IFE data logging are:
The maximum number of log entries per device is fixed to 12960.
Select maximum of 13 devices for data logging.
Select maximum of 24 topics per device for data logging (topics are kVAh, kWh, kVARh, and so on).
Select the desired device and list of topics for data logging.
NOTE: Number of days of logging is impacted only by the log interval selected. It is independent of number
of devices selected, number of topics selected per device, and type of topic selected.
Logging interval is a predefined time for the IFE interface to log data received from the device. The logging
capacity of a device is calculated by multiplying the log capacity factor with the logging interval set in the
Device Logging page.
Logging capacity (in days) = Log capacity factor * logging interval (in minutes)
The log capacity factor is 9 and is calculated as follows:
Log capacity factor = 12960/1440
Where:
12960 is the maximum number of log entries per device
1440 is the number of minutes per day
Example: If the Logging Interval in the Device Logging page is set to 5 minutes, then the logging capacity
is 45 days.
The table shows the logging capacity for the corresponding logging interval:
1040IB1401-05 07/2017 63
IFE Web Server
Logging
To disable logging, select the logging interval as Disabled, ensure that the logging selections are cleared,
then click Apply.
Purge Data
To delete a data log, check Purge Data for the topics to be deleted.
Customize
To customize logging content, enable device logging. Click Topics under Customize for the device to be
configured.
64 1040IB1401-05 07/2017
IFE Web Server
Description
The Device Log Export page is used to export the device logs automatically by IFE interface. The device
log export allows you to configure IFE interface to export device logs periodically. You can choose to export
the device log files through email or FTP.
NOTE: If the email and the FTP servers are not located on the same Ethernet network segment as the IFE
interface, ensure that the IFE default gateway is properly configured.
Transport
Schedule
To Addresses
FTP Parameters
1040IB1401-05 07/2017 65
IFE Web Server
SNMP Parameters
Manage IP Parameters
The IFE interface supports SNMP, allowing a network administrator to access remotely an IFE interface
with an SNMP manager and to view the networking status and diagnostics of the IFE interface in the MIB-
II format.
Read-write Community Name Allows you to configure the SNMP read-write community name. Private (Factory setting)
Trap Allows you to trap the community name. Public (Factory setting)
Enabled Traps
66 1040IB1401-05 07/2017
IFE Web Server
Preferences
General Settings
1040IB1401-05 07/2017 67
IFE Web Server
Industrial Protocol
Services Configuration
Enable device announcement Allows you to enable/disable the DPWS service. Enabled (Factory setting)
Disabled
68 1040IB1401-05 07/2017
IFE Web Server
User Accounts
Description
The IFE users are assigned with user names and passwords. Each user belongs to a group, and each
group has access rights to the IFE webpages assigned by the IFE administrator.
NOTE: There are three pre-defined user accounts:
Administrator (the pre-defined password is Gateway)
Guest (the pre-defined password is Guest)
EcoStruxure Facility Expert (the login credentials are not provided to log into the webpages). However,
if you have the EcoStruxure Facility Expert account, you can receive the alarm event notifications by
enabling the EcoStruxure Facility Expert feature.
Groups
To change the group name, enter a new name in one of the group text boxes.
NOTE: The administrator group name cannot be changed.
Users
Parameter Description
Name Enter a name (1 to 15 characters) for a new user.
NOTE: User names are case-sensitive and can contain only alphanumeric characters.
Password Enter a password (0 to 11 characters) for a new user.
Email ID Enter a valid email address for the selected name.
Group Select a group for the new user.
Language Select the language for the new user and click the Apply button to view the webpages in the selected language.
NOTE: When the administrator switches to a different language for the user account, make sure to refresh the
webpage manually to display the webpages in a selected language.
Accounts Password
Administrator Gateway
Guest Guest
User-defined accounts (11 User-defined passwords
accounts possible)
NOTE:
You can change your password.
If you forget the password, contact your local Schneider Electric service team for retrieving the
password.
1040IB1401-05 07/2017 69
IFE Web Server
Webpage Access
Group Access
Group Access
Administrator Full access to all webpages.
NOTE: It is recommended to change the default administrator password for system security
the first time you log in.
Guest Read-only access to selected webpages.
User-defined groups Choosing from the following options, the administrator assigns webpage access for each
group. The access levels are as follows:
None: A group has no access to selected webpage
Read-Only: The password grants a group read-only access to the selected webpage
Full: A group has the same access as the administrator group to the selected webpage
NOTE:
The Webpage Access is available for the Administrator only.
The Administrator has full access to all the webpages.
70 1040IB1401-05 07/2017
IFE Web Server
Section 2.3
IFE Web Server - Monitoring Pages
1040IB1401-05 07/2017 71
IFE Web Server
Description
The Real Time Data page provides:
the basic readings of the selected devices in real time on Single Device Pages.
the device summaries on Summary Device Pages.
the real-time trending for the selected device for the selected topics on Trending.
NOTE: Refresh the webpage by action on the function key F5 when out of service is displayed.
For BCPM devices, the auxiliary and branch circuit parameters can be monitored for real-time values. If
you have Administrator privilege, you can modify or configure the circuit names for BCPM devices.
Trending
72 1040IB1401-05 07/2017
IFE Web Server
Trending Parameters
1040IB1401-05 07/2017 73
IFE Web Server
Device Logging
Introduction
The Device Logging page provides the graphic and table representations of the selected device log data.
For more details on configuring device logging, refer to Device Logging (see page 63).
6 Hold the left mouse button and drag a selection box around a graph Zooms in on the selected graph area.
area to zoom in on it.
7 To return to the original full view, enter Z on your keyboard, or The view zooms out.
double-click the graph.
8 Click Data Points to view the selected interval data log table. Opens the selected Interval Data Log table.
9 To view different topics, click New Topic(s). Enable the check Enables the display of the selected topics.
boxes of the topics to be displayed, and click Apply.
The data logged from each device is displayed in a webpage in a time-trend chart format. The time-trend
chart is preconfigured to display data from the Last Full Day, Last Full Week, Last Full Month, or All.
Energy parameters are logged as accumulating values but are displayed as incremental values on an
interval basis. All other parameters are logged and displayed as the actual value recorded.
To view the list of all the available log files, follow steps 2 to 4 in the section Getting an Interval Data Log
using FTP (see page 75). Files are in the format: Device Name.csv where the device name is the name
given to the slave device. For example, a device named building 1 utility entrance is Building 1 Utility
Entrance.csv.
When the log files are exported, the date and time are appended to the file name in the following format:
_YYYYMMDDHHMMSS. For example, Building 1 Utility Entrance_20100218115216.csv. This indicates
that the file was exported on 2010 February 18 at 11:52:16 AM.
NOTE:
The circuit breaker status in log file is coded by numbers. For information on circuit breaker status, refer
to the description of the Modbus register 12001 in the Modbus Communication Guides.
The device log file may contain invalid values (-9999, -99999, 32768) for electrical parameters based
on the data read from the device.
74 1040IB1401-05 07/2017
IFE Web Server
Log Format
Data is logged in the CSV file with the following format:
If a spreadsheet application is used to view the CSV file, data should look similar to the interval data log
opened in a spreadsheet application.
Contact technical support if you need assistance in resolving these or other error conditions.
4 Navigate to the directory/logging/data on the IFE interface. Opens the data logging directory on the IFE interface.
5 Copy the log file and paste it into the folder created in step 1. Copies the data log to the folder.
1040IB1401-05 07/2017 75
IFE Web Server
The topic logged from the selected devices is displayed in a webpage in a time-trend chart format. The
time-trend chart is preconfigured to display data from the last full day, last full week, last full month, or last
6 weeks.
Energy parameters are displayed as incremental values on an interval basis. All other parameters are
logged and displayed as the actual value recorded.
76 1040IB1401-05 07/2017
IFE Web Server
Section 2.4
IFE Web Server - Control Page
1040IB1401-05 07/2017 77
IFE Web Server
Device Control
Reset Commands
The Device Control page allows you to execute one or more reset commands per device type.
From the Control menu, in the Device Control submenu, on the device list, select the device and click
Reset. Select an Operation in the Resets list to reset.
This feature is always enabled.
Application Control
The Device Control page allows you to control the following applications remotely:
Breaker application
IO application
Password Management
When the application control operation is performed, an Authorization Required dialog box appears in the
IFE webpage. Enter the password in the Authorization Required dialog box to perform the application
control operation.
The password required is for PowerPact H-, J-, and L-frame circuit breaker with BSCM and
Masterpact NT/NW or PowerPact P- and R-frame circuit breaker with BCM ULP.
The following operations in the Device Control page require a password:
78 1040IB1401-05 07/2017
IFE Web Server
Breaker Application
From the Device Control page, in the Breaker Application, the authorized group can perform the following
operations:
NOTE: Pop-up message confirms that the command is successfully sent. It does not confirm whether the
complete operation is successful.
IO Application
From the Device Control page, in the IO Application, the authorized group can perform the following
operations:
NOTE:
The IO application control is possible only when the IO module is connected to a circuit breaker.
The light and the load control are available when the application rotary switch of IO 1 or IO 2 is in
position 4.
The user-defined output control is available only when the user-defined output has been assigned with
Ecoreach software.
If the input is assigned as a pulse counter, the operation is P1, P2, P3, P4, P5, and P6 for IO 1. For IO 2,
the pulse counter operation is #P1, #P2, #P3, #P4, #P5, and #P6.
1040IB1401-05 07/2017 79
IFE Web Server
Description
The Set Device Time page allows you to synchronize the date and time of the slave devices connected to
the IFE interface to IFE date and time. It also allows you to get the device time that are connected to the
IFE interface. This page lists the slave devices that require an external interface to set their date and time.
Parameter Description
Device Selection Allows you to select the device from the list for synchronizing, getting, and synchronizing the time.
Localized Time Displays the time of the selected device.
Status Displays the status of the selected device.
Get Time Allows you to get the time of the selected device.
Set Device Time Allows you to set the time of the selected device.
80 1040IB1401-05 07/2017
IFE Web Server
Section 2.5
IFE Web Server - Diagnostics Pages
1040IB1401-05 07/2017 81
IFE Web Server
Statistics
Description
The Statistics page shows the readings accumulated since the IFE interface was last activated. If the
power to the IFE interface is terminated or the device is reset due to a configuration change or other event,
all cumulative values are reset to 0.
Reset Procedure
Statistic Description
Port status Status of the connected Ethernet port
Opened TCP connections Number of active connections
Received messages Number of messages received
Transmitted messages Number of messages transmitted
Reset counters Resets the received and transmitted messages
Statistic Description
CPU Status of the CPU:
Nominal
Degraded
Out of service
82 1040IB1401-05 07/2017
IFE Web Server
Statistic Description
Date Current date
Time Current time
Uptime Run time during the system power-up
Statistic Description
Last Synchronization
Last Synchronization Since Time elapsed since the last synchronization has happened
Time Source Source of time with which the last synchronization has happened
Date Last synchronization date
Time Last synchronization time
Synchronization with SNTP
Status The following is the status of synchronization with SNTP:
If SNTP is disabled, the status is displayed as “--”
If SNTP is enabled but not synchronized, then the status is displayed as “NOK”
If SNTP is enabled and successfully synchronized, then the status is displayed as “OK”
Statistic Description
Transmitted Message A counter that increments each time a frame is sent.
Received Message A counter that increments each time a frame is received.
Error Message An error marked from the slave or the response timeout.
Statistic Description
Frames Transmitted Number of CAN frames transmitted successfully
Frames Received Number of CAN frames received successfully
Max Transmit Error Maximum number of CAN transmitted errors (TEC)
Max Receive Error Maximum number of CAN received errors (REC)
Bus off CAN Bus off count
Max Bus off Maximum number of bus off counts
Statistic Description
Total Size Total amount of the IFE disk size in kilobytes
Used Size Total amount of used disk size on the IFE disk in kilobytes
Free Size Total amount of unused disk space on the IFE disk in kilobytes
Bad Size Amount of corrupted disk space on the IFE disk in kilobytes
1040IB1401-05 07/2017 83
IFE Web Server
Statistics Description
Remote IP Remote IP address
Remote Port Remote port number
Transmitted messages Number of messages transmitted
Received message Number of messages received
Sent Errors Number of error messages sent
Reset Counters Resets the transmitted and received messages
84 1040IB1401-05 07/2017
IFE Web Server
Device Identification
Parameter Description
Device name Device name which is updated in the device name field
Product name Name of the product
Serial number Device serial number
Product model number Device model number
Firmware version Current firmware version
Unique Identifier Combination of MAC address and the time
MAC address Unique MAC address
IPv4 address IP address of the IFE interface
IPv6 link local address Address used to communicate on the local network
1040IB1401-05 07/2017 85
IFE Web Server
IMU Information
Description
The IMU Information page gives the information about the devices which are connected to the ULP port of
the IFE interface. The devices connected are:
BCM ULP module
Micrologic trip unit
BSCM module
FDM121 display
IO module IO 1
IO module IO 2
UTA module
86 1040IB1401-05 07/2017
IFE Web Server
Description
Read device registers allows the IFE interface to read Modbus registers from the selected device.
Read Procedure
Decimal, Select an option to specify how the value column data is displayed. Decimal (Factory setting)
Hexadecimal,
Binary, or ASCII
options
1040IB1401-05 07/2017 87
IFE Web Server
Communication Check
88 1040IB1401-05 07/2017
IFE Web Server
IO Readings
Description
The IO Readings page shows the IO module input/output configuration. It displays six digital inputs, three
digital outputs, and one analog input. The IO application control is possible only when the IO module is
connected to a circuit breaker.
The table shows the steps to access the IO Readings page:
Force/Unforce Displays the six digital inputs and three digital outputs are forced or UNFORCED
unforced FORCED
1040IB1401-05 07/2017 89
IFE Web Server
Section 2.6
IFE Web Server - Maintenance Pages
Indicators
Description
The Indicators page provides the maintenance counter information for the selected device. The page
displays the information about the remaining service life of the circuit breaker, contact wear counters,
circuit breaker operation counters, and the cradle counters.
90 1040IB1401-05 07/2017
Enerlin’X IFE
1040IB1401-05 07/2017
Appendices
1040IB1401-05 07/2017 91
92 1040IB1401-05 07/2017
Enerlin’X IFE
Appendix A - List of IFE Supported Devices
1040IB1401-05 07/2017
Appendix A
Appendix A - List of IFE Supported Devices
1040IB1401-05 07/2017 93
Appendix A - List of IFE Supported Devices
94 1040IB1401-05 07/2017
1040IB1401-05