E310 Manual (English) v01

Download as pdf or txt
Download as pdf or txt
You are on page 1of 95

Microprocessor Controlled

I G B T Drive
Inverter Motor Speed Regulator
Operating Manual

E310 Series 200V class 0.4~1.5KW


(1.2~2.9KVA)
400V class 0.75~3.7KW
(1.7~6.7KVA)
E310 Table of Contents
Chapter 0 Preface 0-1
0.1 Preface 0-1
0.2 Product Inspection 0-1
Chapter 1 Safety Precautions 1-1
1.1 Operation Precautions 1-1
1.1.1 Before Power UP 1-1
1.1.2 During Power UP 1-2
1.1.3 Before Operation 1-2
1.1.4 During Operation 1-3
1.1.5 During Maintenance 1-3
Chapter 2 Definition of Model 2-1
Chapter 3 Ambient Environment and Installation 3-1
3.1 Environment 3-1
3.2 Environmental Precautions 3-2
3.3 Electrical Installation 3-3
3.3.1 Wiring guidelines 3-3
3.3.2 Contactor and Circuit Breaker specification and wiring 3-4
3.3.3 Precautions for Peripheral Applications 3-5
3.4 Specifications 3-8
3.4.1 Product Specifications 3-8
3.4.2 General Specifications 3-9
3.5 Wiring Diagram E310 Series Inverter 3-11
3.6 Description of connection terminals 3-12
3.7 Outline Dimension 3-13
Chapter 4 Software Index 4-1
4.1 Keypad Description 4-1
4.1.1 Keypad Display and Operation Instruction 4-1
4.1.2 Operation Instruction of the LED keypad 4-2
4.2 Control Mode Selection 4-3
4.3 E310 Programmable Functions List 4-4
4.4 Parameter Function Description 4-18
Chapter 5 Troubleshooting and Maintenance 5-1
5.1 Error Display and Corrective Action 5-1
5.1.1 Faults which can not be recovered manually 5-1
5.1.2 Special conditions 5-2
5.1.3 Operation errors 5-3
5.2 General Troubleshooting 5-4
5.3 Quick Troubleshooting of E310 5-5
5.4 Routine and periodic inspection 5-11
5.5 Maintenance and Inspection 5-12
Chapter 6 Peripheral Components 6-1
6.1 Reactor Specification at Input Side 6-1
6.2 Braking unit and braking Resistor 6-1
6.3 Digital operator and extension cable 6-2
AppendixⅠ E310 Parameters Setting List App1

i
Index of Figures

Figure 2-1 Inverter Nameplate .....................................................................................2-1


Figure 3-1 Panel and enclosure arrangement for E310 inverters ...................................3-1
Figure 3-2 Din rail mounting of the E310 inverter ........................................................3-1
Figure 3-3 Typical Installation Schematic.....................................................................3-5
Figure 3-4a) Installation Examples...............................................................................3-6
b) Installation Examples Using a Filter and Isolation transformer ................3-6
c) Installation Examples with Adjacent Signal Conductors ...........................3-6
Figure 3-5 Control Cable requirements ........................................................................3-7
Figure 3-6 Grounding Examples ..................................................................................3-7
Figure 3-7 Wiring Diagram.......................................................................................... 3-11
Figure 3-8 Frame size 1 Dimensions ............................................................................. 3-13
Figure 3-9 Frame size 2 Dimensions ............................................................................. 3-14

Figure 4-1 Keypad Layout ...........................................................................................4-1


Figure 4-2 LED Keypad Operations Sequence..............................................................4-2
Figure 4-3 Control Mode Selection Chart.....................................................................4-3
Figure 4-4 Frequency reference limits .......................................................................... 4-18
Figure 4-5 Terminal Board Drive Operation Modes ..................................................... 4-19
Figure 4-6 3-Wires Start/Stop Wiring........................................................................... 4-19
Figure 4-7 Drive Start/Stop Operation sequences ......................................................... 4-20
Figure 4-8 Acceleration and deceleration Prohibit ........................................................ 4-22
Figure 4-9 UP/DOWN original mode example .............................................................. 4-24
Figure 4-10 UP/DOWN with incremental steps............................................................. 4-24
Figure 4-11 Frequency reached example ...................................................................... 4-25
Figure 4-12Frequency within specified range example.................................................. 4-26
Figure 4-13 Frequency outside of range example .......................................................... 4-26
Figure 4-14 Frequency at or below specified range example.......................................... 4-27
Figure 4-15 Over torque detection example .................................................................. 4-27
Figure 4-16 Analog scaling examples ........................................................................... 4-29
Figure 4-17 Multifunction analog output ...................................................................... 4-29
Figure 4-18 KEB function diagram .............................................................................. 4-34
Figure 4-19 DC Injection Braking Example.................................................................. 4-34
Figure 4-20 Custom V/F settings .................................................................................. 4-35
Figure 4-21 Custom V/F Patterns................................................................................. 4-36
Figure 4-22 V/F curve with torque boost ...................................................................... 4-37
Figure 4-23 Output Torque Capacity .......................................................................... 4-38
Figure 4-24 Slip Compensation .................................................................................... 4-39
Figure 4-25 Low Frequency Voltage Compensation...................................................... 4-39
ii
Figure 4-26 PID block diagram .................................................................................... 4-43
Figure 4-27 PID sleep wake mode diagram................................................................... 4-45
Figure 4-28 S-Curve Characteristics ............................................................................ 4-47
Figure 4-29 Single cycle auto run ................................................................................. 4-51
Figure 4-30 Periodic cycle auto run .............................................................................. 4-52
Figure 4-31 Single cycle auto run: final step hold.......................................................... 4-52
Figure 4-32 AUTO_RUN cycle with interrupt ............................................................. 4-53

Figure 5-1 E310 Fault Display and Troubleshooting Flow Chart...................................5-6


Figure 5-2 OC, OL Fault Display Flow Chart...............................................................5-7
Figure 5-3 OV, LV Fault Display Flow Chart ..............................................................5-8
Figure 5-4 Motor RUN failure Flow chart ...................................................................5-9
Figure 5-5 Motor Overheat Troubleshooting Flow Chart.............................................. 5-10
Figure 5-6 Motor Instability Troubleshooting Flow Chart ............................................ 5-10

Figure 6-1 Digital Operator Extension Cable................................................................6-2

iii
Chapter 0 Preface
0.1 Preface
To extend the performance of the product and ensure personnel safety, please read this manual
thoroughly before using the inverter. Should there be any problem in using the product that
cannot be solved with the information provided in the manual, contact your nearest Taian’s
technical or sales representative who will be willing to help you.
※Precautions
The inverter is an electrical product. For your safety, there are symbols such as “Danger”,
“Caution” in this manual as a reminder to pay attention to safety instructions on handling,
installing, operating, and checking the inverter. Be sure to follow the instructions for highest
safety.

Indicates a potential hazard that could cause death or serious personal injury if
Danger
misused.

Indicates that the inverter or the mechanical system might be damaged if


Caution
misused.

Danger

z Do not touch any circuit boards or components after the power is turned off and while the
charging indicator is still lit. (The light will fade)
z Do not make any connections when the inverter is powered on. Do not check parts and
signals on circuit boards during the inverter operation.
z Do not disassemble the inverter or modify any internal wires, circuits, or parts.
z Ground the ground terminal of the inverter properly.
For 200V class ground resistance 100 Ω or below. For 400V class 10Ω or below.
Make sure that grounding conductors are adequately sized and are according to your
local safety regulations.

Caution

z Do not perform a voltage test on parts inside the inverter. High voltage can destroy the
semiconductor components.
z Do not connect T1, T2, and T3 terminals of the inverter to any AC input power supply.
z CMOS ICs on the inverter’s main board are susceptible to static electricity. Do not touch
the main circuit board
0.2 Product Inspection
Taian inverters have all passed the function test before delivery. Please check the following
when you receive and unpack the inverter:
z The model of the inverter are the same as those specified in your purchase order.
z Check for any damages caused by transportation. Please do not apply power, and
contact a Taian sales representative if any of the above problems occurred.

0-1
Chapter 1 Safety Precautions
1.1 Operation Precautions
1.1.1. Before Power Up

Caution
The line voltage applied must comply with the inverter’s specified input voltage.(See
product nameplate)

Danger
Make sure the main circuit connections are correct. L1, L2 and L3 are power-input
terminals and must not be mistaken for T1, T2 and T3. Otherwise, inverter damage can
result.

Caution
z To avoid the front cover from disengaging or other damage, do not carry the inverter by
its cover. Support the drive by its heat sink when transporting. Improper handling can
damage the inverter or injure personnel, and should be avoided.

z To avoid the risk of fire, do not install the inverter on flammable objects. Install on
nonflammable objects such as metal surfaces.

z If several inverters are placed in the same control panel, provide heat extraction means
to keep the temperature below 40℃ to avoid overheat or fire hazard.

z When removing or installing the operator keypad, turn OFF the power first, and secure
the keypad correctly to avoid keypad operation or display failure.

Warning
This product is sold subject to IEC 61800-3. In a domestic environment this product may
cause radio interference in which case the user may be required to apply corrective
measures.

1-1
1.1.2. During Power Up

Danger
z Do not insert or remove input connections to the inverter when powered up to avoid
damage to the control board resulting from possible voltage surge due to contact
bounce.

z When momentary power loss is longer than 2 seconds (the larger of horse power, the
longer of time), the inverter does not have enough storage power to control the circuit;
Therefore, when the power is re-applied, the operation of the inverter is based on the
setup of 00-03(or00-04) /04-09 and the condition of external switch, this is considered
to be「restart」in the following paragraphs.

z When the momentary power loss is short, the inverter still has enough storage power to
control the circuit. Therefore, when power is re-applied, the inverter will automatically
restart depending on the setup of 04-03/04-04.

z When restarting the inverter, the operation of the inverter is based on the setup of 00-
03(or00-04) and 04-09 and the condition of external switch (FWD/REV button).
Attention: the start operation will be regardless of 04-03/04-04/04-06/04-07.

1. When 00-03(or00-04) =0, the inverter will not automatically run after restart.

2. When 00-03(or00-04) =1 and the external switch is OFF, the inverter will not run
after restart.

3. When 00-03(or00-04) =1, the external switch is ON, and 04-09=0, the inverter will
run automatically after restart.

Attention: To ensure safety, please turn off the external switch (FWD/REV button)
after power loss, to protect machines from possible damage and potential injury to
personnel on sudden resumption of power.

z If 4-09 is set to 0 (direct start up), please refer to the description and warnings for 04-09
to verify the safety of operator and machine.

1.1.3. Before Operation

Danger
Make sure the model and inverter capacity are the same as that set in parameter 12-00.

Caution

On power up the supply voltage set in parameter 05-03 will flash on display for 2 seconds.

1-2
1.1.4. During Operation

Danger
Do not connect or disconnect the motor during operation. Otherwise, the over-current will
cause the inverter to trip or damage the unit.

Danger
z To avoid electric shock, do not take the front cover off when power is on.
z The motor will restart automatically after stop when auto-restart function is on. In this
case, use caution while working near the drive, motor, or driven equipment.
z Note: The stop push button and external stop command have no safety function.
For Emergency stop, it is necessary to use a correct latch type push button and an
appropriate circuit or devices to ensure safety.

Caution
z Do not touch heat-generating components such as heat sinks and braking resistors.
z The inverter can drive the motor from low speed to high speed. Verify the allowable
speed range of the motor and the load before operation.
z Note the settings related to the braking unit.
z Do not check signals on circuit boards while the inverter is running.

Caution
Allow 5 minutes after disconnecting power before disassembling or checking the
components. The power led should not be illuminated.
1.1.5. During Maintenance

Caution
The Inverter can be used in a non-condensing environment in temperature range from
14˚-104℉ (-10-40℃) and relative humidity of 95%
Inverter Disposal
Caution
z Please dispose of this unit with care as an industrial waste and according to your
required local regulations.
z The capacitors of inverter main circuit and printed circuit board are considered as
hazardous waste and must not be burnt.
z The Plastic enclosure and parts of the inverter such as the top cover board will release
harmful gases if burnt.

1-3
Chapter 2 Definition of model

Inverter model → MODEL: E310-201-H

Input voltage → I/P: AC 1 OR 3PH


200~240V 50/60Hz
Output specifications→ O/P: AC 3PH 0~240V
1.7 KVA 4.5 A
TECO Electric & Machinery co., Ltd.
E310Series:
E31 0 - 2 01 - H
Supply voltage Specification
2 200Vclass H
4 400Vclass

Adhibition Horsepower
0 standard Type P5 0.5 HP
01 1 HP
02 2 HP
03 3 HP Power supply
05 5 HP
3 Three phase
common model
for single /Three
Blank phase

Figure 2-1 Inverter Nameplate

2-1
Chapter 3 Ambient Environment and Installation
3.1 Environment
The environment will directly affect the proper operation and the life span of the inverter, so install
the inverter in an environment complying with the following conditions:

z Ambient temperature: 14-104℉(-10oC - +40oC)


z Avoid exposure to rain or moisture. z Avoid direct sunlight.
z Avoid oil mist and salinity. z Avoid corrosive liquid and gas.
z Avoid dust, lint fibers, and small metal z Keep away from radioactive and
filings. flammable materials.
z Avoid electromagnetic interference (soldering machine, power machine).
z Avoid vibration (stamping, punching machine). Add a vibration-proof pad if the situation
cannot be avoided.
z If several inverters are placed in the same control panel, provide heat removal means to
maintain temperatures below 40oC.

Fan Fan
E310
CONTROL
CONTROL
PANEL PANEL Enclosure Enclosure

E310 E310 E310

(Correct configuration) (Incorrect configuration) (Correct configuration) (Incorrect configuration)


Figure 3-1 Panel and enclosure arrangement for E310 inverters
z Place the inverter facing forward and its top facing upward to assist with cooling.
12cm

E310
73000CV
Installing
direction
12cm

5cm 5cm 5cm


Air convection
-10oC - +40oC
(a) Front view (b) Side view

Figure 3-2 Din rail mounting of the E310 Inverter

3-1
3.2 Environmental precautions
Do not use the inverter in an environment with the following conditions:

3-2
3.3 Electrical Installation
3.3.1 Wiring guidelines
A. Power Cables
Power cables are connected to TM1 terminal block, terminals L1, L2, L3, T1, T2, T3, P, R.
Choose power cables according to the following criteria:
(1)Use copper wires only. Correct wire diameters should be based on ratings at 105oC.
(2)For rating voltage of wires, the minimum voltage of 200V class type is 300V, and 400 V class
type is 600V.
B. Control Cables
Control cables are connected toTM2 control terminal block.
Choose control cables according to the following criteria:
(1) Use copper wires only. Correct wire diameters should be based on ratings at 105oC.
(2) For rating voltage of wires, the minimum voltage of 200V class type is 300V, and 400 V class
type is 600V.
(3) To avoid noise interference, do not route power and control cables in the same conduit or
trucking.
(4) Where possible use screened / shielded control cables to minimizes electromagnetic
interference.
(5) To avoid ground loops always earth the shield of control cables at one end only.
C. Nominal electrical specifications of the terminal Block TM1:
Horsepower Power source Amps Volts
0.5/1/ 2 200-240V
15
1/ 2 380-480V 600
3/ 5 380-480V 40
※Note: Nominal values of input and output signals (TM2,TM3) – follow the specifications of
class 2 wiring.
D. Fuse types
Drive input fuses are provided to disconnect the drive from power in the event that a component
fails in the drive’s power circuitry. The drive’s electronic protection circuitry is designed to clear
drive output short circuits and ground faults without blowing the drive input fuses. Table below
shows the E310 input fuse ratings.
To protect the inverter most effectively, use fuses with current-limit function.
Horsepower power supply standard Fuse types
1/2 200-240V 15A, 600VAC, 100KA I.R.
1 5A, 600VAC, 100KA I.R.
2 10A, 600VAC, 100KA I.R.
380-480V
3 15A, 600VAC, 100KA I.R.
5 20A, 600VAC, 100KA I.R.
※Notice
z To avoid shock hazards, do not touch any electrical component when the power is applied or
with in five minutes after the power is disconnected. Any inspection should be performed after
the charge indicator goes off.
z Do not perform wiring on the inverter with power on. Disregard of this notice may result in
serious injury.

3-3
3.3.2 Contactor and Circuit Breaker specification and wiring.
Molded-case circuit breaker/magnetic contactor
z Teco bears no responsibility to service for failures caused by the following conditions:
(1) A molded-case circuit breaker is not installed, or an improper or overrated breaker is used,
between the power source and the inverter.
(2) A magnetic contactor, a phase capacitor, or a burst absorber is connected between the
inverter and the motor.

model: 2 P5 201 202


E310-□□□-XXX

Molded-case circuit 50 E 50E 50E


breaker made by Teco 10 A 20 A 30 A

Magnetic contactor CN-11


(MC) made by Teco
Main circuit terminals Wire gauge 2.0 mm2
(TM1) terminal screw M3.5
Wire gauge 0.80mm2 ( # 18 AWG)
Signal terminals
(TM2,TM3 ) terminal screw M3

model:
E310-□□□-XXX
401/402/403/405
Molded-case circuit
50 E 15A
breaker made by Teco
Magnetic contactor
CN-11
(MC) made by Teco
Wire gauge 2.0 mm2
Main circuit terminals
(TM1) terminal screw M3.5
Signal terminals Wire gauge 0.80mm2 ( # 18 AWG)
(TM2,TM3 ) terminal screw M3

z Use three-phase squirrel cage induction motor with capacity suitable for the inverter.
z If one inverter is driving several motors, the total current of all motors running simultaneously
must be less than the rated current of the inverter, and each motor has to be equipped with a
proper thermal relay.
z Do not add capacitive components, such as a phase capacitors, LC or RC, between the inverter
and the motor.

3-4
3.3.3 Precautions for peripheral applications:
Power supply:
z Make sure the correct voltage is applied to avoid
damaging the inverter.
z A molded-case circuit breaker or fused disconnect
must be installed between the AC source and the
inverter
Molded-case circuit breaker:
z Use a molded-case circuit breaker that conforms to the
rated voltage and current of the inverter to control the
power ON/OFF and protect the inverter.
z Do not use the circuit breaker as the run/stop switch
for the inverter.
Leakage breaker:
z Install a leakage breaker to prevent problems caused
by electric leakage and to protect personnel.
z Setting current should be 200mA or above and the
operating time at 0.1 second or longer to prevent
malfunctions.
Magnetic contactor:
z Normal operations do not need a magnetic contactor.
However a contactor has to be installed in primary
side when performing functions such as external
control and auto restart after power failure, or when
using a brake controller.
z Do not use the magnetic contactor as the run/stop
switch of the inverter.
E310 AC reactor for power quality improvement:
z When inverters below 200V/400V class 15KW are
supplied with high capacity (above 600KVA) power
source or an AC reactor can be connected to improve
the power performance.
Install fast action fuse:
z To ensure the safety of peripheral devices, please
install fast action fuse. Regarding the specification,
please refer to P3-3.
Input noise filter:
z A filter must be installed when there are inductive
loads affecting the inverter
Inverter:
z Input power terminals L1, L2, and L3 can be used in
any sequence regardless of phase.
z Output terminals T1, T2, and T3 are connected to U,
V, and W terminals of the motor. If the motor is
reversed while the inverter is set to run forward, just
swap any two terminals of T1, T2, and T3.
z To avoid damaging the inverter, do not connect the
input terminals T1, T2, and T3 to AC input power.
z Connect the ground terminal properly. 200V class:
class 3 grounding, <100Ω; 400V class : <10Ω.

Figure 3-3 Typical Installation Schematic

3-5
Make external connections according to the following instruction. Check connections after wiring
to make sure all connections are correct. (Do not use the control circuit buzzer to check connections)
(A) Main circuit’s wiring must be separated from other high voltage or high current power line to
avoid noise interference. Refer to the figures below:

Figure 3-4a) Installation Examples

Figure 3-4b) Installation Examples using a filter and Isolation transformer


z A noise filter in the output of the main circuit can suppress conducted noise.
z To prevent radiated noise, the wires should be put in a metal pipe and distance from signal
lines of other control equipment should be more than 30 cm.

MCCB Metal Box


Metal Pipe
Power Supply
Noise Noise
Filter E310 Filter

30 cm above

Signal Wire
Controller

Figure 3-4c) Installation Examples with Adjacent Signal Conductors

3-6
z When the connection between the inverter and the motor is too long,consider the voltage
drop of the cables. Phase-to-phase voltage drop (V) =
3 ×resistance of wire (Ω/km)×length of line (m)×current×10-3.
z Carrier frequency must be adjusted based on the motor cable length.
Cable length between the inverter and
Below 150ft Below 300ft Above 300ft
the motor
Recommended
Below 12KHz Below 8KHz Below 5KHz
carrier frequency
Setting of parameter 10-03 12 8 5
(B) The control circuit wiring must be separated and routed away from the main circuit control line
or other high voltage or current power lines to avoid noise interference
● To avoid erroneous operation caused by noise interference, shield the control circuit wiring
with twisted-wires, and connect the shielded wire to a ground terminal. Refer to the figure below.
The wiring distance should not exceed 50 meters.
Protective covering
Shielding sheath

To ground terminal Do not connect this end

Wrapped with insulating tape


Figure 3-5 Control Cable requirements
(C)Inverter Ground terminal must be connected to installation ground correctly and according to
the required local wiring regulations.
For 200V class ground resistance should be 100Ω or less.
For 400V class ground resistance should be 10Ω or less.
●Ground cable size must be according to the required local wiring regulations. The shorter the

better.
●Do not share the ground of the inverter with other high current loads

(Welding machine, high power motor). Connect the terminals to their own ground.
●Do not make a loop when several inverters share a common ground point.

E310 E310 E310 E310 E310 E310 E310 E310 E310

(a) Good (b) Good (c) Bad


Figure 3-6 Grounding Examples
(D) To ensure maximum safety, use correct wire size for the main power circuit and control circuit.
(According to the required local regulations)
(E) Verify that all wiring is correct, wires are intact, and terminal screws are secured.
3-7
3.4 Specifications
3.4.1 Product Specifications
Single / Three phase, 200-240V model
Model: E310-□□□-XXX 2 P5 201 202
Horsepower(HP) 0 .5 1 2
Max Applicable Motor Output
0 .4 0 .75 1 .5
(KW)
Rated Output Current(A) 3 .1 4 .5 7 .5
Rated Capacity(KVA) 1 .2 1 .7 2 .9
Max Applicable Motor Output
Sing le/Th ree Ph ase: 200 ~240V +10% -15%, 50 /60H Z ± 5 %
(KW)
Max. Output Voltage Th ree Phase: 200 ~240V
Net Weight (KG) 1.37 1.37 1.47
Allowable momentary power loss
1.0 1.0 2.0
time (second)

Three phase, 380 – 480V model

Model:E310-□□□-XXX 401 402 403 405

Horsepower(HP) 1 2 3 5
Max Applicable Motor Output
0.75 1.5 2.2 3.7
(KW)
Rated Output Current(A) 2.3 3.8 5.2 8.8
Rated Capacity(KVA) 1.7 2.9 4.0 6.7
Max Applicable Motor Output
Th re e phase:380 ~480V +10% -15%, 50 /60H Z ± 5%
(KW)
Max. Output Voltage Th re e phase : 380~480V
Net Weight (KG) 1.33 1.35 2.22 2.25
Allowable momentary power loss
1.0 1.0 2.0 2.0
time (second)

3-8
3.4.2 General Specifications
Item E310

Control Mode V/F or Vector Control

Range 0.01~400.00 Hz

Start control torque 150%/1Hz ( Vector)

Speed control range 1:100 ( Vector)

Speed Control Precision ±0.5% (Vector)


Frequency Control

Setting resolution Digital: 0.01Hz, Analog: 0.06Hz/ 60Hz(10bits)

Keypad setting Set directly with▲▼ keys or the VR on the keypad

Five digital LED and status indicator; display frequency/ line


speed/ DC voltage/ Output voltage/ Current/ Rotation direction/
Display Function
Inverter parameter/ Fault Log/ Program Version / Heat sink
temperature/PID feed back
1. External potentiometer0-10V/ 0-20mA
2. Provides up/down controls, speed control or automatic
External signal setting procedure control with multifunctional contacts on the terminal
block (TM2)
Frequency Limit Upper/lower frequency limits and three programmable skip
Function frequencies
Carrier frequency 1 ~ 12 kHz

V/F pattern 18 fixed patterns, 1programable curve

Two-stage Acc/Dec time (0.1 – 3,600 seconds) and four-stage S


Acc/Dec control
curves (refer to descriptions on 10-07.)
Multifunction analog
5 functions (refer to description on 2-12)
output

Multifunction input 22 functions (refer to description on 01-00~01-05)

Multifunction output 14 functions (refer to description on 01-09~01-10)


Momentary Power Loss Restart, Speed Search, Overload
Detection, 8 preset speeds. Acc/Dec Switch (2 Stages), S Curves,
Other Functions 3-wire Control, PID control, torque boost, Slip Compensation,
Frequency Upper/ Lower Limit, Auto energy saving, Modbus
slave and PC/PDA Link, Auto Restart, Encoder input.

3-9
Item E310
1. Control by RS485
Communication Control 2. One to one or one to many control.
3. BAUD RATE/STOP BIT/PARITY/bit can be set

About 20﹪, the model below 20HP with built-in braking


Braking Torque transistor and the specified external braking resistors can provide
100%
Operation temperature 14-120℉(-10 ~ 50℃)
Storage temperature 4-140℉(-20 ~ 60℃)
Humidity 0 – 95% Relative Humidity(Non-condense)
Vibration 1G (9.8m/ S2 )
Enclosure IP20
The relays to protect the motor (the curve can be set) and the
Overload protection
inverter (150 % / 1min)

Over Voltage 200V class: DC Voltage>410V 400Vclass: DC Voltage>820V

Under Voltage 200V class: DC Voltage<190V 400Vclass: DC Voltage<380V


Protective Functions

Momentary Power Restart can be initiated with spin start after momentary power loss
Loss Restart in Max 2 sec.
Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation.

Short-circuit output Electronic Circuit Protection


terminal
Grounding Fault Electronic Circuit Protection
Protection for overheating of heat sink, over torque detection,
Other Function error contact control, reverse prohibit, prohibit for direct start
after power up and error recovery, parameter lock up.

3-10
3.5 Wiring diagram E310 series inverter

(
(
(

RY1

TR1

Figure 3-7 Wiring Diagram

Note 1: Please refer to description of main circuit terminals (P, R) and specification of braking
resistor for value selection.
2: please avoid connecting output of inverter to the earth.

3-11
3.6 Description of connection terminals
Descriptions of main circuit terminals

Symbol Description
L1
Main power input Single-phase: L1/ L2
L2
Three-phase: L1/L2/L3
L3
P Braking resistor connection terminal: Used in applications
TM1
220V:0.5~2HP,
when it is required to stop a high inertia load rapidly. (refer
R 380V:1~5HP
to specifications of the braking resistor)
T1
T2 Inverter outputs
T3

Descriptions of E310 control circuit terminals

Symbol Description
Normal open
RA Contact rated capacity:
contact Multifunctional
(250VAC/1A or30VDC/1A)
Normal close output
RB Contact using description:
contact terminals
(refer to parameters 01-09, 01-10)
RC Common contact
10V Frequency knob (VR) power source terminal (pin 3)
TM2
AVI Analog frequency signal input terminal AVI (0~10VDC/2~10VDC)
ACI PID signal input terminal or Bias signal input terminal ACI(0~20mA /4~20mA)
GND ground
SYN+ Positive terminal for multi-function output
30VDC/200mA
SYN- Negative terminal for multi-function output
COM Common for digital input signal for S1~S6 input.
S1
S2 multifunction input terminals (refer to parameter 1-00~1-02 description)
S3
COM Common for digital input signal for S1~S6 input.
TM3
S4
S5 multifunction input terminals (refer to parameter 1-03~1-05 description)
S6
The positive multifunction analog output signal for multifunction (refer to
FM+ parameter 2-12 description), the signal for output terminal is 0-10VDC (below
2mA).

3-12
3.7 Outline Dimensions (unit: mm)
(1) Frame1 : single /Three phase: E310-2P5/201/202 Three phase: E310-401/402

+ a
530

)5(4
6(7

Figure 3-8 Frame size 1 Dimensions

E310-2P5/201/202/401/402

3-13
(2) Frame2 : Three phase E310-403/405

+ a
530

)5(4
6(7

Figure 3-9 Frame size 2 Dimensions

MODEL : E310-403/405

3-14
Chapter 4 Software Index

4.1 Keypad Description

4.1.1Keypad Display and Operation Instruction

Figure 4-1 Keypad Layout


1. Four actions of FUN mode: Hz/RPM, and display of five 7-segment display. (Refer to operation
description of the keypad).
2. FWD LED: Forward Direction, LED action (Flash while stopped, solid Lit during operation).
3. REV LED: Reverse Direction, LED action (Flash while stopped, solid Lit during operation).

Caution

To avoid keypad damage, do not operate it with a screwdriver or any sharp and hard tool.

4-1
4.1.2 Operation Instruction of the LED keypad

Power On
● : LED fully Lit
: LED flashing

2seconds later or after Enter operation signal, Press DSP to modify the display

HZ/RPM ‧ HZ/RPM ‧

HZ/RPM ‧

FUN

— FUN


FUN — FUN

VOLT VOLT

‧ AMP

PID
Counter
Output

Figure 4-2 LED Keypad Operations Sequence

4-2
4.2 Control Mode Selection
The E310 Series inverter has two control modes:
1. V/F Control Mode. 2. General Vector Control Mode.
The user can choose these modes with the digital keypad according to the application requirement.
The factory setting is V/F Control Mode. Before operation, please set the control mode and the
related motor parameters in accordance with the following flow chart. (The Vector control mode is
suitable for the motors with the same power rating as the inverter, or one size bigger or smaller if
necessary).
Setting procedure for
control mode
Vector Control
Control Mode
V/F Control

Control mode selection


Control mode selection
00-00=0
00-00=1
Set the following parameters:
V/F Pattern 00-01
Torque Boost 05-00
Set the following parameters:
Motor no load current 05-01 (<=06-01)
Motor rated voltage 06-00
Motor Rated Slip 05-02
Motor rated current 06-01
Max output frequency 05-04
Motor power 06-02
Max output voltage 05-05
Motor rated Speed 06-03
Mid output Frequency 05-06
Motor rated Frequency 06-04
Mid output voltage 05-07
Min output frequency 05-08
Min output voltage 05-09 Perform Auto tuning (06-05=1)
Motor Rated Current 06-01 (OL1 reference)
End
※Note: Figure 4-3 Control Mode Selection Chart
1. Use V/F Control Mode:
(1) Use one inverter to drive several motors simultaneously
(2) Motor’s nameplate is unknown or motor ’s specifications are too special, it will
cause Auto-tuning fault.
(3) Specification of inverter and motor differs by more than 1 size.
2. One inverter drives several motors (Only in V/F mode), set the motor parameters according to the
following rules:
(1). Sum the rated current of all motors for total inverter current.
(2). Input correct VF Pattern parameter (05-04~05-09).
3. When the nameplate of the motor is unknown, the inverter will be set by default to parameters
according to the standard TECO motor.
4. When parameter 00-00=0, the keypad will display ‘Err2’ when performing Auto tuning.
5. In VECTOR MODE, the max. & min. value of 06-01~06-05 will be limited by one size higher or
lower than TECO standard motor specification. In VF MODE control, there is no limitation.

4-3
4.3E310 Programmable Functions List

Parameter
Description
Group No.
00- The basic parameters group

01- External terminal digital signal input function group

02- External terminal analog signal input function group

03- Preset Frequency function group

04- Start/Stop command group

05- V/F command group

06- Motor parameter group

07- Protection function group

08- Communication function group

09- PID function group

10- Assistant function group

11- Keypad display group

12- User parameter group

13- Auto Run(Auto Sequencer) function group


0- The basic parameters group
FunctionCode Factory
Description Range/Code Remarks
No. Setting
0:Volts/Hz
00-00 Control Mode 0
1:Vector
00-01 Volts/Hz Patterns(V/F) 0~18 0/9 *5
0:Forward
00-02 Motor rotation 0 *1
1:Reverse
0:Keypad
Main Run
00-03 1:External Run/Stop Control 0
Command Source Selection
2:Communication
0:Keypad
Subsidiary Run
00-04 1:External Run/Stop Control 0
Command Source Selection
2:Communication
0:Keypad
1:Potentiometer on Keypad
Main Frequency
00-05 2:External AVI Analog Signal Input 0
Command Source Selection
3:External Up/Down Frequency Control
4:Communication setting Frequency

4-4
FunctionCode Factory
Description Range/Code Remarks
No. Setting
0:Keypad
1:Potentiometer on Keypad
Subsidiary Frequency
00-06 2:External AVI Analog Signal Input 0
Command Source Selection
3:External Up/Down Frequency Control
4:Communication setting Frequency
00-07 Frequency Upper Limit (Hz) 0.01~400.00 50.00/60.00
00-08 Frequency Lower Limit (Hz) 0.01~399.99 0.00
00-09 Acceleration Time 1(S) 0.1~3600.0 10.0 *1
00-10 Deceleration Time 1(S) 0.1~3600.0 10.0 *1
0:Forward/Stop-Reverse/Stop
Operation modes for external
00-11 1:Run/Stop-Forward/Reverse 0
terminals
2:3-Wire Control Mode-Run/Stop
00-12 Jog Frequency (Hz) 0.00~25.00 2.00 *1
00-13 Jog Acceleration Time (MFIT) (S) 0.1~25.5 0.5 *1

00-14 Jog Deceleration Time (MFIT) (S) 0.1~25.5 0.5 *1

1- External terminal digital signal input function group


FunctionCode Factory
Description Range/Code Remarks
No. Setting
01-00 Multifunction Input Term. S1 0 : Forward/Stop Command 0
01-01 Multifunction Input Term. S2 1 : Reverse/Stop Command 1
01-02 Multifunction Input Term. S3 2 : Preset Speed unit 0 (3-02) 2
01-03 Multifunction Input Term. S4 3 : Preset Speed unit 1 (3-03) 3
01-04 Multifunction Input Term. S5 4 : Preset Speed unit 2 (3-05) 4
5 : Jog Forward Command
6 : Jog Reverse Command
7 : Acc/Dec 2
8 : Emergency Stop
9 : Base Block
10 : Main/Alt run Command select
11 : Acc/Dec Disabled
12 : Up Command
13 : Down Command
01-05 Multifunction Input Term. S6 14 : Main/Alt Frequency Command 17
select
15 : PID Function Disabled
16 : Integration Value Resets to Zero
17 : Reset
18 : KEB function
19 : Auto _ Run Mode
20 : Counter Trigger Signal
21 : Counter Reset
Multifunction terminal S1~S6 confirm
01-06 1~ 200(X 4ms) 5
the scan times
01-07 Up/Down (Hz) 0.00~ 5.00 0.00

4-5
FunctionCode Factory
Description Range/Code Remarks
No. Setting
0 : When Up/Down is used, the preset
frequency is held as the inverter stops,
and the UP/Down function is disabled.
1 : When Up/Down is used, the preset
01-08 Up/Down keep Frequency mode frequency is reset to 0 Hz as the 0
inverter stops.
2 : When Up/Down is used, the preset
frequency is held as the inverter stops,
and the UP/Down is available.
01-09 Output Relay RY1 Operation Mode 0 : Run 1
1 : Fault
2 : Frequency Reached
3 : Set Frequency
4 : Frequency Threshold Level
(> 1-11) - Frequency Reached
5 : Frequency Threshold Level
(< 1-11) - Frequency Reached
6 : Auto Restart
01-10 Output Relay TR1 Operation Mode 0
7 : Momentary AC Power Loss
8 : Emergency Stop Mode
9 : Base Block Stop Mode
10 : Motor Overload Protection(OL1)
11 : Drive Overload Protection(OL2)
12 : PID Feedback Signal Loss
13 : Top Count Value Attained

01-11 Frequency Output Setting (Hz) 0.00 ~ 400.00 0.00 *1


01-12 Frequency Detection Range 0.00 ~ 30.00 2.00 *1
xxxx0 : S1 NO xxxx1 : S1 NC
xxx0x : S2 NO xxx1x : S2 NC
01-13 S1~ S5 switch type select xx0xx : S3 NO xx1xx : S3 NC 00000
x0xxx : S4 NO x1xxx : S4 NC
0xxxx : S5 NO 1xxxx : S5 NC
xxxx0 : S6 NO
01-14 S6 switch type select 00000
xxxx1 : S6 NC
※ “NO”: Normal open, “NC”: Normal close.

4-6
2- External terminal analog signal input function group
Function Factory
Description Range/Code Remarks
Code No. Setting
setting AVI ACI
0 0~10V 0~20mA
AVI/ACI analog Input signal type
02-00 1 0~10V 4~20mA 0
select
2 2~10V 0~20mA
3 2~10V 4~20mA
02-01 AVI Signal Verification Scan 1 ~ 100(x 4ms) 50
02-02 AVI Gain (%) 0 ~1000 100 *1
02-03 AVI Bias (%) 0 ~100 0 *1
0 : Positive
02-04 AVI Bias Selection 0 *1
1 : Negative
0 : Positive
02-05 AVI Slope 0 *1
1 : Negative
0 : PID feedback signal
02-06 ACI function Select 0
1 : ACI Bias signal input
02-07 ACI Signal Verification Scan 1 ~ 100(x 4ms ) 50
02-08 ACI Gain (%) 0 ~1000 100 *1
02-09 ACI Bias (%) 0.0 ~100.0 0.0 *1
0 : Positive
02-10 ACI Bias Selection 0 *1
1 : Negative
0 : Positive
02-11 ACI Slope 0 *1
1 : Negative
0 : Output Frequency
1 : Frequency Setting
02-12 Analog Output Mode(FM+) 2 : Output Voltage 0 *1
3 : DC Bus Voltage
4 : Motor Current
02-13 Analog Output FM+ Gain (%) 0 ~1000 100 *1
02-14 Analog Output FM+ Bias (%) 0 ~100 0 *1
0 : Positive
02-15 FM+ Bias Selection 0 *1
1 : Negative
0 : Positive
02-16 FM+ Slope 0 *1
1 : Negative

3-preset Frequency function group


Function Factory
Description Range/Code Remarks
Code No. Setting
0 : common

Preset Speed Control mode (Is uniform time( Acc1/Dec1or Acc2/Dec2)


03-00 0
Selection 1 : special
(is single time Acc0/Dec0~ Acc7/Dec7)

4-7
Function Factory
Description Range/Code Remarks
Code No. Setting
03-01 Preset Speed 0 (Hz) 0.00 ~ 400.00 5.00 Keypad Freq

03-02 Preset Speed1 (Hz) 0.00 ~ 400.00 5.00 *1


03-03 Preset Speed2 (Hz) 0.00 ~ 400.00 10.00 *1
03-04 Preset Speed3 (Hz) 0.00 ~ 400.00 20.00 *1
03-05 Preset Speed4 (Hz) 0.00 ~ 400.00 30.00 *1
03-06 Preset Speed5 (Hz) 0.00 ~ 400.00 40.00 *1
03-07 Preset Speed6 (Hz) 0.00 ~ 400.00 50.00 *1
03-08 Preset Speed7 (Hz) 0.00 ~ 400.00 60.00 *1
03-09~
Reserved Reserved
03-16
03-17 Preset Speed0-Acctime(s) 0.1 ~ 3600.0 10.0 *1
03-18 Preset Speed0-Dectime(s) 0.1 ~ 3600.0 10.0 *1
03-19 Preset Speed1-Acctime(s) 0.1 ~ 3600.0 10.0 *1
03-20 Preset Speed1-Dectime(s) 0.1 ~ 3600.0 10.0 *1
03-21 Preset Speed2-Acctime(s) 0.1 ~ 3600.0 10.0 *1
03-22 Preset Speed2-Dectime(s) 0.1 ~ 3600.0 10.0 *1
03-23 Preset Speed3-Acctime(s) 0.1 ~ 3600.0 10.0 *1
03-24 Preset Speed3-Dectime(s) 0.1 ~ 3600.0 10.0 *1
03-25 Preset Speed4-Acctime(s) 0.1 ~ 3600.0 10.0 *1
03-26 Preset Speed4-Dectime(s) 0.1 ~ 3600.0 10.0 *1
03-27 Preset Speed5-Acctime(s) 0.1 ~ 3600.0 10.0 *1
03-28 Preset Speed5-Dectime(s) 0.1 ~ 3600.0 10.0 *1
03-29 Preset Speed6-Acctime(s) 0.1 ~ 3600.0 10.0 *1
03-30 Preset Speed6-Dectime(s) 0.1 ~ 3600.0 10.0 *1
03-31 Preset Speed7-Acctime(s) 0.1 ~ 3600.0 10.0 *1
03-32 Preset Speed7-Dectime(s) 0.1 ~ 3600.0 10.0 *1

04-start/stop command group


Function Factory
Description Range/Code Remarks
Code No. Setting
0 : Normal Start
04-00 Starting Method Selection 0
1 : Enable Speed Search

0 : braking capacity
04-01 Stopping Method Selection 0
1 : Coast to stop
0 : Stop Button Enabled
04-02 Keypad Stop Button 0
1 : Stop Button Disabled

4-8
Function Factory
Description Range/Code Remarks
Code No. Setting
0 : Momentary Power Loss and Restart
disable
1 : Momentary power loss and restart

Momentary Power Loss and enable


04-03 0
Restart 2 : Momentary power loss and restart
enable while CPU is operating.
(According to the capacity of DC
power)
Momentary Power Loss
04-04 0.0 - 2.0 0.5
Ride-Thru Time (Seconds)
0 : Enable Speed Search
04-05 Auto Restart Method 0
1 : Normal Start
04-06 Auto Restart Delay Time (Seconds) 0.0 - 800.0 0.0
04-07 Number of Auto Restart Attempts 0-10 0
0 : Enable Reset Only when Run
Command is Off
04-08 Reset Mode Setting 0
1 : Enable Reset when Run
Command is On or Off
0 : Enable Direct running after power
up
04-09 Direct Running After Power Up 1
1 : Disable Direct running after power
up
04-10 Delay-ON Timer (Seconds) 1.8 ~300.0 1.0
Kinetic Energy 0.0 : Disable
04-11 0.0
Back-up Deceleration Time 0.1~25.0:KEB Deceleration Time
04-12 Lower Limit of Power Voltage Detect 150.0~210.0/300.0~420.0 190.0/380.0
04-13 DC Injection Brake Level (%)@start 0.0~150.0 50.0
DC Injection Brake Time
04-14 0.0~25.5 0.5
(Seconds) @start
DC Injection Brake Start
04-15 0.10~10.00 1.50
Frequency (Hz) @stopped
DC Injection Brake
04-16 0.0~150.0 50.0
Level(%)@Stopped
DC Injection Brake Time
04-17 0.0~25.5 0.5
(Seconds) @stopped

05-V/F command group


Function Factory
Description Range/Code Remarks
Code No. Setting
Volts/Hz Curve Modification
05-00 0 ~ 30.0 10.0 *5
(Torque Boost) (%)
05-01 Motor No Load Current(Amps AC) ----- *5
4-9
Function Factory
Description Range/Code Remarks
Code No. Setting
05-02 Motor rated Slip Compensation (%) 0.0 ~ 100.0 0.0 *5
220V series : 170.0 ~ 264.0 *5
05-03 v/f max voltage
440V series : 323.0 ~528.0
05-04 Maximum Frequency (Hz) 0. 20 ~ 400.00 50.00/60.00 *5
05-05 Maximum Frequency VoltageRatio (%) 0.0 ~ 100.0 100.0 *5
05-06 Medium Frequency 2(Hz) 0.10 ~ 400.00 25.00/30.00 *5
05-07 Medium Frequency Voltage Ratio2 (%) 0.0 ~ 100.0 50.0 *5
05-08 Medium Frequency1 (Hz) 0. 10 ~ 400.00 10.00/12.00 *5
05-09 Medium Frequency Voltage Ratio1 (%) 0.0 ~ 100.0 20.0 *5
05-10 Minimum Frequency (Hz) 0. 10 ~ 400.00 0.50/0.60 *5
05-11 Minimum Frequency VoltageRatio (%) 0.0 ~ 100.0 1.0 *5
05-12 V/F start Frequency 0.00 ~ 10.00 0.00 *5

06-Motor parameter group


Function Factory
Description Range/Code Remarks
Code No. Setting
06-00 Motor Rated Voltage (VAC) ----- *4
06-01 Motor Rated Current (Amp AC) ----- *4
06-02 Motor Rated Power (kW) ----- *4

06-03 Motor Rated Speed (RPM) ----- *4

06-04 Motor Rated Frequency (Hz) ----- *4


06-05 Reserved Reserved
06-06 Torque Boost Gain (Vector) 0~ 600 *3*4
Slip Compensation Gain
06-07 0 ~ 600 *3*4
(Vector)
06-08 Reserved Reserved
06-09 Reserved Reserved
06-10 Reserved Reserved
06-11 Low-frequency compensation Gain 0 ~ 100 30

4-10
07-Protection function group
Function Factory
Description Range/Code Remarks
Code No. Setting
xxxx0 : Enable Trip Prevention During
Acceleration
xxxx1 : Disable Trip Prevention During
Acceleration
xxx0x : Enable Trip Prevention During
Deceleration
xxx1x : Disable Trip Prevention During
07-00 Trip Prevention Selection Deceleration 00000
xx0xx : Enable Trip Prevention in Run Mode
xx1xx : Disable Trip Prevention in
Run Mode
x0xxx : Enable over voltage Prevention in
Run Mode
x1xxx : Disable over voltage Prevention in
Run Mode
Inverter
Trip Prevention Level During Rated
07-01 50 ~ 200 200
Acceleration (%) Current
200%
Inverter
Trip Prevention Level During Rated
07-02 50 ~ 200 200
Deceleration (%) Current
200%
Inverter
Trip Prevention Level In Run Mode Rated
07-03 50 ~ 200 200
(%) Current
200%
over voltage Prevention Level in Run 350.0 VDC ~ 390.0 VDC 380.0/
07-04
Mode 700.0 VDC ~ 780.0 VDC 760.0
0 : Enable Electronic Motor
Electronic Motor Overload Protection Overload Protection
07-05 1
Operation Mode 1 : Disable Electronic Motor
Overload Protection
0 : Electronic Motor Overload Protection Set
for Non-Inverter Duty Motor
07-06 Motor type Selection 0
1 : Electronic Motor Overload Protection Set
for Inverter Duty Motor
0 : Constant Torque (OL =103 %)
Motor Overload Protection (150 % for 1 Minute)
07-07 0
Curve Selection 1 : Variable Torque (OL = 113 %)
(123 % for 1 Minute)
0 : Coast-to-Stop After Overload
Operation After Overload Protection is Protection is Activated
07-08 0
Activated 1 : Drive Will Not Trip when Overload
Protection is Activated (OL1)
0 : Disable Over torque Operation
1 : Enable Over torque Operation
Over torque Detection Selection
07-09 Only if at Set Frequency 0
(OL3)
2 : Enable Over torque Operation
while the Drive is in Run Mode
4-11
Function Factory
Description Range/Code Remarks
Code No. Setting
0 : Coast-to-Stop After Over
Operation After Over torque Detection torque is Activated
07-10 1
is Activated 1 : Drive will Continue to Operate After
Over torque is Activated (OL3)
07-11 Over torque Threshold Level(%) 30 ~ 300 160
07-12 Over torque Activation Delay Time (S) 0.0 ~ 25.0 0.1
0 : Auto (Depends on temp.)
OH over heat Protection ( cooling fan 1 : Operate while in RUN mode
07-13 1
control) 2 : Always Run
3 : Disabled

08-Communication function group


Function Factory
Description Range/Code Remarks
Code No. Setting
Assigned Communication
08-00 1~ 32 1 *2*4
Station Number
0 : RTU code
08-01 RTU code /ASCII code select 0 *2*3
1 : ASCII code
0 : 4800
1 : 9600
08-02 Baud Rate Setting (bps) 2 *2*3
2 : 19200
3 : 38400
0 : 1 Stop Bit
08-03 Stop Bit Selection 0 *2*3
1 : 2 Stop Bits
0 : Without Parity
08-04 Parity Selection 1 : With Even Parity 0 *2*3
2 : With Odd Parity
0 : 8-Bits Data
08-05 Data Format Selection 0 *2*3
1 : 7-Bits Data
Communication time-out
08-06 0.0 ~ 25.5 0.0
detection time
0 : Deceleration to stop
(00-10 : Deceleration time 1)
Communication time-out 1 : Coast to stop
08-07 0
operation selection 2 : Deceleration to stop
(10-06 : Deceleration time 2)
3 : continue operating
08-08 Err6 fault tolerance times 1 ~ 20 3
08-09 Drive Transmit Wait Time(ms) 1 ~ 16(×4ms) 2

4-12
09-PID function group
Function Factory
Description Range/Code Remarks
Code No. Setting
0 : Disabled
1 : Bias D Control
2 : Feedback D Control
09-00 PID Mode Selection 0
3 : Bias D Reversed Characteristics Control
4 : Feedback D Reversed Characteristics
Control
09-01 Feedback Gain coefficient 0.00 ~ 10.00 1.00 *1
09-02 Proportional Gain (%) 0.0 ~ 10.0 1.0 *1
09-03 Integration Time (S) 0.0 ~ 100.0 10.0 *1
09-04 Differentiation Time (S) 0.00 ~ 10.00 0.00 *1
0 : Positive
09-05 PID Offset 0 *1
1 : Negative
09-06 PID Offset Adjust (%) 0 ~ 109 0 *1
09-07 PID Output Lag Filter Time(S) 0.0 ~ 2.5 0.0 *1
0 : Disabled
1 : Enabled - Drive Continues to
09-08 Feedback Loss Detection Mode Operate After Feedback Loss 0
2 : Enabled - Drive "STOPS"
After Feedback Loss
Feedback Loss Detection Level
09-09 0 ~100 0
(%)
Feedback Loss Detection Delay
09-10 0.0 ~ 25.0 1.0
Time (S)
09-11 Integration Limit Value (%) 0 ~ 109 100 *1
09-12~09-13 Reserved Reserved
Allowable Integration Error
09-13 Margin (Units) 0 ~100 0
(1 Unit = 1/8192)
09-14 Sleep Frequency Level 0.00 ~ 400.00 0.00
09-15 Sleep Function Delay Time 0.0 ~ 25.5 0.0
09-16 Wake up frequency Level 0.00 ~ 400.00 0.00
09-17 Wake up function Delay Time 0.0 ~ 25.5 0.0

10-Assistant function group


Function Factory
Description Range/Code Remarks
Code No. Setting
0 : Reverse command is enabled
10-01 Reverse operation control 0
1 : Reverse command is disabled
0 : ‘Enter’ must be pressed after
Frequency change with Up/Down Keys on
Keypad Operation with keypad.
10-02 0
Up/Down Keys in Run Mode 1 : Frequency will be changed
directly when Up/Down Keys
are Pressed
10-03 Carrier Frequency (kHz) 1~ 12 5

4-13
Function Factory
Description Range/Code Remarks
Code No. Setting
0 : Carrier mode0
3-phase PW M modulation
1 : Carrier mode1
10-04 Carrier mode Selection 1
2-phase PW M modulation
2 : Carrier mode2
2-phase randomized PW M modulation
10-05 Acceleration Time 2 (MFIT) (s) 0.1 ~ 3600.0 10.0 *1
10-06 Deceleration Time 2 (MFIT) (s) 0.1 ~ 3600.0 10.0 *1
10-07 S-Curve Acc/Dec 1 (s) 0.0 ~ 4.0 0.2
10-08 S-Curve Acc/Dec 2(s) 0.0 ~ 4.0 0.2
10-09 S-Curve Acc/Dec 3 (s) 0.0 ~ 4.0 0.2
10-10 S-Curve Acc/Dec 4 (s) 0.0 ~ 4.0 0.2
10-11 Skip Frequency 1 (Hz) 0.00 ~ 400.00 0.00 *1
10-12 Skip Frequency 2 (Hz) 0.00 ~ 400.00 0.00 *1
10-13 Skip Frequency 3 (Hz) 0.00 ~ 400.00 0.00 *1
10-14 Skip Frequency Bandwidth (±Hz) 0.00 ~ 30.00 0.00 *1
Carrier Frequency 0 : disabled
10-15 0
Reduction by temperature raising 1 : enabled
0 : AVR function disabled
10-16 Auto Voltage Regulation (AVR) 1
1 : AVR function enabled
10-17 Count Down Completion 0 ~9999 0

11-Keypad display group


Function Factory
Description Range/Code Remarks
Code No. Setting
xxxx0 : Disable Motor Current Display
xxxx1 : Enable Motor Current Display
xxx0x : Disable Motor Voltage Display
xxx1x : Enable Motor Voltage Display
xx0xx : Disable Bus Voltage Display
11-00 Display Mode 00000 *1
xx1xx : Enable Bus Voltage Display
x0xxx : Disable temperature Display
x1xxx : Enable temperature Display
0xxxx : Disable PID feedback Display
1xxxx : Enable PID feedback Display
Custom Units (Line Speed)
11-01 0~65535 1800 *1
Value
0 : Drive Output Frequency is Displayed
1 : Line Speed is Displayed in Integer (xxxxx)
2 : Line Speed is Displayed with One Decimal Place
Custom Units (Line Speed) (xxxx.x)
11-02 0 *1
Display Mode 3 : Line Speed is Displayed with Two Decimal
Places (xxx.xx)
4 : Line Speed is Displayed with Three Decimal
Places (xx.xxx)
11-03-06 Reserved Reserved
0 : Disable data Display
11-07 Counter display 0
1 : Enable data Display

4-14
12-User parameter group
Function Factory
Description Range/Code Remarks
Code No. Setting
12-00 Drive Horsepower Code ----- *3
12-01 Software Version ----- ----- *3

12-02 Fault Log (Last 3 Faults) ----- *3

Accumulated Operation Time1


12-03 0~23 ----- *3
(Hours)
Accumulated Operation Time2
12-04 0~65535 ----- *3
(Days)
0 : Time Under Power
12-05 Accumulated Operation Time Mode 0 *3
1 : Run Mode Time Only
1150 : Reset to the 50Hz factory setting
12-06 Reset Drive to Factory Settings ----
1160 : Reset to the 60Hz factory setting
0 : Enable all Functions
1 : 03-01~03-08 cannot be changed
12-07 Parameter Lock 2 : All Functions cannot be changed 0
Except 03-01~ 03-08
3 : Disable All Function
12-08 Parameter password 00000~65535 00000

13-Auto Run function group


Function Factory
Description Range/Code Remarks
Code No. Setting
0 : Disabled.
1 : Single cycle. (Continues to run from the
unfinished step if restarted).
2 : Periodic cycle. (Continues to run from the
unfinished step if restarted).
Auto Run( sequencer) mode 3 : Single cycle, then holds the speed Of final step to
13-00 0
selection run.(Continues to run from the unfinished step if
restarted).
4 : Single cycle. ( starts a new cycle if restarted).
5 : Periodic cycle. ( starts a new cycle if restarted).
6 : Single cycle, then hold the speed of final step to run.
( starts a new cycle if restarted).
Auto _ Run Mode
13-01 0.00 ~ 400.00 (Hz) 0.00
Frequency Command 1
Auto _ Run Mode
13-02
Frequency Command 2
Auto _ Run Mode
13-03
Frequency Command 3
Auto _ Run Mode
13-04
Frequency Command 4
Auto _ Run Mode
13-05
Frequency Command 5
Auto _ Run Mode
13-06
Frequency Command 6

4-15
Function Factory
Description Range/Code Remarks
Code No. Setting
Auto _ Run Mode
13-07
Frequency Command 7
13-08~
Reserved Reserved
13-15
Auto_ Run Mode Running
13-16
Time Setting 0
Auto_ Run Mode Running
13-17
Time Setting 1
Auto_ Run Mode Running
13-18
Time Setting 2
Auto_ Run Mode Running
13-19
Time Setting 3 0.0 ~ 3600.0 (second)
0.0
Auto_ Run Mode Running
13-20
Time Setting 4
Auto_ Run Mode Running
13-21
Time Setting 5
Auto_ Run Mode Running
13-22
Time Setting 6
Auto_ Run Mode Running
13-23
Time Setting 7
13-23~
Reserved Reserved
13-31
Auto_ Run Mode Running
13-32
Direction 0
Auto_ Run Mode Running
13-33
Direction 1
Auto_ Run Mode Running
13-34
Direction 2
Auto_ Run Mode Running
13-35 0: stop
Direction 3 0
1: forward
Auto_ Run Mode Running
13-36 2: reverse
Direction 4
Auto_ Run Mode Running
13-37
Direction 5
Auto_ Run Mode Running
13-38
Direction 6
Auto_ Run Mode Running
13-39
Direction 7
※Notes : *1 Can be modified during run
*2 cannot be modified while communication is active
*3 do not change while making factory setting
*4 the parameter will be changed by replacing model
*5 only available in V/F mode

4-16
4.4 Parameter Function Description
Group0- The basic parameters group

00-00 : Control Mode 0 : V/F mode 1 : Vector mode (General Purpose)


To select the appropriate vector control mode or V/F mode according to the load characteristics.
1. If V/F mode is selected, please set parameters, group5 to comply with the load features.
Vector is best suited to control the general load or rapidly-changed torque load.
00-01 : Volts/Hz Patterns (V/F) = 0 ~ 18
1.00-01= 0 ~17, V / F Pattern. (Refer to group5)
2.00-01=18,Flexiable V/F pattern, programmable according to parameters 05-04~05-09.
00-02 :Motor rotation = 0 : forward 1 : reverse
Note:when10-01is set to 1, 00-02 is not set to1
00-03 : Main Run Command Source Select
=0 : Keypad =1 : External Run/Stop Control
=2 : Communication
00-04 : Alternative Run Command Source Select
=0 : Keypad =1 : External Run/Stop Control
=2 : Communication
1. 00-03/00-04=0, the inverter is controlled by the keypad.
2. 00-03/00-04=1, the inverter is controlled by the external terminals, and the Stop key for emergency
stop is operational. (Refer to 04-02 description)
※Note: 00-03/00-04=1,please refer to parameter 04-03,04-04,04-06,04-07 for detailed description
in order to ensure safety of operators and machines.
3. 00-03/00-04=2, the inverter is controlled by Communication.
4. When 01-00 ~ 01-05 is set 10(Main/Alt Control Signal Select),if the terminal is ON, the inverter is
controlled by parameter 00-03,if the terminal is Off, the inverter is controlled by parameter 00-04.
00-05 : Main Frequency Command Source Select
=0 : UP/DOWN of Keypad
=1 : Potentiometer on Keypad
=2 : External AVI Analog Signal Input
=3 : External Up/Down Frequency Control
=4 : Communication setting Frequency
00-06 : Alternative Frequency Command Source Select
=0 :UP/DOWN of Keypad
=1 : Potentiometer on Keypad
=2 : External AVI Analog Signal Input
=3 : External Up/Down Frequency Control
=4 : Communication setting Frequency
1. Please refer to description of parameter group 01-00 ~ 01-05 (multifunction input terminals) for
the function Up/Down terminal.
2. The priority in reading frequency is Jog> preset speed>▲▼ on keypad or Up / Down or
communication control.
3. When 01-00 ~ 01-05 is set 14(Main/Alt Frequency Command Select),if the terminal is ON, the
inverter frequency command is set by parameter 00-05,if the terminal is Off, the inverter
frequency command is set by parameter 00-06.

4-17
00-07 : Frequency Upper limit(Hz) 0.01 ~ 400.00
00-08 : Frequency Lower limit(Hz) 0.01 ~ 399.99

Internal frequency
00-07 (upper frequency limit)

00-08 (lower frequency


(Note)

Figure 4-4 Frequency reference limits


※Note: When 00-08 = 0 Hz and frequency command is 0 Hz; the inverter will stop at 0 speed.
When 00-08 > 0 Hz and frequency command ≦00-08, the inverter will output the
00-08 preset value.

00-09 : Acceleration time 1 (s) =0.1 ~ 3600.0


00-10 : Deceleration time 1 (s) =0.1 ~ 3600.0

1. Formula for calculating acceleration and deceleration time: The denominator is base on the

rated frequency of motor.


0 0- 09( or10- 05)× p reset freq uency
acc el er at i on t i me =
0 6 − 04
deceleration time = 0 0- 10( or 10- 06)× pr eset f r equency
06 − 04
2. When 01-00~01-05 is set 07 (the second acceleration and deceleration time),the first
acceleration/ deceleration or the second acceleration/ deceleration/ will be set by OFF or
ON the external input terminal.
3. When 01-00~01-05 is set 05/06 (Jog),Jog run is controlled by external terminals.
The acceleration and deceleration action will be at Jog acceleration and deceleration time.
The list setting:
Function Acc/ Dec time 1 Acc/ Dec time 2 JOG Acc/Dec time
(00-09/0-10) (10-05/10-06) (00-13/00-14)
preset value 00-05/00-06 00-05/00-06 Run at 00-12
determines the output determines the Jog frequency
frequency output frequency
01-00 ~ 01-05=05/06
Off Off On
Jog command
01-00 ~ 01-05=07
Off On Off
Toggle Acc/Dec time

4-18
2. 10-01=1, the reverse command is unavailable

00-11 : Operation modes for external terminals


0 : Forward/stop-reverse/stop
1 : Run/stop-forward/reverse
2 : 3-wire control mode -run/stop
1.) When operation command 00-03/00-04 = 0 (external terminal), 00-11is valid.
2.) When operation command 00-03/00-04 = 1 (external terminal control), the stop button for
emergency is available. (Refer to04-02 for detail description).
3.) That both forward and reverse commands are ON will be treated as STOP.

1. 00-11 = 0, Control mode is as below: 2. 00-11 = 1, Control mode is as below:

Figure 4-5 Terminal Board Drive Operation Modes


3. 00-11 = 2, Control mode is as below:

S1 (RUN)
S2 (STOP)
S3 (FWD/REV)
COM (0V)

Figure 4-6 3-Wire start/stop wiring

4-19
Figure 4-7 Drive start/stop operation sequences
※Note: 1.As 3 wire control mode is selected, the terminal S1, S2 and S3 is not controlled

by 01-00, 01-01 and 01-02.


00-12 : Jog Frequency (Hz) =1.00 ~ 25.00
00-13 : Jog Acceleration Time (MFIT) (S) =0.1 ~ 25.5
00-14 : Jog Deceleration Time (MFIT) (S) =0.1 ~ 25.5
Example:When 1-00(S1)=5,1-01(S2)=6 (Jog), Jog run is controlled by external terminals, S1 on is
Jog-forward, S2 on is Jog-reverse.

Group1- External terminal digital signal input function group

Multifunction input terminals (TM2 S1~S6) controlling:


01-00~05: 0 : Forward/Stop Command
1 : Reverse/Stop Command
2 : Preset Speed unit 0 (3-02)
3 : Preset Speed unit 1 (3-03)
4 : Preset Speed unit 2 (3-05)
5 : JOG Forward Command
6 : JOG Reverse Command
7 : Acc/Dec time 2
8 : Emergency Stop
9 : Base Block
10 : Main/sub Control Signal Select
11 : Acc/Dec Disabled
4-20
12 : Up Command
13 : Down Command
14 : Main/sub Control Signal Select
15 : PID Function Disabled
16 : Integration Value Resets to Zero
17 : Reset
18 : KEB function
19 : Auto _ Run Mode
20 : Counter Trigger Signal
21 : Counter Reset
A. The terminals S1- S6 on terminal block (TM2) are multifunction input terminals. The 22 functions
shown above can be set for these terminals.
B. Function Description for 1-00~05:

1. 01-00~05=0/1(Forward/Reverse/Stop)
As forward command is ON, the inverter runs and stops when the command is OFF. The 1-00
factory setting is forward.
As reverse command is ON, the inverter runs and stops when the command is OFF. The 1-01
factory setting is reverse.
2. 01-00~05=2/3/4 (Frequency Command 1/2/4 at 3-02/3-03/3-05)
When External multifunction input terminals are ON, the inverter is operates at the preset speed and
the duration is determined by the time the input is ON. The corresponding preset frequency will be
according to preset value of parameters 3-01 to 3-07 and in relation to the operation of input
terminals 1 to 3. as shown in the table below:
Output frequency Multifunction terminal 3 Multifunction terminal 2 Multifunction terminal 1
preset value Preset value =4 Preset value =3 Preset value =2
3-01 0 0 0
3-02 0 0 1
3-03 0 1 0
3-04 0 1 1
3-05 1 0 0
3-06 1 0 1
3-07 1 1 0
3-08 1 1 1

3. 01-00~05=5/6(Forward/ Reverse JOG)


When Jog operation, is selected, the inverter operates at the Jog acceleration and
deceleration times. The corresponding jog frequency parameter is shown below:
The priority order of frequency : Jog Speed→Preset Speed→Keypad frequency or
external frequency signal
4. 01-00~05=7 (Acc/Dec time selection)
This input selects the acceleration 1/ deceleration 1 or acceleration 2/ deceleration 2.
5. 01-00~05=8 : External Emergency Stop.
The inverter will decelerate to stop by 10-06 setting and Flash E.S as the emergency stop signal
is received regardless of 04-01 setting. After the emergency stop signal is removed, turn the
RUN switch OFF and then ON again, or press the run key in keypad mode, the inverter will
restart again up and ramps up to the command frequency.

4-21
If the emergency signal is released before the inverter stops completely, the inverter still carries
out the emergency stop. The 01-09/01-10 determines the action of the error terminal. If
01-09/01-10=0: the fault is not enabled when the external emergency signal input. If
01-09/01-10=8, the fault is actuated when the emergency signal input.
6. 01-00~05=9 : Base Block
The inverter immediately stops output, and the motor does a Coast with flashing B.B.

8. 01-00~05=10 : Main/sub Control Signal Selection


When External multifunction input terminals are off, the inverter is operated by 00-03.
When External multifunction input terminals are on, the inverter is operated by 00-04.
9. 1-00~05=11 : Disable acceleration and deceleration
The acceleration and deceleration action is unavailable until the disable signals are released.
The action is illustrated in the graph below:
Note : Operation Switch is OFF, the command of disable
Operation
Signal

Disable
ACC/DEC

Output
Frequency Figure 4-8 Acceleration and deceleration Prohibit

10. 1-00~05=12, 13: UP/DOWN Function (Actual ACC/DEC time is based on the setting) :
(1) 00-05/00-06 = 3 to use the UP/DOWN Function. The other frequency signals are ignored.
(2)Set 01-07=0 and 01-08=0. The inverter accelerates to the preset value of 03-01 when in
RUN, and then it maintains a constant speed. As the inverter receives either the UP/DOWN
command, it will accelerate / decelerate until the command is released. The inverter runs at
the speed setting at the time of release. The inverter will ramp stop or Free-Fun stop which
is determined by the 04-01 as long as the inverter receives the STOP command. The
frequency at Stop time will be stored in03-01. The UP/DOWN KEY is invalid when the
inverter is stopped. It is necessary to use the Keypad to modify the preset parameters.
(3)Set 01-08 = 1, the inverter will operate from 0Hz when the operation terminal is ON. The
action of UP/DOWN is the same as above. The inverter will ramp stop or free-run stop as
determined by 04-01 setting when it receives the Stop Command. The next operation will
start at 0 Hz.
(4)UP/Down Signals simultaneously pressed are invalid
(5)01-07≠ 0, the inverter accelerates to the setting of 03-01 and maintains speed. When the
UP/Down terminal is on, setting frequency is the value 03-01±01-07, and the inverter will
accelerate/ decelerate to frequency 03-01. The upper frequency limit and lower frequency
limit also restrict the operation. If the signal of UP/ DOWN is maintained over 2 seconds,
the inverter will begin to accelerate/ decelerate. If 01-07=0, the operation is the same, until
the UP/ DOWN signal is released. Please refer to the time diagram of 01-07.

4-22
11. 1-00~05=14 Main/sub Frequency Command Selection
When External multifunction input terminals are off, the inverter Frequency Command is operated
by 00-05.
When External multifunction input terminals are on, the inverter Frequency Command is operated
by 00-06.
12. 01-00~05=15(PID Function Disable)
When the PID Function Disable is ON, PID is not controlled by 09-00.
13. 01-00~05=16 (Integration Value Resets to Zero)
When the multifunction terminal 01-00~05 is set at 16 and the input terminal is on , the
Integration Value of PID Resets to Zero .
14. 01-00~05=17(Reset Command)
The Reset command is same as the Reset Key on the panel. When the command is OFF, the
inverter does not respond.
15. 01-00~05=18 (Power Source Detect for KEB)
Please refer to 4-11description.
16. 01-00~05=19(Auto _ Run Mode)
The function of auto-run is like a simple built-in PLC function, when the extermal terminal
function is set to 19, and turns on. Autorun function will be executed according to group
13.( Please refer to group13)
17. 01-00~05=20(Counter Trigger Signal)
when the extermal terminal s6 is set a function of 20,after turning it on then off once the counter
value increase 1.

Indication value c0000 c0001 c0002 c0003 c0004 c0005 c0001 c0002
11-07=1
Counter trigger signal
Multi-function input termin
1.5ms
The trigger timing can't be less than
1.5ms.

Signal output with10-17


counter value is attained. 10-17=5

In vector mode, the extermal terminal S6 function of "counter trigger signal input" is disabled.
18. 01-00~05=21(Counter Reset)
When anyone of the extermal terminals S1~S6 is set a function of 21 and turned on, the counter
value will be cleared, and display "c0000", only after this signal turns off, the inverter can
receive trigger signal and count up.
Digital /Analog input signal scan times:
01-06: Multifunction terminal S1~S6 confirm the scan times (x 4ms),1~200 times
1. TM2 terminal is used for scanning. If there are the same signals continuously input for N times, the
inverter will treat the signal as normal. During the signal evaluation, if the scan times are less than N,
the signal will be treated as noise.
2. Each scan period is 4ms.
3. The user can specify the scan times interval duration according to the noise environment. If the
noise is serious, increase the value of 01-06, however the response will be slower.

4-23
Step of Up/Down Function (Hz):
01-07: Up/Down (Hz) 0.00 ~ 5.00
There are two modes covered below:
1 .01-07 = 0.00, the operation is just as the original one. When the UP terminal is ON, the frequency
increases while the DOWN terminal is ON, the frequency decreases. (Refer to the following
graph).

Figure 4-9 UP/DOWN original mode example


2. 01-07 = 0.01 to 5.00, and UP/ DOWN terminal ON, is equivalent to a step increase/ decrease at
the increment frequency in 01-07. If UP/DOWN is pressed over 2 seconds, the original
UP/DOWN mode is restored (Please refer to the following diagram)

Figure 4-10 UP/DOWN with incremental steps

Stop Mode Using Up/Down:


01-08 : Up/Down keep Frequency mode
0 : When Up/Down is used, the preset frequency is held as the inverter stops,
and the UP/Down function is disabled.
1 : When Up/Down is used, the preset frequency is reset to 0 Hz as the inverter stops.
2 : When Up/Down is used, the preset frequency is held as the inverter stops, and the
UP/Down is available.
1. 01-08=0 : the inverter will accelerate to the speed set in parameter 03- 01 as receiving the Run
command and run at such certain speed. The inverter begins to accelerate (decelerate) as the UP
(Down) terminal is energized. The inverter will hold the speed as the UP/DOWN command
released. When the Run Signal releases, the inverter will ramp stop or stop which determined by
the 04-01. It will store the frequency when the run signal is removed. UP/DOWN keys are idle
4-24
when the inverter is stopped. The keypad is available to modify the preset frequency (03-01). If
1-08=2, the UP/Down is available as the inverter stops.

2. 01-08=1 : as the Run terminal is energized, the inverter operates from 0 Hz, the Function of
UP/DOWN is same as the above description. When the Run signal is released, the inverter will
ramp stop or stop output (determined by 04-01) to 0 Hz. The next run command will always
begin from 0 Hz.

Multifunction output terminals control:


01-09 : Output Relay RY1 Operation Mode (RC,RB,RA terminal )
01-10 : Output Relay TR1 Operation Mode (SYN+, SYN- terminal)
0 : Run
1 : Fault
2 : Frequency Reached
3 : Set Frequency (01-11 ±01-12)
4 : Frequency Threshold Level (> 01-11) - Frequency Reached
5 : Frequency Threshold Level (< 01-11) - Frequency Reached
6 : Auto-restart
7 : Momentary AC Power Loss
8 : Emergency Stop Mode
9 : Base Block Stop Mode
10 : Motor Overload Protection
11 : Drive Overload Protection
12 : Over-torque Threshold Level
13 :Top Count Value Attained
14 :Preliminary Counter Value Attained
01-11 : Frequency Reached Output Setting =0.00 ~ 400.00Hz
01-12 : Frequency Detection Range =0.00 ~ 30.00Hz

01-09/10= 2:
The preset frequency is reached (± 01-12)

Figure 4-11Frequency reached example

4-25
01-09/10= 3:
Arbitrary frequency consistency Fout = 01-11 ±01-12

Figure 4-12 Frequency within specified range example

01-09/10= 4 : Frequency detection Fout > 01-11

Figure 4-13 Frequency outside of range example

4-26
01-09/10= 5 : Frequency detection Fout < 01-11

Figure 4-14 Frequency at or below specified range example

1-09/10=12 : over torque detection

Figure 4-15 Over torque detection example


01-09/10=13
Terminal output is activated when counter reaches the Top Count Value.

01-13: S1~ S5 switch type select


xxxx0 : S1 NO xxxx1 : NC
xxx0x : S2 NO xxx1x : NC
xx0xx : S3 NO xx1xx : NC
x0xxx : S4 NO x1xxx : NC
0xxxx : S5 NO 1xxxx : NC
01-14: S6 switch type select
xxxx0 : S6 NO
xxxx1 : S6 NC
※Note: “NO” : Normal open, “NC” : Normal close.
The switches type is decided by 01-13/01-14,
Because of different types of switches, select switches type is necessary.
If set 01-13=0 0 0 0 0, means S1~S5 types of switches is Normal open, otherwise, if each bit of
01-13 is set to “1”, types of switches is Normal close.

Don’t set 00-03/00-04=1, before you set 01-13, 01-14 (external terminal controlled)

4-27
Group2- External terminal analog signal input function group

02-00 : AVI/ACI analog Input signal type select


=0 : AVI 0~10V, ACI 0~20mA
=1 : AVI 0~10V, ACI 4~20mA
=2 : AVI 2~10V, ACI 0~20mA
=3 : AVI 2~10V, ACI 4~20mA

02-01 : AVI signal verification Scan Time 1~100 (×4ms)


02-02 : AVI Gain(%) 0 ~ 1000
02-03 : AVI Bias(%) 0.0 ~ 100.0
02-04 : AVI Bias Selection 0 : positive 1 : Negative
02-05 : AVI Slope 0 : positive 1 : Negative

02-06 : ACI function Select


=0 : PID feedback signal =1 : ACI Bias signal input

1. 02-06=0 (PID feedback input)


When 02-06 is set 0 means the PID feedback input terminal is controlled by the setting of 09-00.
2. 02-06=1 (Bias Input)
ACI To regulate the Offset of the Keypad VR or AVI analog input, only the signal of 0~20
mAor4~20mA .
Hz
Freq upper limit
02-06=1function
00-07

0V 10
AVI+ACI

02-07 : ACI signal verification Scan Time 1~100 (× 4ms)


02-08 : ACI Gain(%) 0 ~ 1000
02-09 : ACI Bias(%) 0 .0~ 100.0
02-10 : ACI Bias Selection 0 : positive 1 : Negative
02-11 : ACI Slope 0 : positive 1 : Negative
Note : When 02-06 is set to 1, settings of 02-07~02-11 will not be effective.
Example:
The setting of figure 4-18A: The setting of figure 4-18B:
2-02 2-03 2-04 2-05 2-02 2-03 2-04 2-05
2-09 2-09
/2-08 /2-09 /2-10 /2-11 /2-08 /2-09 /2-10 /2-11
A 100% 50% 0 0 100% C 100% 50% 0 1 100%
B 100% 0% 0 0 100% D 100% 0% 0 1 100%

Bias Hz
Bias Hz
100% 60Hz Upper Frequency 100% 60Hz Upper Frequency Limit
A (00-07=60) C (00-07=60)
50% 30Hz
50% 30Hz
B
0Hz V D
0V 5V 10V 0Hz V
0V 5V 10V
(0mA) (20mA)
(0mA) (20mA)
4-28
The setting of figure 4-18C : The setting of figure 4-18D :
2-02 2-03 2-04 2-05 2-02 2-03 2-04 2-05
2-09 2-09
/2-08 /2-09 /2-10 /2-11 /2-08 /2-09 /2-10 /2-11
E 100% 20% 1 0 100% F 100% 50% 1 1 100%

Hz Hz

60Hz Upper Frequency Limit 60Hz


Upper Frequency Limit
(00-07=60) (00-07=60)
30Hz 30Hz
Bias Bias F
0% E
0Hz V -0% 0Hz V
-50% 2V 5V 10V
10V -50%
(4mA) (20mA) (20mA)
-100% -100%

Figure 4-16 Analog scaling examples


1) The inverter reads the average value of A/D signals once per (02-01/02-07 x 4ms). Set scan
intervals according to possible noise interference in the environment. Increase 02-01/02-07 in an
environment with noise interference, but the response time will increase accordingly.

Multifunction analog output control


02-12 :Analog Output Voltage Mode
0 : Output frequency 1 : Frequency Setting
2 : Output voltage 3 : DC Bus Voltage 4 : Output current
02-13 : FM+ Gain(%) 0 ~ 1000
02-14 : FM+ Bias(%) 0 .0~ 100.0
02-15 : FM+ Bias Selection 0 : positive 1 : Negative
02-16 : FM+ Slope 0 : positive 1 : Negative
1. The multifunction analog output terminal of the terminal block , is 0~10Vdc analog output. The
output type is determined by the02-12. The output voltage level can be scaled by parameter 02-13 to
suit external meters and peripherals.
Note: the max output voltage is 10V due to hardware of the circuit. Use only devices that require a
maximum of 10V signal.
2. FM+ Function Description
10V

0
Xmax
Figure 4-17 Multifunction analog output
2-12=0 Output Frequency Xmax= upper frequency limit
=1 frequency setting upper frequency limit
=2 Output Voltage Motor Rated Voltage (VAC)
=3 DC Bus Voltage 220V: 0~400V
440V: 0~800V
=4 Motor Current 2 times rated current of inverter
Note: 02-13~02-16, refer to Figure 4-19 Analog scaling examples.
4-29
Group3- preset Frequency function group

03-00 : Preset Speed Control mode Selection


=0 : common Is uniform time( Acc1/Dec1or Acc2/Dec2)
=1 : Special (is single time Acc0/Dec0 ~ Acc7/Dec7)
Setting frequency 03-01~03-08 :
Preset Speed 0 ~ Preset Speed 7(Hz) : =0.00 ~ 400.00
Setting time 03-17~03-32 :
Preset Speed 0~7 Acceleration time(second) : =0.1 ~ 3600.0
Preset Speed 0~7 Deceleration time(second) : =0.1 ~ 3600.0
1. When 03-00 is set to 0, Acc-time (Dec-time) is determined by the 00-09/00-10(10-05/10-06).
2. When03-00 is set to 1, Acc-time (Dec-time) is determined by the03-01~03-08.
Function Description:

1) Formula for calculating acceleration and deceleration time:The denominator is base on the
rated frequency of motor (06-04).
Acctime parameter ×preset frequency
Actual Acctime =
06 −04
Dectime parameter×pr eset f r equency
Actual Dectime =
06 − 04
Example: 06-04=50hz (motor Rated frequency), 03-02=10hz (preset speed),
03-19=5s (Acc time), 03-20=20s (Dec-time),
03−19×10(hz )
Preset speed 1 Actual Acc time=
06 −04
= 1(s)
03− 20×10(hz )
Preset speed 1 Actual Dec time =
06 −04
= 4(s)
2) When 03-00is set to 1,the time has two modes to be set:
Example: 00-03=1,01-00=0 (S1=RUN/STOP),
01-01=1 (S2=forward/reserve),
01-02=2 (S3=preset speed1), 01-03=3 (S4= preset speed 2),
01-03=4 (S5= preset speed 4);
mode1: When the run command is uncontinuous, calculate acceleration and deceleration time of
each segment like this
(03−17)×(03− 01) (03−18)×(03− 01) (03−19)×(03− 02) (03− 20)×(03−02)
a= ,b = ,c= ,d = ……
06 − 04 06 − 04 06 −04 06 − 04

4-30
Frequency
Hz Forward

……

Time
a b c d e f

Panel freq Preset speed 1 Preset speed 2


S1
S2
S3
S4
S5

mode2: When the run command is continuous , calculate acceleration and deceleration time of each
segment like this
(03−17)×(03− 01) (03− 20)×[(03− 01) − (03−02)] (03− 21)×[(03−03) − (03− 02)]
a= ,b= ,c=
06 − 04 06 −04 06 −04
(03− 24)×(03−03) (03− 23)×(03−04) (03− 26)×(03−04) (03− 25)×(03−05)
d = , e= ,f= ,g = ,
06 − 04 06 − 04 06 − 04 06 − 04
(03− 26)×(03−05)
h= ……
06 −04
frequency Forward
Hz

……
e f

Time
a b c d g h

面Panel freq Preset Preset Preset Preset


S1 speed1 speed2 speed3 speed4
S2
S3
S4
S5

4-31
Group4- Start/Stop command group

04-00 : Starting Method Selection


=0 : Normal start
=1 : Enable Speed Search
1.04-00=0: On starting, the inverter accelerates from 0 to target frequency in the set time.
2.04-00=1: On starting, the inverter accelerates to target frequency from the detected speed of
motor.
04-01 : Stopping Method Selection
=0: braking capacity
=1: Coast to stop
1.04-01=0 : the inverter will decelerate to 0Hz in preset deceleration time after receiving the stop
command.
2.04-01=1: the inverter will stop output as receiving the stop command. The motor will inertia
Coast to stop.
04-02 : Stop Key on keypad
=0 : Stop Button Enabled
=1 : Stop Button Disabled
04-02=0, The STOP key is available for controlling the inverter to stop.
04-03 : Momentary power loss and restart
=0 : Momentary Power Loss and Restart disable
=1 : Momentary power loss and restart enable
=2 : Momentary power loss and restart enable while CPU is operating.
(According to the capacity of DC power)
04-04 : Momentary Power Loss Ride-Thru Time (Seconds) : 0.0 ~ 2.0 second
1.If the input power supply due to sudden increase in supply demand by other equipment results in
voltage drops below the under voltage level, the inverter will stop output at once. If the power
supply voltage level recovers in the 04-04 preset time, it will spin start tracing from the trip
frequency, or otherwise the inverter will trip with ‘LV-C’ fault displayed.
2. The allowable power loss time differs with the models. The range is from 1second to 2 second.
3. 04-03=0: as power lost, the inverter will not start.
4. 04-03=1: if the loss time is less than the value of 04-04, the inverter will Spin Start in 0.5 second
as the power is resumed and restart times are infinite.
5. 04-03=2:the power lost for long time, before the inverter lost the control power for the CPU, the
inverter will restart according to the 00-03 and 04-05 setting and status of external switch as the
resumed.
Note: 00-03=1 04-05=0 04-03=1or 2 after a power loss for a long time, please turn OFF the power
and power switches to avoid any possible injury to operators and machines when the power is
resumed unexpectedly.
04-05 : Auto Restart Method:
=0 : Enable Speed Search
=1 : Normal Start
1. 04-05=0: When auto-restarting the inverter will detect the rotating speed of the motor. The Motor
will be controlled to accelerate from the present speed to the target speed.
2. 04-05=1: The inverter restart from 0 speed to set frequency in acceleration time when
auto-restart.

4-32
04-06 : Auto Restart Delay Time (Seconds) : 0 ~ 800.0 second
04-07 : Number of Auto Restart Attempts : 0 ~ 10 times
1. 04-07=0: The inverter will not auto restart after trips due to fault.
2. 04-07>0, 04-06= 0:
The inverter will conduct SPIN START in 0.5 second after trips due to fault. The motor will
Coast to stop while the output is switched off, once the rotating speed is determined then it will
accelerate or decelerate from this speed to the running speed before the fault.
3. 04-07>0, 04-06>0:
The output will be stopped for a period which is determined by the 04-06 after a fault trip. Then,
spin start to set target frequency.
4. Auto restart after a fault will not function while DC injection braking or decelerating to stop.
04-08 : Reset Mode Setting
0 : Enable Reset Only when Run Command is Off
1 : Enable Reset when Run Command is On or Off
04-08=0 Once the inverter is detected a fault, please turn Run switch Off and then On again to
perform reset, otherwise restarting will not be possible.
04-09 : Direct Running After Power Up
0 : Enable Direct running after power up
1 : Disable Direct running after power up

Danger:
1. 04-09=0 and the inverter is set external terminal controlled (00-03/00-04=1), if the run switch is
ON as power is supplied, the inverter will auto start. It is recommend that the power is turned off
and the run switch is also off to avoid possibility of injury to operators and machines as the
power is reapplied.
Note: IF this mode is required all safety measures must be considered including warning labels.
2. 04-09=1and the inverter is set external terminal controlled (00-03/00-04=1), if the run switch is
ON as power is supplied, the inverter will not auto start and the display will flash with STP1.
It is necessary to turn OFF the run switch and then ON to start normally.
04-10 : Delay-ON Timer (Seconds) : 1.8 ~ 300.0 second
As power on and 04-09=0, the inverter will perform auto restart in the setting time for delay.
04-11 : Kinetic Energy Back-up Deceleration Time (S)
= 0.0 : Disable
= 0.1~25.0 : KEB Deceleration Time
04-11 = 0 KEB function disable 04-11≠ 0 KEB function enables
Example : 220V system

4-33
Figure 4-18 KEB function diagram
※Note:
1. When 04-11≠0, the momentary power loss and Restart is disabled, the inverter will do KEB
Function.
2. When input power is turned off, CPU detects the DC bus Voltage and as soon as DC bus Voltage
becomes lower than190V (220V system) or 380V (440V system), then the KEB function is
activated.
3. When KEB function is enabled, the inverter decelerate to zero by 04-11, and the inverter stop
4. IF the power on signal enabled during the KEB function, the inverter accelerate to original
frequency.
04-12 : Lower Limit of Power Voltage Detect = 150.0 ~ 210.0/300.0 ~ 420.0
04-13 : DC Injection Brake Level(%) @start = 0.0 ~150.0
04-14 : DC Injection Brake Time (Seconds) @start = 0.0 ~ 25.5

04-15 : DC Injection Brake Start Frequency (Hz) @Stopped = 0.10 ~ 10.00


04-16 : DC Injection Brake Level (%)@Stopped = 0.0 ~ 150.0
04-17 : DC Injection Brake Time (Seconds)@stopped = 0.0 ~ 25.5
1. 04-17 / 04-15is the action time and start frequency of DC braking, as graph below:

Figure 4-19 DC Injection Braking Example

4-34
Group5- V/F command group

V/F PATTERN Selection


05-00 : Volts/Hz Curve Modification (Torque Boost) (%) =0 ~ 30.0
05-01 : Motor no load current(Amps AC) -------------
05-02 : Motor rated Slip Compensation (%) = 0.0 ~ 100.0
05-03 : v/f Maximum voltage (Vac)
05-04 : Maximum Frequency (Hz) = 0.20 ~ 400.0Hz
05-05 : Maximum Frequency Voltage Ratio (%) = 0.0 ~100.0
05-06 : Medium Frequency2 (Hz) = 0.10 ~400.0Hz
05-07 : Medium Frequency Voltage Ratio2(%) = 0.0 ~100.0
05-08 : Medium Frequency1 (Hz) = 0.10 ~400.0Hz
05-09 : Medium Frequency Voltage Ratio1 (%) = 0.0 ~100.0
05-10 : Minimum Frequency (Hz) = 0.10 ~400.0Hz
05-11 : Minimum Frequency Voltage Ratio (%) = 0.0 ~100.0
05-12 : V/F start Frequency =0.00~ 10.00

1.00-01=18, set the V/F pattern freely complying with 05-04 ~ 05-09 (Refer to following diagram)
(V)%

05-05 (Vmax)

05-07

05-09 Figure 4-20 Custom V/F Settings

05-11 (Vmin)

05-10 05-08 05-06 05-04 400.00

4-35
2. 00-01 = 0 ~ 17 V / F Pattern (Refer to following list )

Func Funct
type 00-01 V/F pattern type 00-01 V/F pattern
tion ion

V (%) V (%)
100
100
General Use

General Use
0 B 9 B

50 C 60 C
1.5 2.5 50 400 Hz
1.5 3.0 60 400 Hz

V (%) V (%)
10
1
High start torque

High start torque


100 100

B 11 B
Hz Hz
2
C C

1.3 2.5 50 400 Hz


12 1.5 3.0 60 400 Hz
3

V (%) V (%)
Decreasing torque

Decreasing torque

4 100 13 100

B B

C C
5 14
1.3 25 50 400 Hz 1.5 30 60 400

V (%) V (%)
6 15
Constant torque

Constant torque

100 100

7 16 B
B

C C
8 0.5 25 50 400 Hz 17 0.6 30 60 400 Hz

Figure 4-21 Custom V/F Patterns

4-36
00-01 B C
0/9 7.5% 4.5%
1 / 10 10.0% 7.0%
2 11.0% 8.5%
3 12.0% 9.5%
4 17.5% 4.0%
5 25.0% 5.0%
11 11.0% 8.0%
12 12.0% 9.0%
13 20.5% 7.0%
14 28.5% 8.0%
6 / 15 45.0% 1.0%
7 / 16 55.0% 1.0%
8 / 17 65.0% 1.0%

3. The inverter will output the value of B, C voltage (refer to 00-01) plus the 05-00 V/F pattern
setting. The starting torque will be raised as shown.

Voltage
Figure 4-22 V/F curve with torque boost

100%

05-00=

C
Hz
1 2.5/3.0 50/60

※Note: 05-00=0, Torque boost function is invalid

4. When the induction motor is in running, there must be slip due to the load. It is necessary to boost
voltage to improve the precision of the speed.

Output Current-(05-01) Note : 06-01=motor rated current


Slip frequency boost = × (05-02)
(06-01)-(05-01) 05-01=motor no load current
05-02 approximate
(Motor synchronization speed– Rated speed) / Motor synchronization speed
value=
Marked on the motor nameplate
120
Motor synchronization speed (RPM)= × Motor rated frequency (50Hz or 60Hz)
Motor Poles

4-37
120
Example: 4 Poles,60Hzinduction motor synchronization speed = × 60=1800 RPM
4

※ Note: Motor no load current (05-01) differs with the inverter capacities (12-00) (Refer to 06-01
note). It should be regulated according to actual conditions.

Group6- Motor parameter group

06-00 : Motor Rated Voltage (VAC)


06-01 : Motor Rated Current (Amp AC)
06-02 : Motor Rated Power (kW)
06-03 : Motor Rated Speed (RPM)
06-04 : Motor Rated Frequency (Hz)

06-06 : Torque boost gain (Vector)


Performance: If the motor load is determined to be too large increase the output torque.

ΔTe ≒ I Gain gain)


¯(compensation
(load current)
• Torque/Speed curve pattern :
Torque

B
ΔTe: Increase output torque capacity

RPM
Q
A: before torque boost
B: after torque boost
Figure 4-23 Output Torque Capacity

• Operating frequency range: 0~Motor rate frequency


• When the motor output torque is not enough and increase 06-06 setting value.
• When the motor is erratic or vibrates decrease 06-06 setting value.
• The max. Output torque limit to the inverter is current rated.
• If increase 06-06 setting value then the output current is too large. Please increase 06-07 setting
value on the same time.

4-38
06-07 : Slip compensation gain (vector)
Performance : If the motor load appears too large, increase slip compensation.

ΔFslip ≒ I ¯ Gain
(load current) (compensation gain)
• Torque/Speed curve pattern :

Torque

ΔFslip

A: before slip compensation


A B B: after slip compensation

RPM
Q
Figure 4-24 Slip Compensation

• Operating frequency range : 0~motor rated frequency.


• When the motor output rotation speed is too low increase 06-07 setting value.
• When the motor is erratic or vibrates, decrease 06-07 setting value.
• The max. output rotation speed limit to the motor max. setting frequency.
• If increase 06-07 setting value then the output current is too large. Increase 06-05 setting value at
the same time.
06-11:Low frequency voltage compensation
Performance : During low frequency
Increase 06-11 setting value to increase output voltage and low frequency torque.
Decrease 06-11 setting value to decrease output voltage and low frequency torque.
• Output voltage/frequency curve pattern :

Figure 4-25 Low Frequency Voltage Compensation

06-07 F

• Operating frequency range : 0~12HZ / 60HZ 0~10HZ / 50HZ


• During low frequency use :
When the motor output torque is insufficient, increase 06-07 setting value.
When the motor is vibrating excessively, decrease 06-07 setting value.
4-39
Group7- Protection function group

07-00: Trip Prevention Selection


=xxxx0 : Enable Trip Prevention During Acceleration
=xxxx1 : Disable Trip Prevention During Acceleration
=xxx0x : Enable Trip Prevention During Deceleration
=xxx1x : Disable Trip Prevention During Deceleration
=xx0xx : Enable Trip Prevention in Run Mode
=xx1xx : Disable Trip Prevention in Run Mode
=x0xxx : Enable over voltage Prevention in Run Mode
=x1xxx : Disable over voltage Prevention in Run Mode

07-01 : Trip Prevention Level During Acceleration (%) 50 ~ 200


07-02 : Trip Prevention Level During Deceleration (%) 50 ~ 200
07-03 : Trip Prevention Level In Run Mode (%) 50 ~ 200
07-04 : Over voltage Prevention Level in Run Mode 350.0 VDC ~ 390.0 VDC
700.0 VDC ~ 780.0 VDC
Note:
1. In acceleration, the inverter will delay the acceleration time if the time is too short resulting in the
over current in order to prevent the inverter trips.
2. In deceleration, the inverter will delay the acceleration time if the time is too short resulting in the
over voltage of DC VUS in order to prevent the inverter trips with ‘OV’ displayed.
3. Some mechanical characteristics (such as press) or unusual breakdown (seize due to insufficient
lubrication, uneven operation, impurities of processed materials, etc.) will cause the inverter to
trip, thus inconvenience users. When the operating torque of the inverter exceeds the setting of
07-03, the inverter will lower the output frequency following the deceleration time , and return to
the normal operation frequency after the torque get steady.
07-05: Electronic Motor Overload Protection Operation Mode :
0 : Enable Electronic Motor Overload Protection
1 : Disable Electronic Motor Overload Protection
07-06 : Motor type selection:
0 : Electronic Motor Overload Protection Set for Non-Inverter Duty Motor
1 : Electronic Motor Overload Protection Set for Inverter Duty Motor
07-07 : Motor Overload Protection Curve Selection:
0 : Constant Torque (OL =103 %) (150 % for 1 Minute)
1 : Variable Torque (OL = 113 %)(123 % for 1 Minute)
07-08 : Operation After Overload Protection is Activated
0 : Coast-to-Stop After Overload Protection is Activated
1 : Drive Will Not Trip when Overload Protection is Activated (OL1)
Description of the thermal relay function:
1. 07-07 = 0: To protect the general mechanical load, as long as the load is less than 103% rated
current, the motor continue to run. The load is larger than 150% rated current, the
motor will run for 1 minute. (Refer to following curve (1)).
= 1: To protect HVAC load(FAN、PUMP…so on):as long as the load is less than 113%
rated current, the motor continue to run. The load is larger than 123% rated current,
the motor will run for 1 minute.
4-40
2. The heat sinking function will not be as effective when the motor run at low speed. So the
thermal relay action level will decline at the same time. (The curve 1 will change to curve 2).
3. 07-06 = 0: Set 06-04 as the rated frequency of the serve motor.
4. 07-08 = 0: the inverter coast to stop as the thermal relay acts and flash OL1. Press the
‘Reset’ or the external reset terminal to continue to run
= 1: the inverter continues to run as the thermal relay acts and flash OL1. Until the
current decline to 103% or 113 %( determined by 9-10), OL1 will disappear.

Minute

(1)

1.0 (2)
Current Percent
150
07-09 : Over torque Detection Selection(OL3)
= 0 : Disable Over torque Operation
= 1 : Enable Over torque Operation Only if at Set Frequency
= 2 : Enable Over torque Operation while the Drive is in Run Mode
07-10 : Operation After Over torque Detection is Activated
= 0 : Coast-to-Stop After Over torque is Activated
= 1 : Drive will Continue to Operate After Over torque is Activated
07-11 : Over torque Threshold Level(%) : 30~300
07-12 : Over torque Activation Delay Time (S) : 0.0~25.0
1. Over Torque is detected when the output torque level exceeds the level set in
Parameter 07-11 ( Inverter rated torque is 100%) and if it is detected for a duration of time
which is set in parameter 07-12.
2. 07-10 =0 : If there is over torque, the inverter coasts to stop and flashes OL3. It is necessary to
press’RESET’ or external terminal to continue to run.
=1 : If there is over torque, the inverter can continue to run and flashes OL3 until the output
torque is less than the 07-11 set value.
3. Parameter 01-09/10(Multifunction output terminal) = 12, the output terminal signal will be set
for over torque condition.
Note: Over torque detection will be enabled only when parameter 07-09 is set to options 1or2.
07-13 : OH over heat Protection ( cooling fan control)
0 : Auto (Depends on temp.)
1 : Operate while in RUN mode
2 : Always Run
3 : Disabled
1. 07-13=0 : The fan runs as the inverter senses temperature rises. Thusly, extend the service period.
2. 07-13=1 : The fan runs while the inverter is running.
3. 07-13=2 : The fan is continuously running regardless of the action of the inverter.
4. 07-13=3 : The fan is Disabled.

4-41
Group8- Communication function group

08-00 : Assigned Communication Station Number = 1 - 32


08-00 : to set the communication station codes which are suitable for driving more than one
inverters situations.
08-01 : RTU code /ASCII code Selection = 0 : RTU code =1 : ASCII code

08-02 : Baud Rate Setting (bps) = 0 : 4800 = 1 : 9600


= 2 : 19200 = 3 : 38400
In vector control mode, the communication baud rate setting (8-02) is limited under 9600 (includ).
08-03 : Stop Bit Selection = 0 : 1 stop bit = 1 : 2 stop bits

08-04 : Parity Selection =0 : no parity =1 : even parity


=2 : odd parity

08-05 : Data Format Selection =0 : 8 bit data =1 : 7 bit data


1.RS-485 Communication:
a. One to one communication: A controller, PC or PLC, controls one inverter. (set 08-00 = 1~32)
b. One to many communication: A controller, PC or PLC ,controls multiple inverters (Up to 32
inverters as max. Set 08-00 = 1~32).
c. When any inverter receive the communication station number 0, from the PC or PLC
( Broadcast mode) then all these inverters will be controlled in communication mode
regardless of the setting of parameter 08-00.
Note:
a. Communication data parameters (08-02/08-03/08-04/8-05) for controller, PC or PLC and
inverters should all be set the same.
b. The inverter will confirm the validity of new parameters set by PC.
c. Please refer to the E310 Communication instruction manual for communication protocol.
d. when 08-01=0, can not set 08-05=1.
08-06 : Communication time-out operation selection(S) = 0.0 ~ 25.5
08-07 : Communication time-out detection time
1)Time-out detection time: 00.0~25.5sec; setting 00.0 sec: disable time-out function.
2)Time-out operation selection:
0: Deceleration to stop (00-10: Deceleration time 1).
1: Free run to stop.
2: Deceleration to stop (10-06: Deceleration time 2).
3: Continue operating.
*Cannot be modified during communication.
08- 08 : Err6 fault tolerance times = 1 ~ 20
When communication error times ≥ 08-08 setting, display ERR6 on the keypad.
08- 09 : Drive Transmit Wait Time (ms) = 1 ~ 16(×4ms)
Setting the time from the beginning of receiving to the end of transmitting.

4-42
Group9- PID function group
1 PID function description
The Proportional, Integral and Derivative control function provides closed –loop control, or
regulation of a system process variable (Flow, Pressure, temperature, etc).This regulation is
obtained by comparing a feed back signal with a reference (target) signal, which results in an error
signal. The PID control algorithm then performs calculations on this error signal, based upon the
PID parameter group9.The result of the PID algorithm is then used as the new frequency reference,
or is added to the existing speed reference. The PID target value can be set by parameter 00-05/006,
for example the frequency command (target) can be set from Operator keypad, AI1 Analogue input
or multi function analog input terminals. Select the PID control feed back signal from external
terminal AI2 for a current signal (0-20ma) or a voltage (0-10vdc), depending on setting of Jumper 3
on control board and setting of parameter 2-06.

See PID block diagram below.


※Note : PID Function is available for controlling the output flow, external fan flow and temperature.
The PID block diagram is as follows:

Figure 4-26 PID block diagram

1. To enable PID control, set 02-06=0, ACI on TM2 is defined as the PID feedback signal.
2. The set point in the above diagram is the 00-05/00-06 input frequency.

4-43
2 PID Group 9 parameter descriptions
09-00: PID operation selection
=0 : disable
=1 : enable (Deviation is D-controlled)
=2 : Feedback D-controlled
=3 : D Reverse characteristic controlled
=4 : Feedback D characteristic controlled

09-00 =1, D is the deviation of (target value –detected value) in the unit time (09-04).
=2, D is the deviation of the detected values in unit time (09-04).
=3, D is the deviation of (target value – detected value) in the unit time (09-04). If the deviation is
positive, the output frequency decreases, vice versa.
=4, D is the deviation of detected value in unit time (09-04). When the deviation is positive, the
frequency decreases, vice versa.

09-01 : Feedback Gain coefficient (%) 0.00 ~10.00


09-01 is the calibration gain. Deviation = set point –(feedback signal×09-01)

09-02 : Proportional Gain(%) 0.00 ~ 10.00


09-02 : Proportion gain for P control.

09-03 : Integration Time(s) 0.0 ~100.0


09-03 : Integrate time for I control

09-04 : Differentiation Time(s) 0.00 ~ 10.00


09-04 : Differential time for D control

09-05: PID Offset 0 : Positive Direction


1 : Negative Direction
09-06 : PID Offset Adjust (%) 0 ~ 109
09-05/09-06: Calculated PID output is offset by 09-06 (the polarity of offset is according to 09-05).
09-07: PID Output Lag Filter Time(s) 0.0 ~ 2.5
09-07: Update time for output frequency.
09-08 : Feedback Loss Detection Mode
0 : Disable
1 : Enable – Drive Continues to Operate After Feedback Loss
2 : Enable – Drive “STOPS” After Feedback Loss
09-08= 0: Disable; 09-08= 1 : detect, continue running, and display ‘PDER’; 09-08= 2: detect, stop,
and display ‘PDER’.

09-09 : Feedback Loss Detection Level (%) 0 ~ 100


09-09 is the level for signal loss. Error = (Set point – Feedback value). When the error is larger than
the loss level setting, the feedback signal is considered lost.

09-10:Feedback Loss Detection Delay Time (s) 0.0 ~25.5


09-10 : the minimum time to consider the feedback signal lost.

09-11 : Integration Limit Value (%) 0 ~ 109


09-11 : the Limiter to prevent the PID from saturating.

4-44
09-13 : Allowable Integration Error Margin (Unit) (1 Unit = 1/8192) =0 ~ 100
09-13=0 ~ 100% unit value : Restart the tolerance after the integrator reset to 0.
09-14 : Sleep Frequency Level(Hz) = 0.00 ~ 400.00
09-15 : Sleep Function Delay Time(S) = 0.0 ~ 25.5
09-16 : Wake up frequency Level(Hz) = 0.00 ~ 400.00
09-17 : Wake up function Delay Time(S) = 0.0 ~ 25.5
PID SLEEP MODE:
09-00=1(PID Enable)
02-06=0(PID FEEDBACK Enable)
00-05=PID setting frequency source (Target Value)
09-14 : set the sleep threshold frequency, Unit:HZ
09-15 : set the time for sleep delay, Unit: sec
09-16 : set the wake threshold frequency, Unit:HZ
09-17 : set the time for wake delay, Unit: sec
When PID output frequency is less than the sleep threshold frequency and exceeds the time of sleep
delay, the inverter will decelerate to 0 and enter PID sleep mode.
When PID output frequency is larger than the Wake threshold frequency for Wake start the inverter will
reactivate and enter PID wake mode. The time diagram is as follow:

Figure 4-27 PID sleep wake mode diagram

4-45
Group10- Assistant function group

10-01: Prevention of Reverse operation


0 : Reverse command is enabled
1 : Reverse command is disabled
10-01=1, the reverse command is disabled.
10-02 : Keypad Operation with Up/Down Keys in Run Mode
0 : ‘Enter’ must be pressed after frequency change with Up/Down Keys on keypad.
1 : Frequency will be changed directly when Up/Down Keys are Pressed
10-03 : Carrier Frequency (KHz) 1-12
Carrier Carrier Carrier
10-03 10-03 10-03
Frequency Frequency Frequency
1 1KHz 5 5KHz 9 9KHz
2 2KHz 6 6KHz 10 10KHz
3 3KHz 7 7KHz 11 11KHz
4 4KHz 8 8KHz 12 12KHz
Note:
1. In applications where there is excessive audible noise from the motor or it is required to
reduce electrical interference (RFI) from the inverter caused by use of long cable then
the carrier frequency can be adjusted. To reduce electromagnetic interference due to long cable
etc, decrease carrier frequency. To reduce motor audible noise, increase carrier frequency.
2. The carrier frequency as minimum should be set higher than ten times the max running
frequency.Example: If the Max running frequency=400Hz, then set the carrier Frequency
higher than 4 KHz. If the Max running frequency =300Hz, then set the carrier frequency higher
than 3 KHz. 3.In the vector control mode, set carrier frequency lower than 6K, to reduce noise,
set random carrier frequency mode(10-04 = 2)
10-04 : Carrier mode selection
=0 : Carrier mode0 3-phase PWM modulation
=1 : Carrier mode1 2-phase PWM modulation
=2 : Carrier mode2 2-phase randomized PWM modulation
1. 10-04=0 : Carrier mode0 is recommended in environments where low noise is required.
Correct ambient temperature and cooling is necessary.
2. 10-04=1 : Carrier mode 1 is recommended in locations where fan or pumps is required.
3. 10-04=2 : Carrier mode 2 Help to slow down the temperature raise, prolong life-span of IGBT
and control electromagnetism noise.
Note: When the inverter is running at high speed and high carrier frequency is selected then,
please set 10-04=1 this can reduce the IGBT switching losses (heat loss).
10-05 : Acceleration Time 2 (MFIT) (s) 0.1 ~ 3600.0
10-06 : Deceleration Time 2 (MFIT) (s) 0.1 ~ 3600.0
10-07 : S-Curve Acc/Dec 1 (s) 0.0 ~ 4.0
10-08 : S-Curve Acc/Dec 2(s) 0.0 ~ 4.0
10-09 : S-Curve Acc/Dec 3 (s) 0.0 ~ 4.0
10-10 : S-Curve Acc/Dec 4 (s) 0.0 ~ 4.0

4-46
Use S Curve parameters where a smooth acceleration or deceleration action is required, this will
prevent possible damage caused to machines by sudden acceleration/deceleration.
Four parameters can be selected as shown on the diagram below:

Figure 4-28 S-Curve Characteristics


Note:
a. Regardless of the stall prevention period, actual acceleration and deceleration time =preset
acceleration / deceleration time + S curve time.
b. Please set the S curve time separately in the parameter (10-07~10-10)
c. When S curve time (10-07~10-10) is set as 0, the S curve function is disabled.
d. Note : The calculating of S curve time is based on the rated frequency of motor (06-04), Please
refer to the parameter (00-09/00-10).
10-11 : Skip frequency 1(Hz) = 0.00 ~ 400.00
10-12 : Skip frequency 2(Hz) = 0.00 ~ 400.00
10-13 : Skip frequency 3(Hz) = 0.00 ~ 400.00
10-14 : Skip frequency range (± Hz) = 0.00 ~ 30.00
Skip frequency parameters can be used to avoid mechanical resonance in certain applications.
Example:10-1=10.00(Hz); 10-12=20.00(Hz); 10-13=30.00(Hz); 10-14=2.00(Hz).
10Hz ±2Hz=8~12Hz
20Hz ±2Hz=18~22Hz Skip frequency
30Hz ±2Hz=28~32Hz

10-14
10-13
10-12
10-11

10-15 : Carrier Frequency reduced by temperature raising


=0 : disable =1 : Enable
When inverter is temperature overrun 80°C on keypad display(11-00=01000), Carrier Frequency
reduced 4K.when inverter is temperature reduced less than 70°C, Carrier Frequency resume.

4-47
temperature

80°C
70°C

Time
Carrier Frequency
0 t1 t2

10k

4k

Time
0 t1 t2
10-16 : Auto Voltage Regulation (AVR):
0 : AVR Function disable 1 : AVR Function enable
AVR function automatically regulates the AC motor drive output voltage to the Maximum
Output Voltage
10-17 : Count Down Completion =00~9999
This parameter sets purpose value of E310 built-in counter, this counter can take extermal terminal
S6 as a trigger in control circuit. When count value reaches purpose value ,multi-RELAY output
terminal acts.

Group11-keypad display group

11-00 : Display Mode


=xxxx0 : Disable Motor Current Display =xxxx1 : Enable Motor Current Display
=xxx0x : Disable Motor Voltage Display =xxx1x : Enable Motor Voltage Display
=xx0xx : Disable Bus Voltage Display =xx1xx : Enable Bus Voltage Display
=x0xxx : Disable temperature Display =x1xxx : Enable temperature Display
=0xxxx : Disable PID feedback Display =1xxxx : Enable PID feedback Display

11-01 : Custom Units (Line Speed) Value =0~65535


The max preset line value of 11-01 is equal to the rated frequency (06-04) of the motor. For
instance, given line speed 1800 is equal to display 900 when output is 30Hz while the operation
frequency is 60Hz.
11-02 : Custom Units (Line Speed) Display Mode
0 : Drive Output Frequency is Displayed
1 : Line Speed is Displayed in Integer (xxxxx)
2 : Line Speed is Displayed with One Decimal Place (xxxx.x)
3 : Line Speed is Displayed with Two Decimal Places (xxx.xx)
4 : Line Speed is Displayed with Three Decimal Places (xx.xxx)
When 11-02=1/2/3/4, line speed is displayed while the inverter is running or stopped.

11-07 : Counter display =0 Disable data Display =1 Enable data Display


4-48
Group12- User parameter group

12-00 : Drive Horsepower Code

12-00 Inverter Model 12-00 Inverter Model


20P5 20P5 4001 4001
2001 2001 4002 4002
E310- E310-
2002 2002 4003 4003
4005 4005

12-01 : Software Version


12-02 : Fault Log (Latest 3 times)
1. When the inverter trips on a fault, the previous fault log stored in2.xxx will be transferred to
3.xxx, the one in 1.xxx to 2.xxx. The present fault will be stored in the empty register 1.xxx. The
fault stored in 3.xxx is the last one of the most recent three, while the one 1.xxx is the latest.
2. When pressing ‘ENTER’ at 12-02, the fault 1.xxx will be displayed first. Press▲, to read
2.xxx→3.xxx→1.xxx press▼ and the order is 3.xxx→2.xxx→1.xxx→3.xxx.
3. When pressing ‘Reset’ at 12-02, the three fault log will be cleared when the reset key is pressed.
The log content will change to 1.---, 2.---, 3.---.
4. E.g. the fault log content is ‘1.OC-C’; this indicates the latest fault is OC-C, etc.
12-03 : Accumulated Operation Time 1 (Hours) : 0 ~ 23
12-04 : Accumulated Operation Time 2 (Days) : 0 ~ 65535
12-05 : Accumulated Operation Time Mode 0 : Power on time 1 : Operation time
1. When the operation time is to23 as the elapsed time 1 is set. The next hour will be carried to
operation12-04. Meanwhile, the recorded value will be cleared to 0000, and the record value of
operation duration 2 will be 01.
2. Description of operation time selection:
Preset value Description
0 Power on, count the accumulated time.
1 Inverter operation, count the accumulated operation time

12-06 : Reset Drive to Factory Settings


1150 : Reset to the 50Hz factory setting
1160 : Reset to the 60Hz factory setting

12-07 : Parameter lock


0 : Enable all Functions
1 : 03-01~ 03-08 cannot be changed
2 : All Functions cannot be changed Except 03-01~ 03-08
3 :Disable All Function

4-49
12-08 : Parameter password = 00000 ~ 65535
This function is used to prevent parameter from being modified by disrelated personnels, keep
parameter safety.
When a password has been set, parameters cannot be modified, and it is forbidden to reset to factory
set.
(1) Setting password:
① open 12-08, ”00000”is shown on keypad, input password, press” enter”,
display “End".
② When open 12-08 again, display “00001”, input password again, press” enter”,
display “LOC” display .
If setting is different from the first time, display “Err2”, setting failed
(2) cancel password:
① open 12-08, display ”00002”,input the correct password, press” enter” key
,display“End", Disable the password is successed.
If typing a wrong password, display “LOC”(password is still holded)
Note: set 12-08=00000, password can’t work

Group13- Auto Run (Auto Sequencer) function group

Auto Run( sequencer) mode selection:


13-00:
0 : Disabled.
1 : Single cycle. (Continues to run from the unfinished step if restarted).
2 : Periodic cycle. (Continues to run from the unfinished step if restarted).
3 : Single cycle, then holds the speed of final step to run.
(Continues to run from the unfinished step if restarted).
4 : Single cycle. (Starts a new cycle if restarted).
5 : Periodic cycle. (Starts a new cycle if restarted).
6 : Single cycle, then hold the speed of final step to run.
(Starts a new cycle if restarted).
13-01 : Auto _ Run Mode Frequency Command 1 (0.00 ~ 400.00Hz)
13-02 : Auto _ Run Mode Frequency Command 2 (0.00 ~ 400.00Hz)
13-03 : Auto _ Run Mode Frequency Command 3 (0.00 ~ 400.00Hz)
13-04 : Auto _ Run Mode Frequency Command 4 (0.00 ~ 400.00Hz)
13-05 : Auto _ Run Mode Frequency Command 5 (0.00 ~ 400.00Hz)
13-06 : Auto _ Run Mode Frequency Command 6 (0.00 ~ 400.00Hz)
13-07 : Auto _ Run Mode Frequency Command 7 (0.00 ~ 400.00Hz)
13-16 : Auto_ Run Mode Running Time Setting 0 ( 0.0 ~ 3600.0s)
13-17 : Auto_ Run Mode Running Time Setting 1 ( 0.0 ~ 3600.0s)
13-18 : Auto_ Run Mode Running Time Setting 2 ( 0.0 ~ 3600.0s)
13-19 : Auto_ Run Mode Running Time Setting 3 ( 0.0 ~ 3600.0s)
13-20 : Auto_ Run Mode Running Time Setting 4 ( 0.0 ~ 3600.0s)
13-21 : Auto_ Run Mode Running Time Setting 5 ( 0.0 ~ 3600.0s)
13-22 : Auto_ Run Mode Running Time Setting 6 ( 0.0 ~ 3600.0s)

4-50
13-23 : Auto_ Run Mode Running Time Setting 7 ( 0.0 ~ 3600.0s)
13-32 : Auto_ Run Mode Running Direction 0 (0 : STOP 1 : forward 2 : reverse)
13-33 : Auto_ Run Mode Running Direction 1 (0 : STOP 1 : forward 2 : reverse)
13-34 : Auto_ Run Mode Running Direction 2 (0 : STOP 1 : forward 2 : reverse)
13-35 : Auto_ Run Mode Running Direction 3 (0 : STOP 1 : forward 2 : reverse)
13-36 : Auto_ Run Mode Running Direction 4 (0 : STOP 1 : forward 2 : reverse)
13-37 : Auto_ Run Mode Running Direction 5 (0 : STOP 1 : forward 2 : reverse)
13-38 : Auto_ Run Mode Running Direction 6 (0 : STOP 1 : forward 2 : reverse)
13-39 : Auto_ Run Mode Running Direction 7 (0 : STOP 1 : forward 2 : reverse)
Note:
1. Auto Run (sequencer) various modes cab is selected by parameter 13-00.
2. Auto Run (sequencer) mode set up parameters are parameters (13-01 ~ 13-39).
3. Auto run mode (sequencer) operation as selected by parameter 13-00 can be set up as follows : -
a. Setting multi-step frequency commands, by using the available multi-step frequency
commands 0~7as required can be set by parameters (13-00 ~ 13-07).
b. Setting multi-step run time, by parameters (13-16 ~ 13-23) for each required step.
c. FWD/REV direction can be selected by setting of parameters (13-32 ~ 13-39).
d. d. Auto _ Run Mode Frequency Command 0 is3-01, running time is 13-16, Running Direction
13-32.
Some examples in auto_run mode as follows:
(A) Single Cycle Running (13-00= 1, 4)
The inverter will run for a single full cycle based upon the specified setting mode. Then, it
will stop.
‧ For example :
13-00=1(or 4)
‧ Panel Frequency (3-01)=15 Hz 13-01=30Hz 13-02=50Hz 13-03=20Hz
13-16=20s 13-17=25s 13-18=30s 13-19=40s
13-32=1 13-33=1 13-34=1(FWD) 13-35=2(REV)
‧ 13-04 ~ 13-07=0Hz, 13-20 ~ 13-23=0s,13-36 ~ 13-39=0

Figure 4-29 Single cycle auto run

4-51
(B) Periodic cycle Running (13-00=2, 5)
The inverter will repeat the same cycle periodically.
For example:
13-00=2(or 5)
13-01 ~ 13-03 , 13-16 ~ 13-23 , 13-32 ~ 13-39 : Same setting as the example (A)

Figure 4-30 Periodic cycle auto run

(C) Auto_Run Mode for Single Cycle (13-00 = 3, 6)


The speed of final step will be held to run.
For example:
13-00 = 3(or 6)
Panel Frequency (3-01) =15 Hz 13-01=30Hz 13-02=50Hz 13-07=20Hz
13-16=20s 13-17=25s 13-18=30s 13-23=40s
13-32=1 13-33=1 13-34 = 1 13-39=1(FWD)
13-04 ~ 13-06=0Hz ,13-20 ~ 13-22=0s ,13-35 ~ 13-38 = 0

13-07

(13-16) (13-17) (13-18) (13-23)

Figure 4-31 Single cycle auto run: final step hold

Note: 13-00 = 1~3 : If the inverter stops and re-starts, it will continue running from the unfinished
step, according to the setting of 13-00.
= 4~6 : If the inverter stops and re-starts, it will begin a new cycle and continue
running according to the setting of 13-00.

4-52
13-00 1~3 4~6
Run Run
Command run stop run Command run stop run
Output Frequency

Output Output
Frequency
Frequency begin a new cycle

Continue running from


unfinished step
time time

Figure 4-32 AUTO_RUN cycle with interrupt

●ACC/DEC time follow the setting of 00-09/00-10 or 10-05/10-06 in Auto Run Mode.

4-53
Chapter 5 Troubleshooting and maintenance
5.1. Error display and corrective action
5.1.1. Faults which can not be recovered manually
1. Faults which can not be recovered manually
Display Fault Cause Corrective action

-OV- Voltage too high Detection circuit malfunction Return the inverter
when stopped
1. Power voltage too low 1. Check if the power voltage is
2. Pre-charge resistor or fuse correct
-LV- Voltage too low
burnt out. 2. Replace the pre-charge resistor
when stopped
3. Detection circuit malfunction or the fuse
3. Return the inverter
The inverter is 1. Detection circuit malfunction 1. Return the inverter
-OH- overheated 2. Ambient temperature too high 2. Improve ventilation
when stopped or bad ventilation conditions
Current Sensor Current sensor error or circuit
CTER Return the inverter
detection error malfunction
EPR EEPROM
Faulty EEPROM Replace EEPROM
problem
2. Faults which can be recovered manually and automatically
Display Fault Cause Corrective Action
1. Short circuit between the
1. Inspect the motor
Over current at motor coil and the case
OC-S 2. Inspect the wiring
start 2. Short circuit between motor
3. Replace the transistor module
coil and ground
3. the IGBT module damaged
Over-current at The preset deceleration time is
OC-D Set a longer deceleration time
deceleration too short.
1. Acceleration time too short
2. The capacity of the 1. Set a longer acceleration time
motor exceeds the capacity of 2. Replace inverter with one that
the inverter has the same rating as that of the
Over-current at
3. Short circuit between motor
OC-A acceleration
the motor coil and the case 3. Check the motor
4. Short circuit between 4. Check the wiring
motor wiring and ground 5. Replace the IGBT module
5. the IGBT module damaged
1.Increase the capacity of the
inverter
2.Repeat parameter auto tuning
Over-current at 1. Transient load change
OC-C (06-05= 1)
fixed speed 2. Transient power change 3.Reduce stator resistance
(06-06) if the above actions are
ineffective
1. Set a longer deceleration time
Excessive 1. Deceleration time setting too 2. Add a brake resistor or brake
OV-C Voltage during short or excessive load inertia module
operation/ 2. Power voltage varies widely 3. Add a reactor at the power input
deceleration (fluctuates) side
4. Increase inverter capacity
Unacceptable Return unit if this happens
Err4 External noise interference
CPU interrupt regularly

5-1
3. Faults which can be recovered manually but not automatically
Display Fault Cause Corrective Action
1. Detection circuit
OC Over-current during malfunction 1.Check the noise between Power
stop 2. Bad connection for CT line and motor line
signal cable 2.Return the inverter for repair

1. Excessive load 1. Increase the motor capacity


OL1 Motor overload 2. Incorrect settings for
06-01, 07-05~08 2. set 06-01, 07-05~08 correctly

OL2 Inverter overload Excessive Load Increase the inverter capacity

1. Excessive Load 1. Increase the inverter capacity


OL3 Over torque 2. Incorrect settings for
07-11, 07-12 2. set 07-11, 07-12 correctly
1. Improve power quality or
increase the value of 4-04
1. Power voltage too low
LV-C Voltage too low 2. Set a longer acceleration time
2. Power voltage varies widely
during operation 3. Add a reactor at the power input
(fluctuates)
side
4. Increase the motor capacity
5.1.2. Special conditions
Display Fault Description

STP0 Zero speed at stop Occurs when preset frequency <0.1Hz

1. If the inverter is set for external terminal control mode


(00-03/00-04=1) and direct start is disabled (04-09=1)
STP1 Fail to start directly
The inverter cannot be started and will flash STP1.
On power up.
The run input is active at power-up, refer to descriptions of (04-09).
2. Direct start is possible when 04-09=0.

1. With the function of Stop key enabled by (04-02=0)


And if the Stop key is pressed while the inverter is set to external
control mode (00-03/00-04=1) then, the inverter will stop according
to the setting of 04-01 and the error message, ‘STP2’flashes after
Keypad Stop
stop.
Operated
STP2 Release and re-activate the run contact to restart the inverter.
when inverter
2. If the inverter is in communication mode and the Stop key is enabled
in external
(04-02=0), the inverter will stop in the way set by 04-01 when Stop
Control mode.
key is pressed during operation and then flashes STP2. The Host
controller has to send a Stop command then a Run command to the
inverter for it to be restarted.
3. Stop key will be disabled when 04-02=1

The inverter will decelerate to stop and then flash E.S., when input
External
E.S. external Rapid stop signal via the multifunctional input terminal
Rapid stop
activates (refer to descriptions of 01-00~01-05).

5-2
The inverter stops immediately and then flashes b.b., when external
External base
b.b. base block is input by the multifunctional input terminals.
block
(Refer to descriptions of 01-00~01-05).

PDER PID feedback loss PID feedback loss detect

Communication
COT Communication error detect (refer group 8 )
error

5.1.3. Operation errors

Display Error Cause Corrective Action


Parameter and 1.Attempt to modify frequency
frequency reverse parameter while 12-07>0 1. Set 12-07=0
LOC already locked 2.Attempt to reverse while 2. Set 10-01=0
10-01=1
1.The ▲ or▼ is available
1. Press ▲ or ▼while 00-05/00- for modifying the
06>0 or running at preset speed. parameter only when 00-
Keypad
Err1 05/00-06=0
operation error 2. Attempt to modify the Parameter.
2. Modify the parameter
Can not be modified during operation
in STOP mode.
(refer to the parameter list).
1. 00-08 is within the range of
1. Modify 10-11~10-13 or
10-11 ± 10-14 or 10-12 ± 10-14 or
10-14
10-13 ± 10-14
Parameter setting 2. Set 00-07>00-08
Err2 2. 00-07≤00-08
error 3. Set 00-03/00-04=0 and
3.Setting error while
05/00-06=0,
Performing Auto tuning.
during Auto tuning
(e.g.00-03/00-04≠0,00-05/00-06 ≠ 0 )
1. Control command sent during 1. Issue enable command
Modification of
communication. before communication
parameter is not
Err5 2. Attempt to modify the function 2. Set parameters
available in
08-02 ~ 08-05 during 08-02 ~ 08-05 function
communication
communication before communication
1. Wiring error
Communication 2. Communication parameter setting 1.Check hardware and wiring
Err6 failed error. 2.Check Functions
3. Check-Sum error 08-02 ~ 08-05
4. Incorrect communication protocol
1. Attempt to modify the function 12-
Err7 00/12-06. If Reset is not possible,
Parameter conflict
2. Voltage and current detection circuit please Return the inverter
is abnormal

5-3
5.2 General troubleshooting
Status Checking point Remedy
‧Is the power applied?
Is power applied to L1, L2, and L3 terminals
(is the charging indicator lit)? ‧Turn the power OFF and then ON
again.
‧Make sure the power voltage is correct.
‧Make sure screws are secured firmly.
Is there voltage across the output terminals T1,
‧Turn the power OFF and then ON again.
T2, and T3?
Motor can Is overload causing the motor to stall? ‧Reduce the load so the motor will run.
not run Are there any abnormalities in the inverter?
‧See error descriptions to check wiring
Is forward or reverse run command issued? and correct if necessary.
‧ Is analog frequency input signal wiring
Has the analog frequency signal been input? correct?
‧Is voltage of frequency input correct?
Is the operation mode setting correct? ‧Operate through the digital keypad .

Are wiring for output terminals T1, T2, and T3 ‧Wiring must match U, V, and W
Motor runs correct? terminals of the motor.
in wrong
direction Are wiring for forward and reverse signals ‧Check for correct wiring.
correct?
Is the wiring for the analog frequency inputs
‧Check for correct wiring.
correct?
The motor
speed can ‧Check the operation mode of the
Is the setting of operation mode correct?
not be operator.
regulated.
Is the load too excessive? ‧Reduce the load.

Check the motor specifications (poles, ‧Confirm the motor specifications.


Motor voltage…) correct?
running
speed too Is the gear ratio correct? ‧Confirm the gear ratio.
high or too
low Is the setting of the highest output frequency ‧Confirm the highest output frequency.
correct?
Is the load too excessive? ‧Reduce the load.
‧Minimize the variation of the load.
Motor Does the load vary excessively? ‧Increase capacities of the inverter and
speed the motor.
varies ‧Add an AC reactor at the power input
unusually Is the input power erratic or is a phase loss side if using single-phase power.
occurring? ‧Check wiring if using three-phase
power.

5-4
5.3 Quick troubleshooting of E310

E310 INV Fault

z DM =Diode Mdule
Is fault known? NO
z I.G.B.T =Insulat Gate Bipolar Transistor
YES
Any
Symptoms other than burn NO Symptoms of burn YES Check burnt and damaged
out, damage, or fuse meltdown in parts
the inverter?
out and damage?

YES

Fault signal? NO
Is the main circuit NO Replace DM
DM intact?
YES
Check according to displayed
fault messages YES

Is the fuse NO Replace fuse


intact?

YES

Is the main circuit NO Replace I.G.B.T


I.G.B.T intact?
Visually check controller and YES
Drive boards

Any visual abnormalities? YES


有 Replace the defective boards

Apply the power

Are displays and


indicators of the NO
operating unit working
normally?
YES Is LED lit? NO Replace the pre-charge resistor
Any fault NO
display? YES

Any fault Is the DC input voltage NO


controlling the power
Check terminals and wiring
display?
What’s the correct
message? YES

3 fault values in Is +5V control NO Replace the driver board


12-2 voltage correct?
Check 3 fault values of 12-2 with
▼key. YES
Replace control board and
digital operating unit

Is the error eliminated NO


after replacing control
board?
YES The inverter has faulted
Perform detailed check

*to next page

5-5
*From previous page
Check Inverter parameters

Perform parameter
initializations

Specify operation control


mode

FWD or REV LED NO Replace the control board


light after flashes ?

YES

Set up frequency command

Is the frequency value NO


Replace the control board
displayed in operation
unit?

YES

Are there NO
voltage outputs at Replace the control board
terminalsT1 T2 T3

YES
Connect the motor to run Does the control NO
Board function after
replacement

YES

Is there any fault YES


display?

NO

Are output
currents of each phase
even?

YES
NO


The inverter is failed
Perform detailed check
The inverter is OK

Figure 5-1 E310 fault display and troubleshooting flow chart

5-6
Troubleshooting for OC, OL error displays
The inverter displays OC, OL
errors

Is the main circuit NO Replace I.G.B.T


I.G.B.T working

YES

YES
Any visual abnormalities? Replace faulty circuit board

Apply power

YES
Any abnormal NO
Is the current detector
indications?
OK?
YES
Input operation command Replace control board Replace the current controller

Is FWD LED Replace control board


illuminated? NO
YES
Input frequency command

Is the output frequency of the NO Replace control board


operating unit displayed?

YES

Is there NO
Voltage at T1-T2-T3 output Replace control board
terminals?
YES
Is the inverter
NO
Connect the motor to run operating well after
ports replacement?

Any fault values displayed? YES YES

NO

Is the output current of


each phase even?

YES
The inverter’s output is OK
NO


The inverter is faulted
Perform detailed check

Figure 5-2 OC, OL Fault Display Flow Chart

5-7
Troubleshooting for OV, LV error
The inverter displays OV, LV

NO Replace the main circuit fuse


Is the main circuit fuse
intact?
YES

YES Replace the faulty circuit


Any visual abnormalities?
board

NO
Apply power

Any abnormal YES Replace the control board


indications?

NO
Input operation command

Is FWD LED still Replace the control board


illuminated after flash NO
YES
Input frequency commands

Is the output frequency of the


NO
Replace the control board
operating unit displayed?

YES
Is there NO
Voltage at T1,T2,T3 output Replace the control board
terminals?

Is the inverter NO
YES working well after
Connect the motor to run replacement?

YES

YES
Any abnormal value?

NO

Is the current on all


phases even?

YES
The inverter’s output is OK
NO


The inverter is failed
Perform detailed check

Figure 5-3 OV, LV Fault Display Flow Chart

5-8
The motor can not run

YES Is MCCB
applied?

NO

Can MCCB be NO
applied? Short circuited wiring

YES (within ±3% of the normal value)

Are voltages NO ․The power is abnormal


between power
․Incorrect wiring
terminals correct?

Is LED lit? NO
E310fault

Is the operation switch NO The operation switch is set to


in “RUN’ ? “RUN’ position

YES

Are there outputs between the NO


U-V-W terminals of the motor? E310fault

Are outputs between U- NO


V-W even E310fault

YES (voltage deviation between output pairs are even if


within ±3% of the normal value without the motor
․Motor
․Motor faults
․Incorrect wiring

z Figure 5-4 Motor RUN failure Flow chart

5-9
Motor Overheating

Is load or current Reduce the load.


YES Increase capacities of E310
exceeding the specified
value? and the motor.
NO

Is motor running at YES


Select the motor again
low speed for a long
time?
NO

Is motor voltage E310faults


betweenT1-T2-T3
correct?
YES (within ±3% of the normal value)
Is there any YES
deterrence preventing Clear the deterrence
cooling of the motor

NO
Bad connection between YES Correct the bad connection
E310 drive and the motor

Figure 5-5 Motor Overheat Troubleshooting Flow Chart

Motor runs unevenly

Does it happen YES Is the NO


acceleration time Increase the Acc/ Dec time
during deceleration?
correct?
NO Reduce the load.
YES
Increase capacities of E310
and the motor.

Are the output voltages NO


between T1-T2-T3 E310 faults
balanced?

YES (within ±3% of rated output voltage

Is the load YES Reduce the load fluctuation


fluctuating? or add a flywheel.

NO

Any mechanical vibration or Inspect the mechanical system


gear backlash?

Minimal
E310 faults

Figure 5-6 Motor Instability Troubleshooting Flow Chart

5-10
5.4 Routine and periodic inspection
To ensure stable and safe operations, check and maintain the inverter at regular intervals.
The table below lists the items to be checked to ensure stable and safe operations.
Check these items 5 minutes after the “Charge” indicator goes out to prevent injury to personnel by
residual electric power.
Checking
Items Details period Methods Criteria Remedies
Daily 1Year
Measure with Temperature:
Confirm the
thermometer and -10 – 40oC (14-
temperature and
○ hygrometer 120℉) Improve the
Ambient humidity at the
according to Humidity: Below ambient or
conditions machine
installation notices. 95% RH relocate the
around the
Are there drive to a
machine
inflammable better area.
○ Visual check Keep area clear
materials in the
vicinity?
Any unusual vibration
○ Visual, hearing check No vibration Secure screws
from the machine
Installation
200Vclass: below
and grounding Measure the
Is the grounding 100Ω Improve the
of the inverter ○ resistance with a
resistance correct? 400V class: below grounding
multi-tester
10Ω
Voltage must
Input power Is the voltage of the Measure the voltage Improve input
○ conform with the
voltage main circuit correct? with a multi-tester voltage
specifications
External Are secure parts

terminals and loose?
Visual check
internal Is the terminal base Secure terminals Secure or send
○ Check with a
mounting damaged? and no rust back for repair
screwdriver
screws of the Visual rust stains

inverter present?
Any unusual bends or
○ Replace or
Internal wiring breaks?
Visual check No abnormalities send back for
of the inverter Any damage of the
○ repair
wire insulation?
Excessive dust or Clean up
Heat sink ○ Visual check No abnormalities
debris debris or dust
Excessive conductive
metal shavings or oil ○
Clean or
Printed sludge
Visual check No abnormalities replace the
circuit board Discolored, circuit board
overheated, or ○
burned parts
Unusual vibration and Visual or hearing Replace the

noise check cooling fan
Cooling fan No abnormalities
Excessive dust or
○ Visual check Clean fan
debris
Excessive dust or Clean
○ Visual check No abnormalities
debris component
Power Replace
component Check resistance No short circuit or
Measure with a power
between each ○ broken circuit in
multi-tester component or
terminals three-phase output
inverter
Any unusual odor or
○ Replace
leakage
Capacitor Visual check No abnormalities capacitor or
Any deformity or inverter

protrusion

5-11
5.5 Maintenance and Inspection
Inverter doesn’t need daily inspection and maintenance.
To ensure long-term reliability, follow the instructions below to perform regular inspection. Turn
the power off and wait for the charge indicator (LED) to go out before inspection to avoid potential
shock hazard from the charge stored in high-capacity capacitors.

(1) Clean up the accumulation of any dust inside the inverter.


(2) Check if there are any loose terminal screws and tighten them.
(3) Insulation tests
(a) Disconnect all leads connecting the INVERTER with external circuits when performing
insulation tests on external circuits.
(b) Internal insulation test should be performed against the main circuit of the
INVERTER body only. Use a high resistance DC 500V meter with insulating resistance
higher than 5MΩ.

Caution! Do not perform this test against the control circuit.

E310

Insulation Test Diagram

5-12
Chapter 6 Peripherals Components
6.1 reactor specification at Input side

AC inductance at input side DC reactor specification at input side


Model
Current (A) Inductance (mH) Current (A) Inductance (mH)
E310-2P5-XXX 2.5 4.2 3.1 5.65
E310-201-XXX 5.0 2.1 4.5 3.89
E310-202-XXX 10.0 1.1 7.5 2.33
E310-401-XXX 2.5 8.4 2.3 15.22
E310-402-XXX 5.0 4.2 3.8 9.21
E310-403-XXX 7.5 3.6 5.2 6.73
E310-405-XXX 10.0 2.2 8.8 3.98

6.2 Braking unit and braking resistor


Suitable Suitable Braking resistor Specification
Inverter Motor Motor Braking resistor Braking torque
Model Capacity Capacity Number Duty Cycle (%) (%)
(W) (Ω)
(HP) (KW) used
2P5 0.5 0.375 60 200 - 8 218
201 1 0.75 60 200 - 8 119
202 2 1.5 150 100 - 10 119
401 1 0.75 60 750 - 8 125
402 2 1.5 150 400 - 10 119
403 3 2.2 200 250 - 8 128
405 5 3.7 300 150 - 8 127

※ Formula for brake resistor: W= (Vpnb * Vpnb) * ED% / R


1. W: braking resistor power (Watts)
2. Vpnb: braking voltage (220V=380VDC, 440V=760VDC)
3. ED%: braking effective period
4. R: braking resistor rated ohms

6-1
6.3 Digital operator and extension cable

A. Content
c Inverter
d LED Keypad (E31DOP-01)
e Remote Cable for Keypad
※e using standard network cable connection.

Figure 6-1 Digital Operator Extension Cable

B. Operation procedure:

1. Turn off the power Supply; the following procedures should be performed after there is no display
on the keypad.
2. Remove the keypad.
3. Connect the inverter and the keypad with REMOTE cable in accordance with the diagram below.
4. Apply power to operate once the installation is complete.

6-2
Extension KEYPAD installation
(1) KEYPAD installation Dimensions:

+ a
530

)5(4
6(7

底面尺寸图

2. Dimension for remote keypad


a. Keypad hatch Installation Dimension

E31DOP-01

6-3
b. Keypad Installation Dimension for nut( superaddition gasket and nut)

fixing board

flap gasket (M3)


elastomeric gasket (M3)
E31DOP-01 nut (M3)

c. none gasket and nut, Keypad Installation Dimension


fixing board

E31DOP-01

6-4
Appendix

Appendix1: E310 parameter setting list


Customer Inverter Model
Site Location Contact Phone
Address
Parameter Setting Parameter Setting Parameter Setting Parameter Setting
code content code content code content code content
00-00 02-11 04-10 07-08
00-01 02-12 04-11 07-09
00-02 02-13 04-12 07-10
00-03 02-14 04-13 07-11
00-04 02-15 04-14 07-12
00-05 02-16 04-15 07-13
00-06 03-00 04-16 08-00
00-07 03-01 04-17 08-01
00-08 03-02 05-00 08-02
00-09 03-03 05-01 08-03
00-10 03-04 05-02 08-04
00-11 03-05 05-03 08-05
00-12 03-06 05-04 08-06
00-13 03-07 05-05 08-07
00-14 03-08 05-06 08-08
01-00 03-17 05-07 08-09
01-01 03-18 05-08 09-00
01-02 03-19 05-09 09-01
01-03 03-20 05-10 09-02
01-04 03-21 05-11 09-03
01-05 03-22 05-12 09-04
01-06 03-23 06-00 09-05

01-07 03-24 06-01 09-06


01-08 03-25 06-02 09-07
01-09 03-26 06-03 09-08
01-10 03-27 06-04 09-09
01-11 03-28 06-05 09-10
01-12 03-29 06-06 09-11
01-13 03-30 06-07 09-13
01-14 03-31 06-08 09-14
02-00 03-32 06-09 09-15
02-01 04-00 06-10 09-16
02-02 04-01 06-11 09-17
02-03 04-02 07-00 10-01
02-04 04-03 07-01 10-02
02-05 04-04 07-02 10-03
02-06 04-05 07-03 10-04
02-07 04-06 07-04 10-05
02-08 04-07 07-05 10-06
02-09 04-08 07-06 10-07
02-10 04-09 07-07 10-08

Appendix 1
Appendix
Parameter Setting Parameter Setting Parameter Setting Parameter Setting
code content code content code content code content
10-09 11-07 13-02 13-22
10-10 12-00 13-03 13-23
10-11 12-01 13-04 13-32
10-12 12-02 13-05 13-33
10-13 12-03 13-06 13-34
10-14 12-04 13-07 13-35
10-15 12-05 13-16 13-36
10-16 12-06 13-17 13-37
10-17 12-07 13-18 13-38
11-00 12-08 13-19 13-39
11-01 13-00 13-20
11-02 13-01 13-21

Appendix 2
Distributor
TECO Electric & Machinery Co., Ltd.
10F.,No.3-1 , Yuancyu St., Nangang District
Taipei City 115, Taiwan

Tel : +886-2-6615-9111 Ext:1721


Fax : +886-2-6615-0933

Http://www.teco.com.tw
4KA72X254T01 VER:01 2010.6

This manual may be modified when necessary because of improvement of the product,
modification, or changes in specification, this manual is subject to change without notice.

You might also like