2001 Net A Tables
2001 Net A Tables
2001 Net A Tables
Test Values
1. Compare bolted connection resistace to values of similar connections. TABLE(s) 10.12
2. Bolt-Torque level shall be in accordance with table 10.12 unless otherwise specified by Bolt Torque
manufacturer.
3. Microohm or millivolt drop values shall not exceed the high levels of the normal range as
indicated in the manufacturer's published data. If manufacture's data is not available, Grade SAE 1&2 SAE 5 SAE 7 SAE 8
investigate any values which deviate from adjacent poles or similar switches by more than
25 percent of the lowest value. Minimum
4. Circuit breaker insulation resistance shall be in accordance with table 10.1. Torque (PSI)
64K 105K 133K 150K
5. Control wiring insulation resistance shall be a minimum of two megaohms.
6. Trip characteristics of breakers shall fall within the manufacturer's published time-current Bolt Diameter
in inches Torque (Foot Pounds)
characteristics tolerance band, including adjustment factors.
7. For molded-case circuit breakers all trip times shall fall within table 10.7. Circuit breakers
1/4 4.0 5.6 8.0 8.4
exceeding specified trip time at 300 percent of pickup shall be toggled defective.
8. For molded-case circuit breakers instantaneous pickup value shall be within values shown in 5/16 7.2 11.2 15.2 17.6
table 10.8. 3/8 12.0 20.0 27.2 29.6
7/16 19.2 32.0 44.0 48.0
1/2 29.6 48.0 68.0 73.6
TABLE 10.1 9/16 42.4 70.4 96.0 105.6
Insulation Resistance Tests 5/8 59.2 96.0 133.6 144.0
on 3/4 96.0 160.0 224.0 236.8
7/8 152.0 241.6 352.0 378.4
Electrical Apparatus and Systems 1 225.6 372.8 528.0 571.2
Range of Rated Maximum Trip Time for Each Ampere Tolerance of High and
Continuous Current Maximum Frame Rating *1 Rating Low Settings
Derived form ANSI/IEEE C37.20.1 - 1993, Paragraph 5.5, standard for Metal-Enclosed Low-Voltage
Power Circuit Breaker Switchgear, C37.20.2 - 1993, Paragraph 5.5, Standard for Metal-Clad and Amperes <= 250V 251-600V High Low
Station-Type Cubicle Switchgear and C37.20.3 - 1993, Paragraph 5.5, Standard for Metal Enclosed 0-30 50 70 <250 +40% +40%
Interrupter Switchgear, and includes 0.75 mulitplier with fraction rounded down. 31-50 80 100 -25% -30%
51-100 140 160 +25% +30%
>250
The column headed "DC" is given as a reference only for those using dc tests to verify the integrity of 101-150 200 225 -25% -30%
connected cable installations without disconnecting the cables from the switchgear. It represents 151-225 230 275
values believed to be appropriate and approximately equivalent to the corresponding power frequency 226-400 300 350
For circuit breakers with nonadjustable
withstand test values specified for the voltage rating of switchgear. The presence of this column in no 401-600 450
601-800 500 instantaneous trips, tolerences apply to
way implies any requirements for a dc withstand test on ac equipment or that a dc withstand test the manufacturer's published trip range,
801-1000 600
represents an acceptable alternative to the low-frequency withstand tests specified in this
1001-1200 700 i.e. +40% on the high side, -30% on the
specification, either for design tests, production tests, conformance tests, or field tests. When making
dc tests, the voltage should be raised to the test value in descrete steps and held for a period of one
1201-1600 775 low side.
1601-2000 800
minute. 2001-2500 850 Reproduction of Table 5-4 from NEMA publication
2501-5000 900 AB4 - 199
Because of the variable voltage distribution encountered when making dc withstand tests, the
manufacturer should be contacted for reccomendations before applying dc withstand tests to the
switchgear. Voltage transformers above 34.5kV should be disconnected when testing with dc. Refer *1 for integrally-fused circuit breakers, trip times may be substantially
to ANSI/IEEE c57-13-1987 (R1987) IEEE Standard Requirements for Instrument Transformers [10], longer if tested with the fuses replaced by solid links (shorting bars).
Section 8 and, in particular 8.8.2, (the last paragraph)which reads "Periodic kenotron tests should not
be applied to transformers of higher than 34.5 kV voltage rating."
+ Consult Manufacturer