Two Sensor Symmetrical Muting (TSSM) Wiring and Programming Example
Two Sensor Symmetrical Muting (TSSM) Wiring and Programming Example
Instruction Set (17691.htm) > Safety Instructions (14880.htm) > Two Sensor
Search
Symmetrical Muting (TSSM) wiring and programming example
Quick Start Steps
programming example
Module Information
(249.htm)
Instruction Set
This example complies with ISO 13849-1 Category 4 operation. The
(17691.htm)
standard control portion of the application is not shown.
Logix 5000 Controllers
This wiring diagram shows how to wire a light curtain and two muting Instruction and
sensors to a 1791DS-IB12 module to illustrate the use of the Two Application
Sensor Symmetrical Muting instruction. Considerations
(197522.htm)
Logix Designer
Application Instruction
Set (14446.htm)
Interpret the Attribute
Tables (14924.htm)
Array Concepts
(14430.htm)
CIP Axis Attributes
(14966.htm)
Module Con guration
Attributes
(300135.htm)
Bit Addressing
(299394.htm)
(14429.htm)
Motion Error Codes
(.ERR) (14987.htm)
Structures (14459.htm)
Equipment Sequence
instructions
(187594.htm)
Equipment Phase
Instructions
(14487.htm)
Alarm Instructions
(14488.htm)
Advanced Math
Instructions
(14481.htm)
Array (File)/Misc
Instructions
(14503.htm)
Array (File)/Shift
Instructions
(14534.htm)
ASCII Conversion
Instructions
(14550.htm)
ASCII Serial Port
Filter Instructions
file:///C:/program%20files%20(x86)/rockwell%20software/studio%205000/help/enu/v31/rs5000/261895.htm 2/8
7/9/2018 Two Sensor Symmetrical Muting (TSSM) wiring and programming example
(14787.htm)
Function Block
Attributes (14770.htm)
Structured Text
Attributes (14774.htm)
Compute/Math
Instructions
(14622.htm)
Move/Logical
Instructions
(14807.htm)
Input/Output
Instructions
(14648.htm)
License Instructions
(322384.htm)
Math Conversion
Instructions
(14673.htm)
Metal Form
Instructions
(22148.htm)
Motion Con guration
Instructions
(motion_con guration
_instructions.htm)
Motion Event
Instructions
(14971.htm)
Motion Group
Instructions
(14973.htm)
Motion Move
Instructions
(14963.htm)
Motion State
Instructions
(14972.htm)
Multi-Axis Coordinated
Motion Instructions
(15054.htm)
Move/Logical Process
Instructions
(224692.htm)
Program Control
Tip: The tag in the preceding diagram is an internal Boolean tag
file:///C:/program%20files%20(x86)/rockwell%20software/studio%205000/help/enu/v31/rs5000/261895.htm 3/8
7/9/2018 Two Sensor Symmetrical Muting (TSSM) wiring and programming example
Tip: The tag in the preceding diagram is an internal Boolean tag
Instructions
that represents the nonhazardous portion of the machine
(14679.htm)
cycle. Its value is determined by other parts of the user
application that are not shown in this example. When the Sequencer
protected hazard is present, the tag value should be False (0). Instructions
When the protected hazard is not present, this tag value (14705.htm)
should be true (1). When the value of the tag is true (1), the Special Instructions
muting instruction allows the light curtain to become muted (14720.htm)
only if the proper input sequence is detected. When the value Timer and Counter
of the tag is False (0), the muting instruction does not allow Instructions
the light curtain to become muted, even if the proper input (14732.htm)
sequence is detected.
Trigonometric
Instructions
The programming software is used to con gure the input and output (14767.htm)
parameters of the Guard I/O module, as illustrated. Process Control
Instructions
When de ning the module, setting the Input Status to Combined
Status-Muting provides the smallest input packet possible and lets the (14812.htm)
muting lamp status be monitored. Choosing Test for Output Data lets Select/Limit
safety logic control Test Output 3 to drive the Muting Lamp and Test Instructions
Output 2 to drive the Clear Area Lamp. (14827.htm)
Sequential Function
The safety inputs that interface with the Light Curtain (Points 1 and 2) Dual Channel
file:///C:/program%20files%20(x86)/rockwell%20software/studio%205000/help/enu/v31/rs5000/261895.htm 4/8
7/9/2018 Two Sensor Symmetrical Muting (TSSM) wiring and programming example
are not pulse-tested because the Light Curtain pulse-tests its own Analog Input (DCA -
signals. integer version)
and (DCAF -
See also
Stop with Test and
Mute (DCSTM)
Two-sensor Symmetrical Muting (TSSM) (14872.htm) wiring and
programming
example
(261397.htm)
Emergency Stop
(ESTOP)
(14823.htm)
Enable Pendant
(ENPEN)
(14831.htm)
Five Position Mode
Selector (FPMS)
(14838.htm)
Four Sensor Bi-
Directional Muting
(FSBM) (14856.htm)
Four Sensor Bi-
Directional Muting
(FSBM) wiring and
programming
example
(262088.htm)
(14875.htm)
Redundant Input
(RIN) (14876.htm)
Redundant Output
(ROUT)
(14879.htm)
Safety Mat (SMAT)
(14853.htm)
Safety Mat (SMAT)
wiring and
programming
example
(261769.htm)
Two Hand Run
Station Enhanced
(THRSe)
(14874.htm)
Two Hand Run
Station Enhanced
(THRSe) wiring and
programming
example
(261782.htm)
Two Hand Run
Station (THRS)
(14877.htm)
Two Sensor
Asymmetrical
Muting (TSAM)
(14873.htm)
Two Sensor
Asymmetrical
Muting (TSAM)
wiring and
programming
example
(261825.htm)
Two-sensor
Symmetrical
Muting (TSSM)
(14872.htm)
Two Sensor
Symmetrical
Muting (TSSM)
wiring and
programming
file:///C:/program%20files%20(x86)/rockwell%20software/studio%205000/help/enu/v31/rs5000/261895.htm 7/8
7/9/2018 Two Sensor Symmetrical Muting (TSSM) wiring and programming example
example
(261895.htm)
Execution Times
for Safety
Application
Instructions
(14828.htm)
Studio 5000 Logix
Designer Glossary
(223429.htm)
Legal Notices
(201810.htm)
file:///C:/program%20files%20(x86)/rockwell%20software/studio%205000/help/enu/v31/rs5000/261895.htm 8/8