Short Circuit Calculation
Short Circuit Calculation
Short Circuit Calculation
*Note 2. For single-phase center-tapped transformers, the L-N fault current is higher Phase-Phase (L-L): 87%
than the L-L fault current at the secondary terminals. The short-circuit current available Phase-Ground (L-G) 25-125% (Use 100% near transformer, 50% otherwise)
(I) for this case in Step 4 should be adjusted at the transformer terminals as follows: Phase-Neutral (L-N) 25-125% (Use 100% near transformer, 50% otherwise)
At L-N center tapped transformer terminals
IL-N = 1.5 x IL-L at Transformer Terminals Note 6: Approximation of arcing fault values for sustained arcs as percentage
of 3-Phase (L-L-L) bolted fault values are shown below.
At some distance from the terminals, depending upon wire size, the L-N fault current is
lower than the L-L fault current. The 1.5 multiplier is an approximation and will theoret-
ically vary from 1.33 to 1.67. These figures are based on change in turns ratio between 3-Phase (L-L-L) Arching Fault 89% (maximum)
primary and secondary, infinite source available, zero feet from terminals of trans- Phase-Phase (L-L) Arcing Fault 74% (maximum)
former, and 1.2 x %X and 1.5 x %R for L-N vs. L-L resistance and reactance values.
Begin L-N calculations at transformer secondary terminals, then proceed point-to-point. Phase-Ground (L-G) Arcing Fault 38% (minimum)