100% found this document useful (1 vote)
197 views1 page

Short Circuit Calculation

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 1

Calculation Of Short-Circuit Currents — Example Of 3-Phase Short-Circuit Calculation

Point-To-Point Method. Fault #1


Adequate interrupting rating and protection of electrical components 300 KVA, 2%Z, 3
120/208V Secondary MAIN SERVICE
are two essential aspects required by the NEC® 110.3(B), 110.9, PANEL Fault #2
110.10, 240.1, 250.4, 250.90, 250.96, and Table 250.122 Note.
The first step to ensure that system protective devices have the prop-
er interrupting rating and provide component protection is to determine
the available short-circuit currents. The application of the Point-To- Infinite
Primary
Point method can be used to determine the available short-circuit cur- Available
rents with a reasonable degree of accuracy at various points for either
3or 1electrical distribution systems. The example shown here 20', (2) 4-500 kcmil CU
Steel conduit
assumes unlimited primary short-circuit current (infinite bus). 20', 4 - 2 AWG CU
Steel conduit
BRANCH CIRCUIT PANEL
Basic Short-Circuit Calculation Procedure.
Procedure Formula FAULT #1
Step 1 Determine transf. KVA x 1000 KVA x 1000 300 x 1000
3o transf. IFLA = Step 1 IFLA = = = 833A
full-load amperes EL-L x 1.732 EL-L x 1.732 208 x 1.732
from either: 100 100
a) Name plate KVA x 1000 Step 2 Multiplier = = = 55.55
1o transf. IFLA =
b) Tables 3A & 3B EL-L .9x Transf. % Z
†† 1.8
c) Formula
Step 2 Find transformer 100 Step 3 ** ISCA (L-L-L) = 833 X 55.55 = 46,273
multiplier Multiplier = 3-Phase Short-Circuit Current at Transformer Secondary
Transf. % Z
See Note 3.
Step 3 Determine transf. Step 4 f = 1.732 x L x lL-L-L= 1.732 x 20 x 46,273 = .174
C x n x EL-L 22,185 x 2 x 208
let-through short- †I = Transf. x multiplier
SCA FLA
circuit current 1
1
(Formula or Table 5) Step 5 M= = 1 + .174 = .852 (See Table 4)
1+ f
See Note 1 and Note 4.
Step 4 Calculate 3o faults f = 1.732 x L x lL-L-L †I
SCA (L-L-L) = 46,273 x .852 = 39,425A
“f” factor. C x n x EL-L Step 6
3-Phase Short Circuit Current at Fault #1
1o line-to-line
(L-L) faults f = 2 x L x lL-L FAULT #2 (Use ISCA (L-L-L) at Fault #1 to calculate)
See Note 5 C x n x EL-L

1o line-to-neutral Step 4 f = 1.732 x 20 x 39,425 = 1.11


5,907 x 1 x 208
(L-N) faults f = 2 x L x lL-N*
See Note 2 and 1
Note 5 C x n x EL-N Step 5 M= 1 = .474 (See Table 4)
=
1+ f 1 + 1.11
L = length (feet) of conduit to the fault.
†I = 39,425 x .474 = 18,687A
C = conductor constant. See Tables 1, 2. Step 6 SCA (L-L-L)

n = number of conductors per phase 3-Phase Short-Circuit Current at Fault #2


(Adjusts C value for parallel runs)
I = available short-circuit current in **The motor contribution and voltage variance should be accounted for at this
amperes at beginning of circuit. point. See Notes 1 and 4.
†† Transformer %Z is multiplied by .9 to establish a worst case condition.
Step 5 Calculate “M” See Note 3.
(multiplier) or take M= 11
+f
from Table 4. Note 3: The marked impedance values on transformers may vary ±10% from
Step 6 Compute the the actual values determined by ANSI / IEEE test. See U.L. Standard 1561.
†I = ISCA x M Therefore, multiply transformer % Z by .9. Transformers constructed to ANSI
available short- SCA

at at standards have a ± 7.5% impedance tolerance (two-winding construction).


circuit current beginning of circuit.
fault
(RMS symmetrical) Note 4. Utility voltages may vary ±10% for power, and ±5.8% for 120-volt light-
See Note 1, Note 2, and Note 5 ing services. Therefore, for worst case conditions, multiply values as calculated
in Step 3 by 1.1 and/or 1.058 respectively.
† Note 1. Motor short-circuit contribution, if significant, should be added at all fault
locations throughout the system. A practical estimate of motor short-circuit contri- Note 5: The calculated short-circuit currents above represent the bolted fault
bution is to multiply the total motor full-load current in amperes by 4. Values of 4 to values that approximate worst case conditions. Approximations of Bolted fault
6 are commonly accepted values as percentage of 3-Phase (L-L-L) bolted fault values are shown below.

*Note 2. For single-phase center-tapped transformers, the L-N fault current is higher Phase-Phase (L-L): 87%
than the L-L fault current at the secondary terminals. The short-circuit current available Phase-Ground (L-G) 25-125% (Use 100% near transformer, 50% otherwise)
(I) for this case in Step 4 should be adjusted at the transformer terminals as follows: Phase-Neutral (L-N) 25-125% (Use 100% near transformer, 50% otherwise)
At L-N center tapped transformer terminals
IL-N = 1.5 x IL-L at Transformer Terminals Note 6: Approximation of arcing fault values for sustained arcs as percentage
of 3-Phase (L-L-L) bolted fault values are shown below.
At some distance from the terminals, depending upon wire size, the L-N fault current is
lower than the L-L fault current. The 1.5 multiplier is an approximation and will theoret-
ically vary from 1.33 to 1.67. These figures are based on change in turns ratio between 3-Phase (L-L-L) Arching Fault 89% (maximum)
primary and secondary, infinite source available, zero feet from terminals of trans- Phase-Phase (L-L) Arcing Fault 74% (maximum)
former, and 1.2 x %X and 1.5 x %R for L-N vs. L-L resistance and reactance values.
Begin L-N calculations at transformer secondary terminals, then proceed point-to-point. Phase-Ground (L-G) Arcing Fault 38% (minimum)

You might also like