Functions Range Operate Reset Timer Accuracy Trip Time: Rotection Ccuracy

The document summarizes the protection accuracy functions, ranges, operating parameters, and timing accuracy of an overcurrent/overvoltage protection device. Key specifications include: 1) Undervoltage/overvoltage protection ranges of 5-130V and 20-480V with trip thresholds within ±2% of the nominal voltage and trip times of 30ms ±10ms. 2) Residual voltage protection ranges of 0.5-130V and 2-480V with trip thresholds within ±2% or ±7.5% of the nominal voltage and trip times of 30ms ±10ms. 3) Under/over frequency protection range of 40-70Hz with trip thresholds within ±10mHz of the
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views1 page

Functions Range Operate Reset Timer Accuracy Trip Time: Rotection Ccuracy

The document summarizes the protection accuracy functions, ranges, operating parameters, and timing accuracy of an overcurrent/overvoltage protection device. Key specifications include: 1) Undervoltage/overvoltage protection ranges of 5-130V and 20-480V with trip thresholds within ±2% of the nominal voltage and trip times of 30ms ±10ms. 2) Residual voltage protection ranges of 0.5-130V and 2-480V with trip thresholds within ±2% or ±7.5% of the nominal voltage and trip times of 30ms ±10ms. 3) Under/over frequency protection range of 40-70Hz with trip thresholds within ±10mHz of the
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

PROTECTION ACCURACY

Functions Range Operate Reset Timer Accuracy Trip time


Undervoltage protection 5-130V (range A) DT : Vs ±2% (1.02-1.05) Greater of 2% or 40ms 30 ms; +/- 10 ms
(V<, V<< and V<<<) 20-480V (range B) IDMT : Voperate = 0.95Vs ±2% Voperate ±2% Greater of 5% or 40ms
Timers 200ms; +/- 10 ms
Overvoltage protection 0.5-260V (range A) 5-260V: DT: Vs ±2% (0.95-0.98) Greater of 2% or 40ms 30 ms; +/- 10 ms
(V>, V>> and V>>>) Voperate ±2% Greater of 5% or 40ms
20-960V (range B) 0.5-5V: DT: Vs ±20% Timers 200ms; +/- 5%

IDMT : Voperate = 1.1Vs ±2%

Residual voltage 0.5-130V (range A) 5-130V: DT : Vs ±2% 0.95 Greater of 2% or40ms 30 ms; +/- 10 ms
protection 2-480V (range B) Voperate ±2% Greater of 5% or 40ms
(V0>, V0>> and V0>>>) 0.5-5V: DT : Vs ±7,5%
IDMT : Voperate = 1.1Vs ±2%
(if direct measurement)

Under/Over frequency 40 – 70Hz DT : fs ±10mHz with fs ±50mHz Greater of 2% or 80ms 75 ms; +/- 25 ms
>30% of Un or
<30% of Un and df/dt < 10 Hz/s

df/dt 5-130V (range A) +/- 0.5Hz/IT Greater of 2% or 20ms 75 ms; +/- 25 ms


20-480V (range B)
(IT = number of frequency
40 – 70Hz filtering periods)
>30% of Un or
<30% of Un and df/dt < 10 Hz/s
U/ T 5-130V (range A) U : 1% U if 5%Un<U<Umax U: 1% if (20 ms + n * 20 ms)
20-480V (range B) 5%Un<U<Umax +/- 30 ms
5 % U if 1%Un<U<5%Un 3 % othewise.
∆T: 0.5% or 3 ms (n = number of confirmation
T : 0,5% or 3 ms period).

Note: For residual voltage protection :


– 0.5V → 4V (range A) :
hysteresis = Voperate – 0.2V
– 2V → 16V (range B) :
hysteresis = Voperate – 0.8V

P92x Technical Data Sheet P92x/EN TDS/C34