Power Transformer
Power Transformer
PROF. D. G. CHOUGULE
Department of Electronics, Tatyasaheb Kore Institute of Engineering and Technology, Warananagar
4
second is constituted by two equal parallel windings
PRIMARY
3
2
MOVABLE ARM
having similar connections 1a to 5a and 1b to 5b. Under
1 normal operating conditions, switches A, B and branches
with the same number are closed and each secondary
SECONDERY winding employs a total current means. Referring to Fig.
2, the secondary voltage will be maximum when the
Fig.1: Off load tap changing transformer switches a, b and 5a, 5b are closed. However, the
Fig.1 shows the arrangement in which several secondary voltage will be minimal when the switches A,
shots have been provided in the secondary. As the B and 1a, 1b are closed. Assume that the transformer
position of the tap is varied, the effective number of operates with the pickup position at 4a, 4b and wishes to
secondary turns varies and, therefore, the output voltage change its position to 5a, 5b. For this purpose, one of
of the secondary can be changed. Thus, with reference to switches A and B is opened, for example. This takes the
Fig. 1, when the movable arm contacts the stud 1, the secondary winding controlled by the switch. Now, the
secondary tension is minimal and when contacts the stud secondary winding controlled by the gate current switch
5, it is maximum. During the light charging period, the b total current is twice its rated capacity. Then the
voltage across the primary is not well below the intermediate connection winding disconnected changes
alternator voltage and the movable arm is placed on the from 5a and the switch is closed. Subsequently, b opens
pin 1. When the load increases, the voltage across the the switch to disconnect the winding thereof, the start
primary falls, but the voltage Secondary can be position of this winding is changed by 5b and then
maintained in the previous value by placing the movable switch b is closed. This changes the firing position
arm on a higher bolt. When a faucet is changed on this without interrupting the power supply.
type of transformer, the load is maintained and hence This method has the following disadvantages:
the name of the load change transformer. During switching increases impedance
The main disadvantage of the circuit transformer and there will be an increase in
arrangement shown in Figure 1 is that it cannot be used voltage.
to change the load-taking. Let's assume for a moment There are twice as many tappings as the voltage
that the change of take from position 1 to position 2 steps.
when the transformer is supplying the load. If the
contact with the stud 1 is broken before the stud 2 is C. SWITCHING PRINCIPLE:
contacted, a breakage occurs in the circuit and arcs The OLTC changes the proportion of a
occur. On the other hand, if contact with the stud 2 is transformer by adding curves or subtracting curves from
made before the contact with the stud 1 is broken; the the primary or secondary winding. Therefore, the
coils connected between these two sockets are short transformer is equipped with a regulation winding or
circuited and carry harmful heavy currents. For this connectors connected to the OLTC. The main
reason, the above circuit arrangement cannot be used to components of an OLTC are the contact systems for
change the tap on load. rupture and rupture currents, as well as transport
currents, transition impedances, gears, spring energy
B. ON-LOAD TAP-CHANGING TRANSFORMER: accumulators and a drive mechanism. Depending on the
In the supply system, the change of intake different winding devices and OLTC designs, selector
should normally be made in the load so that there is no switches and selector switches (reverse or coarse type)
interruption in supply. are used separately. The transition impedance in the
form of a resistor or reactor is constituted by one or
a
4a 4a
3a 3a
interruption or a significant change in the load current.
2a
for the period in which both taps are used. Typically, the
OLTC reactor type uses the jumper position as a service
SECONDARY position and therefore the reactor is designed for
continuous loading. The voltage between the indicated
Fig.2: On-load tap-changing transformer
192 | P a g e
NOVATEUR PUBLICATIONS
International Journal of Research Publications in Engineering and Technology [IJRPET]
ISSN: 2454-7875
VOLUME 3, ISSUE 4, Apr.-2017
faucets is the phase voltage; normally it is between 0.8% The application of semiconductor or solid state
and 2.5% of the rated voltage of the transformer. device gets advantage of rapid response in designing tap
changer, compared to its conventional equivalent, almost
II. LITERATURE SURVEY: free maintenance-free and better performance in terms
The problem for the conventional tap of power quality [4].
changer contributes to its mechanical structure of
complicated gear selector, diverter and switch gears. III. RESEARCH METHODOLOGY:
These arrangements are slow in response and The main concern of this work is to design a
susceptible to the condition of contact wear and damage completely electronic shifts with a prototype built as the
of the insulating oil, so they require regular maintenance model of operation as shown in Figure 3. The triac is
[1]. used as a switching device to turn on the selected power
Earn during the mechanical change on the on- tap transformer. The step down transformer and opto-
load tap transformer power transformer faucet process. isolator connected between the input and output of the
To address this situation, Roberts and Ashman had microcontroller respectively isolating the high voltage
described the arrangement of the switches to switch the power transformer damage of the low voltage circuit
thyristor pairs of arcing contacts. It has been further microcontroller circuit.
developed for a single driver resistance and then to
reverse the parallel thyristor pair which is a set of
mechanical switch contacts [2] [3].
TRIAC
Output
voltage
HIGH
VOLTAGE
SUPPLY
POWER
TRANSFORMER
WITH TAPPINGS
STEP-DOWN
TRANSFORMER
OPTO-
COUPLER MICROCONT
ISOLATOR ROLLER Vref
The peak signal peak output detector of the used as a central processing control logic to process the
rectifier is detected and provides an equivalent constant input signal and produces an appropriate output signal
DC voltage and then filters any noise is filtered and according to the program loaded in the microprocessor.
further improves the signal so that it is free from The microcontroller acts as a trigger by injecting
undulations and within the true range of frequency. impulses to the selected TRIAC representing the
While the opto-isolator acts as an electrical insulator to appropriate taps. At any time, only a TRIAC is in its ON
protect the input of the microcontroller. Microcontroller status while others are OFF.
IV. TAP CHANGER DESIGN:
193 | P a g e
NOVATEUR PUBLICATIONS
International Journal of Research Publications in Engineering and Technology [IJRPET]
ISSN: 2454-7875
VOLUME 3, ISSUE 4, Apr.-2017
Fig.4 shows the block diagram of the detailed The result of project power transformer tap
semiconductor tap changer used in this work. Some switching using semiconductor devices in which
additional devices are inserted into the prototype to increasing voltage from 227 volt to 255 volt by
provide greater precision and security for the system. In increasing order, then gets output voltage 110 ±4V.as
the 120V / 6V transformer step down loop feedback per table 1.
prototype, rectifier, peak detector, filter and transistor
opto-isolator is incorporated. Its function is to convert B. FOR INPUT VOLTAGE DECREASING ORDER:
the voltage of the 120V AC line voltage to an acceptable Table 2: Project output voltage and tap depending on
DC level for the operation of the microcontroller and input voltage decreasing order
provide protection against microcontroller damage. The SR. INPUT PAST PRESENT OUTPUT
NO VOLTAGE TAP TAP VOLTAGE
rectifier converts the alternating voltage signal into
continuous voltage signal. As the output of the rectifier is 1 255 4 4 112
not constant but with ripples, the peak detector and filter
2 253 4 4 111
are used to get better signals. 3 248 4 4 109
The signal is first converted to digital value by 4 240 4 3 110
the analog to digital converter internally before the 5 235 3 3 108
microcontroller can process information. If the value is 6 233 3 3 107
10% or 10% lower than the nominal value, the 7 231 3 2 111
microcontroller will quickly change the tap settings to a 8 227 2 2 109
lower or higher value, respectively. The microcontroller
will continue to change the setting to keep the voltage The result of project power transformer tap
within the set value. switching using semiconductor devices in which
decreasing voltage from 255volt to 227 volt by
V. PROJECT RESULT: decreasing order, then gets output voltage 110 ±4V.as
per showing table 2.
C. THE RESULT CHECKING THROUGH BULB
LUMINOUS:
VII. CONCLUSION:
Any variation of the output voltage of the power
transformer will be detected by the microcontroller
which in term computes and executes necessary
command instruction to be passed on to the appropriate
TRIAC. The semiconductor tap changer will change the
tap position if the variation is out of the permissible
range 110±4VAC. Thus the voltage, the system could be
maintained at normal value. From the result, the
semiconductor tap changer could be associated as an
automatic electronic on load tap changer for power
transformer to improve the voltage regulation of the
system during variation of system voltage. Distinguished
characteristics of this semiconductor tap changer are fast
response and less negligible spark during tap changing
process. TRIAC devices as the switching device that had
eliminated all disadvantages of arching, contact wear
and maintenance that associated with conventional
mechanical tap changer.
REFERENCES:
1) Han Jiang, Roger Shuttle worth, Bmhar A. T. AI
Zahawi Xiaolin Tian and Andrew Power, “Fast
response GTO assisted novel tap changer,” IEEE
Transmissions on Power Deliwry, vol. 16, no. I, pp.
111-1 15, Jan.2001.
2) M. E. Robert sand, W. G. Ashman, “A thyristor assisted
mechanical on load tap changer,” in IEEE Conference
Publication 53, Power Thyristor and Their
Applications, pp. 185-192, 1969.
3) G. H. Cwke and K. T. Williams, ‘New thyristor assisted
diverter switch for on-load transformer tap changers,”
in IEEE Proceedings-B, vol. 139,no. 6, 507- 511,Nav.
1992.
4) R.C. Degeneff, “A new concept for solid-state on-load
tap changers,” in CIRED 97, IEE Conference
Publication No. 438, pp. 1.7.1-1.7.4, June1997.
195 | P a g e