Optimal Power Flow Analysis
Optimal Power Flow Analysis
_____________________________________________________________________________________________________________
The total power losses of the system can be The generators data are presented in table 1, the cost
expressed as: coefficients for the generating units are presented in
ǻS= PL+jQL (3) table 2, while the load data are presented in table 3.
where: The data for the generators, loads and the cost
• PL- active power losses of the system; coefficients are presented in [12,13].
• Q L- reactive power losses of the
system.[2,11,12] TABLE 1. Generators data.[12]
The function is subjected to the following
restrictions: Generator PGimin PGimax QGimin QGimax
[MW] [MW] [MVAr] [MVar]
Pi (V,ș)=PGi-PDi
1 0 232.4 0 10
Qi (V, ș)= QGi-QDi
PGmin PG PGmax 2 0 40 -40 50
QGmin QG QGmax
Vimin Vi Vimax 3 0 0 0 40
Plmin Pl Plmax (4)
where: 6 0 0 -6 24
• PGi- active power supplied by the generator
connected to bus i; 8 0 0 -6 24
• QGi- reactive power supplied by the generator
HG 0 2 0 0
connected to bus i;
• PDi- active power demand of the load connected PPP 0 2 0 0
to bus i;
• QDi- reactive power demand of the load
connected to bus i; TABLE 2. Cost coefficients.[13]
• Pi- total active power injection at bus i;
• Qi- total reactive power injection at bus i; Generator a b c
• Vi- voltage magnitude at bus i; [EUR/MWh2] [EUR/MWh] [EUR/h]
1 0.0016 2.00 150
• Pl- the power flow for the line l from bus j to bus
k.[2,11,12] 2 0.0100 2.50 25
The optimal power flow will be performed with the
Neplan software [14]. 6 0.0083 3.25 0
Load PC [MW] QC [MVAr] The active power losses and the generation cost for
the steady-state condition of the system, for the case
1 0 0 when the distributed generators are connected to the
system are:
2 21.7 12.7 • active power losses: 12.86 MW;
• total generation cost: 853.39 EUR/h.
3 94.2 19
The active power losses and the generation cost for
4 47.8 0 the steady-state condition of the system, for the case
when the distributed generators are not connected to the
5 7.6 1.6 system are:
6 11.2 7.5 • active power losses: 13.59 MW;
• total generation cost: 842.755 EUR/h.
7 0 0 The active power losses and the generation cost after
8 0 0 the optimization was performed (optimal power flow),
for the case when the distributed generators are
9 29.5 16.6 connected to the system are:
• active power losses: 2.35 MW;
10 9 5.8
• total generation cost: 513.718 EUR/h.
11 3.5 1.8 The active power losses and the generation cost after
the optimization was performed (optimal power flow),
12 6.1 1.6 for the case when the distributed generators are not
connected to the system are:
13 13.5 5.8 • active power losses: 3.12 MW;
• total generation cost: 584.41 EUR/h.
14 14.9 5
The optimal power flow analysis results for the
whole day are presented in Fig. 5 (active power losses)
and in Fig. 6 (total generation cost).
For the IEEE 14 bus system, the installed load power
is 259 MW, corresponding to 1 load factor.
The load demand for the whole day is presented in
Fig. 4.
! "#
$
%
&&&
'(&
))
&*& +,
! "#
$
%
&&&
'(&)
))
&*& +,