BPVC I p-2

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

FORM P-2 MANUFACTURER’S DATA REPORT FOR ALL TYPES OF BOILERS

EXCEPT WATERTUBE AND ELECTRIC


As Required by the Provisions of the ASME Code Rules, Section I Page 1 of 2

1. Manufactured by THERMO PRESSION S.A.S


(Name and address of manufacturer)

2. Manufactured for ALMASUR C.A.


(Name and address of purchaser)

3. Location of Installation Av. Leonardo Da Vinci con Av. Lincoln, C.C. Bello Monte, Piso 4, Ofic. 4-A, Urb. Colinas de Bello Monte, Caracas - Vzla
(Name and address)

4. Type PHT - 150BHP Boiler No. N/A N/A N/A N/A Year Built 2018
(HRT, etc.) (Mfr’s. Serial No.) (CRN) (Drawing No.) (Nat’l Board No.)
5. The chemical and physical properties of all parts meet the requirements of material specifications of the ASME BOILER AND PRESSURE VESSEL
CODE. The design conforms to Section I of the ASME BOILER AND PRESSURE VESSEL CODE 2017 ,
(Year)

Addenda to 2018 (if applicable), and Code Cases N/A


(Date) (Numbers)

Manufacturer’s Partial Data Reports properly identified and signed by Commissioned Inspectors are attached for the following items of this report:
N/A
(Name of part, item number, mfr’s. name and identifying Certification Mark)

6. Shells or drums 1 SA 516 GR. 70 0.5" 82.68" 160"


(no.) (mat’l. spec. gr.) (thickness) [diameter (ID)] (length, inside) [diameter (ID)] (length, inside)

7. Joints BUTT WELD 0.85 WELDED 2


[long (seamless, welded)] [efficiency (as compared with seamless)] [girth (seamless, welded)] (no. of shell courses)

8. Heads SA 516 GR.70 - THCK 0,625" - FLAT - Radius of Dish 40.84"


(Material Specification No.: Thickness — Flat, Dished, Ellipsoidal — Radius of Dish)

9. Tubesheet SA 516 GR. 70 - THCK 0.625" Tube Holes 86 HOLES, 3,1" DIAMETER
(Mat’l. Spec., Grade, Thickness) (Diameter)

10. Boiler Tubes: No. ASTM 192 STRAIGHT


(Mat’l. Spec., Grade) (Straight or Bent)

Diameter 3" Length N/A Gage 0.12"


(If various, give max. & min.) (or thickness)

11. Furnace No. Size 34,25" Length, each section 146" Total
(O.D. or WxH)

Type CORRUGATED
(Plain, Adamson, Ring Reinforced, Corrugated, Combined, or Stayed)
SA 516 GR. 70 Seams: Type WELDED
(Mat’l. Spec., Grade, Thickness) (Seamless, Welded)
12. Staybolts: No. Size 1,5"
(Diameter, Mat’l. Spec., Grade, Size Telltale, Net Area)

Pitch N/A MAWP N/A psi.


(Horizontal and Vertical)
13. Stays or braces

Material No. Maximum Fig. PFT-32 Dist. Tubes


Location Spec. No. Type and Size Pitch L/I to Shell MAWP
(a) F.H. above tubes N/A
(b) R.H. above tubes N/A
(c) F.H. below tubes N/A
(d) R.H. below tubes N/A
(e) Through stays N/A
(f) Dome braces N/A

14. Other Parts. 1. N/A 2. N/A 3. N/A


(Brief Description — i.e., Dome, Boiler Piping, etc.)
1. N/A
2. N/A
3. N/A
(Mat’l. Spec., Grade, Size, Material Thickness, MAWP)

(07/15)
FORM P-2

Manufactured by THERMO PRESSION S.A.S Page 2 of 2

Mfr’s. Serial No. N/A CRN N/A National Board No. N/A

15. Openings: (a) Steam 3" FLANGED (b) Pressure Relief Valve 1 1/2" FULL COUPLING
(No., Size, and Type) (No., Size, and Type)
(c) Blowoff 1" FULL COUPLING (d) Feed 1 1/4" FULL COUPLING
(No., Size, Type, and Location) (No., Size, Type, and Location)

(e) Manholes: No. Size 12" x 16" Location TOP - BOTTOM

(f) Handholes: No. Size 4" x 5" Location TOP - BOTTOM AND SIDES

16. Fusible Plug (if used) N/A


(No., Diameter, Location, and Mfr’s. Certification Mark)
17. Boiler Supports: No. Type SADDLES Attachment WELDED
(Saddles, Legs, or Lugs) (Bolted or Welded)

18. MAWP N/A Based On N/A Heating Surface 750 ft^2


(Code Para. and/or Formula) (Total)

19. Shop Hydrostatic Test 250 PSIG 20. Maximum Designed Steaming Capacity 5300 lb/h

21. Remarks

CERTIFICATE OF SHOP COMPLIANCE


We certify that the statements made in this data report are correct and that all details of design, material, construction, and workmanship of this
boiler conform to Section I of the ASME BOILER AND PRESSURE VESSEL CODE.
Our Certificate of Authorization no. to use the (S) Designator expires

Date Signed Name


(Authorized Representative) (Manufacturer)

CERTIFICATE OF SHOP INSPECTION


Boiler constructed by at .
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and employed by

have inspected parts of this boiler referred to as data items


and have examined Manufacturer’s Partial Data Reports for items
and state that, to the best of my knowledge and belief, the manufacturer has
constructed this boiler in accordance with Section I of the ASME BOILER AND PRESSURE VESSEL CODE.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the boiler described in
this Manufacturer’s Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or
property damage or a loss of any kind arising from or connected with this inspection.

Date Signed Commission


(Authorized Inspector) [National Board Authorized Inspector Commission Number]

CERTIFICATE OF FIELD ASSEMBLY COMPLIANCE


We certify that the field assembly construction of all parts of this boiler conforms with the requirements of Section I of the ASME BOILER AND
PRESSURE VESSEL CODE.
Our Certificate of Authorization no. to use the (A) or (S) Designator expires

Date Signed Name


(Authorized Representative) (Assembler)

CERTIFICATE OF FIELD ASSEMBLY INSPECTION


I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and employed by

have compared statements in this Manufacturer’s Data Report with the described boiler and state that the parts referred to as data items
, not included in the certificate of shop inspection, have been inspected by me and that, to the best of my knowledge and
belief, the manufacturer and/or the assembler has constructed and assembled this boiler in accordance with the applicable sections of the ASME
BOILER AND PRESSURE VESSEL CODE. The described boiler was inspected and subjected to a hydrostatic test of .
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the boiler described in
this Manufacturer’s Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or
property damage or a loss of any kind arising from or connected with this inspection.

Date Signed Commission


(Authorized Inspector) [National Board Authorized Inspector Commission Number]

(07/17)

You might also like